Katronic Technologies KATflow 230 Operating Instructions Manual

Operating Instructions
Portable
Ultrasonic Flowmeter
KA
Tflow 230
Katronic Technologies Ltd.
Leamington Spa
Warwickshire CV32 4PX
United Kingdom
Tel. +44 (0)1926 882954 Fax +44 (0)1926 338649
Internet www.katronic.co.uk E-mail mail@katronic.co.uk
Operating Instructions KATflow 230
Version V09E1108
Copyright © 2008
All rights reserved.
KATflow 230 Table of Content
KATflow 230 Operating Instructions
Table of Content
Page
1 Safety instructions, legal requirements, warranty, return policy..................7
1.1 Symbols used in these operating instructions...............................................7
1.2 Safety instructions.........................................................................................7
1.3 Warranty........................................................................................................8
1.4 Return policy.................................................................................................8
1.5 Legislative requirements...............................................................................8
2 Introduction........................................................................................................9
3 Installation..........................................................................................................10
3.1 Unpacking and storage.................................................................................10
3.1.1 Unpacking..............................................................................................10
3.1.2 Storage and preservation.......................................................................10
3.1.3 Identification of components..................................................................10
3.2 Clamp-on sensor installation.........................................................................11
3.3 Installation location........................................................................................11
3.4 Pipe preparation............................................................................................13
3.5 Clamp-on sensor mounting configurations and separation distance............14
3.6 Flowmeter installation...................................................................................15
3.6.1 Outline dimensions.................................................................................15
3.6.2 Electrical interconnections.....................................................................17
3.7 Clamp-on sensor mounting...........................................................................17
3.7.1 Sensor pipe mounting configurations.....................................................17
3.7.2 Acoustic coupling gel.............................................................................18
3.7.3 Correct positioning of the sensors.........................................................19
3.7.4 Sensor mounting with fixtures and chains.............................................19
4 Operation............................................................................................................21
4.1 Switching On/Off...........................................................................................21
4.2 Battery charging............................................................................................21
4.3 Keypad and display.......................................................................................22
4.3.1 Keypad key functions.............................................................................22
4.3.2 Display functions....................................................................................24
4.4 Quick setup wizard........................................................................................25
4.5 Measurements..............................................................................................27
4.5.1 Main process value (PV) display............................................................27
4.5.2 3-line display..........................................................................................27
4.5.3 Diagnostic displays................................................................................27
4.5.4 Totalisers................................................................................................28
5 Commissioning..................................................................................................29
5.1 Menu structure..............................................................................................29
5.2 Diagnostics....................................................................................................34
5.3 Display settings.............................................................................................34
5.3.1 Main PV..................................................................................................34
5.3.2 Line 1......................................................................................................34
5.4 Output configurations....................................................................................34
5.4.1 Serial interface RS 232..........................................................................35
3
KATflow 230 Table of Content
5.4.2 Analogue current output 0/4 ... 20 mA...................................................35
5.4.3 Digital Open-Collector output.................................................................35
5.4.4 Digital relay output.................................................................................35
5.5 Input configurations.......................................................................................36
5.5.1 PT100 inputs..........................................................................................36
5.6 Heat quantity measurement (HQM)..............................................................36
5.7 Sound velocity measurement (SVM)............................................................36
5.8 Dual-channel flow calculations (maths functions).........................................36
5.9 KATdata+ software.......................................................................................36
5.10 Wall thickness measurement (WTM).........................................................36
6 Maintenance.......................................................................................................36
7 Troubleshooting.................................................................................................37
8 Technical data....................................................................................................39
9 Specification.......................................................................................................45
4
KATflow 230 1 Safety instructions, legal requirements, warranty, return policy
1 Safety instructions, legal requirements, war­ranty, return policy
1.1 Symbols used in these operating instructions
Danger
This symbol represents an immediate hazardous situation which could result in a serious injury, death or damage to the equipment. Where this symbol is shown, do not use the equipment further unless you have fully understood the nature of the hazard and have taken the required precautions.
Attention
This symbol indicates important instructions which should be respected in order to avoid damage or destroy the equipment. Follow the the precautions given in these instructions to avoid the hazard. Call our service team if necessary.
Call service
Where this symbol is shown call our service team for advise if necessary.
Note
This symbol indicates a note or detailed set-up tip.
This symbol represents enumeration.
Operator keys are printed in bold typeface and placed in pointed brackets.
1.2 Safety instructions
Do not install, operate or maintain this flowmeter without reading, under-
standing and following these operating instructions, otherwise injury or damage may result.
Study these operating instructions carefully before the installation of the
equipment and save them for future reference.
Observe all warnings, notes and instructions as marked on the packaging,
on the equipment and those detailed in the operating instructions.
Do not use the instrument with removed or opened battery cover under wet
conditions.
Consider the unpacking, storage and preservation instructions to avoid
damage to the equipment.
Install the equipment and cabling securely and safely according to the re-
spective regulations in place.
If the product does not operate normally, please refer to the service and
trouble shooting instructions or contact KATRONIC for help.
5
!
<BRK>
!
KATflow 230 1 Safety instructions, legal requirements, warranty, return policy
1.3 Warranty
Any product purchased from KATRONIC is warranted in accordance with
the relevant product documentation and as specified in the sales contract provided it has been used for the purpose for which it has been designed for and operated as outlined in these operating instructions. Misuse of the equipment will immediately revoke any warranty given or implied.
Responsibility for suitability and intended use of this ultrasonic flowmeter
rests solely with the user. Improper installation and operation of the flow­meter may lead to a loss of warranty.
Please note that there are no operator-serviceable parts inside the equip-
ment. Any unauthorised interference with the product will invalidate the warranty.
1.4 Return policy
If the flowmeter has been diagnosed to be faulty, it can be returned to KATRONIC for repair using the Customer Returns Note (CRN) attached to the Appendix of this manual. KATRONIC regret that we cannot accept the return of the equipment un­less accompanied by the completed CRN for Health & Safety reasons.
1.5 Legislative requirements
The flowmeter is designed to meet the safety requirements in accordance with sound engineering practise. It has been tested and left the factory in a condition in which it is safe to operate. The equipment is in conformity with the statutory re­quirements of the EC directive and comply with applicable regulations and stand­ards for electrical safety EN 61010 and electro-magnetic compatibility EN 61326. A CE Declaration of Conformity is issued in that respect, a copy of which can be found in the Appendix of these operating instructions.
The Waste Electrical and Electronic Equipment Directive (WEEE Directive) aims to minimise the impact of electrical and electronic goods on the environment, by in­creasing re-use and recycling and reducing the amount of WEEE going to landfill. It seeks to achieve this by making producers responsible for financing the collection, treatment, and recovery of waste electrical equipment, and by obliging distributors to allow consumers to return their waste equipment free of charge.
KATRONIC offers its customers the possibility of returning unused and obsolete equipment for correct disposal and recycling. The Dustbin Symbol indicates that when the last user wishes to discard this product, it must be sent to appropriate fa­cilities for recovery and recycling. By not discarding this product along with other household-type waste, the volume of waste sent to incinerators or landfills will be reduced and natural resources will be conserved. Please use the Customer Return Note (CRN) in the Appendix for the return to KATRONIC.
The European Union’s RoHS (“Restriction of the use of certain Hazardous Sub­stances”) Directive (2002/95/EC) goes into effect on July 1, 2006. All of the instru­mentation manufactured by KATRONIC falls under Category 9, Measurement and Control Equipment. Currently this category is exempt from RoHS compliance until at least 2010, when it andother exemptions will be reviewed. Regardless of this, all products manufactured by KATRONIC are compliant with the RoHS Directive.
