KAEL Muhendislik Elektronik VARkombi-12-PC-TFT-OG User Manual

KAEL Mühendislik Elektronik
Tic. ve San. Ltd.Şti.
Reactive Power Control Relay
Industrial Facilities Markets Oil Stations Schools Workshops Hotels
12 Step
VARkombi-12-PC-TFT-OG
Connection type selective
V
A
R
k
o
m
b
i
-
1
2
-
P
C
-
T
F
T
-
O
G
Contents
Introduction .......................................
Warnings ...........................................
Specifications......................................
General ..............................................
Step Panel ..........................................
Making the Connections .......................
Connections .......................................
Alerts .................................................
Commisioning .....................................
Main Screens ......................................
% Instant Consumption........................
CosФ ..................................................
PF Power Factor .................................
Σ Accumulated Energy Ratios................
Steps ..................................................
1. MENU ................................................
1.1 Harmonics ..........................................
1.2 Step Indicator .....................................
1.3 Voltage, Current, Frequency.................
1.4 Power ................................................
1.5 Energy ...............................................
1.6 Counter Index ....................................
1.7 Settings .............................................
1.7.1 Measurement Types .........................
1.7.2 Target CosФ .......................................
1.7.3 Switch on(decharge) Time ...................
1.7.4 Switch off Time ...................................
1.7.5 Switch min. Time ...............................
1.7.6 Limit of Inductive Penalty.....................
1.7.7 Limit of Capacitive Penalty....................
1.7.8 Current Transformer (Primary) Value ...
1.7.9 Number of Steps .................................
1.7.10 Advanced Set-up Menu.........................
1.7.10.1 ΔT on Transition(Delay) Time...............
1.7.10.2 ΔT off Transition(Delay) Time..............
1.7.10.3 Current Flow Direction Detection ..........
1.7.10.4 Fast Step Mode....................................
1.7.10.5 Step Parameters..................................
1.7.10.5.1 Continuous Step Power Detection ........
1.7.10.5.2 Constant Step Function ......................
1.7.10.5.3 Step Synch. Time Sharing ....................
1.7.10.5.4 Enter Step Powers ..............................
1.7.10.5.5 Delete Step Powers ............................
1.7.10.5.6 Step Change Control ...........................
1.7.10.6 Alarm & Protection ..............................
1.7.10.6.1 Alarm Control .....................................
1.7.10.6.1.1 Phase Alarms .....................................
1.7.9.10.1.1.1 Over Voltage.......................................
1.7.9.10.1.1.2 Under Voltage ....................................
1
1 2 3 3
3 4 4 5
6
6 7 7
7 8 8 8 8
8
9 9
9 10 12
12 13 13 14 14 14
14
15 15 15
15 16
16 16
16 16 17 17
18 18 18 19
19 19
6
Contents
1.7.10.6.1.1.3 Over Current.......................................
1.7.10.6.1.1.4 Over Compensation.............................
1.7.10.6.1.1.5 Under Compensation ..........................
1.7.10.6.1.1.6 No Phase ...........................................
1.7.10.6.1.1.7 THD on Voltage...................................
1.7.10.6.1.1.8 HD on Voltage.....................................
1.7.10.6.1.1.9 THD on Current...................................
1.7.10.6.1.1.10 HD on Current...................................
1.7.10.6.1.2 General Alarms........................................
1.7.10.6.1.2.1 Connector Failure(1)............................
1.7.10.6.1.2.2 Connector Failure(2)............................
1.7.10.6.1.2.4 Total Over Compensation.....................
1.7.10.6.1.2.5 Total Under Compensation...................
1.7.10.6.1.2.6 System Error.....................................
1.7.10.6.1.2.7 Over Temperature...............................
1.7.10.6.1.2.8 Voltage Connection Failure...................
1.7.10.6.1.2.9 Step Change ......................................
1.7.10.6.1.2.10 Step Zero..........................................
1.7.10.6.1.2.11 Modbus Security Failure.....................
1.7.10.6.2 Alarm Setting Values. ..........................
1.7.10.6.2.1 Over Voltage Setting ...........................
1.7.10.6.2.2 Low Voltage Setting ............................
1.7.10.6.2.3 Over Temperature .............................
1.7.10.6.2.4 Voltage THD Setting ............................
1.7.10.6.2.5 Voltage HD Setting ..............................
1.7.10.6.2.6 Current THD Setting ............................
1.7.10.6.2.7 Current HD Setting ..............................
1.7.10.6.3 Fan Settings .......................................
1.7.10.6.3.1 Fan Temperature Value .......................
1.7.10.6.3.2 Fan Output .........................................
1.7.10.6.4 Step Protection Function......................
1.7.10.6.4.1 Temperature Protection.......................
1.7.10.6.4.2 Voltage Protection...............................
1.7.10.6.4.3 Harmonic Protection............................
1.7.10.7 Password Settings................................
1.7.10.7.1 Password Enable/Disable......................
1.7.10.7.2 Change Password ................................
1.7.10.8 Generator Parameters.. .......................
1.7.10.8.1 TanΦ2-CosΦ2 Target...........................
1.7.10.8.2 Generator Input Enable/Disable............
1.7.10.9 MODBUS RTU Settings ........................
1.7.10.9.1 Data Write Protection...........................
1.7.10.9.2 Data Read Protection...........................
1.7.10.9.3 Data Write Password............................
1.7.10.9.4 Data Read Password............................
1.7.10.9.5 Port Settings .......................................
1.7.10.10 Connection Settings ............................
1.8 Factory Defaults ..................................
19
19 19 19 19
19 19 19 20
20 20 20 20
20 20 20 20 20
20
21 21 21 21 22
22 22 22 23 23 23
23
23 23 24
24 24
24
25
25
25 25 25
25 25 25 26
26 27
Introduction
Warnings
All the information you need to know and the warnings regarding 3 Phase controlled VARkombi­12-PC-TFT-OG reactive power control relay are described in the user manual.
Prior to taking the circuit for the device read this booklet carefully for your system and your own safety. Do not act without getting touch with our company for the issues that can not be understood.
Tel: 0090.232.877 14 84 (pbx) Fax: 0090.232.877 14 49 Factory: Atatürk mah. 78 sok. No:10 Ulucak köyü, Kemalpaşa - İZMİR
1- The device should be commisioned and programmed by the authorized and certificated
personels. If necessary, checks should be made by that person again.
2- As compensation is a complex system, subscriber' s system are advised to keep under control by licensed - professional electrical engineers and technicians that company owned or agreed.
3- Do not open the device and not let it open. There are not any parts in the device that the user or someone can cut in.
4- Prior to making electrical connections to the terminals of the device, make sure that there is no energy in the cable and terminals. There shouldn' t be energy at the control panel.
5- Do not use the device for different purposes other than compensation system.
6- Fix the device tightly on the control panel with the apparatus given on the device without
hanging around.
7- Do not interfere to the keys on the front panel with an object other than your fingers.
8- Wipe your device with dry cloth being sure to disconnect the power. Water or chemicals used
for cleaning damage to the device.
9- Make sure that the terminal connections are made in accordance with the connection scheme and without causing contact problem (loose binding or multiple copper cables touching to each other, etc.), prior to commissioning (supplying energy) of your device.
10- Use compensation contactors compatible to the power of the capacitor in your compensation system. Select the fuses in the power line of the capacitor compatible to the current of the capacitor.
11- Select the current value of the fuses connected to the C1, C2 and C3 terminals which are input of contact phase considering the sum of the current drawn by the coils of connectors in each group (senary). In case of using connectors with high current coil, auxiliary relay must be used to prevent damage to the contact outputs of the device.
12- The alerts and the warnings above are just for your security. In case of not applied, KAEL Elektronik Ltd. or its seller is not responsible for undesirable conditions.
1
Specifications
Easy to use with English menu Advanced dynamic software Easy to commissioning Large color LCD screen ( 320 x 240 pixel 3,2” ) Enough number of steps needed ( 18 steps ) Quickly and accurately detection power of capacitors Normal or fast operation mode selection Connecting triphase, double-phase and single-phase capacitor Connecting shunt reactors Displaying the current and voltage up to the 31. harmonic simultaneously with the
graphics
Total current and voltage harmonics Displaying the phase or phases to which connected capacitors in color on the screen Making compensation even at low currents (min. 10 mA) 40 ms measurement, calculation and response time Making compensation for the generator according to the second Cos Φ2 set-up Displaying many guiding screens operating system is used in the micro-processor Computer communicated (RS485 MODBUS RTU) Password protected For balance or unbalance operatings Ensuring equal-aging of the capacitors in the same power Informing the user for the capacitors losing power Measuring temperature Following electrical parameters of three phases at the same time
Voltage of phases V( L1,2,3 – N)
Current of phases I( L1,2,3 – N)
CosΦ value of phases CosΦ(1,2,3)
TanΦ value of phases TanΦ(1,2,3)
Power factor value of phases PF(1,2,3)
Active powers ΣP,P1,P2,P3
Inductive reactive powers ΣQ(ind),Q1(ind),Q2(ind),Q3(ind)
Capacitive reactive powers ΣQ(Cap),Q1(Cap),Q2(Cap),Q3(Cap)
Apparent powers ΣS,S1,S2,S3
Total active energy ΣWh
Total inductive reactive energy ΣVARh(ind)
Total capacitive reactive energy ΣVARh(Cap)
2
General
Electricity networks are gradually overloaded as a result of increasing use and demand of emerging technologies In all sectors. While the compensation becomes a nightmare for the companies having unstable load, even the companies having stable load in the past have now difficulties to provide reactive compensation. Therefore, the period of reactive power relays measured by single-phase will be over in the close future. KAEL Elektronik has incorporated a brand-new device to the electricity sector having much more steps, quite good equipped in terms of function means and software with improved running algorithms, by combining the achievements and experiences coming along with VARkombi-12-PC-TFT-OG regarding the reactive power compensation. Facilities are provided to the users with many graphics and animation by using large 3.2 " color LCD screen on the device. Moreover, the microprocessor in the device is running very fast and an operating system is used. This provides to reach all transactions running simultaneously.
