Kaysun KAY-26 DN7, KAE-26 DN7, KAY-35 DN7, KAE-35 DN7, KAY-52 DN7 Technical Manual

...
PRODIGY 3D Inverter
Technical Manual
PRODIGY Technical Manual
CONTENTS
1. Precaution .................................................................................................................................................... 3
1.1 Safety Precaution .......................................................................................................................... 3
1.2 Warning ......................................................................................................................................... 3
2. Function and specifications ....................................................................................................................... 5
3. Dimension .................................................................................................................................................. 10
3.1 Indoor Unit ................................................................................................................................... 10
3.2 Outdoor Unit ................................................................................................................................ 14
4 .Refrigerant Cycle Diagram ....................................................................................................................... 18
5 .Installation Details ..................................................................................................................................... 19
5.1 Wrench torque sheet for installation ........................................................................................... 19
5.2 Connecting the cables ................................................................................................................ 19
5.3 Pipe length and the elevation ..................................................................................................... 20
5.4 Installation for the first time ......................................................................................................... 21
5.5 Adding the refrigerant after running the system for many years ................................................ 23
5.6 Re-installation while the indoor unit need to be repaired ........................................................... 24
5.7 Re-installation while the outdoor unit need to be repaired ......................................................... 25
6. Disassemble Guide.................................................................................................................................... 27
7. Operation Characteristics ......................................................................................................................... 33
8. Electronic function .................................................................................................................................... 34
8.1 Abbreviation ................................................................................................................................ 34
8.2 Display function ........................................................................................................................... 34
8.3 Main Protection ........................................................................................................................... 35
8.4 Operation Modes and Functions ................................................................................................. 36
8.5 Multi-function board instruction (This multi-function board is optional) ...................................... 43
9. Troubleshooting ......................................................................................................................................... 46
9.1 Indoor Unit Error Display ............................................................................................................. 47
9.2 Trouble shooting.......................................................................................................................... 48
PRODIGY Technical Manual
3
1. Precaution
1.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. Before service the unit, be sure to read this service manual at first.
1.2 Warning
Installation Do not use a defective or underrated circuit
breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock. Always ground the product. There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock. Always install a dedicated circuit and breaker. Improper wiring or installation may cause fore or electric shock. Use the correctly rated breaker of fuse. There is risk of fire or electric shock. Do not modify or extend the power cable. There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an authorized service center. Do not install the product on a defective
installation stand.
Be sure the installation area does not deteriorate
with age.
If the base collapses, the air conditioner could fall with it,
causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time
when the humidity is very high and a door or a window is left open.
Take care to ensure that power cable could not be
pulled out or damaged during operation.
There is risk of fire or electric shock. Do not place anything on the power cable. There is risk of fire or electric shock.
Do not plug or unplug the power supply plug
during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet
hands.
Do not place a heater or other appliance near the
power cable.
There is risk of fire and electric shock. Do not allow water to run into electrical parts. It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible
near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space
for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and
open a window for ventilation before turn the product on.
If strange sounds or smoke comes from product,
turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or
hurricane. If possible, remove the product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or
electric shock.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
PRODIGY Technical Manual
4
When the product is soaked, contact an authorized service center.
There is risk of fire or electric shock. Be caution that water could not enter the product. There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage. Keep level even when installing the product. It can avoid vibration of water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product. Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operational Do not expose the skin directly to cool air for long
time. (Do not sit in the draft). Do not use the product for special purposes, such as preserving foods, works of art etc. It is a
consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow. Use a soft cloth to clean. Do not use harsh
detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp. Do not step on or put anything on the product. (outdoor units) Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through air inlet or outlet while the product is operated.
Do not drink the water drained from the product. Use a firm stool or ladder when cleaning or
maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
PRODIGY Technical Manual
5
2. Function and specifications
Model Names of Indoor/Outdoor Units
3D inverter
Capacity
Indoor units
Outdoor units
9k
KAY-26 DN7
KAE-26 DN7
12k
KAY-35 DN7
KAE-35 DN7
18k
KAY-52 DN7
KAE-52 DN7
24k
KAY-71 DN7
KAE-71 DN7
PRODIGY Technical Manual
6
Specifications
Indoor
KAY-26 DN7
KAY-35 DN7
Outdoor
KAE-26 DN7
KAE-35 DN7
Power supply
Ph-V-Hz
220-240V~ 50Hz, 1Ph
220-240V~ 50Hz, 1Ph
Rated Cooling
Capacity
Btu/h
9000(4000-11300)
12000(4300-15200)
Cooling Power input
W
816(100-1270)
1153(110-1720)
Cooling Current
A
3.5(0.4-5.5)
5.0(0.5-7.5)
Rated Heating
Capacity
Btu/h
10000(2800-12700)
13000(3640-16600)
Heating Power input
W
811(140-1330)
1055(170-1740)
Heating Current
A
3.5(0.6-5.7)
4.6(0.7-7.6)
Seasonal Cooling Pdesignc
kW
2.6
3.5
SEER
W/W
6.8
6.7
Energy Efficiency Class
A++
A++
Heating(Average )
Pdesignh
kW
2.4
2.6
SCOP
W/W
4.1
4.2
Energy Efficiency Class
A+
A+
Tbiv
-7
-7
Heating(Warmer )
Pdesignh
kW
3.0
3.0
SCOP
W/W
5.1
5.2
Energy Efficiency Class
A+++
A+++
Tbiv
2
2
Tol
-15
-15
Moisture Removal
L/h
1.0
1.2
Max. input consumption
W
2075
2200
Max. current
A
9.5
10
Starting current
A
---
---
Compressor
Model ASN98D22UFZ
ASN98D22UFZ
Type ROTARY
ROTARY
Brand GMCC
GMCC
Capacity
Btu/h
10014
10014
Input W 748
748
Rated current(RLA)
A
5,35
5,35
Locked rotor Amp(LRA)
A
/
/
Thermal protector /
/
Thermal protector position
/
/
Capacitor
uF
/
/
Refrigerant oil/oil charge
ml
ESTER OIL VG74/370
ESTER OIL VG74/370
Indoor fan motor
Model ZKFP-20-8-6
ZKFP-20-8-6
Output W 20
20
Capacitor
uF
----
----
Speed(Hi/Mi/Lo)
r/min
----
----
Indoor coil a.Number of rows 1+2
1+2
b.Tube pitch(a)x row
mm
21x13.37
21x13.37
PRODIGY Technical Manual
7
pitch(b)
c.Fin spacing
mm
1.3
1.2
d.Fin type (code)
Hydrophilic aluminium
Hydrophilic aluminium
e.Tube outside dia.and type
mm
Φ6,innergroove tube
Φ7,innergroove tube
f.Coil length x height x width
mm
510x84x13.37+510x189x26.74
598x84x13.37+598x189x26.74
g.Number of circuits 2
2
Indoor air flow (Hi/Mi/Lo)
m3/h
472/360/254
563/497/224
Indoor sound pressure level (Hi/Mi/Lo/Silent)
dB(A)
40/35/28/20
41/40/33/22
Indoor sound power level (Hi)
dB(A)
53
52
Indoor unit Dimension(W*D*H)
mm
717x193x302
805x193x302
Packing (W*D*H)
mm
785x375x285
875x375x285
Net/Gross weight
Kg
7.0 / 9.3
7.7/10.2
Outdoor fan motor
Model ZKFN-40-8-1L
ZKFN-40-8-1L
Output W 40
40
Capacitor
uF
- -
- -
Speed
r/min
810/710/520
810/710/520
Outdoor coil
a.Number of rows 1
1
b.Tube pitch(a)x row pitch(b)
mm
21x13.37
21x13.37
c.Fin spacing
mm
1,2
1.2
d.Fin type (code)
Hydrophilic aluminium
Hydrophilic aluminium
e.Tube outside dia.and type
mm
Ф7, innergroove tube
Φ7,innergroove tube
f.Coil length x height x width
mm
744x504x13.37
870x504x13.37
g.Number of circuits 2
2
Outdoor air flow
m3/h
1900
2000
Outdoor sound pressure level
dB(A)
55
56
Outdoor sound power level
dB(A)
58
59
Outdoor unit Dimension(W*D*H)
mm
770x300x555
800x333x554
Packing (W*D*H)
mm
900x345x585
920x390x615
Net/Gross weight
Kg
26.6/29
29.1/31.9
Refrigerant Type
R410A
R410A
GWP
2088
2088
Charged quantity
Kg
0.8
0.95
Design pressure
MPa
4.2/1.5
4.2/1.5
Refrigerant piping Liquid side/ Gas side
mm(inch)
Φ6.35/Φ9.52(1/4"/3/8")
Φ6.35/Φ9.52(1/4"/3/8")
Max. refrigerant pipe length
m
25
25
Max. difference in level
m
10
10
Connection wiring
1.5(Optional)
1.5(Optional)
Plug type
--
--
Thermostat type
Remote Control
Remote Control
Operation temperature Indoor(cooling/ heating)
17~32/0~30
17~32/0~30
Outdoor(cooling/heating)
-1550/-1530
-1550/-1530
PRODIGY Technical Manual
8
Indoor
KAY-52 DN7
KAY-71 DN7
Outdoor
KAE-52 DN7
KAE-71 DN7
Power supply
Ph-V-Hz
220-240V~ 50Hz, 1Ph
220-240V~ 50Hz, 1Ph
Rated Cooling
Capacity
Btu/h
18000(6500-20900)
24000(9100-26900)
Cooling Power input
W
1633(150-2350)
2306(230-3030)
Cooling Current
A
7.1(0.7-10.2)
10.0(1.0-13.2)
Rated Heating
Capacity
Btu/h
19000(4870-23000)
26000(7100-31200)
Heating Power input
W
1500(230-2400)
2302(310-3270)
Heating Current
A
6.5(1.0-10.5)
10.0(1.3-14.2)
Seasonal Cooling Pdesignc
kW
5.3
7.0
SEER
W/W
6.8
6.4
Energy Efficiency Class
A++
A++
Heating(Average )
Pdesignh
kW
4.4
5.6
SCOP
W/W
4.2
4.0
Energy Efficiency Class
A+
A+
Tbiv
-7
-7
Heating(Warmer )
Pdesignh
kW
4.7
7.2
SCOP
W/W
5.4
5.2
Energy Efficiency Class
A+++
A+++
Tbiv
5
4
Tol
-15
-15
Moisture Removal
L/h
1.7
2.3
Max. input consumption
W
2550
3700
Max. current
A
11.5
17
Starting current
A
----
----
Compressor
Model ASM135D23UFZ
ATF235D22UMT
Type ROTARY
ROTARY
Brand GMCC
GMCC
Capacity
Btu/h
13836
24345
Input W 1035
1970
Rated current(RLA)
A
7,32
6,95
Locked rotor Amp(LRA)
A
/
/
Thermal protector /
/
Thermal protector position
/
/
Capacitor
uF
/
/
Refrigerant oil/oil charge
ml
ESTER OIL VG74/450
POE(VG74)/670
Indoor fan motor
Model ZKFP-30-8-3
ZKFP-58-8-1
Output W 30(Output)
58
Capacitor
uF
- -
- -
Speed(Hi/Mi/Lo)
r/min
----
----
Indoor coil
a.Number of rows 2
2
b.Tube pitch(a)x row pitch(b)
mm
21x13.37
21x13.37
c.Fin spacing
mm
1.2
1.3
d.Fin type (code)
Hydrophilic aluminium
Hydrophilic aluminium
PRODIGY Technical Manual
9
e.Tube outside dia.and type
mm
Φ7, innergroove tube
Φ7, innergroove tube
f.Coil length x height x width
mm
750x294x26.74
820x315x26.74
g.Number of circuits
3
3
Indoor air flow (Hi/Mi/Lo)
m3/h
870/730/500
1176/921/446
Indoor sound pressure level (Hi/Mi/Lo/Silent)
dB(A)
45/43/34/26
47/45/35/28
Indoor sound power level (Hi)
dB(A)
58
61
Indoor unit Dimension(W*D*H)
mm
964x222x325
1106x232x342
Packing (W*D*H)
mm
1045x405x305
1195x420x315
Net/Gross weight
Kg
10.1/13.6
13.2/17
Outdoor fan motor
Model ZKFN-40-8-1L
ZKFN-50-8-2
Output W 40
50
Capacitor
uF
- -
- -
Speed
r/min
810/700/550
810/750/600
Outdoor coil
a.Number of rows 2
2
b.Tube pitch(a)x row pitch(b)
mm
25.4x22
25.4x22
c.Fin spacing
mm
1.4
1.4
d.Fin type (code)
Hydrophilic aluminium
Hydrophilic aluminium
e.Tube outside dia.and type
mm
Φ9.52,innergroove tube
Φ9.52,innergroove tube
f.Coil length x height x width
mm
860x508x44
730x660x44
g.Number of circuits
4
4
Outdoor air flow
m3/h
2100
2700
Outdoor sound pressure level
dB(A)
58
61
Outdoor sound power level
dB(A)
63
65
Outdoor unit Dimension(W*D*H)
mm
800x333x554
845x363x702
Packing (W*D*H)
mm
920x390x615
965x395x755
Net/Gross weight
Kg
37.8/40.5
48.4/51.6
Refrigerant Type
