Kalatec HMI User Manual

HMI connection manual

 

CATALOG

 

1 SERIAL PORT OF HMI ....................................................................................................................

1

1.1

Download port ..........................................................................................................................

1

1.2

PLC port ...................................................................................................................................

3

1.3

Expand port..............................................................................................................................

3

1.4

Ethernet port ............................................................................................................................

5

2 THE CONNECTION OF PLC AND HMI............................................................................................

8

2.1

XINJE FC series PLC ..............................................................................................................

8

 

2.1.1Model ..............................................................................................................................

8

 

2.1.2 Parameters ....................................................................................................................

8

 

2.1.3 Cable making.................................................................................................................

8

 

2.1.4 Device address ..............................................................................................................

9

2.2

XINJE XC series PLC ............................................................................................................

10

 

2.2.1 Model ...........................................................................................................................

10

 

2.2.2 Parameters ..................................................................................................................

10

 

2.2.3 Cable making................................................................................................................

11

 

2.2.4 Device address ............................................................................................................

12

2.3

Mitsubishi FXseries PLC........................................................................................................

14

 

2.3.1Model ............................................................................................................................

14

 

2.3.2 Parameters ..................................................................................................................

14

 

2.3.3 Cable making...............................................................................................................

15

 

2.3.4 Device address ............................................................................................................

16

2.4

Mitsubishi FX3U/G series PLC ..............................................................................................

17

 

2.4 .1 Model ..........................................................................................................................

17

 

2.4 .2 Parameters .................................................................................................................

17

 

2.4 .3 Cable making..............................................................................................................

18

 

2.4 .4 Device address ...........................................................................................................

18

2.5

Mitsubishi FX BD series PLC (RS232/485) ...........................................................................

20

 

2.5.1 Device type ..................................................................................................................

20

 

2.5.2 Parameters ..................................................................................................................

20

 

2.5.3 Cable making...............................................................................................................

21

 

2.5.3 Device address ............................................................................................................

22

2.6

Mitsubishi Q series PLC.........................................................................................................

23

 

2.6 .1 Model ..........................................................................................................................

23

 

2.6.2 Parameters ..................................................................................................................

23

 

2.6.3 Cable making...............................................................................................................

26

 

2.6.4 Device address ............................................................................................................

27

2.7

Siemens S7-200 series PLC ...............................................................................................

29

 

2.7.1Model ............................................................................................................................

29

 

2.7.2 Parameters ..................................................................................................................

29

 

2.7.3 Cable making...............................................................................................................

30

 

2.7.4 Device address ............................................................................................................

30

 

ii

 

2.8 Siemens S7-300/400 series PLC...........................................................................................

32

2.8.1 Model ...........................................................................................................................

32

2.8.2 Parameters ..................................................................................................................

32

2.8.3 Cable making...............................................................................................................

34

2.8.4 Device address ............................................................................................................

35

2.9 OMRON SYSMAC series PLC............................................................................................

36

2.9.1 Device model ...............................................................................................................

36

2.9.2 Parameters ..................................................................................................................

37

2.9.3 Cable making...............................................................................................................

38

2.9.4 Device address ............................................................................................................

39

2.10 Koyo S series PLC...............................................................................................................

41

2.10.1 Device model .............................................................................................................

41

2.10.2 Parameters ................................................................................................................

42

2.10.3 Cable making.............................................................................................................

43

2.10.4 Device address ..........................................................................................................

44

2.11 Koyo DL series PLC .............................................................................................................

45

2.11.1 Device type ................................................................................................................

45

2.11.2 Parameters.................................................................................................................

45

2.11.3 Cable making .............................................................................................................

45

2.11.4 Device address ..........................................................................................................

46

2.12 Delta DVP series PLC..........................................................................................................

47

2.12.1Model ..........................................................................................................................

47

2.12.2 Parameters ................................................................................................................

47

2.12.3 Cable making.............................................................................................................

47

2.12.4 Device address ..........................................................................................................

48

2.13 LG Master-K(CPU Direct) series PLC .................................................................................

49

2.13.1 Device model .............................................................................................................

49

2.13.2 Parameters ................................................................................................................

49

2.13.3 Cable making.............................................................................................................

50

2.13.4 Device address ..........................................................................................................

50

2.14 LG Master-K(Cnet) series PLC............................................................................................

52

2.14.1 Device model .............................................................................................................

52

2.14.2 Parameters ................................................................................................................

52

2.14.3 Cable making.............................................................................................................

53

2.14.4 Device address ..........................................................................................................

54

2.15 LG Glofa(Cnet) series PLC..................................................................................................

55

2.15.1 Device model .............................................................................................................

55

2.15.2 Parameters ................................................................................................................

55

2.15.3 Cable making.............................................................................................................

57

2.15.4 Device address ..........................................................................................................

58

2.16 LG XGT(CPU Direct) series PLC.........................................................................................

60

2.16.1 Device model .............................................................................................................

60

2.16.2 Parameters ................................................................................................................

60

2.16.3 Cable making.............................................................................................................

60

 

iii

2.16.4 Device address ..........................................................................................................

61

2.17 Matsushita MEWNET FP series PLC ..................................................................................

62

2.17.1Device model ..............................................................................................................

62

2.17.2 Parameters ................................................................................................................

63

2.17.3 Cable making.............................................................................................................

64

2.17.4 Device address ..........................................................................................................

65

2.18 Schneider PLC ..................................................................................................................

67

2.18.1Device model ..............................................................................................................

67

2.18.2 Parameters ................................................................................................................

67

2.18.3 Cable making.............................................................................................................

69

2.18.4 Device address ..........................................................................................................

69

2.19 Fatek FB series PLC............................................................................................................

70

2.19.1 Device model .............................................................................................................

70

2.19.2 Parameters ................................................................................................................

70

2.19.3 Cable making.............................................................................................................

71

2.19.4 Device address ..........................................................................................................

72

2.20 Vigor VIGOR PLC ................................................................................................................

73

2.20.1 Device model .............................................................................................................

73

2.20.2 Parameters ................................................................................................................

73

2.20.3 Cable making.............................................................................................................

73

2.20.4 Device address ..........................................................................................................

75

2.21 Fuji SPB series PLC ............................................................................................................

76

2.21.1 Device model .............................................................................................................

76

2.21.2 Parameters ................................................................................................................

76

2.21.3 Cable making.............................................................................................................

76

2.21.4 Device address ..........................................................................................................

77

2.22 Keyence KV series PLC.......................................................................................................

79

2.22.1Device model ..............................................................................................................

79

2.22.2 Parameters ................................................................................................................

79

2.22.3 Cable making.............................................................................................................

79

2.22.4 Device address ..........................................................................................................

81

2.23 Emerson EC20 series PLC..................................................................................................

82

2.23.1Device model ..............................................................................................................

82

2.23.2 Parameters ................................................................................................................

82

2.23.3 Cable making.............................................................................................................

82

2.23.4 Device address ..........................................................................................................

83

2.24 OEMax NX7 series PLC ......................................................................................................

84

2.24.1 Device model .............................................................................................................

84

2.24.2 Device address ..........................................................................................................

84

2.24.3 Cable making.............................................................................................................

84

2.24.4 Device address ..........................................................................................................

86

2.25 Bosch Rexroth IndraControl L40 series PLC.......................................................................

87

2.25.1 Device model .............................................................................................................

87

2.25.2 Parameters ................................................................................................................

87

iv

 

2.25.3 Cable making.............................................................................................................

87

2.25.4 Device address ..........................................................................................................

88

2.26 OPTO 22 SNAP series PLC ................................................................................................

89

2.26.1 Device model .............................................................................................................

89

2.26.2 Parameters ................................................................................................................

89

2.26.3 Cable making.............................................................................................................

89

2.26.4 Device address ..........................................................................................................

90

2.27 SAIA-Burgess PCD series PLC ...........................................................................................

91

2.27.1 Device model .............................................................................................................

91

2.27.2 Parameters ................................................................................................................

92

2.27.3 Cable making.............................................................................................................

92

2.27.4 Device address ..........................................................................................................

96

2.28 Allen-Bradley series PLC .....................................................................................................

96

2.28.1 Device model .............................................................................................................

96

2.28.2 Parameters ................................................................................................................

96

2.28.3 Cable making.............................................................................................................

99

2.28.4 Device address ..........................................................................................................

99

2.29 Xinje V5 series inverter ......................................................................................................

101

2.29.1 Device model ...........................................................................................................

101

2.29.2 Parameters ..............................................................................................................

101

2.29.3 Cable making...........................................................................................................

102

2.30 SHIMADEN ........................................................................................................................

103

2.30.1 Device model ...........................................................................................................

103

2.30.2 Parameters ..............................................................................................................

103

2.30.3 Cable making...........................................................................................................

103

2.30.4 Device address ........................................................................................................

104

2.31 Modbus RTU (panel is Master)..........................................................................................

105

2.31.1 Device model ...........................................................................................................

105

2.31.2 Parameters ..............................................................................................................

105

2.31.3 Cable making...........................................................................................................

105

2.31.4 Device address ........................................................................................................

106

2.32 Modbus ASCII (Panel is Master)........................................................................................

107

2.32.1Device model ............................................................................................................

107

2.32.2 Parameters ..............................................................................................................

107

2.32.3 Cable making...........................................................................................................

107

2.32.4 Device address ........................................................................................................

108

2.33 Modbus slave (panel is Slave)...........................................................................................

109

2.33.1Device model ............................................................................................................

109

2.33.2 Parameters ..............................................................................................................

109

2.33.3 Cable making...........................................................................................................

109

2.33.4 Device address .........................................................................................................

110

2.34 ABB PLC .............................................................................................................................

111

2.34.1Device model .............................................................................................................

111

2.34.2 Parameters ...............................................................................................................

111

 

v

 

2.34.3 Cable making............................................................................................................

112

 

2.34.4 Device address .........................................................................................................

113

2.35 IDEC....................................................................................................................................

114

 

2.35.1 Device type ...............................................................................................................

114

 

2.35.2 Parameters ...............................................................................................................

114

 

2.35.3 Cable making............................................................................................................

114

 

2.35.4 Device address .........................................................................................................

115

2.36 TAIAN ..................................................................................................................................

116

 

2.36.1 Device type ...............................................................................................................

116

 

2.36.2 Parameters ...............................................................................................................

117

 

2.36.3 Cable making............................................................................................................

117

 

2.36.4 Device address .........................................................................................................

118

2.37 YuDian AI ............................................................................................................................

119

 

2.37.1 Device address .........................................................................................................

119

 

2.37.2 Parameters ...............................................................................................................

119

 

2.37.3 Cable making............................................................................................................

119

 

2.37.4 Device address ........................................................................................................

120

2.38 Inovance PLC.....................................................................................................................

121

 

2.38.1 Device type ..............................................................................................................

121

 

2.38.2 Parameter ................................................................................................................

121

 

2.38.3 Cable making...........................................................................................................

122

 

2.38.4 Device address ........................................................................................................

122

2.39

HaiWell PLC ....................................................................................................................

124

 

2.39.1 Device type ..............................................................................................................

124

 

2.39.2 Parameters ..............................................................................................................

124

 

2.39.3 Cable making...........................................................................................................

124

 

2.39.4 Device address ........................................................................................................

125

2.40

Hollias PLC......................................................................................................................

126

 

2.40.1 Device type ..............................................................................................................

126

 

2.40.2 Parameters ..............................................................................................................

126

 

2.40.3 Cable making...........................................................................................................

126

 

2.40.4 Device address ........................................................................................................