In case the blue led on the lower left corner of the front panel of the device flashes, this means it is close to the value of penalty % and authorized persons should be informed as soon as possible. This is also useful in terms of taking the attention of the end-user in case of penalty who does not know this functional issue.
■ The connections of the device should be made while the system is energy-free.
■ VARkombi-12-PC-TFT-OG should be connected as shown in the connection diagram.
■ Three phase and neutral connections should be made to the voltage input. Phase should not be given instead of neutral. Otherwise the device can be damaged.
■ Current connections should be made as to match the same phase with the same current transformer. Scheme should be followed.
■ The value of the selected current transformers should not be under the real load values but should be X/5 amper. It is also advised to choose 0.5 class.
■ Connect the “C1, C2, C3” common phase inputs to the same phase with FF type fuses seperately. Select the fuses to be used according to the specified current value.
■ The outputs of the steps are not needed to be made in any order. However, the first 6 steps can consist of triple-phase capacitor groups. It is recomended to connect single-phase capacitors to the second and third 6 steps and, to connect capacitors or reactors to the third 6 steps in terms of accepting the statements in this manual.
■ Make the connections to the generator if it is used.
■ Make RS485 connection. (Not applicable in VARkombi-12-TFT-OG)
■ Do not energize the device without ensuring the connections checked by measurement instruments.
Making the Connections
1 2 3
4
5 6 789 11
10 12
30
Temperature (ºC)
1. step
Capacitor step not activated
Capacitor step activated (blue)
1
R S T
Step Indicator
The powers and the phases they are belonging to are not yet informed
A step indicator made by symbols that can be easily realized by the user, is located on the upper part of the screen of VARkombi-12-PC-TFT-OG. No matter which part of the user in, this panel is always located on the top of the screen. Step numbers, the phase or the phases they are connected, whether these are informed or not, whether they are capacitors or reactors, whether the steps and the generators are activated or not and control panel temperature value can all be observed on this panel at the same time.
LCD screen is used in VARkombi-12-PC-TFT-OG to provide it to be more easier in use and be intelligible. In case the keys are not pressed for a long time, the device switch to the screen saver mode to extend the life of the display, and only the step indicator shown on the the top scrolls down step by step from the top to the bottom of the screen. Thus, the condition of the steps can be continued to be monitored. In case of pressing on any key, the main screen image appears again.
Compensation normal
Fast mode activated
The following symbols can be seen on this part of the display.
Manual control
3
!
H
F
I V
I V
I
V
I V
Measurement: Current from
medium volt age side – voltage from low voltage side(non-insulated)
I
V
Measurement: Current from
medium volt age side – voltage from medium volt age side
Measurement: Current from low voltage side – vol tage from low voltage side (insulated)
Measurement: Current from low voltage side – vol tage from low voltage side (non-insulated)
Current direction
~
230Vac 50/60 Hz
Connections
2 3 5 6 8 9 11 12 18741 10
30
ALARMS
R
S
T
Over voltage
Under voltage Over current T. over comp. Under comp.
ExitSelect
2 3 5 6 8 9 11 12741 10
30
Exit
- capacitors and the devices in the system can be damaged.
- capacitors are recommended to be disabled.
Over Voltage
Alarms
In case of alarm in the device, an exclamation mark appears under the main screen. Pressing the exclamation key, the alert page shown on the right side can be displayed on the screen as well as a warning page can only be displayed. In case of more than one alert, they are ranked one under the other according to the priority.
Meanwhile, the phase in which the alarm is given displayed on the screen. Arrow keys can move between the alarms. In case “Select” key is pressed during on any alarm (format is blue colour), warning page of that alert comes to screen. The essential corrections should be made by taking into consideration the recommendations made therebefore. Alarm page is back by pressing the “Exit” key.
L3 (T)
L2 (S)
L1 (R) N
N
L1 (R)
L2 (S)
L3 (T)
Gnd
B
A
TR
Power Supply
I1
k1
I2
k2
I3
k3
Voltage inputs
Current Transformer Inputs
Load
AB
Transformer
CON-2
RS485 - Ethernet
4
connections are shown at pages 10 and 11
connections are shown at pages 10 and 11.
6A
K7
6A
ALR
C1
K1
K2
K3
K4
K5
K6
C2
K7
K8
K9
K10
K11
K12
ALR (Alarm output)
* * *
*
Fuse compatible to the capacitor power
FAN (Fan output)
FAN
2A
2A
K1
Commisioning
Device requires to enter the number of steps. In this case, the screen on the right side will be displayed. The number of step is set-up to the required value by the direction keys and “Apply” is selected. In case “Okay” key is pressed, saves the change. Or, in case no key is pressed, when the time is over on the screen, it switches to the section in which the current transformer ratio is inserted by taking 12 steps in the memory.
The line on which the blue bar locates, is set­up to the required value by using the direction keys and switch to the next side by pressing the left direction key. Inserting the complete primary value, “Apply” key is pressed. In case of pressing “Okay” key, the change is saved.
The device automatically switches to the internalization of current polarity directions mode. In this case, it is required to draw enough current from each phase. If enough current can not be drawn from any phase, the device warns as “current flow directions not detected” and shows the phase or phases which are not internalized by ??? marks. When the total of current polarity directions are internalized, the device switches to the automatic capacitor power internalization mode. P.S.: There is no need to press on the main screen key normally.
2. Step : Number of Steps
3. Step : Current Transformer Ratio
4. Step : Determine of Current Transformer Directions
Device tries to identify capacitor powers and the phases to which they connected, by activating and then removing the steps in sequence. It is recommended the closure of variable loads in the system to ensure instant internalization during this process. If required, the user presses the “Make the steps internalize” key and can make the system internalize by himself. The automatic internalization is put on hold in the meantime. The step is not internalized automatically as long as the user is in the “Make the steps internalize” menu. P.S.1: There is no need to press on the main screen key normally. P.S.2: Despite of the variable loads are disabled, the connections of the device should be checked again in case any power of the steps and their connections are not intenalized for a long time.
5. Step : Learning of step powers
For more info
When all the steps are internalized, the main screen page comes up and the device starts operating in automatic mode. P.S.1: It' s required to enter the Menu for the parameters the user need to set-up. It' s recommended to see the specifications of the device by navigating in the menu. P.S.2: Unless the user disable the password protection, some transactions (eg. set-up, deleting the energy) will be password protection.
6. Step (Main Screen)
5
1
Akım Polarite Yönleri Bulunamıyor
Ana Ekran
1 7 9 5 4
Current from M.V / Voltage from M.V (insulated)
Current from M.V / Voltage from L.V (non-insulated)
1
2 345 6 789 11
10 12
30
Menu %-Cos-PF-Σ Steps
.0
R
-50
-30 -10 10
30 50
cap.
ind..
0
N
+
%
2
.0
S
-50
-30 -10 10 30 50
cap.
ind.
0
N
+
%
9
.0
T
-50
-30 -10 10 30 50
cap.
ind..
0
+
%
5
.0
N
1 2 3 4 5 6 7 8 91011 12
30
Kvar
Make internalizeMain Screen
R S T
Detecting step powers... 10:00
Please close the vari able loads in the system.
K1 -1.0 -1.0 -1.0
1 2 3 4 5 6 7 8 91011 12
30
Main MenuPlease wait
R S T
detected detected detected
T
S
searching for current transformer directions ... 5
R
1 2 3 4 5 6 7 8 91011 12
30
Seaeching for current transformer directions...
Main Menu
Current Flow dir. not Detected
R S T
???????? ???????? ????????
- Make sure all phases have loads
- Check voltage and current inputs
!
1 2 3 4 5 6 7 8 9 10 11 12
30
searching for current transformer directions ... 5
Main MenuPlease wait
R S T
???????? ???????? ????????
Please commision Load on each phase
1 2 3 4 5 6 7 8 91011 12
30
Enter current transformer ratio
seconds
30
00500 / 5A
Apply▲ + ▼ -
1 2 3 4 5 6 7 8 9 10 11 12
30
Insert current transformer ratio
seconds
20
CancelOkay Back
00500 / 5A
Save Changes?
1 2 3 4 5 6 7 8 9 10 11 12
30
Enter number of step
seconds
20
12
Apply▲ + ▼ -
1 2 3 4 5 6 7 8 9 10 11 12
30
Enter number of step
seconds
20
18
CancelOkay Exit
Save Changes?