R410A
R410A
GWP
2088
2088
Charged quantity
Kg
1.48
2.0
Design pressure
MPa
4.2/1.5
4.2/1.5
Refrigerant piping Liquid side/ Gas side
mm(inch)
Φ6.35/Φ12.7(1/4"/1/2")
Φ9.52/Φ15.9(3/8"/5/8")
Max. refrigerant pipe length
m
30
50
Max. difference in level
m
20
25
Connection wiring
2.5(Optional)
2.5(Optional)
Plug type --
--
Thermostat type
Remote Control
Remote Control
Operation
temperature
Indoor(cooling/ heating)
17~32/0~30
17~32/0~30
Outdoor(cooling/heating)
-1550/-1530
-1550/-1530
PRODIGY Technical Manual
10
3. Dimensions
3.1 Indoor Unit
Model
W D H
KAY-26 DN7
717
193
302
KAY-35 DN7
805
193
302
KAY-52 DN7
964
222
325
KAY-71 DN7
1106
232
342
PRODIGY Technical Manual
11
For KAY-26 DN7,
PRODIGY Technical Manual
12
For KAY-35 DN7,
For KAY-52 DN7,
PRODIGY Technical Manual
13
For KAY-71 DN7,
PRODIGY Technical Manual
14
3.2 Outdoor Unit
PRODIGY Technical Manual
15
For KAE-26 DN7,
PRODIGY Technical Manual
16
For KAE-35 DN7, KAE-52 DN7
PRODIGY Technical Manual
17
For KAE-71 DN7,
PRODIGY Technical Manual
18
4 .Refrigerant Cycle Diagram
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
ACCUMULATOR
INDOOR OUTDOOR
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
PRODIGY Technical Manual
19
5 .Installation Details
5.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
Ф15.9
5/8
4500(459kgf.cm)
4700(479kgf.cm)
Ф19
3/4
6500(663kgf.cm)
6700(683kgf.cm)
5.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and ≤6
0.75
>6 and ≤10
1
>10 and ≤16
1.5
>16 and ≤25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
PRODIGY Technical Manual
20
5.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional refrigerant
(g/m)
Gas
Liquid
KAY-26 DN7 + KAE-26 DN7
3/8‟‟
(Ф9.52)
1/4‟‟
(Ф6.35)
5
10
25
15
KAY-35 DN7 + KAE-35 DN7
3/8‟‟
(Ф9.52)
1/4‟‟
(Ф6.35)
5
10
25
15
KAY-52 DN7 + KAE-52 DN7
1/2‟‟
12.7)
1/4‟‟
(Ф6.35)
5
20
30
15
KAY-71 DN7 + KAE-71 DN7
5/8‟‟
(Ф15.9)
3/8‟‟
(Ф9.52)
5
25
50
30
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the system reliability.
PRODIGY Technical Manual
21
5.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and evacuated to remove gas and moisture from the system. Gas leak check (Soap water method): Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and 3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can‟t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
PRODIGY Technical Manual
22
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45‟ for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45‟ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position. Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m. Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe length >5m
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
PRODIGY Technical Manual
23
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
from the 3-way valve‟s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
5.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
side), disconnect the charge hose from the 3-way valve‟s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
PRODIGY Technical Manual
24
5.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa. Disconnect the charge set, and tighten the 2-way and 3-way valve‟s stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m. Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
PRODIGY Technical Manual
25
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45‟ for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45‟ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m. Be sure to check the gas leakage.
5.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve‟s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
PRODIGY Technical Manual
26
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way
valve‟s service port immediately If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage
PRODIGY Technical Manual
27
6. Disassemble Guide
6.1 How to Remove the filter
Step1: Put your hands at A and B, lift the filter a little to loosen the fastener
Step2: Pull the filter gently along the horizontal direction.
Step3: Pull out the filter.
6.2 How to Remove the horizontal louver
Step1: Open the horizontal louver ,push the locker towards right to open it.
Step2: Bend the horizontal louver lightly, remove it from the indoor unit.
PRODIGY Technical Manual
28
6.3 How to hold the indoor for piping
connection
Step1: Open the screw caps A and B, remove the two screws.
Step2: Open the panel assembly, move the slider to fix the panel.
Step3: Press the locker A and B, to lose the indoor from the installation plate
Step4: Unfold the supporter of Installation plate, then let it to hold the indoor unit, helpful to do pipe connection in the back
PRODIGY Technical Manual
29
6.4 How to Remove the panel assembly
Step1: Open the screw caps A and B, remove the two screws.
Step2: Open the panel assembly, loosen the display board connector.
Step3: Pull the panel assembly along the direction indicated in right image to remove it.
PRODIGY Technical Manual
30
6.5 How to Remove the PCB
Step1: Press A to remove the terminal cover.
Step2: Remove screw B to remove the cover of the electronic control box .
Step3: Then you can remove the PCB.
Note: It is not necessary to remove the panel to remove the PCB. in order to show clearly inside, these pictures are without panel.
6.6 How to Remove the Electrical control
box
Step1: Remove screw A,B,C, pull out the coil temp. sensor D from the sensor holders.
Step2: pull out the Electrical control box.
Note: It is not necessary to remove the panel to remove the Electrical control box, in order to show clearly inside, these pictures are without panel.
PRODIGY Technical Manual
31
6.7 How to Remove the Chassis assembly
CAUTION: Because the 24K indoor unit is
relatively large and heavy, it must have two persons to implement the following steps.
Step1: Remove the left and right pipe cover.
Step2: Remove the 5 screws A,B,C,D,E remove support part F and G.
Note: Screw E is behind the E-box by mistake for this sample, you need to remove screw X, to lift the E-box a little, Then you can remove the Screw E. This problem will be solved before mass-production.
Step3: Open the E-box, to lose the fan motor and louver motor connectors from the PCB.
Step4:
Press the locker H and I, to lose the indoor from the installation plate, lift it a little and pull out it along the direction indicated in right image.
Note: It is not necessary to remove the panel to remove the Chassis assembly, in order to show clearly inside, these pictures are without panel
PRODIGY Technical Manual
32
6.8 How to Remove the Evaporator
assembly
CAUTION: Because the 24K indoor unit is
relatively large and heavy, it must have two persons to implement the following steps.
