Just Better SH-36N User Manual

A34000
1/4 SAE TEE
W/SWIVEL COUPLE R
MATCHING
REFRIGERAN T
KE Y
SENSOR
SUCTION LINE
LIQUID LIN E
CONDENSING
UNIT
REFRIGERAN T
TANK
TO
SUCTION SER VICE
VALV E
QC RESTRICT OR
FITTING
TO
LIQUID LINE
SER VICE VALV E
TEMPER ATUR E
SENSO R
SUPERHEAT
SUBCOOL
SUCTION LINE
LIQUID LIN E
MATCHING
REFRIGERAN T
KE Y
TEMPER ATUR E
SENSOR
CONDENSING UNIT
TO
LIQUID
SE RVICE
VALVE
TEMPER ATUR E
SENSOR
SUPERHEAT
SUBCOOL
SUCTION LINE
LIQUI D
LINE
TEMPERA TURE
SENSOR
EX PA NSION
VALV E
MATCHING REFRIGERANT KE Y
EVAPORA TOR
TEMPERA TURE SENSOR
SUPERHEAT
SUBCOOL
1. Connect the gauge to the A34000 tee fitting on the high (liquid) side of the manifold as shown.
2. Install the Temperature Sensor on the liquid line next to the liquid service valve and plug into gauge.
3. For system refrigerants other than R-22, plug in the matching Refrigerant Key into the gauge.
4. Toggle the gauge display to show SUBCOOLING.
5. Very slowly add or remove refrigerant until the gauge displays the required Subcooling value.
SUPERHEAT TEST
SUCTION LINE
LIQUID LI NE
MATCHING
REFRIGERANT
KEY
TEMPERA TURE
SENSOR
CONDENSING UNIT
TO SUCTIO N SER VICE
VALVE
TEMPERA TURE
SENSOR
SUPERHEAT
SUPERHEAT
SUBCOOLING TEST
1. Turn on the gauge.
2. For refrigerants other than R-22, plug in the matching Refrigerant Key.
TESTING FOR CHARGE
EVAPORA TOR
SUCTION LINE
LIQUI D
LINE
EXP ANSION
VALV E
MATCHING
REFRIGERANT
KE Y
TEMPERA TUR E
SENSO R
TEMPERA TUR E
SENSO R
SUPERHEAT
SUPERHEAT
2. Plug in the Temperature Sensor and mount the sensor as shown.
3. Toggle the display to show Superheat or Subcooling.
CHARGING BY THE SUBCOOLING METHOD
APPLICATIONS
?
Refrigeration Systems
?
High Efficiency Residential
?
Large Commercial A/C Rooftop
Packages Up To And Over 100 Tons
Average Subcooling Value is 10°–12°.
Contact manufacturer or wholesaler for specific temperatures.
Systems With TXV And No Receiver
OUTDOOR TEMP°F
EVAPORATOR ENTERING AIR-°F.Wet-Bulb Temperature
50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14 17 20 23 26.9 29 32 35 37 40 42 45 60 7 10 12 15 18 21 24.3 27 30 33 35 38 40 43 65 6 10 13 16 19 21.9 24 27 30 33 36 38 41 70 7 10 13 16 19.6 21 24 27 30 33 36 39 75 6 9 12 16.2 18 21 24 28 31 34 37 80 5 8 13.3 15 18 21 25 28 31 35 85 12.5 11 15 19 22 26 30 33 90 10.2 9 13 16 20 24 27 31 95 6 10 14 18 22 25 29 100 8 12 15 20 23 27 105 5 9 13 17 22 26 110 6 11 15 20 25
115 8 14 18 23
A
WET BULB TEMPERATURE OF EVAPORATOR ENTERING AIR
1. Turn on with zero pressure. Gauge will automatically calibrate to “Zero” for altitude and atmospheric pressure changes.
2. Wet the sock with water and slip on to sensor. Mount on the building return air grill or air return line of blower to measure the Indoor Wet Bulb temperature.