Current from L.V / Voltage from L.V (insulated)
Current from L.V / Voltage from L.V (non-insulated)
1. Step : Number of Steps
When commissioning the first time, measurement type must be selected ( 4 types). The device waits for the user to select one of these types. These are also described in detail on pages 10 and 11.
select
2 3 5 6 8 9 11 12741 10 14
30
1 2 345 6 789 11
10 12
30
Menu %-Cos-PF-Σ Steps
.0
R
-50
-30 -10 10 30 50
kap.
ind..
0
N
+
%
2
.0
S
-50
-30 -10 10 30 50
kap.
ind.
0
O
-
%
9
.12
T
-50
-30 -10 10
30 50
kap.
ind..
0
+
%
5
.16
U
Main Screens
VARkombi-12-PC-OG has color 3.2 "TFT screen. The switch between pages and the key terms are provided on the bottom line of the display. The keys have different meanings in different pages. Steps, to which phase or phases they are connected, whether they are capacitors and/or reactors, temperature value, whether the fan and the generator are activated or not, all these can be observed on all main screens.
Temperature (ºC)
Of R phase Q P
Normal
%
% Over consumption
Shows the system within the normal limits
Steps
%
cos (cosΦ)
(Instant Consumptions)
Instant consumption % values of each phase and their scaled representation, the normal, under and over compensation of the phases, their inductive-capacitive characterized loads and whether the system is normal or not according to the accumulated energy can be observed on consumptions page.
Instant cosΦ value of each phase, angular representation on triple-phase vector diagram, the angle (Φ) values, the normal, under and over compensation condition of the phases, their inductive-capacitive characterized loads and whether the system is normal or not according to the accumulated energy can be observed on this page.
Every time pressing this key, switches next to the right menu
1 2 345 6 7
8
9 11
10 12
30
Menu %-Cos-PF-Σ Steps
.0
R
N
+
0
. 0
S
N
+
T
-
N
01
0
. 0
01
9
. 990
Φ “ angle on R phase
Current vector of T phase
Voltage point on R phase
Inductive
capacitive
R
-1º
S
T
% Under consumption
Over
Under
6
PF Power Factor
The instant reactive power value (Q), active force values (P), power factor values (PF) calculated from their ratios (Q / P), vectoral representation of these forces, inductive - capacitive characterized loads, whether the systems is normal or not as per the accumulated energy can be monitored.
Σ
Ratios of Accumulated Energy
Accumulated energy ratios of each phase, total energy ratios and their scaled respresentation can be monitored. This screen is very useful in terms of realizing the characters of loads connected to the phases and enabling the user to take the necessary actions and make the corrections. Whether the system is under penalty according to the total energy ratios can also be monitored.
Steps
This is the section used to see the conditions (activated-deactivated-holding)of steps more clearly, to examine the reactive power of the system or for commissioning and disabling the steps manually.
You must exit this menu for automatic mode as soon as you complete with manual control. Otherwise, the device remains in manual control continuously.
1 2 3
4
5 6 789 11
10 12
30
Menu %-Cos-PF Steps
.0
R
S T
.0
ind
cap
ind
cap
ind
cap
S T
Q
1,763
K
P 21,44
K
PF 0,991
- 0,155
K
14,66
K
- 0,999
- 1,454
K
10,87
K
- 0,990
Reactive powers
Active powers
Power factors
1
2 345 6 789 11
10 12
30
Menu %-Cos-PF-Σ Steps
.
R
N
%
.
S
T
82
2.5
5
Cap.
İnd.
0 0
1015202530
354045
50
5 10 15 20 25 30
35 40 45
50
N
%
.
53
%
Normal
2.4
%
Normal
3.8
%
Normal
R
S
T
3.5
%
Normal
3.3
%
Normal
3.9
%
Normal
Total capacitive % Total inducitive %
Capacitive % of R phase
Inducitive % of R phase
Capacitive % of S phase
Inducitive % of S phase
Capacitive % of T phase
Inducitive % of T phase
2 3 5 6 8 9 11 12
30
Step Status
Manual Mode
R S T
-0.346 KVAR
Exit VAR-W-VA
0.143 KVAR
0.345 KVAR
1 2 3 4 5
6
8
9 10 11
12
16 17 18
13 14 15
7
Switches to the section enabling the commision and cut off the steps by manual control.
741 10
Can change the power representation from this menu
4,7,10,13,14. steps activated (greenl)
1,2,3,5,6,8,9. steps deactivated (white)
11 and 12. steps holding for decharge period (yellow)
2 3 5 6 8 9 11 12
30
Manual Mode
on-off
R S T
-0.346 KVAR
Exit
0.143 KVAR
0.345 KVAR
1 2 3 4 5
6
8
9 10 11
12
16 17 18
13 14 15
7
741 10
7
2 3 5 6 8 9 11 12
30
Step info.
1 2 3 4 5 6
8
9 10 11
12
16 17 18
13 14 15
7
741 10
Operation Time
34 hours
Number of switching
663 times
-1.000 KVar
R S T
Total power
Select Exit
Current Voltage
2 3 5 6 8 9 11 12
30
741 10 14
Exit Setting
THD = 27.0 THD = 29.0 THD = 29.0
R S T
30
10
3
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31T
1. MENU
This is the section in which many of the electrical measurements are monitored and set-up are made. The parameters are accessed by direction keys in the menu, parameters are inserted by “Select” key and exit from the parameters by “Exit” key.
P.S.: Set-up section can only be accessed by password.
Harmonics
Displays the harmonic amplitude and % values of voltage as well as current of three phases up to 31.harmonic in terms of linear or logarithmic on colour graphics screen.
Total harmonic column(for three phase)
R S T
Allows to switch between the harmonics
The section in which;
- current or voltage,
- % or amplitude
- linear or logarithmic selections of harmonics are made.
Amplitude or % values of harmonic distortion
Step Monitoring
All steps can be accessed by up and down keys. Step information of the step with red frame ( ) among the step boxes is displayed on the left side of the screen while moving with directon keys.
The information regarding the runtime of all steps, number of switching, phase or phase to which they are connected, total power values and whether they are capacitor or reactor can all be accessed.
These values can be deleted when you make a change in step. “Select” key is pressed for deleting on the related step. Selecting the required type of deleting from the sub-screens shown on the right side, operation can be realized.
Voltage, Current, Frequency
This is the section in which the current, voltage and frequency drawn from the system are monitored.
Power
This is the section in which active, reactive and apparent powers drawn from each phase and, total active, reactive and apparent powers are monitored. These values can be observed by selecting “Powers” or “Total” at the bottom of the screen.
1 1
1 3
1 4
100 %f
A
A
A
V
Select Exit
1 1
MENU
Harmonics
Step Monitoring
Voltage,Current,Frequency
Power Energy
2 3 5 6 8 9 11 12741 10
30
ExitAmp-Volt %-Ampl. Log-Lin
ExitDelete all Delete
CancelYes No
2 3 5 6 8 9 11 12
30
V
741 10
R
S T
Exit
219.8
219.2 220.2
A
60.48 71.32 43.29
f
49.9 Hz
2 3 5 6 8 9 11 12
30
Q
Var
741 10
R S T
Exit
0.864 KVar
Total
P
W
R S T
33.17 KW
S
VA
R S T
33.18 KVA
Powers Total
8
1 2
Energy
This is the section in which the actice, reactive (ind. and cap.) and apparent energies consumed one by one in each phase and, the total active, reactive (ind. and cap.) and apparent energy consumed in total of the system are monitored.
If required, “Reset” selection is pressed (eg.when the counter is read for invoicing purpose). Entering the password, “Delete counters ?” question appears on the screen. In case of pressing “Yes”, all the counters are deleted.
P.S.: Password process is described in this section.
Counter Index
The index value of electrical counter connected to the plant is entered in this section. Thus, the energies recorded by electrical counter are compared. P.S.: VARkombi-12-PC-TFT-OG does not use these values for compensation. Press “Setings” selection first inorder to enter energy values. Sub-screen will change and red frame will appear on the index line. Red frame is moved to the line of which value will be entered by using direction keys and, “Select” key is pressed. An underline in blue colour appears in the line with red frame. The value of number in the digit under which the blue line is, is entered by using up and down keys. Then, move to the next digit by left key. When all the digits are changed with the same figures in the counter, “Apply” key is pressed. When the values of all lines are entered, “Okay” key is pressed and, when “Save Changes” appears on the screen, the data are kept in the memory by pressing “Okay” key.
Settings
This is the section in which you can find all set-up regarding the device. Password is entered. After commissioning of VARkombi-12-PC-TFT-OG, any change of parameters is not
required normally. However, it may be necessary for the
users requring to create special conditions or make some adjustments.
1 7
1 6
1 5
2 3 5 6 8 9 11 12
30
KWh
(Active)
741 10
Exit
Σ-L1-L2-L3
Reset
KVARh
(ind.)
KVARh
(cap.)
KVAh
(apparent)
000003035 137
000000108
131
000000087 291 000003058
151
Total
Select ESC
1 7
SET-UP
Target TanΦ - CosΦ Switch On Time Switch Off Time Min. Step Time
2 3 5 6 8 9 11 12741 10
30
1
2 3 5 6 8 9 11 12
30
KWh
(Active)
741 10 14
ExitSettings
KVARh
(ind.)
KVARh
(cap.)
000000056 321
000000001
031
000000000 291
2 3 5 6 8 9 11 12
30
KWh
(Active)
741 10
Cancel
Yes
KVARh
(ind.)
KVARh
(cap.)
