KAEL Muhendislik Elektronik TC - PT100 User Manual

KAEL Mühendislik Elektronik
Tic. ve San. Ltd.Şti.
Temperature Controller
For Dry Type Medium Voltage Transformers
www.kael.com.tr
TC - PT100
Introduction
Warning
Tel: 0.232.877 14 84 (pbx) Fax: 0.232.877 14 49 Factory: Ataturk Mah. 78 Sok. No:10 Ulucak Village, Kemalpaşa - İZMİR.
The device must be commissioned and programmed by authorized and qualified persons in accordance with the instructions in the operating instructions. If necessary, they should also be inspected by these persons.
Do not open the device, do not make it opened. There are no serviceable parts inside the device that any other user or person will intervene.
Use the device in accordance with installation instructions
Before making electrical connections to the terminals of the device, make sure that there is no energy in the cables and terminals. There should not be energy in the panel.
The fuses to be used in the device must be 1A FF type.
Secure the appliance firmly so that it does not swing to the panel with the appliances supplied.
Do not interfere of the keys on the front panel of the device with anything other than your fingers.
Once you are sure that you have cut off your device, wipe it with dry cloth only. Chemicals used in water or cleaning shall damage the device.
Make sure that the terminal connections are made in accordance with the connection diagram and not in contact (loose connection or interconnection of multiple copper wires, etc.) before the device is switched on (before energization).
The above precautions and warnings are for your safety. In case of non-compliance, KAEL Elektronik Ltd. Sti. or vendors are not responsible.
1-
2-
3-
4-
5-
6-
7-
8-
9-
10-
Features
24 - 240 Vac - Vdc 50/60Hz ultra wide feed input
Easy menu design with Turkish, English and Russian language support
Color LCD display (320 x 240 pixel x 2.4 ")
Built on embedded system and working on operating system
It has 4 Pt100 (3-Wires) RTD sensor inputs
Sensor inputs are resistant to electromagnetic interference
Cable lengths in Pt100 are not included in the calculation
It measures temperature between -10°C and 250°C and has ± 1% measurement accuracy
1 ALARM relay output
1 TRIP relay output
There is a relay output (FAULT) for errors in one device operation
1 FAN relay output for cooling
The alarms and faults received by the device are stored in the device memory (the last 40 records)
3VA supply available
Intelligent Fan operation and stop algorithm saves energy in transformer cooling
Continuously monitors temperature sensors for faults. It detects errors "Sensor cable is broken", "Sensor cable short circuit" "Sensor not attached"
Error detection in case of data recording center failure
Password Protection protects the Settings menu against unauthorized users
There is a button for making the alarm silent or for Manual Fan control
General
The device that is developed to protect the windings of MV transformers and high-power motors equipped with today's technology, is quite well equipped in terms of function richness and has added a new product to its sector with its advanced software. Additionally, the microprocessor inside is very fast and uses the operating system. This ensures that all operations can be synchronized simultaneously.
Displaying the error and temperature values that may occur on the main screen during device operation is as follows.
85
Ch1
Menu
0
ºC
TRIP(135ºC)
95ºC
94
Ch2
91
Ch3
32
Ch4
14:2511.10.2016
50
100 150 200 250
FAN Report
ºC
ºC
ºC
ºC
■ The connection of the device should be done without the system power.
■ The device must be connected as shown in the connection diagram.
■ Do the Pt100 sensor inputs as shown on the back of the unit
■ Do not energize the device without checking all connections using the meter.
Making Connections
Information Panel
The upper part of the screen of the device has an information panel consisting of icons easily understood by the user. This panel is always on top of the screen no matter which part the user is in. The date, time, device operation status, FAULT status, ALARM status, TRIP status, FAN status information are observed in this panel at the same time. The operating status indicator indicates OK if the system is normal and returns to exclamation point when an error occurs in the system.
A color LCD display is used in our device to make it much easier and clearer to use. If the keys are not pressed for a long time, the device will switch to screen saver mode to extend the life of the screen and only step down from the top of the screen with the information panel on top. When any key is pressed, the main screen image appears again.
System Normal
FAN
14:2511.10.2016
ALARM TRIP
TRIP
FAULT (error existing)
TC - PT100
Temperature Controller
Power supply
Un : 24 ... 240V AC 50/60Hz / DC Δn : (0,9 – 1,1) x Un
PT100
red red white
PT100
red red
PT100
red red
PT100
red red
ch1ch2ch3ch4
ALARM
TRIP
FAULT
FAN
K-FAN
SYSTEM
STOP
V
V
white
white
white
The fan icon turns on the screen while the fan is running. If the screen shows a fan but does not turn, then the unit has gone into a saving mode for cooling.