6
CE marking
WEEE Directive
RoHS Directive
KATflow 230 2 Introduction
2 Introduction
The KATflow 230 is a portable, battery operated ultrasonic flowmeter utilising clamp-on sensors for the measurement of liquids in full closed pipes. Flow meas­urements can be undertaken without interrupting of the process or interfering with the integrity of the pipeline. The clamp-on sensors are simply attached to the out­side of pipes. The KATflow 230 uses ultrasonic signals for the measurement of the flow, employing the so-called transit-time method.
Ultrasonic signals are emitted by a first transducer installed on one side of a pipe, reflected on the opposite side and received by a second transducer. These signals are emitted alternatively in the direction of flow and against it. Because the medium in which the signals propagate is flowing, the transit time of the sound signals propagating in the direction of flow is shorter than the transit time of the signal propagating against the direction of flow. The transit-time difference T is meas­ured and allows the determination of the average flow velocity along the path of acoustic propagation. A profile correction is then performed to obtain the average flow velocity over the cross-sectional area of the pipe, which is proportional to the volumetric flow rate.
7
Illustration 1: Clamp-on ultrasonic flowmeter configuration
Clamp-on transit­time flowmeter
Measuring principle
Illustration 2: Transit-time measuring principle
KATflow 230 3 Installation
3 Installation
3.1 Unpacking and storage
3.1.1 Unpacking
Care should be taken when opening the box containing the flowmeter, any mark­ings or warnings shown on the parcel should be observed prior to opening. The fol­lowing steps should then be taken:
Unpack the flowmeter in a dry area.
The flowmeter should be handled with care and not left in an area where it
could be subject to physical shocks.
If using a knife to remove packaging care should be taken not to damage
the flowmeter or cables.
The flowmeter package and contents should be checked for completeness
against the delivery note supplied and any missing items reported immedi­ately.
The flowmeter package and contents should be checked for signs of dam-
age during transport and any problems reported immediately.
The vendor accepts no responsibility for damage or injury caused during
the unpacking of the instrumentation supplied.
Excess packing materials should be either re-cycled or disposed of in a
suitable way.
3.1.2 Storage and preservation
If storage or preservation is necessary, the flowmeter and sensors should be stored:
in a secure location,
away from water and harsh environmental conditions,
in a way as to avoid damage,
small items should be kept together in the bags and small plastic boxes
provided to avoid loss.
3.1.3 Identification of components
The following items are typically supplied (please refer to your delivery note for a detailed description of your scope of supply):
KATflow 230 portable flowmeter
Clamp-on sensors (usually one or two pairs depending on pipe sizes to be
measured)
Sensor extension cable(s) (optional)
Sensor mounting accessories
Coupling component
Measuring tape
Operating instructions
Calibration certificate(s) (optional)
8
KATflow 230 3 Installation
3.2 Clamp-on sensor installation
The correct selection of the sensor location is crucial for achieving reliable meas­urements and a high accuracy. Measurement must take place on a pipe in which sound can propagate (see Acoustic Propagation) and in which a rotationally sym­metrical flow profile is fully developed (see Straight Pipe Lengths).
The correct positioning of the transducers is an essential condition for error-free measurements. It guarantees that the sound signal will be received under optimal conditions and evaluated correctly. Because of the variety of applications and the different factors influencing the measurement, there can be no standard solution for the positioning of the transducers.
The correct position of the transducers will be influenced by the following factors:
diameter, material, lining, wall thickness and general condition of the pipe,
the medium flowing in the pipe,
and the presence of gas bubbles and solid particles in the medium.
Check that the temperature at the selected location is within the operating temper­ature range of the transducers (see technical specification in the Appendix).
Acoustic propagation is given when the flowmeter is able to receive sufficient signal from the transmitted ultrasonic pulses. The signals are attenuated in the pipe ma­terial, the medium and at each of the interfaces and reflections. External and in­ternal pipe corrosion, solid particles and gas content in the medium do heavily con­tribute to signal attenuation.
Sufficient straight lengths of pipe on the inlet and outlet of the measuring location guarantee an axi-symmetrical flow profile in the pipe for good measurement accur­acy. If no sufficient straight lengths of pipe are available for your application, meas­urements are still obtainable but the uncertainty of the measurement can be com­promised.
3.3 Installation location
Select an installation location as per recommendations in Table 1 and try to avoid measuring
in the vicinity of deformations and defects of the pipe,
near welding seams,
where deposits could be building up in the pipe.
For a horizontal pipe:
Select a location where the transducers can be mounted on the side of the pipe, so that the sound waves emitted by the transducers propagate horizontally in the pipe. Thus, the solid particles deposited on the bottom of the pipe and the gas pockets developing at the top will not influence the propagation of the signal.
Correct Incorrect
For a free inlet or outlet pipe section:
Select the measuring point at a location where the pipe cannot run empty.
Correct Disadvantageous
9
Acoustic propagation
Straight pipe lengths
KATflow 230 3 Installation
Correct Disadvantageous
For a vertical pipe:
Select the measuring point at a location where the liquid flows upward to insure that the pipe is completely filled.
Correct Incorrect
Look for a sensor installation location with sufficient straight pipe to obtain accurate measurements. Please refer to Table 2 as a guideline for recommended distances to disturbance sources.
Disturbance source: 90°-elbow
Inlet Outlet L 10 D L 5 D
Disturbance source: 2 x 90°-elbows in one plane
Inlet Outlet L 25 D L 5 D
Disturbance source: 2 x 90°-elbows in different pla nes
Inlet Outlet L 40 D L 5 D
10
Table 1: Recommendations for sensor mounting location
KATflow 230 3 Installation
Disturbance source: T-section
Inlet Outlet L 50 D L 10 D
Disturbance source: diffuser
Inlet Outlet L 30 D L 5 D
Disturbance source: reducer
Inlet Outlet L 10 D L 5 D
Disturbance source: valve
Inlet Outlet L 40 D L 10 D
Disturbance source: pump
Inlet L 50 D
3.4 Pipe preparation
Clean the pipework from dirt and dust around the area where the sensors
shall be placed.
Remove loose paint and rust with a wire brush or file.
Firmly bonded paint does not necessarily need to be removed down to bare metal provided the flowmeter diagnostics indicate sufficient signal level strength.
11
Table 2: Recommended dis-
tances from disturbance
sources
KATflow 230 3 Installation
3.5 Clamp-on sensor mounting configurations and separation distance
The most common clamp-on sensor mounting configuration is the Reflection Mode, also known as V-Mode (see Illustration 3, sketch (1). Here the ultrasonic signal pass twice through the medium (2 signal passes). The Reflection Mode is the most convenient mounting method as the transducer separation distance can be meas­ured easily and the sensors can be perfectly aligned. This method should be used whenever possible.
An alternative mounting configuration (Illustration 3, sketch (3)) is the Diagonal mode (Z-Mode). The signals travel here only once through the pipe. This method is often used especially for larger pipes where greater signal attenuation might oc­cur.
Further variation of the Reflection and the Diagonal Mode are possible by altering the number of passes through the pipe. Any even number of passes would require to mount the sensors on the same side of the pipe, whereas with any odd number of passes, the sensors must be mounted on opposite sides of the pipe. Commonly for very small pipes, sensor mounting configurations such as 4 passes (W-mode) or 3 passes (N-mode) are used (Illustration 3, sketch (2)).