Step1: Remove the Electric control box.
Step2: Remove the Chassis assembly
Step3: Unfold the Pipe clamp board C, remove screw A and B.
Step4: Pull out the evaporator.
PRODIGY Technical Manual
33
7. Operation Characteristics
Mode
Temperature
Cooling operation
Heating operation
Drying operation Room temperature
17℃~32℃ (62~90)
0~30 (32~86)
10℃~32℃ (50~90)
Outdoor temperature
0~50 (32~122)
-15~30 (5℉~86℉)
0~50 (32~122)
-15~50 (5~122) (For the models with low temperature cooling system)
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features
may come into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
3. For units with auxiliary electric heater .When outside temperature is below 0°C(32°F ),we strongly recommend keeping the unit plugged in at all times to ensure smooth ongoing performance.
4. The optimum performance will be achieved during this operating temperature zone.
PRODIGY Technical Manual
34
8. Electronic function
8.1 Abbreviation
T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature
8.2 Display function
8.2.1 Icon explanation on indoor display board.
Digital display: Displays the temperature settings when the air conditioner is operational. Displays the room temperature in Fan and Drying mode. Displays the self-diagnostic codes.
Dispalys for three seconds when Timer ON, Fresh, Swing, Turbo or Silence feature is activated.
Dispalys for three seconds when Timer OFF is set.
Dispalys for three seconds when Fresh, Swing, Turbo or Silence feature is cancelled.
Dispalys under deforsting operation.
Dispalys when anti-cold air feature is activated under heating mode.
Dispalys during self clean operation (if aplicable).
Dispalys when freeze protection is turned on (if aplicable).
When ECO function(optional) is actived,the illuminates gradually one by one as
PRODIGY Technical Manual
35
In one second interval.
WIFI control display(optional) Displays when the WIFI control feature is activated. (Not available when the unit does not have this function) NOTE: A guide on using the infrared remote is not included in this literature package.
8.3 Main Protection
8.3.1 Three minutes delay at restart for compressor
Less than 1 minute delay for the 1st time stand-up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the compressor top temp. protector restart.
8.3.3 Temperature protection of compressor discharge
Compressor discharge temp. T5>115for 5s, compressor stops.
8.3.4 Fan speed is out of control
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure
8.3.5 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections happen, the corresponding code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 7s later. If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
8.3.7 Compressor preheating functions
Preheating permitting condition: When T4(outdoor ambient temperature)3°C, the preheating function will be activated.
8.3.8 Sensor protection at open circuit and breaking disconnection.
When there‟s only one temperature sensor in malfunction , the air conditioner will keep working but show the error code, in case of any emergency use. When there‟s more than one temperature sensor in malfunction, the air conditioner will stop working.
8.3.9 Refrigerant leakage detection
This function is only active in cooling mode. It can better prevent the compressor being damaged by refrigerant leakage or compressor overload. Open condition: When compressor is active, the value of the Coil temperature of evaporator T2 has no change or very little change.
PRODIGY Technical Manual
36
8.4 Operation Modes and Functions
8.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan:
a
b
c
d
T1
e
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
When T1- Ts <ΔT -2, the compressor will stop, when T1Ts >ΔT -0.5℃,the compressor will be activated. ΔT is the programmed parameter of temperature compensation. When the AC run in mute mode, the compressor will run with low frequency. When the current is more than setting value, the current protection function will be activated, and the compressor will stop.
8.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4. For different outdoor units, the fan speeds are different.
T4
A+
A
B
C
D
E
8.4.2.3Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. When the setting temp. is reached, if the compressor stop running, indoor fan motor will run in Minimum speed or setting speed. The indoor fan is controlled as below:
PRODIGY Technical Manual
37
Setting fan
speed
Actual fan speed
H+(H+=H+G) A H(=H) B C
M+(M+=M+Z) D M(M=M) E F
L+(L+=L+D) G L(L=L) H I
T1-Td (°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
The auto fan acts as below rules:
a
b
c
d
T1
e
8.4.2.4 Condenser temperature protection
T3
Resume
Off
Decrease
Hold
When condenser temperature temp. is more than setting value, the compressor will stop.
8.4.2.5 Evaporator temperature protection
When Evaporator temperature temp.is less than setting value, the compressor will stop.
8.4.3 Heating Mode
8.4.3.1 Compressor running rules
When T1-Ts>-ΔT, the compressor will stop, when T1-TS<ΔT-1.5the compressor will be on. ΔT is the programmed parameter of temperature compensation. When the AC run in mute mode, the compressor will run with low frequency. When the current is more than setting value, the current protection function will be activated and the compressor will stop.
PRODIGY Technical Manual
38
8.4.3.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4. For different outdoor units, the fan speeds are different
T4
E
D
C
B
A A+
8.4.3.3 Indoor fan running rules When the compressor is on, the indoor fan can be set to high/med/low/auto/mute.
When indoor unit coil temp. is low, the anti-cold air function will start and indoor fan motor will run at low speed, the speed cant be changed ,when the temp. is lower than setting value, the indoor fan motor will stop. When the indoor temp reaches the setting temp., the compressor will stop, the indoor fan motor will run at the minimum speed or setting speed.(The anti-cold air function is valid). The indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H=H
H+(H+=H+G)
M(M=M)
M+(M+=M+Z)
L(L=L)
L+(L+=L+D)
H-(H-=H-G)
M-(M-=M-Z)
L-(L-=L-D)
T1-Td
L
H
M
Auto fan action in heating mode:
T1-Td+¦ ¤T
PRODIGY Technical Manual
39
8.4.3.4Defrosting mode
AC will enter the defrosting mode according to the value of temp. of T3 and the value range of temp. change of T3 and also the compressor running time. During the defrosting mode, the compressor keep running, indoor and outdoor motor will stop, defrost
lamp of the indoor unit will be lighted . Will be displayed. If any one of the following items is satisfied, the defrosting will finish and the machine will turn to
normal heating mode.
----T3 rises to be higher than TCDE1.
----T3 keeps to be higher than TCDE2 for 80 seconds.
----The machine has run for 15 minutes in defrosting mode.
8.4.3.5 Evaporator coil temperature protection
Resume
Off
Decrease
Hold
When evaporator temperature temp. is more than the setting protection value, the compressor will stop.