127

2.41

Delta (temperature controller) .........................................................................................

128

 

2.41.1 Device type ..............................................................................................................

128

 

2.41.2 Parameters ..............................................................................................................

128

 

2.41.3 Cable making...........................................................................................................

128

 

2.41.4 Device address ........................................................................................................

129

2.42

Siemens S7-1200............................................................................................................

130

 

2.42.1 Device type ..............................................................................................................

130

 

2.42.2 Parameters ..............................................................................................................

130

 

2.42.3 Cable making...........................................................................................................

135

 

2.42.4 Device address ........................................................................................................

136

2.43 Mitsubishi FR series inverter .............................................................................................

137

 

2.43.1 Device type ..............................................................................................................

137

 

 

vi

2.43.2 Parameters ..............................................................................................................

137

2.43.3 Cable making...........................................................................................................

140

2.44 Sanken VM06 inverter .......................................................................................................

141

2.44.1 Device type ..............................................................................................................

141

2.44.2 Parameters ..............................................................................................................

141

2.44.3 Cable making...........................................................................................................

143

2.44.4 Device address ........................................................................................................

143

2.45 XINJE XD/XE series ..........................................................................................................

145

2.45.1 Device type ..............................................................................................................

145

2.45.2 Parameters ..............................................................................................................

145

2.45.3 Cable making...........................................................................................................

146

2.45.4 Device address ........................................................................................................

147

2.46 LG XGB series PLC ...........................................................................................................

149

2.46.1 Device type ..............................................................................................................

149

2.46.2 Parameters ..............................................................................................................

149

2.46.3 Cable making...........................................................................................................

153

2.46.4 Device address ........................................................................................................

154

2.47 Koyo Click series ...............................................................................................................

155

2.47.1 Device type ..............................................................................................................

155

2.47.2 Parameter setting ....................................................................................................

155

2.47.3 Cable making...........................................................................................................

156

2.47.4 Device address ........................................................................................................

156

2.48 Mitsubishi Melsec protocol.................................................................................................

157

2.48.1 Device type ..............................................................................................................

157

2.48.2 Parameter settings...................................................................................................

158

2.48.3 Cable making...........................................................................................................

161

2.48.4 Device address ........................................................................................................

162

2.49 Free type (panel is slave)...................................................................................................

162

2.49.1 Device type ..............................................................................................................

162

2.49.2 Parameter setting ....................................................................................................

163

2.49.3 Cable making...........................................................................................................

165

2.49.4 Device address ........................................................................................................

166

2.50 Modbus-TCP device ..........................................................................................................

166

2.50.1 Device type ..............................................................................................................

166

2.50.2 Parameter setting ....................................................................................................

166

2.50.3 Cable making...........................................................................................................

172

2.50.4 Device address ........................................................................................................

173

2.51 Mitsubishi FX5U series ......................................................................................................

173

2.51.1 Device type ..............................................................................................................

173

2.51.2 Parameter setting ....................................................................................................

173

2.51.3 Cable making...........................................................................................................

177

2.51.4 Device address ........................................................................................................

178

2.52 Siemens S7-200 smart series............................................................................................

179

2.52.1 Device type ..............................................................................................................

179

 

vii

2.52.2 Parameter setting ....................................................................................................

179

2.52.3 Cable making...........................................................................................................

182

2.52.4 Device address ........................................................................................................

184

2.53 Siemens S7-300 series......................................................................................................

185

2.53.1 Device type ..............................................................................................................

185

2.53.2 Parameter setting ....................................................................................................

185

2.53.3 Cable making...........................................................................................................

188

2.53.4 Device address ........................................................................................................

190

2.54 X-NET communication .......................................................................................................

191

2.54.1 Device type ..............................................................................................................

191

2.54.2 HMI setting...............................................................................................................

191

2.54.3 XD series PLC setting (PLC hardware V3.2.2 and up) ...........................................

197

2.54.4 Cable making...........................................................................................................

200

2.54.5 Device address ........................................................................................................

202

2.55 Keyence KV5000 ...............................................................................................................

204

2.55.1 Device type ..............................................................................................................

204

2.55.2 Parameter setting ....................................................................................................

204

2.55.3 Cable making...........................................................................................................

207

2.55.4 Device address ........................................................................................................

208

2.56 LG XGT ..............................................................................................................................

209

2.56.1 Device type ..............................................................................................................

209

2.56.2 Parameter setting ....................................................................................................

209

2.56.3 Cable making............................................................................................................

211

2.56.4 Device address ........................................................................................................

212

2.57 Haiwell................................................................................................................................

213

2.57.1 Device type ..............................................................................................................

213

2.57.2 Parameters ..............................................................................................................

213

2.57.3 Cable making...........................................................................................................

215

2.57.4 Device address ........................................................................................................

216

viii

1 Serial port of HMI

This chapter will introduce the serial port of HMI.

1.1 Download port

The HMI of XINJE TP and TH series are configured PLC port and download port. Next, it will introduce the port and function. The following diagram is the port of TP460-L.

Download port:

 

 

 

 

 

 

 

 

 

 

Pin

Name

Explanation

 

9 8 7 6

 

1

NC

Vacant

 

 

2

RXD

RS232 receive

 

 

 

 

 

 

 

 

 

 

3

TXD

RS232 send

 

 

 

 

 

4

A

RS485 +

 

 

 

 

 

5

GND

Ground

 

 

 

 

 

6

NC

Vacant

5

4

3

2

1

7

B

RS485 -

 

 

 

 

 

8

NC

Vacant

 

 

 

 

 

9

NC

Vacant

1. Choose the device to communicate with download port

(a) Build a new project in Touchwin software, choose download port device

1

(b) For current project, please set it in the Touchwin software:

2. Mode switching for download port

The default mode of TH series download port is communication. But it is download mode for TP series. If the download port of TP series needs to switch to communication mode, two pins of the download port must be shorted. Please see the following diagram.

(1)Cut off the power of TP series HMI, connect pin5 and pin6 of TP download port.

(2)Power on the HMI, take away the connection cable, the download port will be in communication mode.

Note: 1. if the HMI needs to download program, please restart the HMI. 2. Please connect the pin 5 and 6 directly.

2

1.2 PLC port

PLC port:

 

 

 

 

 

 

 

 

 

 

 

 

Pin

Name

Explanation

 

9 8 7 6

 

1

TD+

RS422 send -

 

 

2

RXD

RS232 receive

 

 

 

 

 

 

 

 

 

 

3

TXD

RS232 send

 

 

 

 

 

4

A

RS485 +

 

 

 

 

 

5

GND

Ground

 

 

 

 

 

6

TD-

RS422 send -

5

4

3

2

1

7

B

RS485 -

 

 

 

 

 

 

 

 

8

RDD-

RS422 receive -

 

 

 

 

 

9

RDD+

RS422 receive +

For real application, pelase refer to chapter 2 for cable making. Refer to chapter 1.1 for

download port settings.

1.3 Expand port

Expand port:

 

 

 

 

 

Pin

Definition

Explanation

 

9 8 7 6

 

1

A

RS485 +

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

6

B

RS485 -

5

4

3

2

1

7

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

9

 

 

Note: only TH765-NT3/NU3 has this expand port.

1. choose expand port device

(1) Build a new project, click expand port, and choose the device

3

(2) For existed project, click File/setting/device/expand port to set the PLC model.

4

1.4 Ethernet port

RJ45 Ethernet port:

Pin

Color

Definitio

Explanation

8

 

n

 

1

Orange

TXD+

Data send +

1

white

 

 

 

 

 

2

Orange

TXD-

Data send -

3

Green

RXD+

Data receive +

 

white

 

 

 

4

Blue

-

-

5

Blue

-

-

 

white

 

 

 

6

Green

RXD-

Data receive -

7

Brown

-

-

 

 

5

 

 

white

 

 

8

Brown

-

-

Note: only TG765-ET/TG865-ET/TGA62-ET/TGC65-ET has Ethernet port.

1.Build a new project, choose TG model in the list.

2. Click next, choose net device. Set the IP address of TG series HMI.

6

3. Right click net device, build a new Ethernet device.

Note: this function support local area network, but not support wide area network

7

2 The connection of PLC and HMI

This chapter will introduce the connection between PLC and HMI.

Please don’t pull out or plug the cable when power on, the serial port may be damaged.

2.1 XINJE FC series PLC

2.1.1Model

 

Serie

 

 

CPU

 

 

Connecte

 

 

Port

 

 

Cable

 

 

Device

 

 

s

 

 

 

 

d module

 

 

 

 

making

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU

 

RS232

 

Fig1

 

 

 

 

 

 

 

XC32V2-CPU030427

 

 

direct

 

 

 

 

 

 

Xinje FC

 

FC

 

 

 

 

RS485

 

 

 

 

 

 

-R5

 

 

connectio

 

 

 

 

Fig2

 

series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.1.2 Parameters

HMI parameters:

Parameters

Settings

Choices for settings

Item

PLC type

FC series

 

 

 

 

 

 

Port

RS232

RS232or RS485

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Odd parity

Odd/even/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station No.

0

0~255

 

 

 

 

 

The default communication parameters of FC: 9600, 8, 1, odd parity, station No.0.

2.1.3 Cable making

(a) Connect to FC series CPU (RS232 port)

8

Fig1

(b) Connect to FC series PLC CPU (RS485 port)

Fig2

2.1.4 Device address

PLC address

Range

Data type

Explanation

X

0~337

Bit

External input coil

 

 

 

 

Y

0~337

Bit

External output coil

 

 

 

 

M

0~383

Bit

Internal coil

 

 

 

 

SM

0~96

Bit

Special coil

 

 

 

 

T

0~128

Bit

Timer

 

 

 

 

C

0~128

Bit

Counter

 

 

 

 

W

0~2047

Word/DWord

Data register

 

 

 

 

FW

0~191

Word/DWord

FlashROM register

 

 

 

 

TW

0~127

Word/

Timer register

 

 

 

 

CW

0~127

Word/

Counter register

 

 

 

 

SW

0~111

Word//DWord

Special register

 

 

 

 

WX

0~13

Word//DWord

Input coil register

 

 

 

 

WY

0~13

Word//DWord

Output coil register

 

 

 

 

WM

0~23

Word//DWord

Interla coil register

 

 

 

 

9

2.2 XINJE XC series PLC

2.2.1 Model

 

Series

 

CPU

 

Connected module

 

Port

 

Cable making

 

Device

 

 

 

 

 

CPU

direct

 

RS232

 

Fig1

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

XC1\XC2\

 

 

 

RS485

 

Fig 2

 

Xinje XC

 

XC

 

 

 

 

 

 

 

 

 

 

 

 

XC-RS485-BD

 

RS232

 

Fig 3

 

 

 

XC3\XC5

 

 

 

 

series

 

 

 

 

(communication

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

extension board)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.2.2 Parameters

HMI parameters:

Parameter

Recommend settings

Choices of settings

Item

PLC type

XC series

FC/XC series

 

 

 

 

 

Port

RS232

RS232 or RS485

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station No.

1

0~255

 

 

 

 

 

The default communication parameters of XC: 19200, 8, 1, even, station No.1.