The transducer separation distance A is measured from the edges of the sensor heads facing each other as shown in illustration 3. It is automatically calculated by the flowmeter based on the parameter entries for pipe outside diameter, wall thick­ness, lining material and thickness, medium, process temperature, the sensor type and the selected number of signal passes.
A negative separation distance A < 0 can occur for mounting configurations on small pipes where diagonal mode operation has been selected (see Illustration 3, sketch (3).
12
Illustration 3: Clamp-on sensor mounting configurations and separation distances
Reflection Mode
Diagonal Mode
Transducer separa­tion distance
KATflow 230 3 Installation
3.6 Flowmeter installation
3.6.1 Outline dimensions
The KATflow 230 is a portable, battery operated device with the following outline di­mensions.
13
272
266
222
15
5
7
13
37
32
168
ShockProtectors
080610_1
Process I/O connector
Drawing 1: Outline dimensions KATflow 230
Flowmeter outline di­mensions
KATflow 230 3 Installation
14
Drawing 2: Transducers
K1 type transducer
1500
2500
080609_1
1000
1500
080609_1
K4 type transducer
KATflow 230 3 Installation
3.6.2 Electrical interconnections
3.7 Clamp-on sensor mounting
Before the sensors can be mounted
the installation location should have been determined,
a sensor mounting method should be chosen,
the flowmeter batteries must be sufficiently charged,
the sensors must be connected to the transmitter.
Depending on which sensor mounting method is being used (V or Z-mode), the clamp on sensors are either mounted on the same side of the pipe (Reflection Mode) or on opposite sides of the pipe (Diagonal Mode).
3.7.1 Sensor pipe mounting configurations
15
Drawing 3: Electrical interconnections overview KATflow 230
081121_1
Bottomconnections
Flowchannel2
Flowchannel1
Batterycharger
T
emperature
sensorPt1001
Temperature sensorPt1002
RS232serial interface
Input/output systemconnector
Topconnections
KATflow 230 3 Installation
3.7.2 Acoustic coupling gel
In order to obtain acoustical contact between the pipe and the sensors, apply a bead of acoustic coupling gel lengthwise down the centre of the contact area of the sensors.
16
Illustration 4: Sensor pipe mounting configurations
Illustration 5: Application of acoustic coupling gel
AAA<0
A= Transducer distance
Reflection mode
Diagonal mode
080114_1
100_080114_1
KATflow 230 3 Installation
3.7.3 Correct positioning of the sensors
Always mount the transducer pair such that the free front edges of the sensors face each other.
There is a different engraving on the top of each transducer. The transducers are mounted correctly if the engravings on the two transducers are forming an arrow to­gether. The transducer cables should then show in opposite directions.
Later, the arrow, in conjunction with the indicated measured value, will help to de­termine the direction of flow.
The sensor separation distance is automatically calculated by the flowmeter based on the parameter entries for pipe outside diameter, wall thickness, lining material and thickness, medium, process temperature, the sensor type and the selected number of signal passes.
3.7.4 Sensor mounting with fixtures and chains
Insert the retaining clip into the groove on the top of the transducer and se-
cure it using the screw knob.
Apply some acoustic coupling component to the contact surface of the
transducer.
Place the transducer to the side of the pipe or alternatively 45 degrees from
the pipe axis. This is necessary to establish the best acoustic contact since on top of the
pipe air pockets could develop and deposits could accumulate at the bot­tom of the pipe.
17
Drawing 4: Sensors mounted with fixtures and chains
Illustration 6: Correct positioning of the sensors
080123_1
080114_1
KATflow 230 3 Installation
Take the spring end of the chain in one hand and insert the last ball ele-
ment in the vertical slot of the retaining clip. Mount the chain around the pipe.
Pull the chain firmly around the pipe and fasten it in the lateral slot of the
retaining clip. There should be no air pockets between the transducer sur­face and the pipe wall.
Mount the second transducer the same way.
Using a measuring tape, adjust the sensor separation distance as sugges-
ted by the flowmeter.
18
Illustration 7: Sensor mounting with fixtures and chains (retaining clip)
080123_1
KATflow 230 4 Operation
4 Operation
4.1 Switching On/Off
The flowmeter is switched on by the <ON> key for more than 2 seconds continu­ously. Equally it can be switched off by pressing the <OFF> key for more than 2 seconds.
4.2 Battery charging
The internal batteries can be recharged with the supplied external battery charger. Simply connect the battery charger to the charging socket of the flowmeter and to the mains supply 100 ... 240 V AC, 50/60 Hz. The battery charger mains plug is supplied country specific as per order code.
During the charging process, the battery icon is blinking. For a fully charged battery all segments of the battery icon are filled.
19
Illustration 8: Battery charging
KATflow 230 4 Operation
4.3 Keypad and display
4.3.1 Keypad key functions
Key Main function Secondary function
Alphanumerical entry:
1 (1 short key stroke) , (2 short key strokes) . (3 short key strokes)
_ (4 short key strokes)
Show NEXT available item
Alphanumerical entry:
A B C 2
/
QON = Start totaliser function
Alphanumerical entry:
D E F 3 ?
Show next DISPlay
Alphanumerical entry:
G H
I
4
Q
-
= Show negative total value
20
Illustration 9: Keypad and display overview
KATflow 230 4 Operation
<
Alphanumerical entry:
J K L 5 >
Alphanumerical entry:
M N O 6 $
Q
+
= Show positive total value
Alphanumerical entry:
P Q R S 7
Toggle MUltipleXer (for multi-chan­nel functionalities)
Alphanumerical entry:
T U V 8
*
Q
OFF
= Stop totaliser function
Alphanumerical entry:
W
X Y Z 9
DIRECT menu access
Move menu/list selection itemUPAlphanumerical entry:
Character backspace clear
Numerical entry only:
.
(decimal point)
Switch LCD backlight on/off
Alphanumerical entry:
0
Space character
+ = #
Move menu/list selection item
DOWN
Numerical entry only:
- (minus sign)
ESCape menu item
Abort entry without saving Switches the instrument OFF if
pressed for more than 2 s
ENTER menu item
Confirm entry with saving Switches the instrument ON if
pressed for more than 2 s
21
KATflow 230 4 Operation
4.3.2 Display functions
Display icon Function
On Icon not used Off
On Datalogger recording Off Datalogger switched off
On 1 segment = 33% battery power available
2 segments = 66% battery power available 3 segments = 100% battery power available
Off < 5% battery power available Outline blinking Battery charging
On LCD backlight switched on Off LCD backlight switched off
On Signal strength sufficient for measurement Off Signal strength insufficient for measurement
On Without strike-through: Speaker on Off With strike-through: Speaker off
On Poor sensor coupling, low SNR Off Sensor coupling OK
On Icon not used Off
On Icon not used Off
22
Display icons Menu header
Display line 1
Display line 2
Date, time (optional)
Illustration 10: Main display functions
KATflow 230 4 Operation
On RTC operating Off RTC failure
On Error recorded in error log Off No error detected
On Serial output RS 232 switched on Off Serial output RS 232 switched off
4.4 Quick setup wizard
The quick setup wizard allows for a speedy setup of the most important parameters in order to achieve successful measurements in the shortest possible time:
Display screen Operation
Upon first power on and the boot-up sequence, the main menu is displayed.
Use <UP> and <DOWN> cursor keys to select Quick start. Confirm by pressing <ENTER>.
Use cursor keys to select Setup Wizard. Con­firm by pressing <ENTER>.
Choose pipe material using cursor keys and pressing <ENTER>.
