kansai TSK-23, TSK-42, TSK-33, TSK-18, TSK-52HT Operation Manual

...
Page 1
Please send to the customer who is used this operation manual without fail.
Hot-air generator
C-type series
Preservation type
Operation manual
Please read without fail before use.
Thank you very much for purchasing Hot-air generator this time.
Please confirm the model, type, and voltage by the name plate of this machine.
1. Attention on use
2. Installation
3. Piping
4. Power supply
5. Maintenance inspection
6. Name of every part
Total edition
TSK Hot-air generator
TSK-18
TSK-23,33
TSK-42,52
TSK-52HT
TSK-56
TSK-62,72
TSK-82
TSK-92,102
TSK-122,132
7. Service terminal
8. Warning detection Guarantee
Contents of this operation manual are changed without notice. The figure and display in the operation manual does not guarantee actual specification. We prohibit that changes this operation manual without taking our permission.
Kansai Electric Heat Corp.
Page 2
1.Attention on use
For the hot-air generator is used without malfunctioning
Important matters that demand special attention that became the cause of malfunction that occurred in the
past is entered. Please inquire with the use method of your company.
Please attach the demi-filter or CR-filter without fail to the suction side of the hot-air
generator.
Please clean always the filter that is used or wire net of the hot-air generator inlet. (Standard
equipment) Heater inside is overheated by the clogging of the filter and the hot-air generator may can not operate.
Hot-air generator malfunctions when these adhered to the controller inside of the hot-air
generator in the case that dust, mine dust, floating objects that pass electricity of carbon fiber, oil, lampblack, oil mist, moisture, and vapor is included to the atmosphere of the setting place of the hot-air generator.
Please confirm without fail before use.
Leakage of the hot-air is occurred without fail on the characteristic of the flexible hose in the
case of the piping by the flexible hose to the outlet and inlet of hot-air generator. Electron devices inside the operation panel are damaged by the hot-air of the high temp. that leaked flows backward to the hot-air generator inside. So, please execute the glass tape for the air leakage prevention that was enclosed to the outlet and inlet.
Input terminal A1-A10 and output terminal B8-B10 is malfunctioned by the voltage is
applied. And, output terminal B1-B7 is malfunctioned by the voltage more than the rating is applied.
Please do not unite or wire that was adjoined the wiring of the service terminal with the
power supply line, high tone wave line. Electron devices of the inside are damaged by noise.
Please do not stopped the hot-air generator with the electromagnet contact device that was
established to the first side of the hot-air generator. Electron devices of the inside are damaged by serge voltage.
The thunder serge that occurred by falling of a thunderbolt becomes a cause to the wrong
action, damage, and fire accident of the hot-air generator. Please attach the arrester without fail and please perform the falling of a thunderbolt measure in the case that the hot-air generator is used in the place where receives the influence of falling of a thunderbolt.
Please use the commercial power supply (50/60Hz) that has the sine wave-like to the power
supply of the hot-air generator. Please do not use the power supply that has the distortion wave including a high tone wave from the frequency transformation device absolutely. Electron devices of the inside are damaged by high tone wave and noise.
Please do not bend and do not change the height the sensor for the temp. measuring that is
󰶸
equipped to the outlet of the hot-air generator. Short the heater.
-1-
circuit occurs if the sensor contacts to
Page 3
2. Installation
P
P
Pl
ffici
blished f
lease establish to the horizontal position.
Please refer to the figure of the right about the around of inclination. And, please establish to the horizontal position about the right and left.
Please fix it firmly as occasion demands.
Place where can not establish
Place where back is stuck to wall etc.
Place where height is more than 1000m
Outdoor, and place where is exposed to the storm
・・
Places of there are many dust Room where is tightly sealed and case inside
・・
Upper part of generation thing Place where ambient temp. is more than 0 - +40゚C.
・・
Neighborhood of combustible Place where ambient humidity is more than 85%R.H.
・・
Place where air pressure is low Place where has floating objects that pass electricity (Carbon fiber etc.)
・・
15°
10°
Place where acid and corrosiveness gas is floating
Place where has vibration
3. Piping
Please fix the piping to the outlet and inlet certainly.
Leakage of the hot-air is occurred without fail on the characteristic of the flexible hose in the case of the piping by the flexible hose to the outlet and inlet of hot-air generator. Electron devices inside the operation panel are damaged by the hot-air of the high temp. that leaked flows backward to the hot-air generator inside. So, please execute the glass tape for the air leakage prevention that was enclosed to the outlet and inlet.