PLC settings:

Open XCPpro software:

10

2.2.3 Cable making

(a) Connect to XC series PLC CPU (RS232 port)

Fig1

(b) Connect to XC series PLC CPU (RS485 port)

Fig2

(c) Connect via XC-RS485-BD (RS232)

11

Fig3

(d) Connect via XC-RS485-BD (RS485)

Fig4

2.2.4 Device address

PLC address

Range

Data type

Explanation

X

0~543

Bit

External input coil

 

 

 

 

Y

0~543

Bit

External input coil

 

 

 

 

M

0~7999

Bit

Internal coil

 

 

 

 

S

0~1023

Bit

Internal coil

 

 

 

 

M8XXX

0~511

Bit

Internal special register

 

 

 

 

T

0~639

Bit

Timer

 

 

 

 

C

0~639

Bit

Counter

 

 

 

 

D

0~7999

Word//DWord

Data register

 

 

 

 

TD

0~639

Word//DWord

Timer register

 

 

 

 

CD

0~639

Word//DWord

Counter register

 

 

 

 

D8XXX

0~511

Word//DWord

Special register

 

 

 

 

FD

0~1535

Word//DWord

FlashROM register

 

 

 

 

FD8XXX

0~511

Word//DWord

Output register

 

 

 

 

ED

0~36862

Word//DWord

Extend register

 

 

 

 

DM

7984

Word

Data register

 

 

 

 

 

 

12

 

DX

0~52

Word

Data register

 

 

 

 

DY

0~52

Word

Data register

 

 

 

 

DS

0~1008

Word

Data register

 

 

 

 

DM8XXX

0~496

Word

Data register

 

 

 

 

DT

0~603

Word

Data register

 

 

 

 

DC

0~619

Word

Data register

 

 

 

 

ID

0~9999

Word//DWord

Analog input

 

 

 

 

QD

0~9999

Word//DWord

Analog output

 

 

 

 

13

2.3 Mitsubishi FXseries PLC

2.3.1Model

 

Series

 

 

CPU

 

 

Connected

 

 

Port

 

 

Cable

 

 

Device

 

 

 

 

 

 

module

 

 

 

 

making

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX0N

 

CPU direct

 

RS422

 

Fig1

 

Mitsubishi FX

 

 

 

 

FX1N

 

connection

 

 

 

series PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX2N

 

RS232-BD

 

RS232

 

Fig 2

 

Mitsubishi

 

 

 

 

FX1S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485\422-B

 

RS485

 

Fig 3

 

 

 

 

 

 

 

 

 

FXBD(232\485)

 

 

 

 

FX3U

 

D

 

 

 

 

 

 

 

 

FX

 

 

 

RS422

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX3G

 

CPU direct

 

 

 

 

 

 

 

Mitsubishi FX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX0

 

 

RS422

 

Fig 1

 

 

 

 

 

 

connection

 

 

 

series PLC

 

 

 

 

FX1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX2

 

CPU direct

 

RS422

 

Fig 4

 

Mitsubishi FX

 

 

 

 

 

connection

 

 

 

series PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3.2 Parameters

HMI settings:

Parameter

Recommend

Choices of settings

Item

 

settings

 

 

PLC type

FX series

 

 

 

 

 

 

Dat bit

7

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/9600/19200/38400/56000/57600/11

 

 

 

5200/187500

 

 

 

 

 

Station No.

0

0~255

 

 

 

 

 

The default parameters of Mitsubishi FX series PLC: 9600, 7, 1, even, station No.0.

PLC settings:

14

2.3.3 Cable making

(a) FX1N\2N\3U\3G\1S series PLC, RS422 port:

Fig1

(b) FX series PLC uses RS232-BD:

Fig2

(c) FX series PLC uses RS485BD:

Fig3

15

(d) FX2 series PLC:

Fig4

2.3.4 Device address

PLC address

Range

Data type

Explanation

X

0~177

Bit

External input coil

 

 

 

 

Y

0~177

Bit

External output coil

 

 

 

 

M

0~8255

Bit

Internal coil

 

 

 

 

S

0~999

Bit

Stepper coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

C16

0~199

Word/DWord

16-bit counter

 

 

 

 

C32

200~255

DWord

32-bit counter

 

 

 

 

D

0~8255

Word/DWord

Data register

 

 

 

 

T

0~255

Word/DWord

Current value

 

 

 

 

X

0~177

Word/DWord

Data register

 

 

 

 

Y

0~177

Word/DWord

Data register

 

 

 

 

M

0~8255

Word/DWord

Data register

 

 

 

 

S

0~999

Word/DWord

Data register

 

 

 

 

16

2.4 Mitsubishi FX3U/G series PLC

2.4 .1 Model

 

 

 

 

 

 

 

Connected

 

 

 

 

 

 

 

 

Choose PLC type

 

 

Series

 

 

CPU

 

 

 

 

Port

 

 

Cable

 

 

in Touchwin

 

 

 

 

 

 

module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

software

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX

 

FX3U

 

CPU

 

RS422

 

Fig 1

 

Mitsubishi

 

 

FX3G

 

 

 

 

FX3U/G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.4 .2 Parameters

HMI settings:

Parameter

Recommended

Choices of settings

Notes

 

settings

 

 

PLC type

Mitsubishi

 

 

 

FX3U/G series

 

 

 

 

 

 

Data bit

7

 

 

 

 

 

 

Stop bit

1

 

 

 

 

 

 

Parity

Even parity

 

 

 

 

 

 

Baud rate

9600

4800/9600/19200/38400/56000/57600/115200/187500

 

 

 

 

 

Station

0

 

 

no.

 

 

 

 

 

 

 

The default parameters of Mitsubishi FX3U/G series PLC: 9600, 7, 1, even parity, station no.0 PLC settings:

17

2.4 .3 Cable making

(a) FX3U\3G series PLC RS422:

2.4 .4 Device address

PLC address

Range

Type

Explanation

X

0~177

Bit

External input terminal

 

 

 

 

Y

0~177

Bit

External output terminal

 

 

 

 

M

0~8255

Bit

Internal auxiliary coil

 

 

 

 

 

 

18

 

S

0~999

Bit

Stepper coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

C16

0~199

Word/DWord

16-bit counter

 

 

 

 

C32

200~255

DWord

32-bit counter

 

 

 

 

D

0~8255

Word/DWord

Data register

 

 

 

 

T

0~255

Word/DWord

Timer current value

 

 

 

 

X

0~177

Word/DWord

Used as data register

 

 

 

 

Y

0~177

Word/DWord

Used as data register

 

 

 

 

M

0~8255

Word/DWord

Used as data register

 

 

 

 

S

0~999

Word/DWord

Used as data register

 

 

 

 

19

2.5 Mitsubishi FX BD series PLC (RS232/485)

2.5.1 Device type

 

 

Series

 

 

CPU

 

 

Connected

 

 

Port

 

 

Cable

 

 

PLC type in

 

 

 

 

 

 

 

module

 

 

 

 

 

 

Touchwin software

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX0N/1N/2

 

232-BD

 

RS232

 

Fig1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX

 

N

 

 

 

 

 

 

 

 

 

 

Mitsubishi FX

 

 

 

FX1S

 

 

 

 

 

 

 

 

 

 

BD(232\485)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FX3U/3G

 

485-BD

 

RS485

 

Fig2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Do not hot plug the device!

2.The driver of 485-BD supports multi-station.

2.5.2 Parameters

HMI settings:

Paramete

Recommend settings

Choices of settings

Notes

rs

 

 

 

PLC type

Mitsubishi FX BD(232\485)

 

 

 

 

 

 

Data bit

7

 

 

 

 

 

 

Stop bit

1

 

 

 

 

 

 

Parity

Even parity

 

 

 

 

 

 

Baud rate

9600

9600/19200/38400/56000/57600

 

 

 

/

 

 

 

115200/187500

 

 

 

 

 

Station

0

0~255

 

no.

 

 

 

 

 

 

 

The default paramreters of Mitsubishi FX BD (232/485): 9600, 7, 1, even parity, station no.0 PLC settings:

20

Note:

1.Please choose RS232 as H/W type when using 232-BD.

2.Please re-power on the PLC after changing the parameters.

2.5.3Cable making

(a)FX series PLC RS232-BD:

Fig1

(b) FX series PLC RS485-BD:

21

Fig2

2.5.3 Device address

PLC

Range

Data type

Explanation

address

 

 

 

X

0~177

Bit

External input terminal

 

 

 

 

Y

0~177

Bit

External output terminal

 

 

 

 

M

0~8255

Bit

Internal auxiliary coil

 

 

 

 

S

0~999

Bi

Stepper coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

C16

0~199

Word/DWord

16-bit counter

 

 

 

 

C32

200~255

DWord

32-bit counter

 

 

 

 

D

0~8255

Word/DWord

Data register

 

 

 

 

T

0~255

Word/DWord

Current value

 

 

 

 

X

0~177

Word/DWord

Used as data register

 

 

 

 

Y

0~177

Word/DWord

Used as data register

 

 

 

 

M

0~8255

Word/DWord

Used as data register

 

 

 

 

S

0~999

Word/DWord

Used as data register

 

 

 

 

22

2.6 Mitsubishi Q series PLC

2.6 .1 Model

MELSEC-Q series include the CPU unit of Q00, Q01, Q00U and so on. They can connect to the HMI via programmable port or communication module (QJ71C24N).

 

Series

 

 

CPU

 

 

Connected module

 

 

Port

 

 

Cable

 

 

Device

 

 

 

 

 

 

 

 

 

 

making

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q00

 

CPU

direct

 

 

 

 

 

 

 

Mitsubishi Q

 

 

 

 

Q01

 

 

RS232

 

Fig 1

 

 

 

 

 

 

connection

 

 

 

 

 

series

 

 

 

 

Q00U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q

 

Q00J Q00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q01 Q02H

 

 

 

 

 

RS232

 

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial communication

 

 

 

 

 

 

 

Mitsubishi Q

 

 

 

 

Q06H Q12H

 

 

 

 

 

 

 

 

 

 

 

 

module QJ71C24

 

 

 

 

 

 

 

series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q25H Q12PH

 

 

 

 

 

RS422

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q25PH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.6.2 Parameters

HMI settings:

Parameter

Recommend

Choices of settings

Item

 

setting

 

 

PLC type

Q series

 

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Odd parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/9600/19200/38400/56000/57600/115200/187500

 

 

 

 

 

Station

0

0~255

 

No.

 

 

 

 

 

 

 

The default parameter of Q series PLC: 19200, 8, 1, odd parity, station No.0.

PLC settings:

1. Q01\Q00 PLC:

23

2 QJ71C24N serial port module

QJ71C24N can connect to CPU and communicate with other devices. Such as Q02CPU, the settings are as the following:

PLC software version v8.26

(a) Double click PLC parameter, choose I/O assignment:

(b) Change the type of item1 to intelli.

(c) Click “switch setting” :

24

Kalatec HMI User Manual

(d) Set the parameter as the following window:

(e) Click End button to finish the settings, then repower on the PLC.