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between 17°C~30°C In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
T1-Ts
Cooling
Heating*
Fan only
Heating*: For cooling only models, they will run at fan speed Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode. If the machine switches mode between heating and cooling, the compressor will keep stopping for certain time and then choose mode according to T1-Ts. If the setting temperature is modified, the machine will choose running function again.
PRODIGY Technical Manual
40
8.4.5 Drying mode
Indoor fan speed is fixed at breeze and can‟t be changed. The louver angle is the same as in cooling mode. All protections are active and the same as that in cooling mode.
8.4.6 Forced operation function
Forced cooling mode: The compressor and outdoor fan keep running and the indoor fan runs at low speed. After running for 30 minutes, AC will turn to auto mode with 24 setting temperature. Forced auto mode: The action of forced auto mode is the same as normal auto mode with 24 setting temperature. When AC receives signals, such as switch on, switch off, timer on, timer off, mode setting, fan speed setting, sleeping mode setting, follow me setting, it will quit the forced operation.
8.4.7 Economy function
8.4.7.1 The sleep function is available in cooling, heating or auto mode.
8.4.7.2. Operation process in sleep mode is as follow: When cooling, the setting temperature rises 1 (be lower than 30℃) every one hour, 2 hours later the setting temperature stops rising and the indoor fan is fixed at low speed. When heating, the setting temperature decreases 1 (be higher than 17) every one hour, 2 hours later the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the priority).
8.4.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off.
8.4.7.4 Timer setting is available
8.4.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In case of a sudden power failure, the module memorizes the setting conditions before the power failure. The unit will resume the previous operation setting (not including swing function) automatically after 3 minutes when power returns. If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes and turn to auto mode as 24 setting temp. If AC is off before power off and AC is required to start up now, the compressor will have 1 minute delay when power on. Other conditions, the compressor will have 3 minutes delay when restarts.
8.4.9 Refrigerant Leakage Detection
With this new technology, the display area will show “EC” when the outdoor unit detects refrigerant leakage.
8.4.10 8 Heating(optional)
In heating operation, the preset temperature of the air conditioner can be as lower as 8, which keeps the room temperature steady at 8 and prevents household things freezing when the house is unoccupied for a long time in severe cold weather.
PRODIGY Technical Manual
41
8.4.11Self clean(optional)
For heat pump models which are provided with this function, after running in cooling or drying mode, if
the user press “Self Clean” button on remote controller, firstly, indoor unit runs in fan only mode for a
while, then low heat operation and finally runs in fan only again. This function can keep the inside of indoor unit dry and prevent breeding of mold.
8.4.12 Follow me(optional)
1) If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not respond. When the unit is running with follow me function, the PCB will control the unit according to the temperature from follow me signal, and the temperature collection function of room temperature sensor will be shielded, but the error detective function of room temperature sensor will be still valid.
2) When the follow me function is available, the PCB will control the unit according to the room temperature from the remote controller and the setting temperature.
3) The PCB will take action to the mode change information from remote controller signal, but it will not affected by the setting temperature.
4) When the unit is running with follow me function, if the PCB doesn‟t receive any signal from remote controller for 7 minutes or pressing FOLLOW ME button again, the follow me function will be turned off automatically, and the temperature will control the unit according to the room temperature detected from its own room temperature sensor and setting temperature.
8.4.13 Silence operation(optional)
Press the “silence” button on remote controller to initiate SILENCE function. When the Silence function is activated, the compressor running frequency will keep lower than F2 and the indoor unit will bring faint breeze, which will reduce the noise to the lowest level and create a quiet and comfortable room for you.
8.4.14 Easy control(optional)
For AE series,On-off port, XYE port, WIFI,wired controller(5-cored) can be chosen at the same time. Non-polar wired controller,4-cored wired controller, and central controller are mutually exclusive.
8.4.15 Point check function
Press the LED DISPLAY or LED or MUTE button of the remote controller three times, and then press the AIR DIRECTION or SWING button three times in ten seconds, the buzzer will keep ring for two seconds. The air conditioner will enter into the information enquiry status. You can press the LED DISPLAY or AIR DIRECTION button to check the next or front item‟s information within 27 seconds.
PRODIGY Technical Manual
42
When the AC enter the “information enquiry” status, it will display the code name in 2 seconds, the details are as follows.
Enquiry information
Displaying code
Meaning
T1
T1
T1 temp.
T2
T2
T2 temp.
T3
T3
T3 temp.
T4
T4
T4 temp.
T2B
Tb
T2B temp.
TP
TP
TP temp.
TH
TH
TH temp.
Targeted Frequency
FT
Targeted Frequency
Actual Frequency
Fr
Actual Frequency
Indoor fan speed
IF
Indoor fan speed
Outdoor fan speed
OF
Outdoor fan speed
EXV opening angle
LA
EXV opening angle
Compressor continuous running time
CT
Compressor continuous running time
Causes of compressor stop.
ST
Causes of compressor stop.
Reserve
A0 Reserve
A1 Reserve
0 Reserve
1 Reserve
2 Reserve
3 Reserve
4 Reserve
5 Reserve
6
Reserve
L
Reserve
A Reserve
U Reserve
T Reserve
A
Reserve
S
Reserve
T
PRODIGY Technical Manual
43
When the AC enters into the information enquiry status, it will display the code value in the next 25s, the details are as follows.
Enquiry information
Display value
Meaning
Remark
T1,T2,T3,T4, T2B,TP,TH, Targeted Frequency, Actual Frequency
-1F,-1E,-1d,­1c,-1b,-1A
-25,-24,-23,-22,-21,-20
1. All the displaying temperature is actual value.
2. All the temperature is °C no matter what kind of remote controller is used.
3. T1,T2,T3,T4,T2B display range:-25~70, TP display range:-20~130.
4. Frequency display range: 0~159HZ.
5. If the actual value exceeds the range, it will display the maximum value or minimum value.
-1999
-1999
A0,A1,…A9
100,101,…109
b0,b1,…b9
110,111,…119
c0,c1,…c9
120,121,…129
d0,d1,…d9
130,131,…139
E0,E1,…E9
140,141,…149
F0,F1,…F9
150,151,…159
Indoor fan speed /Outdoor fan speed
0
OFF
1,2,3,4
Low speed, Medium speed, High speed, Turbo
For some big capacity motors.
14-FF
Actual fan speed=Display value turns to decimal value and then multiply 10. The unit is RPM.
For some small capacity motors, display value is from 14-FF(hexadecimal), the corresponding fan speed range is from 200-2550RPM.
EXV opening angle
0-FF
Actual EXV opening value=Display value turns to decimal value and then multiply 2.