KVAh
(apparent)
000003035 137
000000108
131
000000087 291 000003058
151
Delete
Counters?
No
Counter Index
2 3 5 6 8 9 11 12
30
KWh
(Active)
741 10
KVARh
(ind.)
KVARh
(cap.)
000000056 321
000000001
031
000000000 291
Counter Index
2 3 5 6 8 9 11 12
30
KWh
(Active)
741 10
ExitSelect
KVARh
(ind.)
KVARh
(cap.)
000000056 321
000000001
031
000000000 291
Counter Index
Apply▲ + ▼ -
2 3 5 6 8 9 11 12
30
KWh
(Active)
741 10
KVARh
(ind.)
KVARh
(cap.)
000000056 321
000000001
031
000000000 291
Counter Index
CancelOkay Exit
2 3 5 6 8 9 11 12
30
KWh
(Active)
74 10
KVARh
(ind.)
KVARh
(cap.)
000000056
321
000000001
031
000000000 291
Counter Index
CancelOkay Exit
Save
changes
1
1 7 9 7
Measurement Types
9
1 7
Settings – Measurement Type
1
The device offers the possibility of 4 types , according to the connection.
Current Inputs
N
L1
Voltage Inputs
L2 L3
I3
I2
I1
L3
L2
L1
N
~~~
I3
k3
I2
k2
I1
k1
select exit
2 3 5 6 8 9 11 12741 10
30
X/5A
X/5A
X/5A
MEDIUM VOLTAGE LOW VOLTAGE
Current from M.V / Voltage from L.V (without voltage transformer)
There are two settings
1) MV – LV Ratio : The ratio of medium voltage to the low voltage value (phase to phase). Forexample ; 33.000V / 400V = 82,5
2) Transformer Type : DYN-11 or DYN-5
NOTE: The current transformer ratio must be entered in the section from the menu 1.7.8
select exit
1 7
Measurement types
MV – LV ratio
Transformer Type
2 3 5 6 8 9 11 12741 10
30
1 1
Enter MV – LV ratio
2 3 5 6 8 9 11 12741 10
30
apply▼ -
0001.000
“Apply” key is pressed to take the target value into memory. “Save Changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into the memory.
cancelokay back
▲ +
Medium Voltage (VOLT)
Low Voltage (VOLT)
select exit
1 7
2 3 5 6 8 9 11 12741 10
30
1 2
Enter Transformer Type
2 3 5 6 8 9 11 12741 10
30
apply▼ -
DYN - 11
cancelokay back
▲ +
DYN – 11 or DYN – 5
Connection :
2A 2A 2A
10
MV – LV ratio
Transformer Type
Measurement types
L1 L2 L3
I3
I2
I1
L3
L2
L1
~~~
I3
k3
I2
k2
I1
k1
X/5A
X/5A
X/5A
select exit
2 3 5 6 8 9 11 12741 10
30
Current from L.V / Voltage from L.V (with voltage transformer)
Current from M.V / Voltage from M.V (with voltage transformer)
NOTE: The current transformer ratio must be entered in the section from the menu 1.7.8
Enter Voltage Trans. Value
2 3 5 6 8 9 11 12741 10
30
apply▼ -
0001.000
cancelokay back
▲ +
Current Inputs
L1
Voltage Inputs
L2 L3
I3
I2
I1
L3
L2
L1
~~~
I3
k3
I2
k2
I1
k1
X/5A
X/5A
X/5A
select exit
2 3 5 6 8 9 11 12741 10
30
Connection:
MEDIUM VOLTAGE LOW VOLTAGE
Voltage become isolated. The value of the voltage transformer must be entered.
NOTE: The current transformer ratio must be entered in the section from the menu 1.7.8
Enter Voltage Trans. Value
2 3 5 6 8 9 11 12741 10
30
apply▼ -
0001.000
cancelokay back
▲ +
2A2A2A
2A2A2A
11
MEDIUM VOLTAGE LOW VOLTAGE
Connection:
Current Inputs Voltage Inputs
L1 L2 L3
I3
I2
I1
L3
L2
L1
~~~
I3
k3
I2
k2
I1
k1
X/5A
X/5A
X/5A
N
N
select exit
2 3 5 6 8 9 11 12741 10
30
Current from L.V / Voltage from L.V (without voltage transformer)
NOTE: The current transformer ratio must be entered in the section from the menu
1.7.7
2A2A2A
MEDIUM VOLTAGE LOW VOLTAGE
Connection:
Current Inputs Voltage Inputs
2 3 5 6 8 9 11 12741 10
30
1 7
Settings Switch on Time (decharge) (1 – 600 sec)
3
Enter Step Switch On (Dis.)
Time
2 3 5 6 8 9 11741 10
30
Apply▲ + ▼ -
020
sec
CancelOkay Exit
This is the enterance section of the value of decharge period (sec) holded for preventing the capacitor to activate again without decharging in the same step in case of requirement, after release of the activated step. The value is setup to the required step starting from the digit under which the blue line is, by using up and down keys. Then left key is pressed and the blue line moves next to left digit. All the values are entered in the same way by using up and down keys. Press “Apply” key inorder to take the period of step activating into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory. Period of activating line is subjected to a function with the % value obtained from the ratio of energies. In case % value is getting close to the inductive penalty line value, the time is reduced automatically by the device. If necessasy, compensation speeds up; and if not, it slows down by means of dynamic control of step activating, and continously do not make fast moves unnecessarily. P.S.: Step activating time counts only for capacitor released newly. If necessary and a close solution is found in another step, device activates the other option on time and the compensation is not delayed. If it' s not required the device to respond so quickly, holding period between the steps can be extended to delay receiving process by increasing the value of ΔT on switching time described in the next chapter.
P.S.3: In case of selecting the switch on time less than min.step time, device accepts the switch on time as constant time value.
1 7 10 1
Other Relays : They proceed the step activating transaction with constant time adjusted. If the time is not over, they will wait for the deadline. This causes delays in the compensation. VARkombi-12-PC-TFT-OG : It collects the energies (ind., cap., active) consumed. Step activating and de-activating periods are decreased or increased automatically by the device according to the consumed enerygy. P.S.: The energies consumed in VARkombi-12-PC-TFT-OG and the % values are calculated separately for each phase. Therefore, step activating and de-activating periods of each phase can vary. For instance, while the step activating time for R-phase down to 2 seconds, the one for S­phase can be 7 sec. VARkombi-12-PC-TFT-OG analyze the system phase by phase and set-up the compensation rate for each phase seperately. The most simple explanation regarding the ratio of energy of step activating period has been given below. In fact the function consists of much more complicated and an array of fuzzy logic. Step sub­period (min) determines the lowest time value of level activating time which can be reduced by the device. This parameter can be specified by the user.
% ind.
Switch on time
0
Min. Switch Time
% ind.penalty line
t(sec)
12
Enter Step Switch On (Dis.)
Time
020
sn
Save
changes
1 7
Settings - Target TanΦ ( % ±75 ) – CosΦ ( ± 0,800 )
2
This is the section in which the required % value of the system is entered. CosΦ value corresponding to the % value is displayed automatically on the other side. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Moving the blue sub-line to the digit where the sign is by using left key, the sign can be changed by pressing upwards key. (+) expresses inductive, (-) expresses capacitive sections..
Enter target TanΦ value
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
CosΦ
1.000
%
+00
Enter target TanΦ value
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
CosΦ
1.000
%
+00
Save
changes
“Apply” key is pressed to take the target value into memory. “Save Changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into the memory.
2 3 5 6 8 9 11 12741 10
30
002
sn
1 7
Settings Min. Switch Time (1 – 600 sec)
5
Enter Min.SwitchTime
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
002
Save
changes
sec
CancelOkay Back
This is the section in which the value of step sub-period (min) is entered (sec). The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Press “Apply” key inorder to take the step sub-period (min) time into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory. Period of activating line is subjected to a function with the % value obtained from the ratio of energies. It represents the minimum value of both step activating and de-activating time which can be changed by the device.
Step sub-period is not taken into account during fast mode.
2 3 5 6 8 9 11 12741 10
30
020
sn
1 7
Settings Switch Off time (1 – 600 sec)
4
Enter Step Switch Off Time
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
020
Save
changes
sec
CancelOkay Back
This is the section in which the value of switch off time is entered (sec). The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Press “Apply” key in order to take the switch off time into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory. Period of activating line is subjected to a function with the % value obtained from the ratio of energies. In case % value is getting close to the capactive penalty line value, the time is reduced automatically by the device. If necessasy, compensation speeds up; and if not, it slows down by means of dynamic control of switch off time, and continously do not make fast moves unnecessarily. P.S.1: Switch off time counts only for capacitor activated newly. If necessary and a close solution is found in another step, device deactivates the other option on time and the compensation is not delayed. If it' s not required the device to respond so quickly, holding period between the steps can be extended to delay releasing process by increasing the value of ΔT off switching time described in the next chapter.
P.S.2: In case fast operating mode is selected, switch off time of the device is 200 msec. It' s independent from switch off time which is set-up. P.S.3: In case of selecting the switch off time less than min.step time, device accepts the switch off time as constant time value.