PLC software version v8.8:

For QJ71C24 module RS232, please set the parameter of CH1:

25

For QJ71C24 module RS422, please set the parameter of CH2:

2.6.3 Cable making

(a) Q series PLC CPU unit, RS232 port:

Fig1

26

(b) Q series PLC uses QJ71C24N module RS232:

Fig2

(c) Q series PLC uses QJ71C24 module RS422:

Fig3

2.6.4 Device address

PLC address

Range

Data type

Explanation

X

0~177

Bit

External input coil

 

 

 

 

Y

0~177

Bit

External output coil

 

 

 

 

M

0~8255

Bit

Internal coil

 

 

 

 

S

0~999

Bit

Stepper coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

C16

0~199

Word/DWord

16-bit counter

 

 

 

 

C32

200~255

DWord

32-bit counter

 

 

 

 

D

0~8255

Word/DWord

Data register

 

 

 

 

T

0~255

Word/DWord

Current value

 

 

 

 

X

0~177

Word/DWord

Data register

 

 

 

 

 

 

 

27

Y

0~177

Word/DWord

Data register

 

 

 

 

M

0~8255

Word/DWord

Data register

 

 

 

 

S

0~999

Word/DWord

Data register

 

 

 

 

28

2.7 Siemens S7-200 series PLC

2.7.1Model

Seris

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

 

CPU212

 

 

 

 

 

 

 

 

 

 

CPU221

 

Connect CPU RS485 port

 

 

 

 

 

Siemens

S7-200

 

CPU222

 

 

RS485

 

Fig 1

 

 

 

directly

 

 

 

S7-200

 

 

CPU224

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU226

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S7-200

 

Smart series

 

CPU directly connect

 

RS485

 

Fig1

 

Siemens

smart

 

 

 

 

 

S7-200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.7.2 Parameters

HMI:

Parameters

Recommend

Choices of settings

Item

 

settings

 

 

PLC type

S7-200

 

 

 

 

 

 

Port

RS485

 

 

 

 

 

 

Data bit

8

 

 

 

 

 

 

Stop

1

 

 

 

 

 

 

Parity

Even parity

 

 

 

 

 

 

Baud rate

9600

9600/19200/187500

 

 

 

 

 

Station no.

2

 

Must use recommend

 

 

 

settings

 

 

 

 

The default communication parameters of Siemens S7-200 series PLC: 9600, 8, even parity, station No.2.

PLC settings:

29

Notes:

1.Siemens PLC has 3 kinds of registers: 8-bitVB, 16-bit VW and 32-bit VD.

2.The space of registers are overlapped, the address of VW must be even numbers, for example: VW0 VW2…., the address of VD must be the multiple of 4, such as VD0 VD4

VD8…..

3 For Data block PSW single word VW single word: as the high byte and low byte problem, the received data maybe dislocated, please use register copy function.

4 For data block PSW single word VD double words: as the unit is different, cannot trasfer the data like this, please use register copy function.

2.7.3 Cable making

HMI connects to S7-200 via RS485:

Fig1

2.7.4 Device address

SIMATIC S7-200 series

30

PLC address

Range

Data type

Explanation

VB

0~4095

Byte

variable byte data register

 

 

 

 

VW

0~4095

Word

variable word data register

 

 

 

 

VD

0~4095

DWord

variable double word data register

 

 

 

 

IB

0~15

Byte

External input byte reflection register

 

 

 

 

IW

0~15

Word

External input word reflection register

 

 

 

 

ID

0~15

DWord

External input double words reflection

 

 

 

register

 

 

 

 

QB

0~15

Byte

External output byte reflection register

 

 

 

 

QW

0~15

Word

External output word reflection register

 

 

 

 

QD

0~15

DWord

External output double words reflection

 

 

 

register

 

 

 

 

MB

0~31

Byte

Internal auxiliary byte register

 

 

 

 

MW

0~31

Word

Internal auxiliary word register

 

 

 

 

MD

0~31

DWord

Internal auxiliary double words register

 

 

 

 

SMB

0~299

Byte

Internal special auxiliary byte register

 

 

 

 

SMW

0~299

Word

Internal special auxiliary word register

 

 

 

 

SMD

0~299

DWord

Internal special auxiliary double words

 

 

 

register

 

 

 

 

SB

0~31

Byte

Special auxiliary byte register

 

 

 

 

SW

0~31

Word

Special auxiliary word register

 

 

 

 

SD

0~31

DWord

Special auxiliary double words register

 

 

 

 

T

0~255

Word

Register

 

 

 

 

C

0~255

Word

Register

 

 

 

 

M

0~31

Bit

Bit register

 

 

 

 

V

0~4095

Bit

Variable register

 

 

 

 

I

0~15

Bit

External input coil

 

 

 

 

Q

0~15

Bit

External output coil

 

 

 

 

SM

0~299

Bit

Special relay

 

 

 

 

S

0~31

Bit

Sequence relay

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

31

2.8 Siemens S7-300/400 series PLC

2.8.1 Model

SIMATIC S7-300/400 PLC (connect to CPU directly)

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

S7-300

 

CPU312 CPU314

 

 

 

 

 

 

 

Siemens SIMATIC

 

 

CPU315

 

RS485 port of CPU

 

 

 

 

 

 

 

 

 

RS485

 

fig 1

 

S7-300/400

 

 

 

 

 

 

 

 

S7-400

 

CPU412-1 CPU412-2

 

 

 

 

 

 

 

 

 

 

 

 

 

PLC

 

 

CPU414-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.8.2 Parameters

HMI settings:

Parameter

Recommend

Choice of settings

Note

 

 

settings

 

 

 

PLC type

S7-300/400

 

 

 

 

 

 

 

 

Port

RS485

 

 

 

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

 

 

Station

2

 

Please

use

no.

 

 

recommend settings

 

 

 

 

 

The default parameters of Siemens S7-300\400: 19200, 8, even parity, station No.2.

PLC settings:

32

Communication notes for S7-300:

1. Siemens baud rate must set to 19200 kbps; don’t set the parameters of PG/PC adapter. 2. Don’t modify the “panel station no.” in the Touchwin software.

33

3.Cable: no need PG/PC adapter

4.Please define the DB register in the PLC when testing the communication.

5.Please note that the port will be operated in PLC program by accident.

6.The default station No. of S7-300 is 2, please don’t modify it.

Example: MPI port of S7-300 connects to HMI, the PLC connects to SCADA software via Ethernet module, PLC station no. is 8, module station no. is 3, HMI station no. is 0. The result is that communication between SCADA and PLC will be cut off. Because the HMI cannot find other devices and modules cannot be inserted in. please change the PLC station no. to 2. These devices can form a loop:

2.8.3 Cable making

HMI connects to S7-300/400 via RS485:

34

 

 

SIEMENS PLC

HMI 9-pin female port

S7-200/300/400

PPI 9-pin male port

 

 

Pin

Name

Pin

Name

4

AI

3

A

5

GND

8

B

7

BI

5

GND

Fig1

2.8.4 Device address

SIMATIC S7-300/400

PLC type

Range

Data type

Explanation

I

0~9999

Byte/Word/DWord

External input register

 

 

 

 

Q

0~9999

Byte/Word/DWord

External output register

 

 

 

 

M

0~9999

Byte/Word/DWord

Internal auxiliary register

 

 

 

 

DB0~DB20

0~9999

Byte/Word/DWord

Data register

 

 

 

 

I

0~9999

Bit

External input coil

 

 

 

 

Q

0~9999

Bit

External output coil

 

 

 

 

M

0~9999

Bit

Internal auxiliary relay

 

 

 

 

DB0~DB20

0~9999

Bit

Internal auxiliary relay

 

 

 

 

35

2.9 OMRON SYSMAC series PLC

OMRON CPM1A, CQM1-CPU series CPU cannot support RS232. It can connect to the Touchwin HMI via

CPM1-CIF01 adapter and modules including C500-LK203, C120-LK201-V1, C500-LK201-V1. The PLC uses Hostlink protocol when communicating. Please change the PLC startup choice to MONITOR RUN.

2.9.1 Device model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The PLC

 

 

 

 

 

Series

 

 

CPU

 

 

Connected

 

 

Communication

 

 

Cable

 

 

device in

 

 

 

 

 

 

 

 

 

module

 

 

mode

 

 

 

 

TouchWin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CP

 

CP1E-30N

 

CPU

direct

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

CP1H

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CP1L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module

 

 

 

RS485

 

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CP1W-CIF11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module

 

 

 

RS422

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CP1W-CIF11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ

 

CJ1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ1G-CPU44

 

CPU direct

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ1G-CPU45

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CJ2M-CPU11

 

 

 

 

 

 

 

 

 

 

 

 

 

Omron

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CP/CJ/CS

 

 

 

CS1

 

CS1H-CPU63/64/65/66/67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1G-CPU42/43/44/45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1G-CPU42H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1G-CPU43H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1G-CPU44H

 

CPU direct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1G-CPU45H

 

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1H-CPU63H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1H-CPU64H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1H-CPU65H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1H-CPU66H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1H-CPU67H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The PLC

 

 

Series

 

 

CPU

 

 

 

Connected module

 

 

Communication

 

 

Cable

 

 

device in

 

 

 

 

 

 

 

 

 

mode

 

 

 

 

TouchWin

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

C200HE

CPU direct connection

 

 

 

 

C200HX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C1000HF

C500-LK203 (communication

 

 

 

 

 

module)

 

 

 

 

 

 

 

 

 

 

 

C120-LK201-V1(communication

RS232

Fig 1

 

 

 

module)

 

 

 

 

 

 

 

 

 

 

 

 

 

C2000

C500-LK201-V1(communication

 

 

 

 

module)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C500-LK203(communication

 

 

Omron

 

 

 

 

 

 

 

module)

 

 

CPM/CQM

 

 

 

 

 

CPM

CPM2A

 

 

 

 

 

CPM2AE

CPU direct connection

 

 

 

 

CPM2AH-40CDR-A

 

 

 

 

 

 

 

 

 

CPM1H

 

 

 

 

 

 

 

 

 

 

 

CPM1A

OMRON CIF01 (RS232)

RS232

Fig 1

 

 

 

 

 

 

 

Communication adapter

 

 

 

 

 

 

 

 

 

CQM

CQM1H-CPU21

CPU direct connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CQM1-CPU

OMRON CIF01 (RS232)

 

 

 

 

 

Communication adapter

 

 

 

 

 

 

 

 

 

2.9.2 Parameters

HMI:

The default parameters of OMRON CP/CJ/CS series PLC: 9600, 7, 2, even parity, station no.0. The default parameters of OMRON CPM/CQM series PLC: 9600, 7, 2, even parity, station no.0.

Parameter

Recommended settings

Choices of settings

Notes

PLC type

OMRON CPM/CQM series

OMRON CP/CJ/CS series

 

 

OMRON CP/CJ/CS series

OMRON CPM/CQM series

 

 

 

 

 

Port

RS232

RS232/RS485

 

 

 

 

 

Data bit

7

7 or 8

 

 

 

 

 

Stop bit

2

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/ no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200

 

 

 

/19200/187500

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

37

2.9.3 Cable making

(a) CPU RS232 port:

 

 

OMROM PLC

 

 

CPU CPM1-CIF01/C500-LK203

 

 

C120-LK201-V1/C500-LK203

HMI 9-pin female port

RS232 9-pin male port

Pin

Name

Pin

Name

2

RXD1

3

RD

3

TXD1

2

SD

5

GND

9

GND

 

 

4

RTS

 

 

5

CTS

Fig1

(b) Through module CP1W-CIF11 RS485:

Fig2

Note: If OMRON RS485 module CPIW-CIF11 uses 485-2 connection mode, turn OFF the SW1 switch on the module, turn ON SW2, 3, 5, 6. SW4 is selectable.

(c) Through the module CP1W-CIF11 RS422:

Fig3

38

Note: If OMRON RS485 module CP1W-CIF11 uses RS422 connection mode, turn OFF the SW1~6 on the module.