Compressor continuous running time
0-FF
0-255 minutes
If the actual value exceeds the range, it will display the maximum value or minimum value.
Causes of compressor stop.
0-99
For the detailed meaning, please consult with engineer
Decimal display
Reserve
0-FF
Reserve
2~28 Reserve
5~20
Reserve
5~25
8.5 Multi-function board instruction (This multi-function board is optional)
8.5.1. Function
The multi-function board receives the signal of 4-cored wired controller(central controller),Non-polar wired controller and CP remote on-off signal( ON-OFF command signal) . Then converting it to the communication signal to the main control board. The multi-function board can output Alarm signal.
PRODIGY Technical Manual
44
The multi-function board has two versions, one for Non-polar wired controller, the other one for 4-cored wired controller or central controller.
8.5.2. CP remote on-off
8.5.2.1 For CP command, closed indicate the remote on-off control signal OFF, Disconnected indicate the remote on-off control signal ON. It needs 3 seconds to determine on/off status. CP command will be delivered one time immediately after power on.
8.5.2.2 Dip-switch F2 setting status are as below:
Dip-switch 2
Dip-switch 1
Remote on-off control status
OFF
OFF
Disconnected send CP, closed cancel CP
ON
OFF
Closed send CP, disconnected cancel CP
8.5.3. ON-OFF control
8.5.3.1 It needs 3 seconds to determine on/off status. ON-OFF command do not be delivered after power on, only when the status changed, It can send the command.
8.5.3.2 When ON-OFF control disconnected, it will send switch-on signal: the unit will run in Auto mode ,Auto fan speed, 24 setting temp. When ON-OFF control closed, it will send switch-off signal.
8.5.3.3 Dip-switch F2 setting status are as below:
Dip-switch 2
Dip-switch 1
Remote on-off control status
OFF
ON
Disconnected send ON, closed send OFF
ON
ON
Closed send OFFdisconnected send ON
8.5.4. 4-cored wired controllerCentral controller and Non-polar wired controller
Note: 4-cored wired controller,Central controller and Non-polar wired controller
are mutually exclusive. They can only be chosen one of three at the same time.
8.5.4.1 For network address, Dip-switch F1 and Rotary switch ENC3 are set as below:
Dip-switch 2
Dip-switch 1
Based address
OFF
OFF
0
OFF
ON
16
ON
OFF
32
ON
ON
48
Note: The network address are the Dip-switch F1 address plus Rotary switch ENC3 address.
8.5.4.2 If it receives the network address set by remote controller, the network address will be changed .If it receives the cancel signal of network address set by remote controller, the network address will be disposed according to the setting of Dip-switch F1 and Rotary switch ENC3.
PRODIGY Technical Manual
45
8.5.4.3 The network address is useless for 4-cored wired controller, only valid for Central controller
and Non-polar wired controller.
8.5.5. Non-polar wired controller
8.5.1 Each Non-polar wired controller can be connect to Max. 16 indoor units .All the indoor units
must be the same series, and in the same network. The address of Multi-function board must be set differently. The connection method must be Bus type.
8.5.2 The setting state are the same for all the indoor units connected to the same Non-polar wired
controller
8.5.6.Alarm port output
8.5.6.1 When the Air-condition in off state, the output signal is closed.
8.5.6.2 When the Air-condition in malfunction state, the output signal is closed.
8.5.6.3 When the Air-condition in on state, the output signal is disconnected.
8.5.7Wiring diagram
8.5.7.1 Connected to 4-cored wired controller or Central controller
8.5.7.2 Connected to Non-poplar wired controller
PRODIGY Technical Manual
46
9. Troubleshooting
Safety
Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug) between +, ­terminals of the electrolytic capacitor on the contrary side of the outdoor PCB.
Note: The picture above is only for reference. The plug of your side may be different.
PRODIGY Technical Manual
47
9.1 Indoor Unit Error Display
Operation
lamp
Timer lamp
Display
LED STATUS
1 time
X
E0
Indoor unit EEPROM parameter error
2 times
X
E1
Indoor / outdoor units communication error
4 times
X
E3
Indoor fan speed has been out of control
5 times
X
E4
Indoor room temperature sensor T1 open circuit or short circuit
6 times
X
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
7 times
X
EC
Refrigerant leakage detection
1 times
O
F0
Overload current protection
2 times
O
F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
3 times
O
F2
Condenser coil temperature sensor T3 open circuit or short circuit
4 times
O
F3
Compressor discharge temperature sensor T5 open circuit or short circuit
5 times
O
F4
Outdoor unit EEPROM parameter error
6 times
O
F5
Outdoor fan speed has been out of control
1 times
P0
IPM malfunction or IGBT over-strong current protection
2 times
P1
Over voltage or over low voltage protection
3 times
P2
High temperature protection of compressor top diagnosis and solution
5 times
P4
Inverter compressor drive error
Olight Xoff ☆(flash
PRODIGY Technical Manual
48
9.2 Trouble shooting
9.2.1 EEPROM parameter error diagnosis and solution(E0/F4)
Error Code
E0/F4
Malfunction decision conditions
Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Supposed causes
Installation mistake
PCB faulty
Trouble shooting:
Yes
Replace the indoor/outdoor
main PCB.
Power off, then restart the
unit 2 minutes later.
EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the below photos.
Note: The two photos above are only for reference, its may be not same totally with the ones on your side.
Indoor PCB
Outdoor PCB
PRODIGY Technical Manual
49
9.2.2 Indoor / outdoor unit’s communication diagnosis and solution(E1)
Error Code
E1
Malfunction decision conditions
Indoor unit does not receive the feedback from outdoor unit during
110 seconds and this condition happens four times continuously.
Supposed causes
Wiring mistake
Indoor or outdoor PCB faulty
Trouble shooting:
Measure Vs, is it positive fluctuation? (Vs is the voltage between S and N of outdoor unit. Red pan-S, Black pan-N)
Measure Vs, is it positive fluctuation? (Vs is the voltage between S and N of outdoor unit. Red pan-S, Black pan-N)
Yes
Power off, then restart the unit 2 minutes later
Power off, then restart the unit 2 minutes later
No
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Check the outdoor wiring connection
Check the outdoor wiring connection
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Yes
Replace the outdoor main PCB.
Replace the outdoor main PCB.
No
Replace the indoor main PCB.
Replace the indoor main PCB.
No
Check the indoor wiring connection
Check the indoor wiring connection
Yes
Yes
Check whether reactor is normal?
Check whether reactor is normal?