3. Turn on the furnace fan to create a flow of air across the wet sock for 5 minutes. The final number will be your Wet Bulb Temperature.
OUTDOOR TEMPERATURE
1. Remove sock and measure the Outdoor Air Temperature.
B C
1. Find the outdoor temperature and evaporator entering air wet­bulb temperature on chart. The target superheat value is at the intersection of the two.
If you have to do repairs, recheck your temperatures.
2. Make your connections and toggle the gauge to show SUPERHEAT. For system refrigerants other than R22, plug in matching Refrigerant Key.
3. Very slowly add or refrigerant to lower superheat or remove refrigerant to raise superheat until the gauge displays the target value.
OBTAINING TARGET SUPERHEAT VALUE
JB INDUSTRIES AURORA, IL 60507 USA
Technical service: 800-323-0811 E-Mail:sales@jbind.com Web Site:www.jbind.com
12.5
Sample Superheat Chart
(Located on condensing unit.
For older models contact manufactu
r
er)
WET SOCK IN AIR FLOW
TEMPER AT URE
SENSO R
TEMPERA TURE
SENSOR
SUCTION LINE
LIQUID LIN E
REFRIGERAN T
TANK
TO
SUCTION SE RVIC E
VALVE
QC RESTRICT OR
FITTING
TO
LIQUID LINE
SER VICE VALV E
TEMPER ATURE
SENSOR
A34000 1/4 SAE TEE W/SWIVEL COUPLE R
MATCHING
REFRIGERAN T
KE Y
TEMPER ATURE
SENSOR
SUPERHEAT
SUPERHEAT
SUPERHEAT
TARGET SUPERHEAT VALVE
SUPERHEAT
Not intended for use on hazardous or corrosive fluids
GAUGE SPECIFICATIONS: Pressure display range: 29 InHg to 600 psig (-98kPa to 4134 kPa)
(+/- 1 PSI to 200 psi, 0.5% to 600 psi) Temperature display range: -40°F to 200°F (-40°C to 93°C) Operating temperature: -10°F to 120°F (-12°C to 49°C)
(+/- 1°F * 32°F/120°F, +/- 1.5°F * -10°F/32°F) Maximum overpressure: 800 psig (5512 kPa) Battery life and type: 100 hours/ 9vAlkaline battery Auto-shutoff time: 60 minutes (extended 60 minutes by upper button action) Refrigerant data source: NIST REFRPRO software and manufacturers data
Uses one 9v Alkaline battery
(not included)
EXTENDING
AUTO-SHUTOFF TIME
Extend time by 60 minutes by pressing upper button.
Push lower button 2 times to select 1 hour or 24 hours.
SUPERHEAT
REFRIGERANT KE Y
(R410A Included)
TEMPERA TURE
SENSO R
2
1
R404A
HP62
PSI/F
MANUFACTURER’S DESIGNATION
“R” NUMBER
UNITS (F or C)
Only a properly charged unit will provide the owner with the design SEER for maximum energy efficiency.
SUPERHEAT, TEMPERATURE, SUBCOOLING AND PRESSURE
PUSH once to toggle between displays PUSH 2 times to recall High, Low & Average
Hold down to clear memory.
ON/OFF
PUSH once to “Turn On” Display shows LAST refrigerant used. HOLD down to "Turn Off" PUSH 2 times to select 1 hour or 24 hour auto-off mode
REFRIGERANT SELECTION
PRESS once at any time to display current refrigerant. Continue pressing to scroll the refrigerant list. (See list of refrigerants on page 4.) Wait 1.5 seconds, then continue pressing to reverse scroll direction.
APPLICATION TIPS: Allow the manifold to Zero at Turn-On:
The manifold displays will zero (CAL) each time the manifold is turned on without pressure . Zeroing the gauge compensates the Pressure display for changes in (1) Altitude and (2) Barometric pressure.