2.9.4 Device address

(a) SYSMAC CPM/CQM series

 

PLC address

Range

Data type

Explanation

 

 

IR

0~65535

Bit

I/O and internal relay

 

 

 

 

 

 

 

 

SR

244~65535

Bit

Relay

 

 

 

 

 

 

 

 

HR

0~65535

Bit

Holding relay

 

 

 

 

 

 

 

 

AR

0~65535

Bit

Auxiliary relay

 

 

 

 

 

 

 

 

LR

0~65535

Bit

Link relay

 

 

 

 

 

 

 

 

PV

0~65535

Bit

Current value of timer and

 

 

 

 

 

counter

 

 

 

 

 

 

 

 

TC

0~65535

Bit

Timer and counter

 

 

 

 

 

 

 

 

IR

0~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

SR

244~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

HR

0~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

AR

0~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

LR

0~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

PV

0~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

TC

0~65535

Word/DWor

Register

 

 

 

 

d

 

 

 

 

 

 

 

 

 

DM

0~65535

Word/DWor

Data register (single/double

 

 

 

 

d

words)

 

 

 

 

 

 

 

(b) SYSMAC CP/CJ/CS series

 

 

 

 

 

 

 

 

 

 

PLC address

Range

Data type

Explanation

 

 

CIO

0~9999

Bit

 

 

 

 

 

 

 

 

 

D

0~99999

Bit

 

 

 

 

 

 

 

 

 

H

0~9999

Bit

 

 

 

 

 

 

 

 

 

W

0~9999

Bit

 

 

 

 

 

 

 

 

 

A

0~9999

Bit

 

 

 

 

 

 

 

 

 

T

0~9999

Bit

Timer

 

 

 

 

 

 

 

 

C

0~9999

Bit

Counter

 

 

 

 

 

 

 

 

 

 

39

 

 

CIO

0~9999

Word/DWor

Register

 

 

d

 

 

 

 

 

D

0~99999

Word/DWor

Register

 

 

d

 

 

 

 

 

H

0~9999

Word/DWor

Register

 

 

d

 

 

 

 

 

W

0~9999

Word/DWor

Register

 

 

d

 

 

 

 

 

A

0~9999

Word/DWor

Register

 

 

d

 

 

 

 

 

T

0~9999

Word/DWor

Register

 

 

d

 

 

 

 

 

C

0~9999

Word/DWor

Register

 

 

d

 

 

 

 

 

40

2.10 Koyo S series PLC

Koyo KOSTA-S and Direct-Logic series PLC

2.10.1 Device model

(a) Kostac S series SH\SM\SN PLC (direct connect to the CPU module)

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

 

 

 

 

 

 

 

 

 

 

SH series

 

SH-48RS

 

CPU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM series

 

SM24-T

 

 

RS232

 

Fig1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SN series

 

 

 

 

 

 

 

 

 

Koyo S series

 

 

 

 

 

 

 

 

 

 

SU-6

 

 

 

CPU

 

RS232

 

Fig1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SU-6B

 

 

 

 

RS232

 

Fig1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS422

 

Fig3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Koyo SH-48RS doesn’t have Run, Stop switch, but only have one AMP port.

(b) Koyo Kostac S series SG-8, SU-5, SU-6, SR-21, SR-22… PLC (use communication module)

CPU

 

Connected module

 

 

Port

 

Cable

 

Device

 

 

 

 

 

 

 

 

 

 

SG-8

G01-DM communication unit

 

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

RS422

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SU-5

U01-DM communication unit

 

 

RS232

 

Fig 1

 

Koyo S series

 

 

 

 

 

 

 

SU-6

 

U01-DM communication unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SR-21

 

E-02DM-R1 communication unit

 

 

RS422

 

Fig 3

 

 

 

 

 

 

 

 

 

 

SR-22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(c) Koyo Direct Logic series DL05, DL250…PLC (connect to CPU directly)

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

 

Device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DL05

 

 

 

 

 

 

 

 

 

 

 

DL105

 

 

 

 

 

 

 

 

 

 

 

DL230

 

Connect to RJ-11port(RS232) of CPU

 

 

 

 

 

 

 

 

 

DL240

 

 

RS232

 

Fig 2

 

 

 

Direct Logic

 

 

 

 

 

 

 

Koyo S series

 

DL250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DL350

 

 

 

 

 

 

 

 

 

 

 

DL450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DL250

Connect to the port of CPU

 

RS422

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

DL430

Connect to the port of CPU

 

 

 

 

DL440

 

RS232

Fig 2

 

 

DL450

 

 

 

 

 

 

 

 

DL350

 

 

 

 

 

 

 

 

 

 

Note: port2 of DL250CPU has RS232 and RS422; please indentify them when making the cable.

2.10.2 Parameters

HMI:

Parameter

Recommend settings

Choices of settings

Notes

PLC

Koyo S series PLC

 

 

 

 

 

 

Port

RS232

RS232 or RS422

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Odd parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

The default communication parameters of Koyo S series PLC: 9600, 8, 1, odd parity, station no.0.

PLC:

42

Note: 1. Koyo K protocol cannot modify station no., the station no. is 0 in the HMI.

2.The register address starts from R2000.

2.10.3Cable making

(a) RS232 25-pin port on CPU or communication unit:

Fig1

RJ-11 6-pin RS232 female port on the CPU:

6 5 4 3 2 1

Fig2

RS422 connection:

43

Fig3

2.10.4 Device address

PLC address

Range

Data type

Explanation

M

0~777

Bit

Internal auxiliary coil

 

 

 

 

I

0~777

Bit

External input coil

 

 

 

 

Q

0~777

Bit

External output coil

 

 

 

 

SP

0~777

Bit

Internal auxiliary coil

 

 

 

 

T

0~777

Bit

Timer

 

 

 

 

C

0~777

Bit

Counter

 

 

 

 

S

0~777

Bit

Stepper coil

 

 

 

 

R

0~41200

Word/DWor

Data register

 

 

d

 

 

 

 

 

44

2.11 Koyo DL series PLC

2.11.1 Device type

Koyo Direct Logic series DL05, DL250 PLC (direct connect to CPU)

Series

 

CPU

 

Connected

 

 

Port

 

Cable

 

Choose PLC type in

 

 

 

 

module

 

 

 

 

 

 

Touchwin software

 

 

DL05

 

 

 

 

 

 

 

 

 

 

 

DL105

 

Connect to

 

 

 

 

 

 

 

 

 

DL230

 

CPU RJ-11

 

 

RS232

 

Fig 1

 

 

Direct

 

DL240

 

port

 

 

 

 

 

 

 

 

DL250

 

 

 

 

 

 

 

 

Koyo DL series

Logic

 

 

 

 

 

 

 

 

 

 

DL350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DL430

 

Connect

to

 

RS422

 

Fig 2

 

 

 

 

DL440

 

CPU com port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DL450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: the port2 of DL250 has RS232 and RS422, please indentify the cable connection for them.

2.11.2 Parameters

HMI settings:

Parameter

Recommend

Choices of settings

Note

s

settings

 

 

PLC type

Koyo DL series

 

 

 

 

 

 

Port

RS232

RS232/RS422

 

 

 

 

 

Data bit

8

7/8

 

 

 

 

 

Stop bit

1

1/2

 

 

 

 

 

Parity

Odd parity

Even /odd /no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200/19200/18750

 

 

 

0

 

 

 

 

 

Station no.

0

0-255

 

 

 

 

 

2.11.3 Cable making

RS232 Connection:

45

Fig1

RS422 connection:

Fig2

2.11.4 Device address

Device address

Range

Data type

Explanation

V

0 41200

Word/DWord

Data register

 

 

 

 

C

0 777

Bit

Counter

 

 

 

 

X

0 777

Bit

Input

 

 

 

 

Y

0 777

Bit

Output

 

 

 

 

SP

0 777

Bit

Auxiliary relay

 

 

 

 

T

0 777

Bit

Timer

 

 

 

 

CT

0 777

Bit

Counter

 

 

 

 

S

0 777

Bit

Auxiliary relay

 

 

 

 

V

0.0 41200.15

Bit

Auxiliary relay

 

 

 

 

46

2.12 Delta DVP series PLC

2.12.1Model

 

Delta DVP series

CPU

 

Connected module

 

Port

 

Cable

 

Deivce

 

ES\EH\EX

 

 

 

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Direct connect to the CPU

 

RS485

 

Fig 2

 

Delta DVP series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SS\SA\SC\SX

 

 

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.12.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Notes

PLC type

Delta DVP series

 

 

 

 

 

 

Port

RS232

RS232 or RS485

 

 

 

 

 

Data bit

7

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default communication parameters of Delta DVP series PLC: 9600, 7, 1, even parity, station no.1.

2.12.3 Cable making

(a) The RS232 port on CPU:

Fig 1

47

(b) RS485 port on the CPU:

Fig2

2.12.4 Device address

PLC address

Range

Data type

Explanation

X

0~377

Bit

External input coil

 

 

 

 

Y

0~377

Bit

External output coil

 

 

 

 

M

0~1279

Bit

Internal auxiliary relay

 

 

 

 

S

0~1023

Bit

Stepper coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

D

0~1279

Word/DWor

Data register

 

 

d

 

 

 

 

 

TD

0~255

Word/DWor

Current value of timer

 

 

d

 

 

 

 

 

CD

0~255

Word/DWor

Current value of counter

 

 

d

 

 

 

 

 

S

0~1023

Word/DWor

Data register

 

 

d

 

 

 

 

 

X

0~377

Word/DWor

Data register

 

 

d

 

 

 

 

 

Y

0~377

Word/DWor

Data register

 

 

d

 

 

 

 

 

M

0~127

Word/DWor

Data register

 

 

d

 

 

 

 

 

48

2.13 LG Master-K(CPU Direct) series PLC

LG Master-K series PLC support CPU(RS232) and Cnet module communication mode. This chapter will introduce CPU mode.

2.13.1 Device model

 

Series

 

Connected module

 

Port

 

Cable

 

Device

 

K80

 

CPU

 

RS232

 

Fig 1

 

LG Master-K80/120 series

 

K120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: before communicating, please write “END” instruction to the PLC. Otherwise, the PLC will report an error and the ERR LED will light.

2.13.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Notes

PLC type

LG Master-K80/120 series

 

 

 

PLC

 

 

 

 

 

 

Port

RS232

RS232

 

 

 

 

 

Dat bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

No parity

Even/odd/no parity

 

 

 

 

 

Baud rate

38400

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

The default communication parameters of LG Master K: 38400, 8, 1, no parity, station no.0.

PLC:

49

2.13.3 Cable making

Master-K 80\120 RS232:

Fig1

2.13.4 Device address

LGMaster-K80/120 series PLC

PLC address

Range

Data type

Explanation

M

0~9999F

Bit

Internal auxiliary relay

 

 

 

 

L

0~9999F

Bit

Link relay

 

 

 

 

K

0~9999F

Bit

Holding relay

 

 

 

 

T

0~9999

Bit

Timer

 

 

 

 

C

0~9999

Bit

Counter

 

 

 

 

P

0~9999F

Bit

I/O coil

 

 

 

 

D

0~9999

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

 

50

 

TD

0~9999

Word/DWor

Current value of timer

 

 

d

 

 

 

 

 

CD

0~9999

Word/DWor

Current value of counter

 

d

 

 

 

 

 

 

 

 

S

0~9999

Word/DWor

Used as register

 

 

d

 

 

 

 

 

K

0~9999

Word/DWor

Used as register

 

 

d

 

 

 

 

 

M

0~9999

Word/DWor

Used as register

 

 

d

 

 

 

 

 

L

0~9999

Word/DWor

Used as register

 

 

d

 

 

 

 

 

F

0~9999

Word/DWor

Used as register

 

 

d

 

 

 

 

 

P

0~9999

Word/DWor

Used as register

 

 

d

 

 

 

 

 

51

2.14 LG Master-K(Cnet) series PLC

LG Master-K80/120 series PLC Cnet communication module

LG Master-K series PLC support CPU(RS232) and Cnet expansion port communication mode. This chapter will introduce Cnet mode.