Enter outside pipe diameter using alphanumer­ical keys and confirm by pressing <ENTER>.
Use key <UP> as character backspace clear to correct for data entry errors.
Enter pipe wall thickness using alphanumerical keys and confirm by pressing <ENTER>.
Use key <UP> as character backspace clear to correct for data entry errors.
23
KATflow 230 4 Operation
Select fluid using cursor keys. Confirm by pressing <ENTER>.
Enter process temperature using alphanumer­ical keys and confirm by pressing <ENTER>.
Use key <UP> as character backspace clear to correct for data entry errors.
Select pipe lining material using cursor keys. Confirm by pressing <ENTER>.
Select transducer configuration (number of passes) using cursor keys.
Auto Automatically Z Z-mode (1 pass), diagonal mode V V-mode (2 passes), reflection mode N N-mode (3 passes), diagonal mode W W-mode (4 passes), reflection mode 5 5 passes, diagonal mode 6 6 passes, reflection mode
Confirm by pressing <ENTER>. Sensor placement screen: Mount transducers
with suggested spacing. Observe signal strength.
Confirm by pressing <ENTER> to obtain measurements.
Success!
24
KATflow 230 4 Operation
4.5 Measurements
4.5.1 Main process value (PV) display
The measurements are started either through the Quick Setup Wizard or the menu structure by selecting Start Measurement upon first power on. Once all the para­meters are programmed, any subsequent power-on sequences will bring up the main PV display immediately.
Display screen Operation
The main process value can be changed by accessing the menu structure.
Press <ESC> at any time to access the main menu.
Change to the 3-line display by pressing
<DISP>.
4.5.2 3-line display
Display screen Operation
Line 1 shows the Tag ID but is universally configurable through the installation menu.
Line 2 displays the main PV. Line 3 displays the flow velocity. Change to diagnostic displays by pressing
<DISP>.
4.5.3 Diagnostic displays
Display screen Operation
Line 1 shows the amplifier gain. Line 2 displays the signal strength. Line 3 indicates the correlation value. Change to more diagnostic displays by
pressing <NEXT>.
25
KATflow 230 4 Operation
4.5.4 Totalisers
The totaliser displays will only be shown when the totalisers are activated.
Display screen Operation
The flow totaliser can be started by press­ing <QON>.
Pressing <Q+> shows the total accumu­lated flow in positive flow direction.
Pressing <Q-> shows the total accumu­lated flow in negative flow direction.
The totalisers can be stopped by activating
<Q
OFF
>.
Change to other measurement displays by pressing <NEXT>.
26
KATflow 230 5 Commissioning
5 Commissioning
5.1 Menu structure
Main menu Menu level 1 Menu level 2 Description/settings
Quick Start
Setup Wizard Single
Units
Select from list ↑↓
m/s f/s in/s m3/h m3/min m3/s l/h l/min l/s USgall/h USgall/min USgall/s bbl/d bbl/h bbl/min g/s t/h kg/h kg/min
Pipe material
Select from list ↑↓
Stainless steel Carbon steel Ductile cast iron Grey cast iron Copper Lead PVC PP PE ABS Glass Cement User (pipe c-speed)
Pipe c-speed
O
nly if user pipe material selected
600 ... 6553.5 m/s
Outside dia­meter
6 ... 6500 mm
Wall thickness 0.5 ... 75 mm Fluid
Select from list ↑↓
Water Salt water Acetone Alcohol Ammonia Carbon Tet Ethanol Ethyl alcohol Ethyl ether Ethylene glycol Glycol/water 50% Kerosene Methanol Methyl alcohol Milk Naphtha Car oil Freon R134a Freon R22
27
KATflow 230 5 Commissioning
Hydrochloric acid Sour cream Sulphuric acid Toluene Vinyl chloride User (kinematic viscosity, density, medium c­speed)
Kinematic vis­cosity
Only if user fluid selected
0.001 ... 30000 mm2/s
Density
Only if user fluid selected
100 ... 2000 kg/m
3
Medium c­speed
Only if user fluid selected
800 ... 3500 m/s
Temperature -30 ... 300 °C L
iner Material Select from list ↑↓
None
Epoxy
Rubber
PVDF
PP
Glass
User (liner c-speed)
Liner c-speed
Only if lining material selected
600 ... 6553.0 m/s Liner thickness Only if lining material selected
1.0 ... 99.0 mm
Passes
Select from list ↑↓
Auto
1
2
3
4
5
6
etc. Sensor type
Indication of sensor type and serial number if
automatically detected, otherwise
select from list ↑↓
K1
K4
M
Q
Special
Sensor fre­q
uency
SP1, only for special, unrecognised sensors
Wedge angle SP2, only for special, unrecognised sensors Wedge c-
speed 1
SP3, only for special, unrecognised sensors
Wedge c­speed 2
SP4, only for special, unrecognised sensors
Crystal offset SP5, only for special, unrecognised sensors Spacing offset
SP6, only for special, unrecognised sensors
Zero flow offset
SP7, only for special, unrecognised sensors
Upstream off­set
SP8, only for special, unrecognised sensors
Sensor place­ment
Setup Wizard Dual
As per setup wizard single for channel 1
Repeat for channel 2
Start Measure-
28
KATflow 230 5 Commissioning
ment
Sensor type
Indication of sensor type and serial number if
automatically detected, otherwise
select from list ↑↓
K1
K4
M
Q
Special
SP 1 ... SP 8
Only for special, unrecognised sensors
Sensor place­ment
Installation
Pipe
Material Select from pipe material list ↑↓ Outside dia-
meter
6 ... 6500 mm
Wall thickness 0.5 ... 75 mm Pipe c-speed 600 ... 6553.5 m/s Pipe circumfer-
ence
18.8 ... 20420.4 mm
Roughness 0.0 ... 10 mm
Medium
Fluid Select from fluid list ↑↓ Kinematic vis-
cosity
0.001 ... 30000 mm
2
/s
Density 100 ... 2000 kg/m
3
C-speed 800 ... 3500 m/s Temperature -30 ... 300 °C
Lining
Material
Select from material list ↑↓
Thickness 1 ... 99 mm C-speed 600 ... 6553.0 m/s
Passes
Passes
Select from list ↑↓
Output
Display
Units
Select from unit list ↑↓
Damping
Smooths the display output, the higher the damp-
ing factor
1 ... 255 s
Current
Mode
Yes – Current output on
No – Current output off Min Value
Min. process variable (PV) value that corres-
ponds to 0/4 mA
Max Value
Max. process variable (PV) value that corres-
ponds to 20 mA
Damping
Additional smoothing of the current output, the
higher the damping factor
1 ... 255 s
Open Collect­or
Mode
Yes – Pulse output on
29
KATflow 230 5 Commissioning
No – Pulse output off Pulse Value
Totaliser value of selected PV at which a pulse is
generated, e.g. PV = [m3/h], Pulse Value = 10, a
pulse is output every 10 m3
0.01 ... 1000
Pulse Width
Width of the pulse
30 ... 999 ms Calc. Max
This is the calculated max. number of pulses per
second., i.e. the max. pulse rate in Hz
Relay
Mode Off – Permanently off
On – Permanently energised
Alarm – PV alarm switch
Fault – Allocated to system failures, see error re-
port list
On Point
Value of PV at which the relay energises when in
alarm m ode
Off Point
Value of PV at which the relay de-energises when
in alarm m ode
Input
Temperature
Source
Fixed – A fixed temperature can be entered under
value
PT100 – Value read from PT100 temperature
sensor in ºC
Value
Enter fixed user defined value
0 ... 250 ºC
System
Instrument info
Model Code 230 Serial No.