Please pipe as thickly, short, and gradual curve as possible.
Please insulate sufficiently without fail to piping.
Please do not hang the pulling load to the outlet flange in the condition that the hot-
air generator with the outlet flange was fixed.
Please do not insert the piping is smaller than the bore of the outlet to the outlet. Outlet sensor is bent, and
the sensor contacts to the heater.
Execution example of the glass tape for the air leakage prevention
4. Power supply
Please ask the connection of the power supply and ground construction work to the electric repairing work
technician. Please connect the power cord in accordance with R(Red), S(White), T(Black), and Ground(Green).
Power cord is not belonged TSK-121. So, please prepare separately.(Recommendation cord : Cab tire cable 100mm2)
lease use the commercial power supply (50/60Hz) that has the sine wave-like to the power supply of the
hot-air generator. Please do not use the power supply that has the distortion wave including a high tone wave from the frequency transformation device absolutely.
Please establish the exclusive use circuit. Please decide the capacity of the sensitivity current in accordance
with the following table in the case that the electric leakage circuit breaker is attached.
Model
TSK-18, 23, 33 50mA
TSK-42, 52, 52HT, 56 50mA
TSK -62, 72, 82 100mA
TSK-92, 102, 122, 132 200mA
* About 10 times of the early period leakage current are general as the sensitivity current of the electric leakage circuit breaker.
Please supply the power supply that the rating frequency that has the sine wave wave-like without fail was secured when the generator is used to the power supply of the hot-air generator. Temp. is not controlled normally and the operation may not produced if the power supply that rating frequency is not secured is supplied.
Please execute the ground construction work to prevent electric shock accident prevention. (Less than 300V
: D-class ground Less than 600V : C-class ground)
Attention The voltage depression is occurred by too long wiring. So, please pay attention. Attention
Attention
Please block the power supply without fail at the time of wiring and inspection. Please block the factory power supply without fail because electricity is flowing to the control circuit even if the breaker (NFB) of the hot-air generator is turned OFF. You receive an electric shock when work is conducted in the condition that the power supply is turned ON.
ease secure su
defectiveness, absence phase, generation, and malfunction by passing year change. So, please refrain from the use of the
ent capacity in the case that the socket was esta
Rough standard of the sensitivity current of the electric leakage circuit
or connection. Socket may cause contact
Attention
Hot-air generator is the device that is used in industry environment mainly. Radio wave obstacle may occur if this is used in residence environment. User of this product must take the appropriate means for obstacle reduction.
-2-
Page 4
5. Maintenance inspectio n
f
P
Test button
This is such a test button that confirms whether the breaker (NFB) of this machine operates normally at the time of overheat. One time in a month, please continue t o push the but t on for several seconds in operation stoppage condition (Electricity is flowing). And, please confirm the illumination of the OVERHEAT lamp, operation display of overheat P.9), and trip action of t he breaker (NFB) of this machine. (TSK-18 is only the illumination of the overheat lamp and display of the overheat operation. )
After confirmation, please turn OFF the source power supply (factory power supply) and breaker (NFB) of this machine at first. And please turn ON once again. (TSK-18 is only input of the
actory power supply.)
Inspection of the inlet wire net and filter
Test button
The wire net is equipped to the inlet of the hot-air generator. (Demi-filter is standard equipped to a part of hot-air generator.) Please inspect the wire net and filter of the inlet always, and please clean periodically. Heater case inside becomes the abnormal high t emp. and ove rheat or temp. warning is occured if the wire net and filter are clogged.
Storage
lease pay attention to the condensation sufficiently in the case that the hot-air generator is stored long time. Condensation occurs by the te mp. of storage at mosphere drops in the winter season. Hot-air generator becomes freezing condition if t his machine i s stored in the c ondit i on that t he c onde nsation oc c urred, and i t becomes the cause of the malf unct i on of an e l ec t rici t y part.
Individual inspection
I recommend that is carried out the individual inspection in the case that the use period exceeded 10 years to have this machine used more safely.
Item of the individual i nspect i on
Measurement of the insulation resistance val ue Measurement of the heater current val ue
・・
Increase bundle inspection of each terminal unit Other inspection by eyes
・・
Foreign substance mixing inspection and cle ani ng inside t he c ont rolle r
Foreign substance mixing inspection and cle ani ng inside t his machine and i nle t
Action of the el e ct ric it y part and gene rati on inspec t ion
Please ask to the adjacent e le c tric i ty busine ssman about the indi v idual inspec t ion.