Yes
Replace the reactor
Replace the reactor
No
PRODIGY Technical Manual
50
Remark:
Use a multi meter to test the resistance of the reactor which does not connect with capacitor. The normal value should be around zero ohm. Otherwise, the reactor must have malfunction and need to be replaced.
PRODIGY Technical Manual
51
9.2.3 Fan speed has been out of control diagnosis and solution(E3)
Error Code
E3/F5
Malfunction decision conditions
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.
Supposed causes
Wiring mistake
Fan ass’y faulty
Fan motor faulty
PCB faulty
Trouble shooting:
Power off, then restart the
unit 2 minutes later
Shut off the power supply, Rotate the fan by hand.
The unit operates normally.
Find out the cause and have
it solved
Check the wiring of fan
motor
No
Yes
No
Correct the connections.
No
NoReplace the fan motor
Yes
Yes
Measure the voltage for the
fan motor from the main
PCB
Yes
Replace the main PCBNo
PRODIGY Technical Manual
52
Index1: 1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced.
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
280V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
14-17.5V
5
Yellow
Vsp
0~5.6V
6
Blue
FG
14-17.5V
2. Outdoor DC Fan Motor (control chip is in outdoor PCB) Power on ,and check if the fan can run normally, if the fan can run normally, the PCB must has problems and need to be replaced, If the fan cant run normally, measure the resistance of each two pins. If the resistance is not equal to each other, the fan motor must have problems and need to be replaced, otherwise the PCB must has problems and need to be replaced.
3. Indoor AC Fan Motor Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or 50V(115V power supply), the PCB must has problems and need to be replaced.
PRODIGY Technical Manual
53
9.2.4 Refrigerant Leakage Detection diagnosis and solution(EC)
Error Code
EC
Malfunction decision conditions
Define the evaporator coil temp.T2 of the compressor just starts running as Tcool. In the beginning 8 minutes after the compressor starts up, if T2 Tcool2 does not keep continuous 4 seconds and compressor running frequency higher than 50H does not keep continuous 3 minutes, and this situation happens 3 times, the display area will show “EC” and AC will turn off.
Supposed causes
T2 sensor faulty
Indoor PCB faulty
System problems, such as leakage or blocking.
Trouble shooting:
Check cool air blowing out from indoor air outlet
Yes
Yes
Check if T2 sensor
is well fixed
No
Check leakage of system
No
Power off, then restart the
unit 2 minutes later.
Replace indoor PCB.
Yes
Repair the leakage and
recharge the refrigerant.
Yes
check blockIng of system and
clear the blocking
9.2.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5)
PRODIGY Technical Manual
54
Error Code
E4/E5/F1/F2/F3
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Supposed causes
Wiring mistake
Sensor faulty
Trouble shooting:
Check the connection between temperature
sensor and PCB.
Correct the connectionNo
Yes
Replace indoor or outdoor
main PCB
Measure the resistance
value of the sensor
Repalce the sensorNo
Yes
PRODIGY Technical Manual
55
9.2.6 Overload current protection diagnosis and solution(F0)
Error Code
F0
Malfunction decision conditions
An abnormal current rise is detected by checking the specified current detection circuit.
Supposed causes
Power supply problems.
System blockage
PCB faulty
Wiring mistake
Compressor malfunction
Check the power supply
Check the connections and wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the outdoor unit
Yes
Check the reactor
No
Replace outdoor main PCB
Check the blockage of system
Yes
No Clear the blockage
Check the compressor
resistance values
Yes
No Replace the compressor
PRODIGY Technical Manual
56
9.2.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0)
Error Code
P0
Malfunction decision conditions
When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.
Supposed causes
Wiring mistake
IPM malfunction
Outdoor fan ass’y faulty
Compressor malfunction
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of Fan
Speed Has Been Out Of Control
malfunction
Yes
Check the compressor resistance
values
No
Replace the compressor.
Yes
Replace the outdoor main PCB
PRODIGY Technical Manual
57
IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red
(-)Black
(Several MΩ)
(+)Red
(-)Black
(Several MΩ)
P
N
U N U V V W W
(+)Red
9.2.8 Over voltage or too low voltage protection diagnosis and solution(P1)
Error Code
P1
Malfunction decision conditions
An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Supposed causes
Power supply problems.
System leakage or block
PCB faulty
Trouble shooting:
Check the power supply
Check the connections and wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No
Replace the IPM board
Power on and when the unit is in standby,
check if the voltage between P and N is
around DC 310V or 340V or 380V? Then
start up the unit, measure the voltage
between P and N. Is it in 220V~400V?
Check the reactor
Yes
No
Replace outdoor main PCB
PRODIGY Technical Manual
58
9.2.9 High temperature protection of compressor top diagnosis and solution(P2)
Error Code
P2
Malfunction decision conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
Power supply problems.
System leakage or block
PCB faulty
Trouble shooting:
Check the air flow system
of indoor and outdoor units
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Power off, then restart the unit 10
minutes later
Check if the temperature
of compressor
No
Check refrigerant system
Yes
Check the overload
protector
Correct the connection.No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
PRODIGY Technical Manual
59
9.2.10 Inverter compressor drive error diagnosis and solution(P4)
Error Code
P4
Malfunction decision conditions
An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.
Supposed causes
Wiring mistake
IPM malfunction
Outdoor fan ass’y faulty
Compressor malfunction
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of Fan
Speed Has Been Out Of Control
malfunction
Yes
Check the compressor resistance
values
No Replace the compressor.
Yes
Replace the outdoor main PCB
PRODIGY Technical Manual
60
Main parts check
1. Temperature sensor checking
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.
Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor. Measure the resistance value of each winding by using the multi-meter.