Example: 23000003 HW Revision
Example: 1.0, 1.0 SW Revision
Example: 1.0, 1.0
Calculation
Low F Cut
± Low flow velocity cut off
0 ... 0.25 m/s Max F Cut
± Maximum flow velocity cut off
0 ... 30 m/s Corrected
Apply flow velocity profile correction
Yes
No PV Offset
Calibration process variable zero offset
-30 ... 30 units
PV Scaling
Calibration process variable gradient scaling
0 ... 10000 units
Zero Cal
Zero calibration settings
Zero P
erform auto zero calibration
Yes
No Track
Track zero offset
Yes
No Delta
Zero flow delta time offset in ns, read from sensor
PROM or entered directly for special sensors
Timeup
Upstream transit-time offset in µs, allows for fixed
delays in special sensors, buffer rods and exten-
sion leads
30
KATflow 230 5 Commissioning
User
Identifier
Example: Pump P3A
9 alphanumeric character string
Tag No.
Example: 1FT-3011
9 alphanumeric character string
Test
Test Mode
Control system simulation: 60 second ramping up
of flow velocity in m/s from 0 to programmed Max
F Cut and subsequent 60 second ramping down,
i.e. the process variable would change over com-
plete possible range. All configured outputs will
exhibit their programmed behaviour.
Yes
No
Settings
Date Example: 03/10/07 Time
Example: 09:27:00 Date Format
Select from list ↑↓
dd/mm/yy
mm/dd/yy
yy/mm/dd Language
Select from list ↑↓
English
German
French
Spanish
R
ussian
Keypad
Enable keypad sound
Yes
No
Defaults
Reload factory default settings, except for date
and time
Yes
No
Diagnostics
Temperature
Shows control unit temperature
Log Memory
Percentage of unused datalogger memory re-
maining
Datalogger
Interval
A value of zero turns the datalogger off, a non-
zero value turns the datalogger on and defines
the logging interval. Going from a value of zero to
a non-zero value, clears the log memory.
0 ... 999 s Overwrite
When the log memory is full, i.e. 0 % remaining,
the logger wraps around and starts to overwrite
memory.
Yes
No Low Memory
Warning output: The amount of memory remain-
ing at which the flowmeter begins to give an aud-
ible warning.
0 ... 100 % Log Download
Sends logger content to selected serial commu-
nication port.
Serial Comm
Mode
Select from list ↑↓
None
Printer
Diagnostic
Log download Baud
Select from list ↑↓
31
KATflow 230 5 Commissioning
2400
9600 (Default)
19200 Parity
Select from list ↑↓
None
Even (Default)
Odd Type
Select from list ↑↓
None
RS232
5.2 Diagnostics
Diagnostic screens can be accessed directly during measurement or through the menu structure.
5.3 Display settings
Customer specific settings for data to be displayed can be achieved by accessing the appropriate menu items.
5.3.1 Main PV
The main Process Value (PV) is the primary measurement data.
5.3.2 Line 1
Display line 1 can be programmed by a list of available items.
5.4 Output configurations
There are 2 output connectors at the bottom of the KF230 enclosure. One is for serial communication through a standard 9-pin D-type RS 232 connector, process outputs (analogue and digital outputs) are available using a system I/O connector which must be connected via an I/O interface cable to a breakout terminal junction box.
32
Illustration 11: Process output breakout box
KATflow 230 5 Commissioning
5.4.1 Serial interface RS 232
The RS 232 serial interface can be used to transmit data on-line or to download the integral datalogger content. The settings can be found in submenu Serial Comm.
5.4.2 Analogue current output 0/4 ... 20 mA
The analogue current output operate in 4 ... 20 mA mode by default. 0 ... 20 mA operation is possible, please contact customer support.
The current output can be programmed, scaled and assigned to flow channel 1 or 2 within the menu structure.
Wiring
Electrical characterist­ics
Range = 0/4 ... 20 mA Resolution = 16 bit U = 30 V R
Load
< 500 Accuracy = 0.1 % Galvanically isolated from main device and other I/O
5.4.3 Digital Open-Collector output The totaliser function is enabled and controlled using the <QON>, <Q+>, <Q-> and
<Q
OFF
> keys and from the menu structure where the pulse value and width are se-
lected. The digital Open-Collector output can be assigned to flow channel 1 or 2.
Wiring
Electrical characterist­ics
U = 24 V I
max
= 4 mA Value = 0.01 ... 1000 Pulse width = 30 ... 999 ms
5.4.4 Digital relay output
The relay outputs are enabled, controlled and assigned to flow channel 1 or 2 using the menu structure.
33
Serial interface RS232
Analogue outputs
Digital outputs
KATflow 230 5 Commissioning
Wiring
Electrical characterist­ics
Form C (SPDT-CO) contacts V = 48 V I
max
= 250 mA
5.5 Input configurations
There are two 4-wire circuit PT100 inputs available at the bottom of the enclosure.
5.5.1 PT100 inputs
Wiring
Electrical characterist­ics
PT100 4-wire circuit Measuring range = -50 ... 400 ºC Resolution = 0.1 K Accuracy = ±0.2 K
5.6 Heat quantity measurement (HQM)
Future implementation.
5.7 Sound velocity measurement (SVM)
Future implementation.
5.8 Dual-channel flow calculations (maths functions)
Future implementation
5.9 KATdata+ software
Please consult customer services for assistance.
5.10 Wall thickness measurement (WTM)
Future implementation.
6 Maintenance
No general maintenance is required for this equipment.
34
Inputs
KATflow 230 7 Troubleshooting
7 Troubleshooting
Should there be the need to call customer service, please let us know the following details:
Model code
Serial number
SW, HW revision
Error log list
Possible error messages may include the following:
Error message Group Description Error handling
USB INIT FAIL Hardware Internal board communic-
ation error
Power on/off, otherwise
call customer support NO SERIAL NO. Hardware Failed to read from FRAM Call customer support NO VERSION NO. Hardware Failed to read from FRAM Call customer support PARA READ FAIL Hardware Failed to read from FRAM Load defaults, other-
wise call customer sup-
port PARA WRITE FAIL Hardware Failed to write to FRAM Load defaults, other-
wise call customer sup-
port VAR READ FAIL Hardware Failed to read from FRAM Call customer support VAR WRITE FAIL Hardware Failed to write to FRAM Call customer support SYSTEM ERROR Hardware Call customer support VISIBILITY ERR Hardware Failed to read from FRAM Call customer support FRAM LONG WRITE
ERR
Hardware Failed to write to FRAM Call customer support
FRAM READ ERR Hardware Failed to read from FRAM Call customer support RTC ERR Hardware Real Time Clock failure Power on/off, otherwise
call customer support EXTMEM ERR Hardware Logger memory failure Power on/off, otherwise
call customer support SPI ERR Hardware SPI bus failure Power on/off, otherwise
call customer support I2C ERR Hardware I2C bus failure Power on/off, otherwise
call customer support MATH ERR Software Internal calculation error Call customer support STACK ERR Software Internal calculation error Call customer support ADDR ERR Software Internal calculation error Call customer support OSC ERR Software Internal calculation error Call customer support ADC ERR Software Internal calculation error Call customer support IO ERR Software Internal calculation error Call customer support TIMING ERR Software Internal calculation error Call customer support COMM INIT ERR Hardware Internal communication
error
Power on/off, otherwise
call customer support COMM START ERR Hardware Internal communication
error
Power on/off, otherwise
call customer support COMM HS0 ERR Hardware Internal communication
error
Power on/off, otherwise
call customer support COMM HS1 ERR Hardware Internal communication Power on/off, otherwise
35
Error list
KATflow 230 7 Troubleshooting
error call customer support
COMM READ AVE ERR
Hardware Internal communication
error
Power on/off, otherwise
call customer support COMM READ RAW
ERR
Hardware Internal communication
error
Power on/off, otherwise
call customer support COMM READ HIS-
TORY ERR
Hardware Internal communication
error
Power on/off, otherwise
call customer support COMM CRC ERR Hardware Internal communication
error
Power on/off, otherwise
call customer support SENSOR COUP-
LING ERR
Application Weak sensor coupling,
low SNR
Recouple sensors,
check installation, re-
duce number of
passes, look for other
location, then have a
cup of tea and call cus-
tomer support!