Attention
Please do not carry out the insulation resistance voltage test of this machine. (It gets finished enforcement at the time of shipment.) It becomes the cause of malfunction.
About the electricity fire
Operation condition of the f ront where stops automatically i s started by t he input of the primary power supply in one second after the hot-air generator stopped instantaneously by power failure etc. We recommend the establishment of t he de v ic e that bl ock s the primary power supply to electricity fire prevention at the time of the disaster of earthquake etc.
-3-
Page 5
6. Name of every part
Control panel (All machine type community)
⑪⑬
⑦⑭ ⑧⑨ ②
④ ⑤
③ ⑥⑮
⑲ ⑱⑰
STOP switch TIMER display
①⑩
This is the stop switch of blow operation and hot-air operation, and for the cancellation of timer operation.
HOT-AIR switch HEATER lamp
②⑪
Hot-air operation is started when the switch was pushed.
BLOW switch
Blow operation is started when the switch was pushed.
OPERATION BY TIMER switch
Time that the operation is started is set up when the switch was pushed. Please push HOT-AIR switch after setting.
STOP BY TIMER switch
Time that the operation is stopped is set up when the switch was pushed. Please push HOT-AIR switch after setting.
EXT. RUN switch
Hot-air generator is operated with the external operation signal and external heater ON/OFF signal by the switch is continued to push (about 2 seconds).
HOT-AIR TEMP. display
Outlet temp. is displayed. Temp. of the external sensor is displayed by the operation condition is changed to the external sensor.
SETTING TEMP. display
Setting temp. of the outlet is displayed. Setting temp. of the external sensor is displayed by the operation condition is changed to the external sensor.
AIR VOL. COTL display PUSH TO TEST
⑨⑱
Setting value of the air volume control (Frequency setting) is displayed.
-4-
Setting time of the timer is displayed. Time is reduced by time counting.
ON/OFF of the heater is displayed by illumination and flickering.
TEMP. ALM lamp
This is lighted within the range of the temp. alarm setting value in the case that temp. alarm setting is input.
EXT. CNTL lamp
This is lighted when the operation condition was changed to the external control.
EXT. SENSOR lamp
This is lighted when the operation condition was changed to the external sensor.
OVERHEAT lamp
This is lighted and the breaker (NFB) is become trip in the case that the heater case inside became a abnormal high temp.
TEMP. WARN. Lamp
Breaker (NFB) is become trip or bloe operation is become in the case that discharge temp. became a high temp. or suction temp. became over the permission temp. of the blower.
BLOWER WARN. Lamp
This is lighted when the blower became the overload and operation stops.
Breaker (NFB) is become trip by the button is pushed.
MODE switch
This is used in the case that the operation condition is changed.
Page 6
MODEL : TSK-52
Hot-air outlet
Outlet temp . sen so r (Thermocouple JISK)
Handle
Service terminal
Control panel
Heatproof blower (Hot-air circulation type)
Breaker (NFB)
MODEL
Outlet temp . sen so r (Thermocouple JISK)
Caster
TSK-102
Hot-air outlet
Eye bolt
Control panel
Heatproof blower (Hot-air circulation type) with demi-filte
Power cord
Breaker (NFB)
Service terminal
-5-
Page 7
7. Service terminal
Pl
EXT. RUN
f
P
Service terminal of the input and output is equipped to all types. Please use as occasion demands.
Type that is used
TSK-18, 23, 33, 42, 52, 56
RC
E. S+ E. S-
Input terminal
Mini terminal (Application electric wire Shield wire AWG24 - 16
Necessary tool : No.1 Plus driver or 3mm Minus driver
E. C+ E. C-
E. R
E. H
COM
Connector for connection of Remote controller
This is the connector for connection of remote cable in the case that the remote controller of the option is
External sensor input terminal
Please connect the terminal of the external sensor K350A.
E. S+, K- → E. S- Tightening torque : 0.5N・m)
(K+
Peel length 7 - 9mm) Tightening torque : 0.4N・m
External temp. control input terminal
This is used in the case that temp. is controlled by other temp. controllers. Please input SSR drive reverse action output (DC12 - 24V). At this time, please use the temp. controller of this machine as outlet temp. upper limiter.