PRODIGY Technical Manual
61
Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4 (°C--K)
°C
°F
K Ohm
°C
°F
K Ohm
°C
°F
K Ohm
°C
°F
K Ohm
-20
-4
115.266
20
68
12.6431
60
140
2.35774
100
212
0.62973
-19
-2
108.146
21
70
12.0561
61
142
2.27249
101
214
0.61148
-18 0 101.517
22
72
11.5
62
144
2.19073
102
216
0.59386
-17 1 96.3423
23
73
10.9731
63
145
2.11241
103
217
0.57683
-16 3 89.5865
24
75
10.4736
64
147
2.03732
104
219
0.56038
-15 5 84.219
25
77
10
65
149
1.96532
105
221
0.54448
-14 7 79.311
26
79
9.55074
66
151
1.89627
106
223
0.52912
-13 9 74.536
27
81
9.12445
67
153
1.83003
107
225
0.51426
-12
10
70.1698
28
82
8.71983
68
154
1.76647
108
226
0.49989
-11
12
66.0898
29
84
8.33566
69
156
1.70547
109
228
0.486
-10
14
62.2756
30
86
7.97078
70
158
1.64691
110
230
0.47256
-9
16
58.7079
31
88
7.62411
71
160
1.59068
111
232
0.45957
-8
18
56.3694
32
90
7.29464
72
162
1.53668
112
234
0.44699
-7
19
52.2438
33
91
6.98142
73
163
1.48481
113
235
0.43482
-6
21
49.3161
34
93
6.68355
74
165
1.43498
114
237
0.42304
-5
23
46.5725
35
95
6.40021
75
167
1.38703
115
239
0.41164
-4
25
44
36
97
6.13059
76
169
1.34105
116
241
0.4006
-3
27
41.5878
37
99
5.87359
77
171
1.29078
117
243
0.38991
-2
28
39.8239
38
100
5.62961
78
172
1.25423
118
244
0.37956
-1
30
37.1988
39
102
5.39689
79
174
1.2133
119
246
0.36954
0
32
35.2024
40
104
5.17519
80
176
1.17393
120
248
0.35982
1
34
33.3269
41
106
4.96392
81
178
1.13604
121
250
0.35042
2
36
31.5635
42
108
4.76253
82
180
1.09958
122
252
0.3413
3
37
29.9058
43
109
4.5705
83
181
1.06448
123
253
0.33246
4
39
28.3459
44
111
4.38736
84
183
1.03069
124
255
0.3239
5
41
26.8778
45
113
4.21263
85
185
0.99815
125
257
0.31559
6
43
25.4954
46
115
4.04589
86
187
0.96681
126
259
0.30754
7
45
24.1932
47
117
3.88673
87
189
0.93662
127
261
0.29974
8
46
22.5662
48
118
3.73476
88
190
0.90753
128
262
0.29216
9
48
21.8094
49
120
3.58962
89
192
0.8795
129
264
0.28482
10
50
20.7184
50
122
3.45097
90
194
0.85248
130
266
0.2777
11
52
19.6891
51
124
3.31847
91
196
0.82643
131
268
0.27078
12
54
18.7177
52
126
3.19183
92
198
0.80132
132
270
0.26408
13
55
17.8005
53
127
3.07075
93
199
0.77709
133
271
0.25757
14
57
16.9341
54
129
2.95896
94
201
0.75373
134
273
0.25125
15
59
16.1156
55
131
2.84421
95
203
0.73119
135
275
0.24512
16
61
15.3418
56
133
2.73823
96
205
0.70944
136
277
0.23916
17
63
14.6181
57
135
2.63682
97
207
0.68844
137
279
0.23338
18
64
13.918
58
136
2.53973
98
208
0.66818
138
280
0.22776
19
66
13.2631
59
138
2.44677
99
210
0.64862
139
282
0.22231
PRODIGY Technical Manual
62
Appendix 2 Temperature Sensor Resistance Value Table for T5 (°C --K)
°C
°F
K Ohm
°C
°F
K Ohm
°C
°F
K Ohm
°C
°F
K Ohm
-20
-4
542.7
20
68
68.66
60
140
13.59
100
212
3.702
-19
-2
511.9
21
70
65.62
61
142
13.11
101
214
3.595
-18
0
483
22
72
62.73
62
144
12.65
102
216
3.492
-17
1
455.9
23
73
59.98
63
145
12.21
103
217
3.392
-16
3
430.5
24
75
57.37
64
147
11.79
104
219
3.296
-15
5
406.7
25
77
54.89
65
149
11.38
105
221
3.203
-14
7
384.3
26
79
52.53
66
151
10.99
106
223
3.113
-13
9
363.3
27
81
50.28
67
153
10.61
107
225
3.025
-12
10
343.6
28
82
48.14
68
154
10.25
108
226
2.941
-11
12
325.1
29
84
46.11
69
156
9.902
109
228
2.86
-10
14
307.7
30
86
44.17
70
158
9.569
110
230
2.781
-9
16
291.3
31
88
42.33
71
160
9.248
111
232
2.704
-8
18
275.9
32
90
40.57
72
162
8.94
112
234
2.63
-7
19
261.4
33
91
38.89
73
163
8.643
113
235
2.559
-6
21
247.8
34
93
37.3
74
165
8.358
114
237
2.489
-5
23
234.9
35
95
35.78
75
167
8.084
115
239
2.422
-4
25
222.8
36
97
34.32
76
169
7.82
116
241
2.357
-3
27
211.4
37
99
32.94
77
171
7.566
117
243
2.294
-2
28
200.7
38
100
31.62
78
172
7.321
118
244
2.233
-1
30
190.5
39
102
30.36
79
174
7.086
119
246
2.174
0
32
180.9
40
104
29.15
80
176
6.859
120
248
2.117
1
34
171.9
41
106
28
81
178
6.641
121
250
2.061
2
36
163.3
42
108
26.9
82
180
6.43
122
252
2.007
3
37
155.2
43
109
25.86
83
181
6.228
123
253
1.955
4
39
147.6
44
111
24.85
84
183
6.033
124
255
1.905
5
41
140.4
45
113
23.89
85
185
5.844
125
257
1.856
6
43
133.5
46
115
22.89
86
187
5.663
126
259
1.808
7
45
127.1
47
117
22.1
87
189
5.488
127
261
1.762
8
46
121
48
118
21.26
88
190
5.32
128
262
1.717
9
48
115.2
49
120
20.46
89
192
5.157
129
264
1.674
10
50
109.8
50
122
19.69
90
194
5
130
266
1.632
11
52
104.6
51
124
18.96
91
196
4.849
12
54
99.69
52
126
18.26
92
198
4.703
13
55
95.05
53
127
17.58
93
199
4.562
14
57
90.66
54
129
16.94
94
201
4.426
15
59
86.49
55
131
16.32
95
203
4.294
16
61
82.54
56
133
15.73
96
205
4.167
17
63
78.79
57
135
15.16
97
207
4.045
18
64
75.24
58
136
14.62
98
208
3.927
19
66
71.86
59
138
14.09
99
210
3.812
PRODIGY Technical Manual
63
2.Compressor checking
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
ASN98D22UFZ
ASM135D23UFZ
ATF235D22UMT
Blue - Red
1.57Ω
(20/68)
1.75Ω
(20/68)
0.75Ω
(20/68)
Blue - Black
Red - Blue
Loading...