Pressure Calibration
Don’t be alarmed if your manifold gauge does not agree with your mechanical gauges. The digital manifold is calibrated with a very accurate pressure and is not affected by vibration, motion or position.
Extending On-Time
The digital manifold will turn off automatically after 60 minutes to save battery life.
If any button is touched the digital manifold will stay on for another 60 minutes.
Over/Under-Range Indicator
Pressures or temperatures below or above the rated
ranges will cause a “1” to be displayed.
Low Battery Indicator
Low batteries will be indicated by a blinking display.
Batteries For Low Temperature Applications
Using the gauge in a low temperature conditions will shorten battery life. Change to the 9 volt Lithium battery (Radio Shack 23-665) to solve this problem.
REFRIGERANT KEY PLUG-IN
See page 4 for other refrigerant keys available. Metric and English keys are not interchangeable.
SH-35N
(°F)
and SH-36N
(°C)
SUPERHEAT and SUBCOOLING GAUGE OPERATING INSTRUCTIONS
REFRIGERATION APPLICATIONS
SETTING FOR THERMOSTAT CONTROLLED CASES AND COOLERS
Without plug-ins, turn on the gauge and zero the display by holding the lower button. Plug in the Temperature Sensor only and toggle to “Temperature.”
SETTING FOR THERMOSTAT CONTROLLED CASES AND COOLERS
Without plug-ins, turn on the gauge and zero the display by holding the lower button. Attempts to zero the gauge with pressure applied will result in (Err) display.
A/C & REFRIGERATION APPLICATIONS
Contact your TXV manufacturer for the exact superheat adjust rate.
0 5 10 15 20 25
20
18
16
14
12
10
8
6
4
Superheat ϒ
F
Time in Minutes
Expansion Valve Superheat SH-35N Average Superheat
Hussmann RHF A 4 Door FF Case 1Ton Lo w Temp. TXV
-2 F Case T emperature 40% Heater Load
SET SUPERHEAT FOR “HUNTING” TXV VALUES
In refrigeration and air conditioning systems, the expansion valve often operates to produce an evaporator superheat which constantly swings up and down in value, called “hunting.” The SH-35N provides the “Average” superheat value for TXV valve adjustment.
CHECKING TXV SETTING
The objectives of the TXV superheat setting is to prevent liquid refrigerant floodback to the compresor and to optimize system operation by the use of a selected setting.
The two temperature method of measuring superheat is not recommended because it can produce a wrong superheat measurement, due to the effect of temperature glide of the blended refrigerants and variations in evaporator pressure drop.
NEW RESIDENTIAL A/C SYSTEMS
For new installations of residential A/C systems, the pre­charge will not provide an accurate amount of refrigerant charge because of the variation in the length of liquid and suction line connecting to the “A” coil.
RETROFITTING SYSTEMS
Retrofitting systems to a new refrigerant can change the TXV superheat setting. The superheat setting should be checked before and after retrofitting to be sure the superheat is right for the equipment.
REPLACEMENT ITEMS
PART NO. DESCRIPTION
A34000 1/4" QC x 1/4" Access Branch Tee SH-54 6' Temperature Sensor SH-55 Plastic Carrying Case SH-56 Socks (5)
ACCESSORIES
SH-51 28' Temperature Sensor Extension
KEY REFRIGERANT LIST “A”
R11 R12 R13 R22 R23 R134A R290 R401A R401B R402A R402B R403B R404A R406A R407A
R408A R409A R410A R411C R413A R414B R416A R417A R422A R500 R502 R507 R508B RB276
SUPERHEAT
JB INDUSTRIES
630.851.9444 Printed in USA
Part No. 10737-308
© 2006 J/B Industries Inc.
Technical service: 800-323-0811 E-Mail:sales@jbind.com Web Site:www.jbind.com
Fahrenheit and Celsius Keys are not interchangeable
SUPERHEAT
TEMPERA TURE
SENSOR
TEMP
PSI
R407B
R407C R422B
Loading...