External operation input terminal
This is used in the case that the hot-air generator is operated by the outside signal. Input is for the contact output. (Terminal voltage is less than DC12V 3.6mA.)
External heater input terminal
This is used in the case that the heater is turned ON/OFF by the outside signal. Input is for the contact output. (Terminal voltage is less than DC12V 3.6mA.)
Input common terminal
This is common for the external operation input terminal E.R and external heater input terminal E.H.
*
Terminal voltage of the external operation input terminal E.R and external heater input terminal E.H is less than DC12V 3.6mA. Please prepare the relay that has the contact capacity that can open and close this voltage.
*
this machine in the case that the external operation input and external heater
Output terminal
ease change the external operation mode by pushing the
Contact capacity is more than DC5V 10mA, less than DC30V 1A, Output common
switch o
terminal total is less than 3A. (Unvoltage point of contact signal output) Mini terminal (Application electric wire Shield wire AWG24 - 16 Peel length 7 - 9mm) Tightening torque : Necessary tool : No.1 Plus driver or 3mm Minus driver
BLW HOT
T. W.
T. A
BW
OVH
COM
Attention
Blow output terminal
Hot-air output terminal
Temp. warning output
Temp. alarm output
Blower warning output
Overheat output terminal
Output common terminal
*
Protection circuit is not installed to unvoltage contact output. So, please do not connect the induction load (solenoid valve and conductor etc.).
lease wire after the power supply is blocked without fail in the case that the service terminal is
This terminal becomes ON when the blower is operating. This terminal becomes ON when the hot-air is operating. This terminal becomes ON at the time of the temp. warning. This terminal becomes ON when the temp. alarm was output. This terminal becomes ON at the time of the blower warning. This terminal becomes ON at the time of overheat.
used. You receive an electric shock if you wired in the condition which electricity is flowing. And, please attach a terminal cover without fail after wiring.
Attention Please do not unite or wire that was adjoined the wiring of the service terminal with the power
-6-
Page 8
P
Type that is used
Input terminal
TSK-52HT, 62, 72, 82, 92, 102, 122, 132
M3 20P The upper row of the terminal Tightening torque : 0.5N・m
A1
A2
A3
A4, A5
A6, A7
A8,A9,A10
Please input DC4 - 20mA only TSK-122 and 132. (4mA : Heater output
*1
External operation ON/OFF terminal
This is used in the case that the hot-air generator is operated by the outside signal. Input is for the contact output. (Terminal voltage is less
External heater ON/OFF terminal
This is used in the case that the heater is turned ON/OFF by the outside signal. Input is for the contact output. (Terminal voltage is less than
Input common terminal
This is common for the external operation ON/OFF terminal A1 and external heater ON/OFF terminal A2.
External temp. control input terminal *1
This is used in the case that temp. is controlled by other temp. controllers. Please input SSR drive reverse action output (DC11 - 24V). At this time, please use the temp. controller of this machine as outlet
temp. upper limiter. (A4
External sensor input terminal
Please connect the terminal of the external sensor. (K+ → A6, K- → A7 Terminal voltage of the external operation ON/OFF terminal A1 and
*
external heater ON/OFF terminal A2 is less than DC24V 7mA. Please prepare the relay that has the contact capacity that can open and close this voltage.
Please change the external operation mode by pushing the EXT. RUN
*
switch of this machine in the case that the external operation ON/OFF and external heater ON/OFF is used.
Terminal for connection of Remote controller
This is the terminal for connection of remote cable in the case that the remote controller of the option is used. (For communication of the remote
+, A5 → -)
0%, 20mA : Heater output 100%)
Output terminal
Contact capacity is more than DC5V 10mA, less than DC30V 1A, Output common
M3 20P The Lower berth of the terminal Tightening torque : 0.5N・m
terminal total is less than 3A. (Unvoltage point of contact signal output)
B1
B2
B3
B4
B5
B6
B7
B8,B9,B10
Blow output terminal
This terminal becomes ON when the blower is operating.
Hot-air output terminal
This terminal becomes ON when the hot-air is operating.
Temp. warning output terminal
This terminal becomes ON at the time of the temp. warning.
Temp. alarm output terminal
This terminal becomes ON when the temp. alarm was output.
Blower warning output terminal
This terminal becomes ON at the time of the blower warning.
Overheat output terminal
This terminal becomes ON at the time of overheat.