2.14.1 Device model

 

Series

 

Connected module

 

Port

 

Cable

 

Device

 

K80

 

Cnet communication module

 

RS232

 

Fig 1

 

LG Master-K80/120 Cnet series

 

K120

 

 

 

 

 

 

 

 

 

RS485

 

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

1.For Master K-cnet communication, turn ON DIP switch 2, turn OFF DIP switch 1. For LG Master KxxxS communication, keep the DIP switch to default settings.

2.LG Master KxxxS CPU only supports RS232 connection. Cnet communication module supports RS232 and RS485 connection.

2.14.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Notes

PLC type

LG Master-K80/120 (Cnet series PLC

 

 

 

 

 

 

Port

RS232

RS232

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200

 

 

 

/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of LG Master K-cnet : 9600, 8, 1, even parity, station no.1.

PLC:

Notes:

1.Turn on the switch BUILT-IN CNET on the PLC.

2.Choose the correct channel, protocol and mode.

0-RS232 communication:

52

1-RS485 communication:

2.14.3 Cable making

(a) Master K-cnet protocol RS232:

53

Fig 1

(b) Master K-cnet protocol RS485-2:

Fig 2

2.14.4 Device address

LGMaster-K80/120 Cnet series PLC

PLC address

Range

 

 

Data type

Explanation

M

0~9999F

 

Bit

Internal auxiliary relay

 

 

 

 

 

L

0~9999F

 

Bit

Link relay

 

 

 

 

 

K

0~9999F

 

Bit

Holding relay

 

 

 

 

 

 

T

0~9999

 

 

Bit

Timer

 

 

 

 

 

 

C

0~9999

 

 

Bit

Counter

 

 

 

 

 

P

0~9999F

 

Bit

I/O coil

 

 

 

 

 

 

D

0~9999

 

 

Word/DWor

Data register

 

 

 

 

d

 

 

 

 

 

 

 

TD

0~9999

 

 

Word/DWor

Current value of timer

 

 

 

 

d

 

 

 

 

 

 

 

CD

0~9999

 

 

Word/DWor

Current value of counter

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

S

0~9999

 

 

Word/DWor

Used as register

 

 

 

 

d

 

 

 

 

 

 

 

K

0~9999

 

 

Word/DWor

Used as register

 

 

 

 

d

 

 

 

 

 

 

 

M

0~9999

 

 

Word/DWor

Used as register

 

 

 

 

d

 

 

 

 

 

 

 

L

0~9999

 

 

Word/DWor

Used as register

 

 

 

 

d

 

 

 

 

 

 

 

F

0~9999

 

 

Word/DWor

Used as register

 

 

 

 

d

 

 

 

 

 

 

 

P

0~9999

 

 

Word/DWor

Used as register

 

 

 

 

d

 

 

 

 

 

 

 

54

2.15 LG Glofa(Cnet) series PLC

2.15.1 Device model

Series

CPU

Connected module

Port

Cable

Device

Glofa

G7M-DR20A

CPU RS232

RS232

Fig 1

LG Glofa Cnet series

 

 

 

 

 

 

Note: please turn on DIP switch2 and turn off switch1 for LG Glofa -cnet communication.

2.15.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Note

PLC type

LG Glofa (cnet)

 

 

 

 

 

 

Port

RS232

RS232

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

No parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

The default parameters of LG Glofa –Cnet: 19200, 8, 1, no parity, station no.0

PLC:

Note:

1.Turn on the switch BUILT-IN CNET on the PLC.

2.“Dedicated-slave” must be choosed in the PLC programming software.

3.The communication area of M must be set in the PLC programming software.

M area size:

Protocol and mode settings:

55

56

2.15.3 Cable making

LG Glofa –Cnet RS232:

Fig 1

57

2.15.4 Device address

PLC type

Range

Data type

Explanation

 

 

 

 

M

0~16383

Bit

Internal auxiliary relay

 

 

 

 

IX

0.0.0-.0.0.11

Bit

External input coil

 

 

 

 

 

0.0.12~0.0.6

Bit

Internal auxiliary input coil

 

3

 

 

 

 

 

 

 

0.1.0~0.1.63

Bit

Internal auxiliary input coil

 

 

 

 

 

0.2.0~0.2.63

Bit

Internal auxiliary input coil

 

 

 

 

 

0.3.0~0.3.63

Bit

Internal auxiliary input coil

 

 

 

 

 

0.4.0~0.4.63

Bit

Internal auxiliary input coil

 

 

 

 

 

0.5.0~0.5.63

Bit

Internal auxiliary input coil

 

 

 

 

 

0.6.0~0.6.63

Bit

Internal auxiliary input coil

 

 

 

 

 

0.7.0~0.7.63

Bit

Internal auxiliary input coil

 

 

 

 

QX

0.0.0~0.0.11

Bit

External output coil

 

 

 

 

 

0.0.12~0.0.6

Bit

Internal auxiliary output coil

 

3

 

 

 

 

 

 

 

0.1.0~0.1.63

Bit

Internal auxiliary output coil

 

 

 

 

 

0.2.0~0.2.63

Bit

Internal auxiliary output coil

 

 

 

 

 

0.3.0~0.3.63

Bit

Internal auxiliary output coil

 

 

 

 

 

0.4.0~0.4.63

Bit

Internal auxiliary output coil

 

 

 

 

 

0.5.0~0.5.63

Bit

Internal auxiliary output coil

 

 

 

 

 

0.6.0~0.6.63

Bit

Internal auxiliary output coil

 

 

 

 

 

0.7.0~0.7.63

Bit

Internal auxiliary output coil

 

 

 

 

IW

0.0.0~0.0.3

Word/DWor

Data register

 

 

d

 

 

0.1.0~0.1.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.2.0~0.2.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.3.0~0.3.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.4.0~0.4.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.5.0~0.5.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.6.0~0.6.3

Word/DWor

Data register

 

 

d

 

 

0.7.0~0.7.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

58

QW

0.0.0~0.0.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.1.0~0.1.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.2.0~0.2.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.3.0~0.3.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.4.0~0.4.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.5.0~0.5.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.6.0~0.6.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

 

0.7.0~0.7.3

Word/DWor

Data register

 

 

d

 

 

 

 

 

MW

0~4095

Word

Data register

 

 

 

 

 

0~4095

Regs

Data register

 

 

 

 

MD

0~2047

DWord

Data register

 

 

 

 

 

0~2038

Regs

Data register

 

 

 

 

59

2.16 LG XGT(CPU Direct) series PLC

2.16.1 Device model

 

Series

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

XGT

 

 

CPU RS232

 

RS232

 

Fig 1

 

LG XGT series

 

 

 

 

 

 

CPU Direct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.16.2 Parameters

HMI:

Parameter

Recommend settings

Choices of settings

Note

PLC type

LG XGT series CPU Direct

 

 

 

 

 

 

Port

RS232

RS232

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

No parity

Even/odd/no parity

 

 

 

 

 

Baud rate

115200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of LG XGT series PLC CPU Direct : 115200, 8, 1, no parity, station

no.1

Note: XGT series CPU Direct only supports the baud rate 115200 and cannot modify the station no.

2.16.3 Cable making

Fig1

60

2.16.4 Device address

PLC address

Range

Data type

 

Explanation

 

 

 

 

 

P

0.0~65535.F

Bit

 

External I/O coil

 

 

 

 

 

 

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

M

0.0~65535.F

Bit

 

Internal auxiliary output coil

 

 

 

 

 

 

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

L

0.0~65535.F

Bit

 

External output coil

 

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

F

0.0~65535.F

Bit

 

Data register

 

 

 

 

 

 

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

T

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

65535

Bit

 

Counter

 

 

 

 

 

C

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

65535

Bit

 

Counter

 

 

 

 

 

D

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

0.0~65535.F

Bit

 

Relay

 

 

 

 

 

S

65535

Bit

 

Relay

 

 

 

 

 

K

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

0.0~65535.F

Bit

 

Relay

 

 

 

 

 

Z

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

0.0~65535.F

Bit

 

Relay

 

 

 

 

 

N

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

0.0~65535.F

Bit

 

Relay

 

 

 

 

 

R

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

0.0~65535.F

Bit

 

Relay

 

 

 

 

 

ZR

65535

Word/DWor

 

Data register

 

 

d

 

 

 

 

 

 

 

 

0.0~65535.F

Bit

 

Relay

 

 

 

 

 

TS

65535

Word

 

Data register

 

 

 

 

 

 

 

 

61

CS

65535

DWord

Data register

 

 

 

 

2.17 Matsushita MEWNET FP series PLC

2.17.1Device model

MatsushitaMewnet FP series PLC include FP0, FP1, FP3, FP2SF, FP10SH and so on. They can communicate with Xinje HMI via the programming port or communication port on the CPU. FP0-CXXCXX only supports RS232 connection.

 

Series

 

CPU

 

 

Connected module

 

Port

 

Cable

 

Device

 

 

 

FP0

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP M

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP X

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP∑

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP2

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU RS232 com port

 

RS232

 

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP2SH

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Matsushita FP0/FP1

 

FP

 

 

CPU RS232 com port

 

RS232

 

Fig 2

 

 

 

 

 

 

 

series

 

 

 

 

 

CPU RS232 com port

 

RS232

 

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU

RS232

programming

 

RS422

 

Fig 3

 

 

 

 

 

 

 

port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP3

 

CPU

RS422

programming

 

RS422

 

Fig 4

 

 

 

 

 

 

port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP10SH

 

CPU RS232 com port

 

RS232

 

Fig 2

 

 

 

 

 

FP10S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP-E

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

2.17.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Note

PLC type

matsushita FP series PLC

 

 

 

 

 

 

Port

RS232

 

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Odd parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of Matsushita FP series PLC: 9600, 8, 1, odd parity, station no.1

PLC:

Note:

1 PLC soft component input example:

LC

HMI

 

 

R45

 

 

 

Y1

 

 

 

63

2 When making the PLC program, set the switch to PPOG; set the switch to RUN when

communicating.

3 Do not choose <Common communication mode>, otherwise, the communication will

be error.

4 FP series PLC default station no. is 1, please note FP3 series PLC station no. must set

to 0.

