Description Trendline 1-2-3 /Troja 1-2-3 / Softline / Zeus / Athene
Hera / Avanti/Fineline 1-2/Cubic series
A. DISTANCE TO SIDE WALL US/CANADA 18" (46 cm)
B. DISTANCE TO BACK WALL US/CANADA 10" (25 cm)
C. CORNER DISTANCE TO SIDE WALLS US/CANADA 7" (18 cm)
D. CONNECTOR PIPE TO SIDE WALL US/CANADA 26" (65 cm)
E. CONNECTOR PIPE TO BACK WALL US/CANADA 16" (41 cm)
F. CORNER PIPE TO SIDE WALLS US/CANADA 16" (41 cm)
G. DISTANCE TO FURNITURE US/CANADA 36“ (92 cm)
H. FRONT FLOOR PROTECTION US 16" (41 cm)
CANADA 18" (46 cm)
I. SIDE FLOOR PROTECTION US 8" (20 cm)
beyond the sides of the fuel loading door
CANADA 8" (20 cm)
beyond the sides of the stove
J. DISTANCE TO WALL TURNABLE US/CANADA 40" (100 cm)
K. CONNECTOR PIPE TO WALL TURNABLE US/CANADA 48" (120 cm)
L. DISTANCE TO FLOOR US/CANADA 20" (50 cm)
CEILING TO TOP OF STOVE US/CANADA 36" (92 cm)
CEILING TO CONNECTOR PIPE US/CANADA 18" (46 cm)
Note: A heat shield or protective wall may be used to reduce clearances if approved by the regulatory authority. Clearances to nonconcombustible materials are 2” (5cm), but note that “noncombustible” must be solid
cement or block (not brick or tile over combustible material).
2. Before installing your stove
Jydepejsen stoves Trendline1+2+3, Troja 1+2+3, Softline, Fineline, Zeus, Athene, Hera,
Avanti, and Cubuc series are tested by OMNI-Test Laboratories, Inc. of Beaverton, Oregon
and are listed to UL 1482 and ULC S627. They are also EPA certied and meet the more
stringent WA State Environmental standards.
Consult your local Building Inspector or Fire Marshall before installation to determine the
need to obtain a permit. Also inquire about restrictions and installation inspection requirements in your area.
If the stove is not installed properly, a home re may result. To reduce the risk of re,
follow the installation instructions. Contact local building or re ocials about restrictions
and installation inspection requirements in your area. Not for use in a mobile home.
A oor plate of non-combustible material (tempered glass oor plates are acceptable)
must cover under the stove and extend 16“ (41 cm) (18“ (45 cm) in Canada) in front of the
stove door, 8“ (20 cm) beyond the sides of the fuel-loading door, and under the pipe and
2“ (5 cm) beyond each side for back venting. In Canada, the 8“ (20 cm) oor protection is
required beyond the sides of the stove and in the back of the stove (0“ in the back for the
US).
Wall and corner Cubic models - If you have a Cubic Wall/Cubic Corner/Cubic W200 the
stove must be installed with the enclosed furnishings and should meet the NFPA211
guidelines. The installation must not weaken the chimney construction. The anhoring
must be done in consultation with your dealer/chimney sweep.
Cubic 166/215 - The taller Cubic models may reach the ceiling (or less than the 18"
distance to the connector pipe). If the unit does not meet the proper clearance to the
ceiling, the chimney pipe must be used to connect to the re box.
4
MIMIMUM CLEARANCES TO COMBUSTIBLES - Refer to diagrams on next 2 pages