KAN-therm B4012, B2012, B2022, B4022 Operation Manual

Package contents: power supply strip (1 pc.), operation manual (1pc.), rule (1 pc.).
Safety directions
Every electric work should be done by an authorized person according to regulations in force and also to recommendations of a local power station. Before installation work switch off power supply!
Safety rules:
Before removing a cover switch off supply voltageFor cleaning power supply strip use a dry cloth.
1
2/2009 © Copyright KAN Sp z o.o. All rights reserved. Text, images and their arrangement in KAN publication are protected by proprietor’s rights.
POWER SUPPLY STRIP
OPERATION MANUAL
B2012/B4012 (without pump module)
B2022/B4022 (with pump module)
ISO 9001 : 2000
Designated use and working principle
A power supply strip is used to connect temperature control devices (actuators and thermostats) in an easy, simple and handy way.
KAN
is not responsible for results of use non-conforming to its designated use.
Connecting PS strip to a power network
Technical specifications
P
S strip code:
B
2012/B2022B4012/B4022
Operation voltage 230V 24V M
ax. power consumption
5
0W 50W
S
upply voltage
2
30V AC, 5A 230V AC, 5A
Fuse
T 4A H T 2A H
Max. number of thermostats
66
Max. number of actuators
12 12
O
ptional heating programs
2
2
P
rotection class
I
I II
Degree of protection
IP20 IP20
Working temperature
from 0 to 60 C from 0 to 60°C
S
torage temperature
f
rom -25 to 60°C from -25 to 60°C
Relative humidity (no condensation)
max 80% max 80%
Dimensions (mm)
41 / 325 / 74,5 41 / 333 / 74,5
Wieght
350g 350g
Recommended wire sections:
0,75 - 1,5 mm² 0,75 - 1,5 mm²
www.kan.com.pl
Electric connection recommendation (Fig.1)
To fix a cable at the point of entry into the PS strip use latches to be broken off (at the bottom of a PS strip). Connect cables to terminals.
INPUT (IN) OUTPUT (OUT)
Connection of room thermostats and electric actuators (Fig. 2)
1. One or two electric actuators connected to one zone (standard).
2. Three or four electric actuators connected to one zone (option).
Timer connection (Fig. 3)
1. External timer connection with maximal two control ciruits (A or B).
2. Room thermostat connection with a timer.
Room thermostat connection with a timer signal. (Fig. 4)
Connect A or B command signal to a room thermostat output - horizontal channel.
Pump connection (Fig. 5)
Having a pump connected to a PS strip it is possible to control it, i.e. to switch it ON/OFF depend on room temperature. Switching off a pump takes place automatically, if all electric actuators get closed. Switching on is also automatically, if any of electric actuator gets open.
Fig.5
Fig.3Fig.2 Fig.4
www.kan.com.pl
2008 © Copyright KAN Sp z o.o. All rights reserved.
Fig.1