1 7 10 2
Other Relays : They proceed the step de-activating transaction with constant time adjusted. If the time is not over, they will wait for the deadline. This causes delays in the compensation. VARkombi-12-PC-TFT-OG : It collects the energies (ind., cap., active) consumed. Step activating and de-activating periods are decreased or increased automatically by the device according to the consumed enerygy. P.S.: The energies consumed in VARkombi-12-PC-TFT-OG and the % values are calculated separately for each phase. Therefore, step activating and de-activating periods of each phase can vary. For instance, while the step de-activating time for R-phase down to 2 seconds, the one for S-phase can be 7 sec. VARkombi-12-PC-TFT-OG analyze the system phase by phase and set­up the compensation rate for each phase seperately. The most simple explanation regarding the ratio of energy of step de-activating period has been given below. In fact the function consists of much more complicated and an array of fuzzy logic. Level sub­period (min) determines the lowest time value of step de-activating time which can be reduced by the device. This parameter can be specified by the user.
% cap.
Switch Off time
0
Min. Step Time
% cap.penalty line value
t(sec)
13
200 msec
Fast Mode
Normal Mode
Enter Step Switch Off Time
Enter Min.Switch Time
1 7
Settings Inductive penalty limit ( % 3 – 50 )
6
This is the section in which the limit value of inductive/active % acceptable in compensation, is entered. This value is determined by electric distribution company and is recommended to setup a value slightly lower than requested to avoid penalty. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Press “Apply” key inorder to take the inductive penalty line into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
Enter inductive penalty limit
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
%
20
Enter inductive penalty limit
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
%
20
Save
changes
1 7
SettingsCapacitive penalty limit ( % 3 – 50 )
7
This is the section in which the limit value of capacitive/active % acceptable in compensation, is entered. This value is determined by electric distribution company and is recommended to setup a value slightly lower than requested to avoid penalty. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Press “Apply” key inorder to take the capacitive penalty line into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
Enter cap.penalty limit
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
%
10
Enter cap.penalty limit
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
%
10
Save
changes
1 7
SettingsCurrent Transformer (Primary) value ( 5.......10000 / 5A )
8
Enter current transformer value
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
00500 / 5A
Enter current transformer value
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
This is the section in which the primary value of current transformers in compensation system, is entered. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Press “Apply” key inorder to take the current transformer (primary) value into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
00500 / 5A
Save
changes
1 7
Settings Number of Steps ( 3 – 12 )
9
Enter number of steps
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
This is the section in which the number of steps will be used for compensation, is entered. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are entered in the same way by using the up and down keys. Press “Apply” key inorder to take the number of steps into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
12 12
Save
changes
14
Enter number of steps
1 7
Settings – Advanced Setting Menu
10
This is the section in which the parameters are not used very often.
1 7 10
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
0000
2 3 5 6 8 9 11 12741 10
30
CancelOK ESC
Enter ΔT On Delay time Enter ΔT On Delay time
0000
Save
changes
1
This is the section in which the holding time between steps during step activating, is entered. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are
entered in the same way by using the up and down keys. Press “Apply” key inorder to take ΔT on switching time into memory. “Save changes” message will appear on the screen. When “OK” key is pressed, the value is taken into memory.
In case at least one of ΔT on or ΔT off time is setup to any value rather than zero and the device runs in quick mode, quick mode is canceled automatically.
1 7
Settings – Advanced Setting Menu - ΔT off Delay Time (0 – 3600 sec)
10
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
0000
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Enter ΔT Off time Enter ΔT Off time
0000
Save
changes
This is the section in which the holding time between steps during step de-activating, is entered. The value is setup to the required step by using up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue line moves next to left digit. All values are
entered in the same way by using the up and down keys. Press “Apply” key inorder to take ΔT off switching time into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
sec
sec
2
1 7
Settings - Advanced Setting Menu – current flow direction detection
10 3
This is the section in which the function of searching of current transformer polarity directions are activated or de-activated. In case “Activated” is selected, internalization of current transformer direction is always “On”, and only checks the directions when the device is powered. If “Off” is selected, then the device internalize the current transformer directions at once and do not change it. The “Off” choice should be selected for some loads (producing negative active load). The required status for function is selected by using the up and down keys. Press “Apply” key inorder to take this parameter into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Enable
Direction Detection Status
Settings – Advanced Setting Menu - ΔT on Delay Time (0 – 3600 sec)
ΔT on
2
ΔT off
1 2
1
15
In case at least one of ΔT on or ΔT off time is setup to any value rather than zero and the device runs in fast mode, quick mode is canceled automatically.
In case internalization of direction is activated, internalization of current transformer direction is always “On”, and only checks the directions when the device is powered. In case the ends of current are changed while the device is running, it can not detect this. It' s needed to turn off and on again.
1 7
Settings – Advanced Setting Menu – Fast Step Mode
10 4
This is the section in which the fast step mode is enable or disable. In case “enable” is selected, the device can activate many steps at the same time as well as de-activate them. If “Off” is selected, then the device makes only one step attempt at each time. The required status for function is selected by using the up and down keys. Press “Apply” key in order to take this parameter into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Enable
Fast Step Mode Status
In case fast step mode is activated, the device set ΔT on and ΔT off times to zero automatically.
If fast step mode is selected, then the contactors which will be used, must be absolutely compensation contactors, and the step activating time (discharge) that the producers recommend, should be entered.
1 7
Settings – Advanced Setting Menu – Step Parameters – Continuos Step Power Detecting
10 5
This is the section in which the continous internalization of step power is activated or de-activated. In case “Activated” is selected, the device checks the step power at each step activating and de­activating operation. In case of a change in power, then the device determine it and start to use this value. If the last value of the capacitor is decreased by 50% than the power value of the initial internalization, the device warns the user about the decrease in power of capacitor. It continues to make compensation with the value internalized finally. In case “Off” is selected, the device can only internalize the capacitor powers on the first commissioning. It determines the change, but continues to compensation with the values of initial internalization.
P.S.: It can be necessary to disable the function of step power İnternalization in some plants (especially, the plants in which the loads are changing very quickly). The required status for function is selected by using the up and down keys. Press “Apply” key inorder to take this parameter into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Enable
Contn. Step Power Detecting
1 7
SettingsAdvanced Setting MenuStep parameters – Constant Step Function
10 5
This is the section in which the constant step function is activated or de-activated.First step switch on and stay at this position if this function is enable . This function is only used in activating constant capacitor to meet the loss of transformers in the counters measure the medium voltage. This capacitor must be connected ahead from the current transformers. Using the step of the device for constant capacitor is not recommended actually. Much more steps are required for compensation. Consequently, constant capacitor can be connected to switch input with a on-off switch. In case “Off” is selected, the device starts to use this step. The required status for function is selected by using the up and down keys. Press “Apply” key inorder to take this parameter into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Constant Step function
1 7
Settings Advanced Setting Menu – Step Parameters – Step Sync.Time Sharing
10 5
This is the section of activating or de-activating the simultaneous use of levels in the same power. In case “Activated” is selected, device tries to make the used hours of capacitors in the same power equal. The required status for function is selected by using the up and down keys. Press “Apply” key inorder to take this parameter into memory. “Save changes” message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Step Sync.Time Sharing
1
2
3
16
1 7
Settings – Advanced Setting Menu – Step Parameters – Enter Step Powers
10 5
This is the section in which the step powers are entered. The device directs the user with subcommand display continuously. It is moved on the step of which the power is required to be entered by using the up and down keys. In the meantime, that line are in red colour. Select key is pressed. The selected step number comes to screen. The selection of triple-phase or single-phase of capacitor or reactor should be made on this screen.
The position of red frame changes when up and down keys are used. In case the reactive load on the step is triple-phase, the frame is moved on triple-phase and “Select” key is pressed. Triple-phase option becomes red in this case. If up or down direction key is pressed, the red frame moves to total value digit. The “Select” key is pressed and a blue underline appears on the last digit inside of the frame. The value is setup by using the up and down keys starting from the digit where the blue line is. Then, left key is pressed and the blue underline moves next to the left digit. All the values are entered in the same way by using up and down keys. The “Apply” key is pressed to take them into memory. The sub­command screen changes and “Okay”, then “Exit” key is pressed. “Save Changes” will appear on the screen. When “Okay” key is pressed, the value is taken into memory.
If the reactive load on the step is single-phase, frame is moved onto single-phase and “Select” key is pressed. Single­phase option becomes red in this case. In case of pressing up or down direction key is pressed, the red frame moves on the lines of R, S and T-phases including total value. In case of which phase the reactive load on the step is connected to, “Select” key is pressed during on that line. Entering the value and taking it into memory is the same as described above.
P.S.: Moving the blue underline to the digit on which the sign is by using the left key, the sign can be changed by pressing upwards key. (+) represents the reactor, (-) represents the capacitor.
2 3 5 6 8 9 11 12741 10
30
Exit
Kvar
4
Select
R S T
K1 --------- --------- ---------
K2 --------- --------- --------­K3 --------- --------- --------­K4 --------- --------- --------­K5 --------- --------- ---------
Step powers are adjusted manually...