Output common terminal
Terminal for connection of Remote controller
This is the terminal for connection of remote cable in the case that the remote controller of the option is used. (For power supply of the remote controller)
Voltage DC24V has occurred to the remote controller power supply terminal B9-B10. Please never
*
short-circuit. Hot-air generator malfunctions without fail if short-circuits.
Attention
lease wire after the power supply is blocked without fail in the case that the service terminal is used. You receive an electric shock if you wired in the condition which electricity is flowing. And, please attach a terminal cover without fail after wiring.
Attention Please do not unite or wire that was adjoined the wiring of the service terminal with the power
-7-
Page 9
Output situation of each output terminal
TSK-18, 23, 33, 42, 56, 56
Action of the hot-air generator
Usually stop
Blow operation ON
Hot-air operation ON ON
Cooling operation ON
Temp. alarm output ON ON
Overheat
Overheat sensor burnout
In the case that the suction temp. upper
limit is exceeded
In the case that the suction temp. upper
limit is exceeded
Outlet sensor burnout
Inlet sensor burnout
Inside temp. warning of the hot-air generator
Blower warning
External sensor burnout
Reverse connection of each temp.
sensor/Minus temp. detection
Blow output Hot-air output
terminal
terminal
Temp. warning Temp. alarm Blower warning Overheat output
output terminal output terminal output terminal
BLW HOT T. W. T. A BW.
OFF OFF OFF OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF OFF
OFF OFF
ON
OFF OFF OFF
ON
OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF
OFF OFF OFF OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF OFF OFF OFF
ON
ON
OFF OFF
OFF
OFF OFF OFF OFF OFF OFF OFF
OFF OFF
OFF OFF
OFF OFF
ON
terminal
OVH
OFF
OFF
ON ON
OFF
OFF
OFF OFF OFF
TSK-52HT, 62, 72, 82, 92, 102, 122, 132
Blow output Hot-air output Temp. warning Temp. alarm Blower warning Overheat output
Action of the hot-air generator
Usually stop
Blow operation ON
Hot-air operation ON
Cooling operation ON
Temp. alarm output ON ON
Overheat
Overheat sensor burnout
In the case that the suction temp. upper
limit is exceeded
In the case that the suction temp. upper
limit is exceeded
Outlet sensor burnout
Inlet sensor burnout
Inside temp. warning of the hot-air generator
SSc temp. warning inside the hot-air generator*1
Blower warning
External sensor burnout
Reverse connection of each temp.
sensor/Minus temp. detection
terminal terminal
B1 B2 B3 B4 B5 B6
OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF
OFF OFF
ON
OFF OFF
OFF
ON ON
OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF
output terminal output terminal output terminal
OFF OFF OFF
ON
OFF OFF OFF OFF OFF
OFF OFF OFF OFF
OFF
OFF OFF OFF
OFF OFF OFF
OFF
ON
ON
ON
ON
ON
ON
ON
OFF OFF OFF
OFF OFF
OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF
OFF OFF
OFF OFF
ON
OFF OFF OFF OFF
*1 Only TSK-122 and TSK-132 (200V type)
terminal
OFF
OFF
OFF
ON ON
OFF
OFF
OFF OFF OFF
-8-
Page 10
t
P
y
P
y
Buzzer sounds at the same time as t he warning detection about TSK-52HT, 62 - 132. Even
8. Warning detection
8-1
Overhea
Overheat is detecte d in t he case t hat the i nside of the he at er case be c ame an abnormal high te mp. Or, burnout is detected in the c ase that t he ov e rheat sensor for the t e mp. c ontrol i nside the he ate r case snapped. And, the breaker (NFB) of this machine does trip and all the ope ration stop. (TSK-18 and Air volume insufficient overheat prevention are only stopped the operation.)
At the time of overheat
At the time of ove rheat sensor burnout
buzze r sound stops when warning w as canceled by the return method of each warning.
Overheat lamp (Red) are lighted, and "nFb" is flickered to HOT-AIR TEMP, "Tcb" to SETTING
Main cause
Clogging of the inlet wire net and filter
Lock of the blower motor by the mixing of the
foreign substance Exhaust outlet of furnace e tc . i s not secured
sufficiently Resista n c e (pressure lo ss) of t h e o utlet is big by
the adjacency of object work
Return method
lease remove the cause of ov erheat . A nd , source power supply and the breaker of this machine are turned OFF at first and are turned ON again after cooling sufficiently. (TSK-18 is onl
Overheat lamp (Red) are flickered, and "---" is flickered to HOT-AIR TEMP.. "Tcb" to SETTING
input of the factory power supply.)