36
Table 3: Error messages
KATflow 230 7 Troubleshooting
8 Technical data
Sound Speed* Shear Wave (at 25 ºC)
Material m/s ft/s
Steel, 1% Carbon, hardened 3,150 10,335 Carbon Steel 3,230 10,598 Mild Steel 3,235 10,614 Steel, 1% Carbon 3,220 10,565 302 Stainless Steel 3,120 10,236 303 Stainless Steel 3,120 10,236 304 Stainless Steel 3,141 10,306 304L Stainless Steel 3,070 10,073 316 Stainless Steel 3,272 10,735 347 Stainless Steel 3,095 10,512 Aluminium 3,100 10,171 Aluminium (rolled) 3,040 9,974 Copper 2,260 7,415 Copper (annealed) 2,325 7,628 Copper (rolled) 2,270 7,448 CuNi (70%Cu 30%Ni) 2,540 8,334 CuNi (90%Cu 10%Ni) 2,060 6,759 Brass (Naval) 2,120 6,923 Gold (hard-drawn) 1,200 3,937 Inconel 3,020 9,909 Iron (electrolytic) 3,240 10,630 Iron (Armco) 3,240 10,630 Ductile Iron 3,000 9,843 Cast Iron 2,500 8,203 Monel 2,720 8,924 Nickel 2,960 9,712 Tin (rolled) 1,670 5,479 Titanium 3,125 10,253 Tungsten (annealed) 2,890 9,482 Tungsten (drawn) 2,640 8,661 Tungsten (carbide) 3,980 13,058 Zinc (rolled) 2,440 8,005 Glass (pyrex) 3,280 10,761 Glass (heavy silicante first) 2,380 7,808 Glass (light brate crown) 2,840 9,318 Nylon 1,150 3,772 Nylon, 6-6 1,070 3,510 Polyethylene (LD) 540 1,772 PVC, CPVC 1,060 3,477 Acrylic 1,430 4,690
* Please note these values are to be considered nominal. Solids may be inhomogeneous and aniso­tropic. Actual values depend on exact composition, temperature, and to a lesser extent, on pressure and stress.
37
KATflow 230 8 Technical data
All data given at 25 ºC (77 ºF) unless otherwise stated
Sound Speed
Change v/ºC
Kinematic Viscosity x10-6
Substance
Chemical Formula
Specific Gravity
m/s ft/s m/s/ºC m2/s ft2/s
Acetic anhydride (CH3CO)2O 1.082 (20 ºC) 1,180 3,871.4 2.5 0.769 8.274 Acetic acid, anhydride (CH3CO)2O 1.082 (20 ºC) 1,180 3,871.4 2.5 0.769 8.274 Acetic acid, nitrile C2H3N 0.783 1,290 4,232.3 4.1 0.441 4.745 Acetic acid, ethyl ester C4H802 0.901 1,085 3,559.7 4.4 0.467 5.025 Acetic acid, methyl ester C3H6O2 0.934 1,211 3,973.1 0.407 4.379 Acetone C3H6O 0.791 1,174 3,851.7 4.5 0.399 4.293 Acetylene dichloride C2H2Cl2 1.26 1,015 3,330.1 3.8 0.400 4.304 Alcohol C2H6O 0.789 1,207 3,960 4.0 1.396 15.02
Ammonia NH3 0.771
1,729 (-33 ºC)
5,672.6 (-27 ºC)
6.68
0.292 (-33 ºC)
3.141
(-27 ºF) Benzene C6H6 0.879 1,306 4,284.8 4.65 0.711 7.65 Benzol C6H6 0.879 1,306 4284.8 4.65 0.711 7.65 Bromine Br2 2.928 889 2,916.7 3.0 0.323 3.475
n-Butane(2) C4H10 0.601 (0ºC)
1,085 (-5º C)
3,559.7 (23 ºC)
5.8
2-Butanol C4H10O 0.81 1,240 4,068.2 3.3 3.239 34.851 sec-Butylalcohol C4H10O 0.81 1,240 4,068.2 3.3 3.239 34.851
n-Butyl bromide (46) C4H9Br 1.276 (20ºC)
1,019 (20ºC)
3,343.2 (68ºF)
0.49 (15ºC)
5.272
(59ºC) n-Butyl chloride (22,46) C4H9Cl 0.887 1,140 3,740.2 4.57
0.529 (15ºC)
5.692
(59ºF) Carbon tetrachloride CCl4 1.595 (20ºC) 926 3038.1 2.48 0.607 6.531 Carbon tetrafluoride (Freon
14)
CF4 1.75 (-150 ºC)
875.2 (-150 ºC)
2,871.5 (-238 ºF)
6.61
Chloroform CHCl3 1.489 979 3,211.9 3.4 0.55 5.918 Dichlorodifluoromethane
(Freon 12)
CCl2F2 1.516 (40 ºC) 774.1 2,539.7 4.24
Ethanol C2H6O 0.789 1,207 3,960 4.0 1.39 14.956 Ethyl acetate C4H8O2 0.901 1,085 3,559.7 4.4 0.489 5.263 Ethyl alcohol C2H6O 0.789 1,207 3,960 4.0 1.396 15.020
Ethyl benzene C8H10 0.867 (20 ºC)
1,338 (20 ºC)
4,.89.8 (68 ºF)
0.797 (17 ºC)
8.575
(63 ºF) Ether C4H10O 0.713 985 3231.6 4.87 0.311 3.346 Ethyl ether C4H10O 0.713 985 3231.6 4.87 0.311 3.346 Ethylene bromide C2H4Br2 2.18 995 3264.4 0.79 8.5 Ethylene chloride C2H4Cl2 1.253 1,193 3,914 0.61 6.563
Ethylene glycol C2H6O2 1.113 1,658 5439.6 2.1
17,208 (20ºC)
185.158
(68ºF) Fluorine F
0.545 (-143 ºC)
403 (-143 ºC)
1322.2 (-225 ºF)
11.31
Formaldehyde, methyl ester C2H4O2 0.974 1,127 3697.5 4.02 Freon R12 774.2 2540 Glycol C2H6O2 1.113 1658 5439.6 2.1 50% Glycol/50% H2O 1,578 5,177
Isopropanol C3H8O 0.785 (20 ºC)
1,170 (20 ºC)
3,838.6 (68 ºF)
2.718 29.245
Isopropyl alcohol (46) C3H8O 0.785 (20 ºC)
1,170 (20 ºC)
3,838.6 (68 ºF)
2.718 29.245
Kerosene 0.81 1,324 4,343.8 3.6 Methane CH4 0.162 (-89 ºC) 405 1,328.7 17.5
38
KATflow 230 8 Technical data
(-89 ºC) (-128 ºF) Methanol CH4O 0.791 (20 ºC) 1,076 3,530.2 292 0.695 7.478 Methyl acetate C3H6O2 0.934 1,211 3,973.1 0.407 4.379 Methyl alcohol CH4O 0.791 1,076 3,530.2 292 0.695 7.478
Methyl benzene C7H8 0.867
1,328
(20 ºC)
4,357 (68 ºF)
4.27 0.644 7.144
Milk, homogenized 1,548 5,080 Naphtha 0.76 1,225 4,019
Natural Gas
0.316 (-103 ºC)
753
(-103 ºC)
2,470.5 (-153 ºF)
Nitrogen N2
0.808 (-199 ºC)
962
(-199 ºC)
3,156.2 (-326 ºF)
0.217 (-199 ºC)
2.334
(-326 ºF) Oil, Car (SAE 20a.30) 1.74 870 2,854.3 190 2,045.093 Oil, Castor C11H10O0 0.969 1,477 4,845.8 3.6 0.670 7.209 Oil, Diesel 0.80 1,250 4,101 Oil, Fuel AA gravity 0.99 1,485 4,872 3.7 Oil (Lubricating X200) 1,530 5,019.9 Oil (Olive) 0.912 1,431 4,694.9 2.75 100 1,076.365 Oil (Peanut) 0.936 1,458 4,738.5
Propane (-45 to -130 ºC) C3H8 0.585 (-45 ºC)
1,003 (-45 ºC)
3,290.6 (-49 ºF)
5.7
1-Propanol C3H8O 0.78 (20 ºC)
1,222 (20 ºC)
4,009.2 (68 ºF)
2-Propanol C3H8O 0.785 (20 ºC)