2 3 5 6 8 9 11 12741 10 14
30
Exit
3-phase
Select
R
S
T
1.Step
1-phase
Σ
0.000
KVAr
0.000 KVAr
0.000 KVAr
0.000 KVAr
2 3 5 6 8 9 11 12741 10
30
3-phase
R
S
T
1.Step
1-phase
Σ
0.000 KVAr
0.000
KVAr
0.000 KVAr
0.000 KVAr
Apply▲ + ▼ -
CancelOkay Exit
ExitSelect
2 3 5 6 8 9 11 12741 10
30
3-phase
R
S
T
1.Step
1-phase
Σ
0.000 KVAr
0.000 KVAr
0.000
KVAr
0.000 KVAr
CancelOkay Exit
Save
changes
1 7
Settings – Advanced Setting MenuStep Parameters – Delete Step Powers
10 5
2 3 5 6 8 9 11 12741 10
30
Exit
Kvar
5
Delete
R
S
T
K1 -0,500 -0,500 -0,500 K2 -1,000 -1,000 -1,000 K3 -1,500 -1,500 -1,500
K4 -2,500 -2,500 -2,500
K5 -3,330 -3,330 -3,330
2 3 5 6 8 9 11 12741 10
30
Kvar
R S T
K1 -0,500 -0,500 -0,500 K2 -1,000 -1,000 -1,000 K3 -1,500 -1,500 -1,500
K4 -2,500 -2,500 -2,500
K5 -3,330 -3,330 -3,330
2 3 5 6 8 9 11 12741 10
30
Kvar
R S T
K1 -0,500 -0,500 -0,500 K2 -1,000 -1,000 -1,000 K3 -1,500 -1,500 -1,500
K4 -2,500 -2,500 -2,500
K5 -3,330 -3,330 -3,330
2 3 5 6 8 9 11 12741 10
30
Kvar
R
S
T
K1 -0,500 -0,500 -0,500 K2 -1,000 -1,000 -1,000 K3 -1,500 -1,500 -1,500
K4 --------- --------- ---------
K5 -3,330 -3,330 -3,330
2 3 5 6 8 9 11 12741 10
30
Kvar
R
S
T
K1 --------- --------- ---------
K2 --------- --------- --------­K3 --------- --------- --------­K4 --------- --------- --------­K5 --------- --------- ---------
CancelOkay ExitCancelOkay Exit
Step
Delete ?
Step
Delete ?
Exit Delete Delete AllExit Delete Delete All
This is the section in which the step parameters are deleted one by one, or all. In case the reactive load is changed in any step, the power of that step must be deleted to let the device internalize the the power of new step. The device fowards the user continuously by sub-command screen. Moving onto the step of which power required to be deleted, the up or down key is pressed. The line is in red colour in the meantime. In case of deleting only that step, “Delete” key is pressed; in case of deleting all steps (if a device used in somewhere else is connected to a new plant), “Delete All” key is pressed. If “Delete” key is pressed, “Step Delete?” warning appears on the screen. When “Okay” key is pressed, the power of that step would be deleted. The device will automatically try to internalize the power of that step again. You can exit the menu by “Exit” key. In case “Delete All?” key is pressed, “Steps Delete?” warning appears on the screen. When “Okay” key is pressed, the power of all steps would be deleted. The device will automatically try to internalize the power of that step again. You can exit the menu by “Exit” key.
17
Delete All
1 7
Settings – Advanced Setting MenuStep Parameters – Step Change Control
10 5
It' a useful function in terms of warning the user. First, it' s better to clarify some definitions step alteration control page: Old value : The first internalized power of step. New value: The power alterated minimum ± 15% with respect to the past value. This page has been designed to identify and enter the real value of steps whose powers are not internalized, even though the powers are alterated over time or replaced with the past one by the user. In case the new value of any step is alterated ± 50% with respect to the first value, the device warns the user as “Change in the power of capacitor”. If the capacitor in which alert is given has really alterated, then the new value should be loaded instead of the past one. The alteration in step power appears on the screen as a warning In case internalization of step power is activated, the device controls the capacitor power at every step activation and de­activation process. In case of a change in the power, the device determines it and continue to compensate with the final value internalized. If “Off” is selected, the device internalize capacitor powers only at the first activation. It determines the alteration, however continues the compensation with the first internalized values.
The device directs the user with sub-command screen continuously. The red frame is moved on the step whose power decreased (box in blue colour) by using up and down keys and “Select” key is pressed. Sub-command screen is alterated. In case of which value will be used, past or new value key is pressed and then load key is presse. “Load selected value to step?” question appears on the screen. If “Yes” key is pressed, load will be completed.
6
2 3 5 6 8 9 11 12741 10
30
Exit
Old value
Select
R
S
T
Σ
0.000 K
0.000 K
0.000 K
0.000 K
Step Change
2 3 4 5 6
8 9
10 11 12
16 17
14 15
1 7 13
2 3 5 6 8 9 11 12741 10
30
ExitLoadNew value
Old value
Old value
R
S
T
Σ
0.000
K
0.000 K
0.000 K
0.000 K
Step Change
2 3 4 5 6
8 9
10 11 12
16 17
14 15
1 7 13
2 3 5 6 8 9 11 12741 10
30
CancelNoYes
R
S
T
Σ
0.000 K
0.000 K
0.000 K
0.000
K
2 3 4 5 6
8 9
10 11 12
16 17
14 15
1 7 13
1 7 10 6
This is the section in which the alerts are set and the value of protection parameters are entered. It consists of nested menus. You can move between the parameters which generate the menu by direction keys, and can enter the next sub-menu or into the parameter by pressing “Select” key on the sub-command screen.
The device directs the user with sub-command screen continuously. In case of entering into the parameter, the commands on the sub-screen are alterated as shown on the right side. In this case blue line appears under the first digit of the parameter. The value is alterated by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
CancelOkay Exit
ExitSelect
Apply▲ + ▼ -
1 7 10 6 1
1 7 10 6 1
Phase alarms
1 7 10 6 1
General Alarms
1 2
Over voltage Under voltage Over current Over compensation Under compensation No phase THD on voltage HD on voltage THD on current HD on current
1st Connector Error 2st Connector Error 3st Connector Error Total over compensation Total under compensation System Error Over temperature Voltage connection Step Change Step Zero Modbus security Error
Settings – Improved Setup MenuAlert & Protection
This is the section in which the activation or de-activation process of alerts are performed.
18
Settings – Advanced Setting Menu – Alarm & Protection – Alarm Control
18
18
18
Old value
Step Change
Load
Selected value
to Step ?
1 7 10 6 1
Phase Alarms – Over Voltage (enable)
1 1
In case of over voltage during the activation of alert, alert is given and device warns the user. In this case;
- capacitors and devices in the system may be damaged.
- “Voltage protection activated” may be preferred in the step protection function(Chapter 1710642)
1 7 10 6 1
Phase Alarms – Under Voltage (enable)
1 2
In case of under voltage during the activation of alert, alert is given and device warns the user. In this case;
- capacitors and devices in the system may be damaged or may not be operated properly.
- “Voltage protection activated” may be preferred in the step protection function(Chapter 1710642)
1 7 10 6 1
Phase Alarms – Over Current (enable)
1 3
In case over current is drawn from the system during the activation of alert, alert is given and device warns the user. In this case;
- Inputs of the device may be damaged any moment. This case is out of warranty.
- Please stop the system and replace the current transformers with the larger ones.
1 7 10 6 1
Phase Alarms – Over Compensation (enable)
1 4
In case the system falls into over compensation in any phase during the activation of alert, device warns the user. In this case;
- Review the capacitor power distribution in the steps, especially in the phase where the alert is given.
- Please allow less powerful capacitors which can reach buffer power values.
1 7 10 6 1
Phase Alarms – Under Compensation (enable)
1 5
In case the system falls into under compensation in any phase during the activation of alert, device warns the user. In this case;
- Review the capacitor power distribution in the steps, especially in the phase where the alert is given.
- Please insert the capacitors which the phase or the phases need.
1 7 10 6 1
Phase Alarms – No Phase (enable)
1 6
In case any phase in the system cut down during the activation of alert, device warns the user. In this case;
- At least one of the phases is not in the system..
- Measure the voltage at the voltage input terminals, control the terminals. You should read 220V between phase-neutral.
1 7 10 6 1
Phase Alarms – THD on Voltage (enable)
1 7
In case total harmonic failure in the phase voltage exceeds the set value during the activation of alert, device warns the user. In this case;
- You should install harmonic filter to protect your devices.
1 7 10 6 1
Phase Alarms – HD on Voltage (enable)
1 8
In case the failure of any harmonics between 3...31 in the phase voltage exceeds the set value during the activation of alert, device warns the user. In this case;
- You should install harmonic filter to protect your devices.
1 7 10 6 1
Phase Alarms – THD on Current (enable)
1 9
In case total harmonic failure in the phase of system exceeds the set value during the activation of alert, device warns the user. In this case;
- You should install harmonic filter to protect your devices.
1 7 10 6 1
Phase Alarms – HD on Current (enable)
1 10
In case the failure of any harmonics between 3...31 in the phase voltage exceeds the set value during the activation of alert, device warns the user. In this case;
- You should install harmonic filter to protect your devices.
19
20
1 7 10 6 1
General Alarms – 1. connector failure (K1...K6) (enable)
2 1
In case of this alarm;
- (C1) common phase input may not be connected.
- The fuse of (C1) common phase input may blowed out.
- Compensation connection may be made prior to current transformers.
- Removing the failure, steps internalized zero should be internalized again.
1 7 10 6 1
General Alarms – 2. connector failure (K7...K12) (enable)
2 2
In case of this alarm;
- (C2) common phase input may not be connected.
- The fuse of (C2) common phase input may blowed out.
- Compensation connection may be made prior to current transformers.