2.17.3 Cable making

(a) CPU 5-pin DIN port:

Fig1

(b) CPU 9-pin port:

Fig2

64

(c) CPU 8-pin port:

Fig3

(d) CPU 15-pin port:

Fig4

2.17.4 Device address

PLC address

Range

Data type

Explanation

X

0~12 0~F

Bit

External input coil (bit)

 

 

 

 

WX

0~12

Word/DWor

Single/double words register

 

 

d

 

 

 

 

 

Y

0~12 0~F

Bit

External output coil (bit)

 

 

 

 

WY

0~12

Word/DWor

Single/double words register

 

 

d

 

 

 

 

 

R

0~62

Bit

Internal auxiliary coil (bit)

 

90~903

 

 

 

 

 

 

WR

0~65535

Word/DWor

Single/double words register

 

 

d

 

 

 

 

 

T

0~99

Bit

Timer

 

 

 

 

L

65535F

Bit

Link coil

 

 

 

 

 

 

 

65

C

100~143

Bit

Counter

 

 

 

 

 

 

 

 

SV

0~143

Word/DWor

Setting register

 

 

 

 

d

 

 

 

 

 

 

 

EV

0~143

Word/DWor

Real value of counter or timer

 

 

d

 

 

 

 

 

 

 

 

 

DT

0~65535

Word/DWor

Single/double

words

data

 

 

d

register

 

 

 

 

 

 

 

 

66

2.18 Schneider PLC

2.18.1Device model

 

Series

 

CPU

Connected module

Port

Cable

 

Device

 

Micro

 

TSX 37-05

Direct connect to CPU

RS485

Fig 1

 

 

 

 

 

TSX 37-08

 

 

 

 

 

 

 

 

TSX 37-10

 

 

 

 

 

 

 

 

TSX 37-21/22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twido

 

Twido series

Direct connect to CPU

RS485

Fig 1

 

Schneider Micro/

 

 

 

CPU

 

 

 

 

NEZA/Twido

 

 

 

 

 

 

 

 

Series PLC

 

M

 

M218

Direct connect to CPU

RS485

Fig 2

 

 

 

 

M238

 

 

 

 

 

 

 

 

M258

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEZA

 

TSX07 series

Direct connect to CPU

RS485

Fig 1

 

 

 

 

CPU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.18.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Note

PLC type

Schneider Micro/NEZA

 

 

 

/Twido series PLC

 

 

 

 

 

 

Port

RS485

 

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of Schneider Micro/NEZA/ Twido series PLC: 19200, 8, 1, even parity, station no.1

67

PLC:

68

Note:

The object address of Twido PLC is dynamic and can be enlarged in the PLC programming software. Please release the max coil address in the program. For example: the max coil address is M127, please output M127 in the program.

2.18.3 Cable making

(a) Direct connect to CPU:

Fig1

(b) M238 RJ-45 RS485:

Fig2

2.18.4 Device address

PLC address

Range

Data type

Explanation

M

0~2047

Bit

Internal coil

 

 

 

 

MW

0.00~65535.15

Bit

Internal coil

 

 

 

 

MW

0~2047

Word/DWord

Register

 

 

 

 

69

2.19 Fatek FB series PLC

2.19.1 Device model

 

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

 

 

FBs -20MN

 

 

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

FBs

 

FBs -32MN

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 2

 

 

 

 

 

FBs -44MN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20MC

 

Direct connect to CPU

 

 

 

 

 

 

 

 

 

28MC

 

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

FB -MC

 

40MC

 

 

 

 

 

 

 

Fatek MU

 

 

19MCT

 

 

 

 

 

 

 

/MA series

 

 

 

 

 

 

 

 

 

 

 

 

 

26MCT

 

 

 

RS485

 

Fig 2

 

 

 

 

 

36MCT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20MA

 

FB-DTBR/DTBR-E

 

RS232

 

Fig 3

 

 

 

 

 

28MA

 

 

 

 

 

 

 

 

FB -MA

 

 

 

RS232

 

Fig 4

 

 

 

 

 

module

 

 

 

 

 

 

 

40MA

 

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: MA series PLC needs to configure FB-DTBR or FB-DTBR-E module, uses RS232 or RS485 connection.

2.19.2 Parameters

HMI:

Parameters

Recommend settings

Choices of settings

Note

PLC type

Fatek MC/MA/MU series PLC

 

 

 

 

 

 

Port

RS232

RS232 or RS485

 

 

 

 

 

Data bit

7

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200

 

 

 

/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of Fatek MC/MA/MU series PLC: 9600, 7, 1, even parity, station

no.1

70

2.19.3 Cable making

(a) FBs Port0 RS232:

CPU port:

Fig1

(b) CPU RS485:

Fig2

(c)FB-DTBR/DTBR-E module RS232:

Fig3

71

(d)FB-DTBR/DTBR-E module RS232:

Fig4

(e) FB-DTBR/DTBR-E module RS485:

Fig5

2.19.4 Device address

FATEK-FB series PLC

PLC address

Range

Data type

Explanation

M

0~2001

Bit

Internal auxiliary coil

 

 

 

 

X

0~255

Bit

External input coil

 

 

 

 

Y

0~255

Bit

External output coil

 

 

 

 

S

0~999

Bit

Sequence control coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

R

0~9000

Word/Dword

Register

 

 

 

 

X

0~255

Word/Dword

Used as register

 

 

 

 

Y

0~255

Word/Dword

Used as register

 

 

 

 

M

0~2001

Word/Dword

Used as register

 

 

 

 

S

0~999

Word/Dword

Used as register

 

 

 

 

D

0~3071

Word/Dword

Used as register

 

 

 

 

TD

0~255

Word/Dword

Used as register

 

 

 

 

C16

0~199

Word/Dword

16-bit counter

 

 

 

 

C32

200~255

Word/Dword

32-bit counter

 

 

 

 

T

0~255

Word/Dword

Timer state

 

 

 

 

72

2.20 Vigor VIGOR PLC

2.20.1 Device model

 

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

 

Device

 

 

 

VB0-14M

 

 

 

 

 

 

 

 

 

 

 

 

VB0-20M

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

VB0-28M

 

 

 

 

 

 

 

 

 

 

 

 

VB0-32M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS232

 

Fig 2

 

 

Vigor VB

 

VB

 

VB1-14MT-D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Series

 

 

 

VB1-24MT-D

 

Connect to the extension

 

 

 

 

 

 

 

 

 

 

 

RS422

 

Fig 3

 

 

PLC

 

 

 

VB1-32MTMT-D

card

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VB2-16M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 4

 

 

 

 

 

 

VB2-32M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VH

 

VH -14MR

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.20.2 Parameters

HMI:

Parameters

Recommend

Choices of settings

Note

 

settings

 

 

PLC type

Vigor VB series

 

 

 

PLC

 

 

 

 

 

 

Port

RS232

RS232/RS485/RS422

 

 

 

 

 

Data bit

7

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

The default parameters of Vigor VB series PLC: 19200, 7, 1, even parity, station no.0

2.20.3 Cable making

73

(a)

CPU

RS232

USB-A:

Fig1

(b) CPU direct connection or RS232 extenstion card:

Fig2

(c) CPU direct connection or RS485 extenstion card: 1 RS422 connection

Fig3

2 RS485 connection

Fi4

74

2.20.4 Device address

PLC address

Range

Data type

Explanation

X

0~777

Bit

External input coil

 

 

 

 

Y

0~777

Bit

External output coil

 

 

 

 

M

0~9255

Bit

Internal auxiliary coil

 

 

 

 

S

0~999

Bit

Special auxiliary coil

 

 

 

 

TSTATUS

0~255

Bit

Status of timer

 

 

 

 

CSTATUS

0~255

Bit

Status of counter

 

 

 

 

TCOIL

0~255

Bit

Timer coil

 

 

 

 

CCOIL

0~255

Bit

Counter coil

 

 

 

 

C16

0~199

Word

16-bit counter

 

 

 

 

C32

200~255

DWord

32-bit counter

 

 

 

 

D

0~9255

Word/

Data register

 

 

DWord

 

 

 

 

 

TW

0~255

Word/

Current timer value

 

 

DWord

 

 

 

 

 

X

0~777

Word/

Used as register

 

 

DWord

 

 

 

 

 

Y

0~777

Word/

Used as register

 

 

DWord

 

 

 

 

 

M

0~9255

Word/

Used as register

 

 

DWord

 

 

 

 

 

S

0~999

Word/

Used as register

 

 

DWord

 

 

 

 

 

75

2.21 Fuji SPB series PLC

2.21.1 Device model

Fuji MICREX-SX SPB series PLC

 

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NW0P20

 

Communication adapter

 

RS232

 

Fig 1

 

 

 

 

 

 

NW0LA-RS2

 

 

 

 

 

 

 

 

 

 

 

Fig 3

 

Fuji SPB

 

SPB

 

NW0P30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

series PLC

 

 

 

Communication adapter

 

 

 

Fig 2

 

 

 

 

NW0P40

 

 

RS485

 

 

 

 

 

 

NW0LA-RS4

 

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.21.2 Parameters

HMI:

Parameter

Recommend

Choices of settings

Note

 

settings

 

 

PLC type

Fuji SPB series PLC

 

 

 

 

 

 

Port

RS232

RS232/RS485

 

 

 

 

 

Data bit

8

7 / 8

 

 

 

 

 

Stop bit

1

1 / 2

 

 

 

 

 

Parity

Odd parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

2.21.3 Cable making

(a) NW0LA-RS2 module RS232:

Fig1

76

(b) NW0LA-RS4 module RS485:

Fig2

(c) RJ-45 RS422:

Fig3

2.21.4 Device address

PLC address

Range

Data type

Explanation

X

0~15

Bit

External input coil

 

 

 

 

Y

0~15

Bit

External output coil

 

 

 

 

M

0~15

Bit

Internal auxiliary coil

 

 

 

 

L

0~15

Bit

Special auxiliary coil

 

 

 

 

T

0~511

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

SM

0~15

Bit

Special auxiliary coil

 

 

 

 

WX

0~63

Word/DWor

Used as register

 

 

d

 

 

 

 

 

WY

0~63

Word/DWor

Used as register

 

 

d

 

 

 

 

 

 

 

77

 

WM

0~63

Word/DWor

Used as register

 

 

d

 

 

 

 

 

WL

0~255

Word/DWor

Used as register

 

 

d

 

 

 

 

 

WSM

32768~3302

Word/DWor

Used as register

 

3

d

 

 

 

 

 

D

0~8191

Word/DWor

Data register

 

 

d

 

 

 

 

 

TW

0~511

Word/DWor

Used as register

 

 

d

 

 

 

 

 

CW

0~255

Word/DWor

Used as register

 

 

d

 

 

 

 

 

LD

0~10000

Word/DWor

Used as register

 

 

d

 

 

 

 

 

SD

32768~3302

Word/DWor

Used as register

 

3

d

 

 

 

 

 

78

2.22 Keyence KV series PLC

2.22.1Device model

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

KV-10DR

 

 

 

 

 

 

 

 

 

KV-24

 

Direct connect to the CPU

 

RS232

 

Fig 1

 

 

 

KV-16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KV-40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keyence KV series

 

KZ-300

Serial port module KZ-L2

 

RS232

 

Fig 2, fig 3

 

 

 

 

 

 

 

 

 

 

RS422

 

Fig 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS232

Fig 5, fig 6

 

 

 

KV-700

Serial port module KZ-L20

 

 

 

 

 

 

 

 

RS422

 

Fig 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.22.2 Parameters

HMI:

Parameters

Recommend

Choices of settings

Note

 

settings

 

 

PLC type

keyence KV series

 

 

 

 

 

 

Port

RS232 port

RS232/RS422

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of Keyence KV series PLC: 9600, 8, 1, even parity, station

no.1

2.22.3 Cable making

(a) CPU RS232 RJ-11:

79

1 2 3 4 5

6

Fig1

(b) Serial port module KZ-L2 Port1, RS232 connects to Keyence KZ-300 PLC:

Fig2

(c) Serial port module KZ-L2 Port2, RS232 connects to Keyence KZ-300 PLC:

Fig3

(d) Serial port module KZ-L2 Port2, RS422 connects to Keyence KZ-300 PLC:

Fig4

80

(e) Serial port module KV-L20 Port1, RS232 connects to Keyence KV-700 PLC:

Fig5

(f) Serial port module KV-L20 Port2, RS232 connects to Keyence KV-700 PLC:

Fig6

(g) Serial port module KV-L20 Port2, RS422 connects to Keyence KV-700 PLC:

Fig7

2.22.4 Device address

PLC address

Range

Data type

Explanation

R

0~999

Bit

Coil

 

 

 

 

DM

0~8000

word

Data register

 

 

 

 

81

2.23 Emerson EC20 series PLC

2.23.1Device model

 

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

 

 

 

 

COM0 port

 

RS232

 

Fig 1

 

Emerson EC20

 

 

 

 

 

 

 

 

 

 

 

 

EC20

 

EC20

 

 

 

RS485

 

Fig 2

 

 

 

 

COM1 port

 

 

 

Series PLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS232

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.23.2 Parameters

HMI:

Parameters

recommend settings

Choices of settings

Note

PLC type

Emerson EC20 series PLC

 

 

 

 

 

 

Port

RS232

RS232/RS485

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200

 

 

 

/19200/187500

 

 

 

 

 

Station no.