1,170 (20 ºC)
3,838.6 (68 ºF)
2.718 29.245
Propene C3H6 0.563 (-13ºC)
963 (-13ºC)
3159.4 (9ºF)
6.32
n-Propyl-alcohol C3H8O 0.78 (20 ºC)
1,222 (20 ºC)
4,009.2 (68 ºF)
2.549 27.427
Propylene C3H6 0.563 (-13 ºC)
963 (-13 ºC)
3159.4 (9 ºF)
6.32
Refrigerant 11 CCl3F 1.49
828.3 (0 ºC)
2,717.5 (32 ºF)
3.56
Refrigerant 12 CCl2F2 1.516 (-40 ºC)
774.1 (-40 ºC)
2,539.7 (-40 ºC)
4.24
Refrigerant 14 CF4 1.75 (-150 ºC)
875.24 (-150 ºC)
2,871.6 (-268 ºF)
6.61
Refrigerant 21 CHCl2F 1.426 (0 ºC)
891 (0 ºC)
2,923.2 (32 ºF)
3.97
Refrigerant 22 CHClF2 1.491 (-69 ºC)
893.9 (50 ºC)
2,932.7 (122 ºF)
4.79
Refrigerant 113 CCl2F-CClF2 1.563
783.7 (0 ºC)
2,571.2 (32 ºF)
3.44
Refrigerant 114 CClF2-CClF2 1.455
665.3 (-10 ºC)
2,182.7 (14 ºF)
3.73
Refrigerant 115 C2ClF5
656.4 (-50 ºC)
2,153.5 (-58 ºF)
4.42
Refrigerant C318 C4F8 1.62 (-20 ºC)
574 (-10 ºC)
1,883.2 (14 ºF)
3.88
Sodium nitrate NoNO3 1.884 (336 ºC)
1,763.3 (336 ºC)
5,785.1 (637 ºF)
0.74
1.37 (336 ºC)
14.74
(637 ºF) Sodium nitrite NoNO2 1.805 (292 ºC)
1876.8 (292 ºC)
6157.5 (558 ºF)
Sulphur S
1177 (250 ºC)
3861.5 (482 ºF)
-1.13
Sulphuric Acid H2SO4 1.841 1,257.6 4,126 1.43 11.16 120.081 Tetrachloroethane C2H2Cl4 1553 (20 ºC)
1,170 (20 ºC)
3,838.6 (68 ºF)
1.19 12.804
Tetrachloro-ethene C2Cl4 1.632 1,036 3,399
39
KATflow 230 8 Technical data
Tetrachloro-Methane CCl4 1.595 (20 ºC) 926 3,038.1 0.607 6.531 Tetrafluoro-methane
(Freon 14)
CF4 1.75 (-150 ºC)
875.24 (-150 ºC)
2,871.5 (-283 ºF)
6.61
Toluene C7H8 0.867 (20 ºC)
1,328 (20 ºC)
4,357 (68 ºF)
4.27 0.644 6.929
Toluol C7H8 0.866 1,308 4,291.3 4.2 0.58 6.24 Trichloro-fluoromethane
(Freon 11)
CCl3F 1.49
828.3 (0 ºC)
2,717.5 (32 ºF)
3.56
Turpentine 0.88 1,255 4,117.5 1.4 15.064 Water, distilled H2O 0.996 1,498 4,914.7 -2.4 1.00 10.76 Water, heavy D2O 1,400 4,593 Water, sea 1.025 1531 5023 -2.4 1.00 10.76
Temperature Sound Speed in Water º C º F m/s ft/s
0 32.0 1402 4600 1 33.8 1407 4616
2 35.6 1412 4633 3 37.4 1417 4649 4 39.2 1421 4662 5 41.0 1426 4679 6 42.8 1430 4692 7 44.6 1434 4705 8 46.4 1439 4721 9 48.2 1443 4734 10 50.0 1447 4748 11 51.8 1451 4761 12 53.6 1455 4774 13 55.4 1458 4784 14 57.2 1462 4797 15 59.0 1465 4807 16 60.8 1469 4820 17 62.6 1475 4830 18 64.4 1476 4843 19 66.2 1479 4853 20 68.0 1482 4862 21 69.8 1485 4872 22 71.6 1488 4882 23 73.4 1491 4892 24 75.2 1493 4899
25
77.0 1496 4908
26 78.8 1499 4918 27 80.6 1501 4925 28 82.4 1504 4935 29 84.2 1506 4941 30 86.0 1509 4951 31 87.8 1511 4958 32 89.6 1513 4964 33 91.4 1515 4971 34 93.2 1517 4977 35 95.0 1519 4984 36 96.8 1521 4984
40
KATflow 230 8 Technical data
37 98.6 1523 4990 38 100.4 1525 4997 39 102.2 1527 5010 40 104.0 1528 5013 41 105.8 1530 5020 42 107.6 1532 5026 43 109.4 1534 5033 44 111.2 1535 5036 45 113.0 1536 5040 46 114.8 1538 5046 47 116.6 1538 5049 48 118.4 1540 5053 49 120.2 1541 5056 50 122.0 1543 5063 51 123.8 1543 5063 52 125.6 1544 5066 53 127.4 1545 5069 54 129.2 1546 5072 55 131.0 1547 5076 56 132.8 1548 5079 57 134.6 1548 5079 58 136.4 1548 5079 59 138.2 1550 5086 60 140.0 1550 5086 61 141.8 1551 5089 62 143.6 1552 5092 63 145.4 1552 5092 64 147.2 1553 5092 65 149.0 1553 5095 66 150.8 1553 5095 67 152.6 1554 5099 68 154.4 1554 5099 69 156.2 1554 5099 70 158.0 1554 5099 71 159.8 1554 5099 72 161.6 1555 5102 73 163.4 1555 5102 74 165.2 1555 5102 75 167.0 1555 5102 76 167.0 1555 5102 77 170.6 1554 5099 78 172.4 1554 5099 79 174.2 1554 5099 80 176.0 1554 5099 81 177.8 1554 5099 82 179.6 1553 5095 83 181.4 1553 5095 84 183.2 1553 5095 85 185.0 1552 5092 86 186.8 1552 5092 87 188.6 1552 5092 88 190.4 1551 5089 89 192.2 1551 5089 90 194.0 1550 5086
41
KATflow 230 8 Technical data
91 195.8 1549 5082 92 197.6 1549 5082 93 199.4 1548 5079 94 201.2 1547 5076 95 203.0 1547 5076 96 204.8 1546 5072 97 206.6 1545 5069 98 208.4 1544 5066 99 210.2 1543 5063 100 212.0 1543 5063 104 220.0 1538 5046 110 230.0 1532 5026 116 240.0 1524 5000 121 250.0 1526 5007 127 260.0 1507 4944 132 270.0 1497 4912 138 280.0 1487 4879 143 290.0 1476 4843
149
300.0 1465 4807
154 310.0 1453 4767 160 320.0 1440 4725 166 330.0 1426 4679 171 340.0 1412 4633 177 350.0 1398 4587 182 360.0 1383 4538 188 370.0 1368 4488 193 380.0 1353 4439 199 390.0 1337 4387 204 400.0 1320 4331 210 410.0 1302 4272 216 420.0 1283 4210 221 430.0 1264 4147 227 440.0 1244 4082 232 450.0 1220 4003 238 460.0 1200 3937 243 470.0 1180 3872 249 480.0 1160 3806 254 490.0 1140 3740 260 500.0 1110 3642
42
KATflow 230 9 Specification
9 Specification
43
Transit-time correlation measurement
Dual DSP-technology, coded signals for
better measurement accuracy
Two channel portable unit with graphic
display
Easy to install clamp-on sensors with no
process interruption
Non-invasive flow measurement of
liquids or liquified gases
Optional wall thickness, heat quanity
and sound velocity measurement
Suitable for all commonly used pipe
materials with pipe diameters from 10 mm (4/10") to 3 m (118")
Ultrasonic Flowmeter
KATflow 230
Description
