Kantech KT-MOD-INP16 User Manual

1. Introduction
Note 1: The KT-400 SPI port maximum current draw, when the 12V AUX terminals are not used, is 500 mA.
Note 2: External power supply (12 VDC, 2 Amps) is required when the total current draw exceeds 500mA on the SPI Port.
2. Specifications
Maximum Current Draw: up to 40 mA per module
Supports single end-of-line (5600 ohm resistors) and
no end-of-line (DRY) zone loops
Supports Normally Closed (NC) and Normally Open (NO) contacts
The C (Common) terminal is +12 VDC
Input change with a debouncing of 500 ms (Slow) or
150 ms (Fast)
Reports one condition per input: SECURE or ALARM
Can be used for contact or elevator input
Cannot be connected to output modules KT-MOD-REL8 and
KT-MOD-OUT16 through SPI OUT, only through its SPI EXP expansion port
3. Installing the KT-MOD-INP16 Module
3.1. Unpacking
The KT-MOD-INP16 package includes the following parts:
One (1) KT-MOD-INP16 module, 14 cm x 8 cm (5.7 in x 3.25 in)
One (1) SPI cable with 1 SPI connector, 41 cm (16 in)
Four (4) plastic standoffs
Two (2) installation sheets, English and French
KT-MOD-INP16
KT-400 Expansion Module 16-Zone Input with SPI Cable Install Sheet
3.2. Mounting
The KT-MOD-INP16 can be installed inside a compatible cabinet (KT-MOD-CAB or KT-400) or mounted in a dry and secure location at less than 1 m (3 ft) from the KT-400.
1. Press the four (4) plastic standoffs through the mounting holes of the cabinet,
2. Secure the cabinet to the wall in the desired location. Use appropriate wall anchors when securing the cabinet to drywall, plaster, concrete, brick or other surfaces.
3. Press the module into the plastic standoffs to secure the module to the cabinet.
3.3. SPI Wiring
Perform the following steps to complete wiring:
Note 1: Before beginning to wire the unit, ensure that all power (AC transformer and battery) is disconnected from the KT-400.
If you are combining input and output modules through
Note 2:
the SPI EXP expansion port of the KT-MOD-INP16, the input module must be the 1 Port.
1. Connect the 6-pin SPI connector to the KT-400 SPI port or to the SPI OUT of the previous KT-MOD-INP16 module.
2. Connect the six SPI wires (blue (BLU), white (WHT), green (GRN), yellow (YEL), black (BLK) and red (RED)) to the SPI IN (TB1) terminals.
3. You can use the SPI EXP of the 1 group of output modules (KT-MOD-REL8 and KT-MOD-
OUT16 only).
4. Connect the 6-pin SPI connector from the SPI OUT to the
next KT-MOD-INP16 module.
5. Complete all zone wiring to the zone input terminals (Z1-Z16).
3.4. Check the power jumper JP5 position. Put it on EXT if you need external power or INT if no external power is required.
st
module connected to the KT-400 SPI
st
KT-MOD-INP16 to start a
Tel.: 1 (450) 444 2030 Toll Free: 1-888-222-1560 Fax: 1 (450) 444 2029 Internet: www.kantech.com DN1776-0809
Copyright © 2008 Tyco International Ltd. and its Respective Companies. All Rights Reserved. Specifications may change without notice. Kantech and the Kantech logo are trademarks of Tyco International Ltd. and its Respective Companies.
4. Configurations with Jumpers
There are 3 jumpers available to configure the KT-MOD-INP16. The jumper settings apply to ALL 16 inputs at the same time.
Note: Jumper JP4 is for future use.
DRY (without end-of-line resistor): In a simple NC dry contact configuration, the secure state is given when a short is detected. The voltage becomes lower than the Level 1 threshold value (1.1V).
The alarm state is given when the input is open. The voltage becomes higher than the Level 2 threshold value (3.75V). If the alarm switch is programmed as NO device, the alarm state will be given when the input is shorted.
EOL (with end-of-line resistor): For NC device, the secure state is given when a single resistor is detected. The voltage becomes lower than the Level 3 threshold value (2.9V) and higher than the Level 2 threshold value (2.25V).
The alarm state is given when the input is open or short. The voltage becomes higher than the Level 4 threshold value (3.75V) or lowers than the Level 1 threshold value (1.1V). If the alarm switch is programmed as NO device, the alarm state will be given when a single resistor is detected.
KT-MOD-INP16
KT-400 Expansion Module 16-Zone Input with SPI Cable Install Sheet
5. Applying Power
After all wiring is completed, connect the 16 VAC to the KT-400. Connect the battery leads to the battery, and then apply power to the AC transformer.
Note: Do not connect power until all wiring is complete.
Terminal Connections
Module no.: ______________________________________________________________________________________
Date of installation: _______________________________________________________________________________
KT-400 Name: ____________________________________________________________________________________
KT-400 SITE NAME: _______________________________________________________________________________
KT-400 Serial Number: _____________________________________________________________________________
AUX: ___________________________________________________________________________________________
SPI BUS (FROM): _________________________________________________________________________________
SPI BUS (TO): ____________________________________________________________________________________
F Z1:
F Z2:
F Z3:
F Z9: __________________________________________
F Z10: _________________________________________
F Z11: _________________________________________
F Z4:
F Z5:
F Z6:
F Z7:
F Z8:
Tel.: 1 (450) 444 2030 Toll Free: 1-888-222-1560 Fax: 1 (450) 444 2029 Internet: www.kantech.com DN1776-0809
Copyright © 2008 Tyco International Ltd. and its Respective Companies. All Rights Reserved. Specifications may change without notice. Kantech and the Kantech logo are trademarks of Tyco International Ltd. and its Respective Companies.
F Z12: _________________________________________
F Z13: _________________________________________
F Z14: _________________________________________
F Z15: _________________________________________
F Z16: _________________________________________