- Removing the failure, steps internalized zero should be internalized again.
1 7 10 6 1
General Alarms – Total Over Compensation (enable)
2 4
In case of this alarm ;
- The system may be kept in penalty.
- Review the capacitor power distribution in the steps.
- Please allow less powerful capacitors which can reach buffer values.
1 7 10 6 1
General Alarms – Total Under Compensation (enable)
2 5
In case of this alarm ;
- The system may be kept in penalty.
- Review the capacitor power selection in the steps.
- Please insert the capacitors which the phase or the phases need.
1 7 10 6 1
General Alarms – System Failure (enable)
2 6
In case of this alarm;
- (C1,C2) common phase inputs may not be connected.
- The fuse of (C1,C2) common phase inputs may blowed out.
- The fuses in the power line of capacitors may blowed out.
- Removing the failure, steps internalized zero should be internalized again.
1 7 10 6 1
General Alarms – Over Temperature (enable)
2 7
In case of this alarm;
- The temperature in the board exceeds the value setted.
- Please empower the panel cooling.
-“Temperature protection enable” may be preferred in the step protection function (Chapter 179641)
1 7 10 6 1
General Alarms – Modbus Firewall (enable)
2 11
In case of this alarm; only for VARkombi-12-PC-TFT-OG
- This means unauthorized access from the outside. Change the password of modbus read-write of the device periodically and prefer to encode read-write different.
1 7 10 6 1
General Alarms – Voltage Connection Failure (enable)
2 8
In case of this alarm;
- R and S phases may shortcircuit to each other, control the connections.
- S and T phases may shortcircuit to each other, control the connections.
- R and T phases may shortcircuit to each other, control the connections.
- Any of R, S, T phase may be connected to Neutral, control the connections.
1 7 10 6 1
General Alarms – Step Change (enable)
2 9
In case of this alarm;
- The old capacitor may be replaced with the new one, but power value is not entered, or the power of capacitor may be decreased 50%.
1 7 10 6 1
General Alarms – Step Zero (enable)
2 10
In case of this alarm;
- The fuses in the power line of capacitors may blowed out or contactor may be damaged.
- Removing the failure, steps internalized zero should be internalized again.
1 7 10 6 2
Setting – Advanced Setting Menu – Alarm & Protection – Alarm Setting Values
This is the section in which the alarm setup values are entered.
1 7 10 6 2
Alarm Setting Values – Over Voltage (230 – 270 V)
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
240
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Over voltage setting
V
Over voltage setting
V
This is the section in which the value of over voltage are entered. You may enter a value between 230 and 270 Volts. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
240
Save
changes?
In case voltage protection is activated in the level protection function (Chapter 1710642), all levels are de-activated one by one to protect the capacitors when over voltage setup value is exceeded.
1 7 10 6 2
Alarm Setting Values – Under Voltage (170 – 210 V)
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
170
2 3 5 6 8 9 11 12741 10
30
CancelOK ESC
Under voltage setting
V
Under voltage setting
V
This is the section in which the value of under voltage are entered. You may enter a value between 170 and 210 Volts. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
170
Save
changes?
In case voltage protection is activated in the step protection function (Chapter 1710642), all steps are de-activated one by one to protect the capacitors when under voltage setup value is exceeded.
1
2
The contactors are in difficulty to stay drawn especially under a certain voltage and, therefore the capacitor as well as contactor are exposed to operate in undesirable overload and arc. For this reason, activating voltage protection function is recommended.
2 3 5 6 8 9 11 12741 10
52
Apply▲ + ▼ -
050
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Over Temp. alarm value
°C
This is the section in which the value of over temperature are entered. You may enter a value between 5 ile 85 °C. The value is setup to the required value by using the up and down key
starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
In case the temperature exceeds the setup value, the value displayed in light blue color becomes red on the upper right of screen.
050
Over Temp. alarm value
°C
Save
Changes ?
In case temperature protection is activated in the step protection function (Chapter 1710641), all steps are de-activated one by one to protect the capacitors when over temperature setup value is exceeded.
21
1 7 10 6 2
Alarm Setting Values – Over Temperature (5 – 85 °C)
3
1 7 10 6 2
Alarm Setting Values – THD Voltage Setting (% 1 – 100)
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
008
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Voltage THD Alarm Setting
THDV
%
This is the section in which total harmonic distortion value (THDV) are entered for voltage. You may enter a value between 1% and 100%. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
4
007
Voltage THD Alarm Setting
THDV
%
Save
Changes ?
In case harmonic protection is activated in the step protection function (Chapter 1710643), all steps are de-activated one by one to protect the capacitors when THDV setup value is exceeded.
1 7 10 6 2
Alarm Setting Values – HD Voltage Setting (% 1 – 100)
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
006
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Voltage HD Alarm Setting
HDV
%
This is the section in which harmonic distortion value (HDV) are entered for voltage. You may enter a value between 1% and 100%. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
5
005
Voltage HD Alarm Setting
HDV
%
Save
Changes ?
In case harmonic protection is activated in the step protection function (Chapter 1710643), all steps are de-activated one by one to protect the capacitors when HDV setup value is exceeded.
1 7 10 6 2
Alarm Setting Values – THD Current Setting (% 1 – 100)
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
020
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Current THD Alarm Setting
THDI
%
This is the section in which total harmonic distortion value (THDI) are entered for current. You may enter a value between 1% and 100%. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
6
020
Current THD Alarm Setting
THDI
%
Save
Changes ?
1 7 10 6 2
Alarm Setting Values – HD Current Setting (% 1 – 100)
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
015
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Current HD Alarm Setting
HDI
%
This is the section in which harmonic distortion value (HDI) are entered for current. You may enter a value between 1% and 100%. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
7
015
Current HD Alarm Setting
HDI
%
Save
Changes
22
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
2 3 5 6 8 9 11 12741 10
30
CancelOkay Exit
Fan Temperature Value
This is the section in which fan output activation value is entered. You may enter a value between 5 and 85 °C. The value is setup to the required value by using the up and down key starting from
the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
1 7 10 6 3
Setting – Advanced Setting Menu – Alarm & Protection – Fan Settings
This is section in which the setup values of fan inputs are entered.
1 7 10 6 3
Fan Settings – Fan Temperature Value (5 – 85 °C)
1
Fan Temperature Value
050
°C
050
°C
Save
Changes ?
In case of requring to use 18 steps in the device, fan output is not used. 17 steps is selected in the device inorder to use fan input or, if fan output is activated, the condition is realized automatically.
The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
1 7 10 6 3
Fan Settings – Fan Output
2
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
disable
Fan Output
1 7 10 6 4
Setting – Advanced Setting Menu – Alarm & Protection – Step Protection Function
De-activation of the capacitors is recommended to protect them against temperature, voltage and harmonics. This is the section in which protection is permitted. P.S.: In case the current connector moves out or there is a connection failure at the voltage inputs, protection is activated automatically and de-activates the steps one by one.
1 7 10 6 4
This is the section in which the temperature protection function is activated or de-activated. The over temperature alarm should also be activated to operate the protection function (Chapter
1.7.10.6.1.2.7). The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
1
Step Protection Function – Temperature Protection
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Temperature Protection
1 7
This is the section in which the voltage protection function is activated or de-activated. The voltage alarms should also be activated to operate the protection function (over voltage, under voltage, no phase). The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
Step Protection Function – Voltage Protection
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Voltage Protection
10 6 4 2
23
1 7
This is the section in which the protection function is activated or de­activated against voltage harmonics. Voltage harmonic alarms (THDV and/or HDV) should be activated in order to operate protection function. The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “OK” key, the value is taken into the memory.
Step Protection Function – Harmonics Protection
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Harmonic Protection
10 6 4 3
1 7 10 7
Setting – Advanced Setting Menu – Password Settings
1 7 10 7
Setting – Advanced Setting Menu – Password Settings – Password Enable/Disable
1
1 7 10 7
Setting – Advanced Setting Menu – Password Settings – Change Password
2
This is the section in which the use of device is activated or de­activated with password. Initial password is “0000”. In case the user changes the password, old password is valid even if returned to the factory settings. In case of forgetting the password, our technical support team should be called. The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Enable
User Password Status
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Enter old
password
0
***
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Enter old password
0
***
Okay
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Enter
New Password
0
***
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Enter New Password
0
***
Okay
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Re-Enter
New Password
0
***
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Re-Enter
New Password
0
***
Okay
2 3 5 6 8 9 11 12741 10
30
Exit
Password active/passive
Password change
1 7 9 7 2
PASSWORD
Tekrar Yeni Şifrenizi Giriniz
0
***
Okay
Save
Password?
This is the section in which password is changed.
First, old password must be entered correctly.
Number value of the digit under which blue line is, is entered by using upwards key. You can move to the next digit by the right key. When the values of all digits are entered in the same way, “Okay” key is pressed. In case the old password is entered correctly, the new password page is displayed inorder to let the user change password.
New password is entered two times in the same way. In case two passwords are the same, “Password Correct” message displays on the screen.
When “Okay” key is pressed, the new password is taken into memory.
24
25
1 7 10 9
Setting – Advanced Setting Menu – MODBUS RTU Settings
1 7 10 9
Setting – Advanced Setting Menu – MODBUS RTU Settings – Data Write Protection
1
This is the section which is used to give writing allowance to the device parameters when connection is made externally via MODBUS RTU.