Main cause
Snapping of a wire of the overheat sensor
Snapping of a wire of overheat sensor wiring
Miss of the overheat sensor wiring connector
Return method
Please turn OFF the first power supply and please order the repair.
At the time of air volume insufficient overheat prevention (Only TSK-52HT, TSK-62 - 132)
Overheat lamp (Red) are lighted, and "oVH" is flickered to HOT-AIR TEMP., "Tcb" to SETTING
This operates when air volume decreased by s om e causes and the heater inside tem p. is exceeded the setting hot-air temp. There is the exchangeability to the above overheat. But, whi c h oper ates by use situation.
Main cause
The same cause as the above overheat
Return method
lease remove the cause of ov erheat . A nd , source power supply and the breaker of this machine are turned OFF at first and are turned ON again after cooling sufficiently. (TSK-18 is onl
input of the factory power supply.)
Please do not operate again until the cause is removed when the overheat is operated.
-9-
Page 11
8-2
g
H
P
p
)
Temp. warnin
ot-air generator is stopped or become blow operation when outlet and inlet temp. exceeded the upper limit, each sensor becomes the burnout by snapping of a wire etc., or the inside t e mp. of t he hot-ai r gene rator became warning too. When the outlet temp. exceeded the upper limit
When the inlet temp. exceeded the upper limit
TEMP. WARN. lamp (Red) is lighted and "nFb" is flickered to HOT-AIR TEMP., "TcA" to SETTING TEMP. And, the breaker (NFB) of this machine does trip and all the operation stop.
Main cause
Outlet temp. exceeded the upper limit at the time
of using the external sensor
Decrease of the air volume by the excessive pressure loss
Decrease of the air volume by t he c l ogging of t he
inlet filter
Return method
lease remove the cause of the outlet temp. upper limit over. And , source power supply and the breaker of this machine are turned OFF at first and are turned ON again after cooling sufficiently. (TSK-18 is only input of the factory
ower supply.
TEMP. WARN. lamp (Red) is lighted and present temp. is lighted to HOT-AIR TEMP., "Tcc" is flickered to SETTING TEMP. And, It becomes blow operation condition.
At the time of the burnout of the out le t sensor
Main cause
When hot-air circulation temp. exceeded the
upper limit of the suction gas te mp. of t he hot -ai r generator
Return method
Please disarm by pushing STOP switch after the temp. of the inle t dropped.
TEMP. WARN. lamp (Red) is lighted and "---" is flickered to HOT-AIR TEMP., "TcA" to SETTING TEMP.. And, the breaker (NFB) of this machine does trip and all the operation stop.
Main cause
Snapping of a wire of the outlet sensor
Snapping of a wire of the outlet sensor wiring
Miss of the outlet sensor wiring connector
Return method
Please ord e r t h e repair af t er turnin g OFF t he first power supply.
Attention : Please block t he source power supply (factory power supply) without fail when the wiring is confirmed and readjusted at the time of abnormal.
-10-
Page 12
At the time of the burnout of the i nle t sensor
P
At the time of the inside temp. warning of the hot-air generator
TEMP. WARN. lamp (Red) is lighted and "---" is flickered to HOT-AIR TEMP., "Tcc" to SETTING TEMP. And, all the operation stop.
Main cause
Snapping of a wire of the inlet sensor
Snapping of a wire of the inlet sensor wiring
Miss of the inlet sensor wiring connector
Return method
Please ord e r t h e repair af t er turnin g OFF t he breaker (NFB) of the this machine.
TEMP. WARN. lamp (Red) is flickered and "OH" is flickered to HOT-AIR TEMP., "ALM to SETTING TEMP. And, It becomes blow operation condition.
Main cause
Establishment atmosphere temp. of the hot-ai r
generator is high. Hot-air that leaked from the outlet flowed
backward to the control panel inside. Influence of the f urnace radiati on t emp. at t he
time of the furnace upper part establ i shment.
Return method
lease stop operation by pushing STOP switch. And, please disarm by turning OFF the breaker (NFB) of this machine after inside temp. of the hot-air generator dropped.
At the time of the i nside SSC t e mp. warning of the hot-air generator (Only TSK-122, 132 200V)
TEMP. WARN. lamp (Red) is flickered and "SSc" is flickered to HOT-AIR TEMP., "ALM" to SETTING TEMP. And, It becomes blow operation condition.