1

0~255

 

 

 

 

 

The default parameters of Emerson EC20 series PLC: 19200, 8, 1, even parity, station no.1

2.23.3 Cable making

(a) Emerson EC20 PLC COM0 (RS232):

Fig1

(b)Emerson EC20 PLC COM1 (RS232):

82

Fig2

(c) Emerson EC20 PLC COM1 (RS485):

Fig3

Note: Emerson EC20 PLC COM1 supports RS232 and RS485.

2.23.4 Device address

PLC address

Range

Data type

Explanation

X

0~377

Bit

External input coil

 

 

 

 

Y

0~377

Bit

External output coil

 

 

 

 

M

0~2047

Bit

Internal auxiliary coil

 

 

 

 

S

0~1023

Bit

Special auxiliary coil

 

 

 

 

T

0~255

Bit

Timer

 

 

 

 

C

0~255

Bit

Counter

 

 

 

 

SM

0~9999

Bit

Special internal auxiliary coil

 

 

 

 

D

0~7999

Word/DWor

Data register

 

 

d

 

 

 

 

 

SD

0~255

Word/DWor

Used as register

 

 

d

 

 

 

 

 

Z

0~15

Word/DWor

Used as register

 

 

d

 

 

 

 

 

T

0~255

Word/DWor

Used as register

 

 

d

 

 

 

 

 

C16

0~199

Word/DWor

16-bit counter

 

 

d

 

 

 

 

 

C32

200~255

Word/DWor

32-bit counter

 

 

 

 

 

 

83

 

d

2.24 OEMax NX7 series PLC

2.24.1 Device model

 

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

 

 

 

 

COM0 port

 

RS232

 

Fig 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NX7

 

NX7

 

 

RS232

 

Fig 2

 

OEMax NX7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Series PLC

 

 

 

COM1 port

 

RS485

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS232

 

Fig 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.24.2 Device address

HMI:

Parameter

Recommend settings

Choices of settings

Note

PLC type

OEMax NX70 series PLC

 

 

 

 

 

 

Port

RS232

RS232/RS485

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

Parity

No parity

Even/odd/no parity

 

 

 

 

 

Baud rate

9600

4800/38400/9600/115200

 

 

 

/19200/187500

 

 

 

 

 

Staion no.

1

0~255

 

 

 

 

 

The default parameterso f OEMax NX7 PLC: 9600, 8, 1, no parity, station no.1

2.24.3 Cable making

(a) OEMax NX7 PLC COM1 (RS232):

Fig1

84

(b) OEMax NX7 PLC COM1 (RS485):

Fig2

(c) OEMax NX7 PLC COM2 RJ-45 (RS232):

8 7 6 5 4 321

Fig3

(d) OEMax NX7 PLC COM2 is RJ-45 8-pin port, short pin1 and 3 means RS485+; short pin2 and 4 means RS485- :

Fig4

OR

Fig5

85

2.24.4 Device address

PLC address

Range

Data type

Explanation

R

R000.00~R31.15

Bit

External I/O coil

 

 

 

 

 

R32.00~R127.15

Bit

Special coil

 

 

 

 

L

L000.00~L063.15

Bit

Internal coil

 

 

 

 

M

M000.00~M127.15

Bit

Internal auxiliary coil

 

 

 

 

K

K000.00~K127.15

Bit

Internal holding coil

 

 

 

 

F

F000.00~F015.15

Bit

Special coil

 

 

 

 

TC

TC0~TC255

Bit

Timer /counter coil

 

 

 

 

W

0~6000

Word/DWord

Data register

 

 

 

 

R

0~127

Word/DWord

Used as register

 

 

 

 

L

0~63

Word/DWord

Used as register

 

 

 

 

M

0~127

Word/DWord

Used as register

 

 

 

 

K

0~127

Word/DWord

Used as register

 

 

 

 

F

0~15

Word/DWord

Used as register

 

 

 

 

SV

0~255

Word/DWord

Timer/counter settings

 

 

 

 

PV

0~255

Word/DWord

Timer/counter current value

 

 

 

 

SR

0~511

Word/DWord

Special register

 

 

 

 

86

2.25 Bosch Rexroth IndraControl L40 series PLC

2.25.1 Device model

Bosch Rexroth IndraControl L40 series PLC can communicate with Xinje HMI via COM0 and COM1.

CPU

Connected module

Port

Cable

Device

 

 

 

 

Bosch Rexroth

IndraControl L40

Direct connect to CPU

RS232

Fig 1

IndraControlL40

 

 

 

 

Series PLC

 

 

 

 

 

2.25.2 Parameters

HMI:

 

Parameters

Recommend settings

 

Choices of settings

 

Note

 

PLC type

IndraControl L40 series PLC

 

 

 

 

 

 

 

 

 

 

Port

RS232

RS232

 

 

 

 

 

 

 

 

 

 

Data bit

8

 

7 or 8

 

 

 

 

 

 

 

 

 

 

Stop bit

1

 

1 or 2

 

 

 

 

 

 

 

 

 

Parity

Even parity

Even/odd/no parity

 

 

 

 

 

 

 

 

 

 

Baud rate

9600

 

4800/38400/9600/115200

 

 

 

 

/19200/187500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Station no.

1

 

0~255

 

 

 

 

 

 

 

 

 

The default parameters of IndraControl L40 series PLC: 9600, 8, 1, even parity, station no.1

2.25.3 Cable making

IndraControl L40 PLC RS232:

Fig1

87

2.25.4 Device address

IndraControl L40 series PLC

PLC address

Range

Data type

Explanation

X

0~9999

Bit

External I/O coil

 

 

 

 

B

0~9999

Byte

Used as register

 

 

 

 

W

0~9999

Word

Used as register

 

 

 

 

D

0~9999

DWord

Used as register

 

 

 

 

R

0~9999

DWord

Used as register

 

 

 

 

SB

0~9999

Byte

Used as register

 

 

 

 

SW

0~9999

Word

Used as register

 

 

 

 

SD

0~9999

DWord

Used as register

 

 

 

 

88

2.26 OPTO 22 SNAP series PLC

2.26.1 Device model

 

Series

 

CPU

 

Connected module

 

Port

 

Cable

 

Device

 

OPTO 22

 

SNAP

 

Direct connect to CPU

 

RS232

Fig 1, fig 2

 

OPTO 22 series

 

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.26.2 Parameters

HMI:

 

Parameters

 

 

Recommend

 

 

Choices of settings

 

 

Note

 

 

 

 

settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLC type

 

OPTO 22

series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Port

 

RS232

 

 

RS232/RS485

 

 

 

 

 

 

 

 

 

 

 

 

 

Data bit

8

 

 

7 or 8

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop bit

1

 

 

1 or 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parity

 

No parity

 

 

Even/odd/no parity

 

 

 

 

 

 

 

 

 

 

 

 

 

Baud rate

115200

 

4800/38400/9600/115200/19200/187500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Station no.

1

 

0~255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The default parameters of OPTO 22 series PLC: 115200, 8, 1, no parity, station no.1

2.26.3 Cable making

(a) RS232 connection:

Fig1

(b) RS485 connection:

89

Fig2

(c) RS232 connection:

Fig3

2.26.4 Device address

PLC address

 

Range

 

 

Data type

Explanation

DI

0~9999

 

 

Bit

External input coil

 

 

 

 

 

 

DO

0~9999

 

 

Bit

External output coil

 

 

 

 

 

 

PID000~PID03

0~6

 

 

Bit

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

0~9999

 

 

DWord

Used as register

 

 

 

 

 

 

F

0~9999

 

 

DWord

Used as register

 

 

 

 

 

 

AI

0~9999

 

 

DWord

Used as register

 

 

 

 

 

 

AO

0~9999

 

 

DWord

Used as register

 

 

 

 

 

 

 

90

2.27 SAIA-Burgess PCD series PLC

2.27.1 Device model

SAIA—Burgess PCD series PLC communicates with Xinje HMI via socket A or socket B port.

(a) Direct connect to CPU

 

CPU

 

Connected module

Port

Cable

 

Device

 

PCD1.M110

 

 

 

 

 

 

 

PCD1.M125

 

CPU PORT #0

RS232

Fig 1

 

 

 

PCD1.M135

 

 

 

 

 

 

 

 

 

 

 

 

 

SAIA—Burgess PCD

 

PCD2.M120

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD2.M150

 

CPU PORT #0

 

 

 

series

 

 

 

 

 

 

 

PCD2.M170

 

 

RS485

Fig 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD2.M480

 

CPU PORT #6

 

 

 

 

 

 

 

 

 

 

 

 

(b) Through serial port

 

CPU

 

 

 

Connected

 

Port

 

Cable

 

Device

 

 

 

 

 

 

module

 

 

 

 

 

 

 

PCD1.M125

 

 

 

 

RS485

 

Fig 4

 

 

 

PCD1.M135

 

 

 

 

 

 

 

 

 

 

PCD7.F110

 

 

 

 

 

 

 

PCD1.M110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD1.M120

 

 

 

 

RS422

 

Fig 5

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD2.M480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD2.M170

 

 

PCD7.F120

 

RS232

 

Fig 3

 

 

 

PCD2.M150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket

 

PCD2.F520

 

RS232

 

Fig 6

 

SAIA—Burgess

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 7

 

 

 

 

 

 

 

 

 

 

 

 

B1

 

PCD7.F772/F802

 

 

 

PCD series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS422

 

Fig 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD2.M170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS232

 

Fig 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket

 

PCD2.F520/F530

 

 

 

 

 

 

 

 

 

 

 

RS485

 

Fig 7

 

 

 

 

 

B2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCD7.F772/F802

 

RS485

 

Fig 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket

 

 

 

RS232

 

Fig 9 or

 

 

 

 

 

 

A

 

 

 

 

fig 11

 

 

 

PCD2.M480

 

 

 

PCD2.F520/F522

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket

 

 

RS422

 

Fig 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

91

2.27.2 Parameters

HMI:

 

Parameters

 

Recommend

Choices of settings

Note

 

PLC type

 

SAIA—Burgess

 

 

 

 

PCD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Port

 

RS232

RS232/RS485

 

 

 

 

 

 

 

Data bit

8

7 or 8

 

 

 

 

 

 

 

Stop bit

1

1 or 2

 

 

 

 

 

 

 

 

Parity

 

No parity

Even/odd/no parity

 

 

 

 

 

 

 

Baud rate

19200

4800/38400/9600/115200/19200/187500

 

 

 

 

 

 

 

Station no.

0

0~255

 

 

 

 

 

 

 

SAIA—Burgess PCD series PLC: 19200, 8, 1, no parity, station no.0

2.27.3 Cable making

(a) Direct connect to PGU RS232:

Fig1

(b) Direct PGU RS485:

92

Loading...