The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “OK” key, the value is taken into the memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Data writing protection
1 7 10 9
Setting – Advanced Setting Menu – MODBUS RTU Settings – Data Read Protection
2
This is the section which is used to give reading allowance to the device parameters and data when connection is made externally via MODBUS RTU. The required condition is selected for function by using up or down keys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “OK” key, the value is taken into the memory.
2 3 5 6 8 9 11 12741 10
30
Apply▲ + ▼ -
Disable
Data reading protection
1 7 10 9
Setting – Advanced Setting Menu – MODBUS RTU Settings – Data Write Password
3
30
Data writing password
0000
Apply▲ + ▼ -
2 3 5 6 8 9 11741 10 12
The password should be entered to write data. This is the section in which the password is entered. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory. P.S.: The security increases when giving different passwords for writing and reading data.
1 7 10 9
Setting – Advanced Setting Menu – MODBUS RTU Settings – Data Read Password
4
30
Data reading password
0000
Apply▲ + ▼ -
The password should be entered to read data. This is the section in which the password is entered. The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory. P.S.: The security increases when giving different passwords for writing and reading data.
2 3 5 6 8 9 11741 10 12
1 7 10 8
Setting – Advanced Setting Menu – Generator Parameters
VARkombi-12-PC-TFT-OG does not have this function.
26
1 7 10 9
Setting – Advanced Setting Menu – MODBUS RTU Settings – Port Settings
5
30
Modbus Settings
Baud Rate Stop Bits Parity Device No
30
Modbus Settings
Baud Rate Stop Bits Parity Device No
9600
Apply▲ + ▼ -
30
Modbus Settings
Baud Rate Stop Bits Parity Device No
19200
1
No
1
ExitSelect CancelExitOkay
30
Modbus Settings
Baud Rate Stop Bits Parity Device No
9600
1
No
2
30
Modbus Settings
Baud Rate Stop Bits Parity Device No
9600
1
No
002
Apply▲ + ▼ -
30
Modbus Settings
Baud Rate Stop Bits Parity Device No
9600
1
No
1
ESCSelect CancelExitOkay
Save
Changes ?
This is the section in which Modbus port setup is entered.
Baud rate: It can be selected as 2400,4800,9600,19200,28800,38400,57600 or 115200. Stop Bits : It can be selected as (0.5) , (1) , (1.5) or (2). Parity : no , even , odd
Up or down key is used for the entry of above parameters. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
Device No : 001 .....255
The value is setup to the required value by using the up and down key starting from the digit where the blue line is. Then left key is pressed and the blue underline moves next to the left digit. All values are entered in the same way by using up and downkeys. “Select” key is pressed to take them into the memory. “Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into the memory.
1
No
1
9600
1
No
1
Save
Changes ?
2 3 5 6 8 9 11741 10 122 3 5 6 8 9 11741 10 122 3 5 6 8 9 11741 10 12
2 3 5 6 8 9 11741 102 3 5 6 8 9 11741 10 122 3 5 6 8 9 11741 10 12 12
The device may be connected as 3 Phase and 3 Phase 4 wires (3P&4W) with neutral or 3Phase without neutral and 3 Phase 3 Wires (3P&4W). Connections without neutral also display phase-neutral voltages correctly thanks to specially designed software.
Type of Connection
3P/4W
Apply▲ + ▼ -
With Neutral
Type of Connection
3P/3W
Apply▲ + ▼ -
Without Neutral
2 3 5 6 8 9 11 12741 10 2 3 5 6 8 9 11 12741 10
1 7
Settings – Advanced Setting Menu – Connection Settings
10 10
27
1 8
Factory Defaults
This is the section which is used to restore factory default values to the device.
Factory Default Values :
Target TanΦ(cosΦ) : % 0 Switch on (Decharge) Time : 20 sec Switch off Time : 15 sec Switch min. Time : 10 sec Inductive Penalty Limit (%) : % 15 Capacitive Penalty Limit (%) : % 10 Current Transformer (Primary) Value : 5 / 5 A Number of steps : 12 ΔT on Transition(Delay) Time : 0 sec ΔT off Transition(Delay) Time : 0 sec Continuous Current Flow Direction Detection : enable Fast Step Mode : enable Connection Type : WYE Continuous Step Power Detection : enable Constant Step Function : disable Step Synch. Time Sharing : disable Phase Alarms – Over Voltage : enable Phase Alarms – Under Voltage : enable Phase Alarms – Over Current : enable Phase Alarms – Over Compensation : enable Phase Alarms – Under Compensation : enable Phase Alarms – No Phase : enable Phase Alarms – THD on Voltage : enable Phase Alarms – HD on Voltage : enable Phase Alarms – THD on Current : enable Phase Alarms – HD on Current : enable General Alarms – 1. connector failure : enable General Alarms – 2. connector failure : enable General Alarms – Total Over Compensation : enable General Alarms – Total Under Compensation : enable General Alarms – System Failure : enable General Alarms – Over Temperature : enable General Alarms – Voltage Connection Failure : enable General Alarms – Step Change : enable General Alarms – Step Zero : enable General Alarms – Modbus Security Failure : enable Alarm Setting Values – Over Voltage : 250V Alarm Setting Values – Under Voltage : 180V Alarm Setting Values – Over Temperature : 70 °C Alarm Setting Values – THD Voltage : % 10 Alarm Setting Values – HD Voltage : % 10 Alarm Setting Values – THD Current : % 30 Alarm Setting Values – HD Current : % 30 Fan Settings – Fan Temperature Value : 50 °C Fan Settings – Fan Output : disable Level Protection Function–Temperature Protection: disable Level Protection Function – Voltage Protection : disable Level Protection Function – Harmonic Protection : disable Password Procedure – Password Settings : enable Password Procedure – Default Password : 0000 (refer to PS1) MODBUS RTU Setup – Data Write Protection : disable MODBUS RTU Setup – Data Read Protection : disable MODBUS RTU Setup – Data Write Password : 0000 (refer to PS2) MODBUS RTU Setup – Data Read Password : 0000 (refer to PS2) MODBUS Port Setup – Baud Rate : 9600 MODBUS Port Setup – Stop Bits : 1 MODBUS Port Setup – Parity : No MODBUS Port Setup – Device No : 1
Select Exit
1 8
SETUP
Factory Defaults
Power Energy Counter Index
Settings
30
Yes Cancel
Device
will return
factory settings
30
Yes Cancel
30
Install the device
to the Factory
Settings
Device
will reset ?
1 2 3 4 5 6 7 8 9 10 11 12
30
Factory defaults
of the device are loading
In case of restoring factory settings, all the changes that the user made, except password, will be cancelled.
PS 1 : User password is defined as “0000” at first. However, after password is changed, password will not change even if returned to the factory settings. The last password that the user entered is valid. PS 2 : It is different than the user password of the device. However it can be entered into the device manually, it can not be changed by remote access. In case of restoring factory settings, “0000” is appointed to modbus password. PS 3 : In case of restoring factory settings, the current directions, capacitor powers, energies and counter indexes that the device internalized before, are reset.
2 3 5 6 8 9 11741 10 12
2 3 5 6 8 9 11741 10 12
2 3 5 6 8 9 11741 10 12
Operating Voltage (Un) : (Phase-Neutral ) 220Vac ; (Phase-Phase) 380 Vac Operating Range : (0,8-1,1) x Un Operating Frequency : 50/60 Hz Supply Power Consumption : < 10VA Power Consumption of Measurement Inputs : < 1VA Contact Current : Max.3A/240 Vac Current Measurement Range : (as secondary current of current transformer)
0,01 - 6 Amp AC Display Range : (Power Factor) 0,000 - 1,000 ind.and cap. Mimimum Current Measurement Value : 10 mA Measurement Accuracy : %1±1 digit
Current Transformer Ratio : 5/5..........10000/5 A
Display : 3,2” coloured LCD
RS485
Baud rate : 2400,4800,9600,19200,28800,38400,57600,115200 Stop Bits : (0.5) , (1) , (1.5) or (2) Parity : no , even , odd
Device No : 1 .....255
Device Protection Class : IP 20 Terminal Protection Class : IP 00
Environment Temperature : - 5 °C .... + 50 °C
Humudity : %15 ...... %95 (without condensation)
Device Standart : EN 55011: 2007 + A2 : 2007 EN 61326 : 2006 EN 61000-3-2 : 2006 EN 61000-3-3 : 1995 + A1 : 2001 + A2 : 2005 EN 61010-1 : 2001 Connection Type : On the front cover of the panel Dimensions : 144x144x45 mm
Technical Info
37 mm
140mm
140mm
50mm
WALL
1- An outlet in square form by 140 mm x 140 mm will be made on the panel where the assembly of the device will be made. 2- Prior to the assembly of the device, remove the apparatus of the panel. 3- Insert the device from the front window drilled at the panel. 4- Fix the device to the panel by using panel holding apparatus at the back of the device.
Installation
Make the assembly as to leave a 50 mm space between the wall and the back of the device for ventilation.
PANEL OUTLET MEASUREMENT
28
APPENDIX-A
CALCULATION CHART ACCORDING TO CAPACITOR CONNECTION FORMAT
Capacitor
Powers
3 Phase
Connection
Phase-Neutral
Connection
Phase-Neutral
bridged
Connection
Phase-Phase
Connection
Phase-Phase
bridged
Connection
Loading...