Main cause
Establishment atmosphere temp. of the hot-ai r
generator is high. Hot-air that leaked from the outlet flowed
backward to the control panel inside. Influence of the f urnace radiati on t emp. at t he
time of the furnace upper part establ i shment. Malfunction of the SSC c ool ing f an
Return method
Please disarm by pushing STOP switch after inside temp. of the hot -air gene rator dropped.
Attention : Please block t he source power supply (factory power supply) without fail when the wiring is confirmed and readjusted at the time of abnormal.
-11-
Page 13
8-3
B
g
play
lower warnin
All the operation of hot -ai r generator is stopped when the blower became overload, overcurrent, and l oc k.
At the time of the blower warning
BLOWER WARN. lamp (Red) is lighted and "InV" is flickered to HOT-AIR TEMP., "ALM" to SETTING TEMP.
Main cause
Wear of the bearing
Abnormal voltage (Voltage more than the rating)
Piping of many pressure loss
Opening the use of an extremel y narrow nozzle
Return method
Abnormality is displayed to the inverter panel * that was established inside. Please turn off the breaker of this machine after the display contents are confirmed. And, please c ommunicat e the dis
contents.
The position of the inverter panel differs by the machine type.
*1
TSK-18 Back side of the control panel service terminal
TSK-23
TSK-42
TSK-52HT The inside of the back panel
TSK-56 The inside of the control panel (Please open the control panel and please confirm.)
TSK-62
TSK-82 The inside of the back panel
TSK-92
TSK-122
33 The inside of the back panel
52 The inside of the control panel (Please open the control panel and please confirm.)
72 The inside of the back panel
102 The inside of the back panel
132 The inside of the grid window of he control panel
: : : : : : : : :
1
Attention : Please block t he source power supply (factory power supply) without fail when the wiring is confirmed and readjusted at the time of abnormal.
-12-
Page 14
P
8-4
g
Other warni n
Frequency warning (Only TSK-52HT, TSK-62 - 132)
"SYS" is flickered to HOT-AIR TEMP., "ALM" to SETTING TEMP. in the case that the frequency t hat is supplied from the primary power supply exceeded
±
3Hz of the ratings. And, all the ope ration stop.
Main cause
Unsupply of rating frequency by the ge nerator
etc. is used to the primary power supply.
Return method
lease confirm the rating frequenc y . And , source power supply and the breaker of this machine are turned OFF at first and are turned ON again.
Attention : Please block t he source power supply (factory power supply) without fail when the wiring is confirmed and readjusted at the time of abnormal.
-13-
Page 15
At the time of the burnout of the e xt e rnal sensor
P
f
Hot-air generator is stopped when the external sensor became the burnout of snapping of a wire etc. in t he case that the temp. of the pl ace t hat parte d i s controll e d by using t he ex t ernal sensor of the opt ion.
"---" is flickered to HOT-AIR TEMP., "TC0" to SETTING TEMP. (EXT. SENSOR lamp is being lighted.)
Main cause
Snapping of a wire of the external sensor
Snapping of a wire of the external sensor
compensating wire Miss of the inlet sensor wiring terminal
Return method
Please disarm by pushing STOP switch after the confirmation of the ext e rnal sensor.
Reverse connecti on by e ac h sensor or detect i on of minus te mp.
Hot-air generator is stopped at the time of the reverse connection of each temp. sensor (External sensor is
included) or perception of -15
C. (Only inside temp. sensor is -10゚C.)
"---" is flickered to HOT-AIR TEMP, display of each sensor to SETTING TEMP
External sensor
Overheat sensor
Inside temp. sensor
Main cause
Reverse connecti on of t he ex t ernal sensor
Reverse connecti on by t he wiring readjustment of
each sensor Atmosphere temp. or suction temp. of minus
Return method
lease disarm by pushing STOP switch after the confirmation of the ext e rnal sensor or the improvement of the minus condition. Please order the repair about except for reverse connection o
: Tc0 Outlet sensor : TcA : TcM Inlet sensor : Tcc : Tcb
the external sensor.
Attention : Please block t he source power supply (factory power supply) without fail when the wiring is confirmed and readjusted at the time of abnormal.
-14-
Page 16
Inquiry regarding the hot-air generator ....
Homepage or, E-mail
www.kansaidennetsu.co.jp sales@kansaidennetsu.co.jp