The KATflow range of non-invasive flowmeters utilises ultrasonic technology for the accurate flow measurement of liquids and liquified gases in full pipes.
The KATflow 230 is designed for portable use to meet the needs of the Service/Maintenance and Commissioning Engineer wishing to check the flow rate at different locations in the plant. The set-up of the unit is simple through a setup wizard in order to obtain the required flow information in minutes.
The measurement of flow is based on the principle that sound waves are influenced by a flowing medium. Measurements are made by penetrating the pipe with ultrasound and subsequently time differences, frequency variations and phase shifts of the ultrasonic signals are evaluated.
The ultrasonic sensors are clamped onto the outside of the pipe, thus eliminating the need to dismantle the pipework and interrupt the process. The KATflow 230 can be applied to any type of standard pipe carrying clean or dirty liquids and liquified gases.
Advantages
• Low installation effort and costs
Measurement is independent of fluid conductivity
• No pressure loss, no possibility of leakage
• Retrospective installation for existing plants possible
• No cutting of pipes necessary, no interruption of process, no plant shut down
• No additional fittings for maintenance required
• Hygienic measurement, no risk of contamination, suitable for ultra clean liquids
• No contact with medium, no risk of corrosion when used with aggressive media
• Cost advantages when used with large diameter pipes, high pressure systems, etc.
Specification
General
Measuring principle : Ultrasonic time difference
correlation principle
Flow velocity range
: 0.01 ... 25 m/s Resolution : 0.25 mm/s Repeatibility : 0.15 % of measured value ±
0.015 m/s
Accuracy : Volume flow
±1 ... 3 % of measured value depending on application, ±0.5 % of measured value with process calibration
Flow velocity
±0.5 % of measured value
Turn down ratio
: 1/100 Gaseous and solid content of liquid media : < 10 % of volume
Flowmeter
Enclosure : Portable Degree of protection
: IP 65 according EN 60529 Operating temperature : -10 ... 60 °C (14 ... 140 °F) Housing material : Extruded aluminium, Al MG Si
0.5, lids die-cast zinc alloy GD-
Zn AL 4 CU 1 Flow channels : 2 Power supply : Internal rechargeable batteries,
8 x NiMH AA 2850 mAh or
external power supply 9 V DC Display : LCD graphic display, 128 x 64
dots, backlit Dimensions : H 266 x W 168 x D 37 mm Weight : Approx. 2.0 kg
KATflow 230 9 Specification
44
Flowmeter (cont.)
Power consumption : < 5 W Signal damping : 0 ... 99 s Measurement rate : 10 ... 1000 s
-1
Operating languages : English, German, French, Spanish,
Russian Response time : 1 s, faster rates upon request Calculation functions : Average/difference/sum
Quantity and units of measurement
Volumetric flow rate : m3/h, m3/min, m3/s, l/h, l/min, l/s,
USgal/h (US gallons per hour),
USgal/min, USgal/s, bbl/d (barrels
per day), bbl/h, bbl/min Flow velocity : m/s, ft/s, inch/s Mass flow rate : g/s, t/h, kg/h, kg/min Volume : m3, l, gal (US gallons), bbl Mass : g, kg, t Heat flow : W, kW, MW (only with heat quantity
measurement option) Heat quantity : J, kJ, MJ (only with heat quantity
measurement option)
Internal data logger
Storage capacity : approx. 30,000 samples (128
kByte), optional > 100,000 samples
(512 kByte) Logging data : All measured and totalised values,
parameter sets
Communication
Serial interface : RS 232 Data : Instantaneous measured value,
parameter set and configuration,
logged data
Software KATdata+
Functionality : Downloading of measured
values/parameter sets, graphical
presentation, list format, export to
third party software, on-line transfer
of measured data Operating systems : Windows 2000, NT, XP, Linux
Mac (optional)
Process inputs : Galvanically isolated from main
electronics and from other I/O's Temperature : PT 100, four-wire circuit, measuring
range -50 ... 400 °C, resolution 0.1
K, accuracy ±0.2 K
Process outputs : Galvanically isolated from main
electronics and from other I/O's Current : 0 ... 20 mA, active (R
Load
< 500 ),
16 bit resolution, U = 30 V,
accuracy 0.1 %
Digital (Open­Collector) : Totaliser, value 0.01 ...
1000/unit, width 30 ... 999 ms, U = 24 V, I
max
= 4 mA
Digital (relay) : Alarm, fault (programmable)
Form C (SPDT-CO) contacts, U = 48 V, I
max
= 250 mA
Clamp-on sensors
Type K1N, K1E
Diameter range
: 50 ... 3000 mm Dimensions : 60 x 30 x 34 mm Material : Stainless steel Temperature range :
Type K1N:
-30 ... 130 °C (-22 ... 266 °F)
Type K1E:
-30 ... 200 °C (-22 ... 392 °F), for short periods up to 300 °C
(572 °F) Degree of protection
: IP 66 acc. EN 60529, IP 67 and
IP 68 optional
Type K4N, K4E
Diameter range : 10 ... 250 mm Dimensions : 43 x 18 x 22 mm Material : Stainless steel Temperature range :
Type K4N:
-30 ... 130 °C (-22 ... 266 °F)
Type K4E:
-30 ... 200 °C (-22 ... 392 °F),
for short periods up to 300 °C
(572 °F) Degree of protection
: IP 66 acc. EN 60529, IP 67 and
IP 68 optional
Loading...