Just Better LD-2500 User Manual

LD-2500 - LEAK DETECTOR
JB INDUSTRIES INC.
Declaration of Conformity
This is to certify that this equipment, designed by JB Industries 601 N. Farnsworth Ave., Aurora, IL 60505 USA meets the essential safety re­quirements of the European Union and is placed on the market according­ly. It has been constructed in accordance with good engineering practice in safety matters in force in the Community and does not endanger the safety of persons, domestic animals or property when properly installed and maintained and used in applications for which it was made.
Equipment Description: LD-2500 HUNTER refrigerant leak detector Applicable Directives: 73/23/EEC as amended by 93/68/EEC 89/336/EEC as amended by 93/68/EEC 2002/95/EC (RoHS) Applicable Standards: EN 61010-1: 1993 EN55011, Group 1, Class A: 1991 EN50082-1: 1992 CE Implementation Date: March 1, 1997 Authorized Representative: Dave Madden Director, Engineering JB Industries
Any questions relative to this declaration or to the safety of JB’s products should be directed, in writing to the quality assurance department at the above address.
WARNING
This symbol is intended to alert the user to the presence of important operation and maintenance (servicing) instructions in the literature accompanying the instrument.
Specifi cations
Usage: Indoor and Outdoor Minimum. Sensitivity to R22, 0.25 oz/yr (high sensitivity) R134a, R404A, R410A: 2.0 oz/yr (low sensitivity)
Operating Temperature Range: +32° to 122° F (0° C to +50° C)* Storage Temperature Range: +14° F to +140° F (-10° C to +60° C) Humidity: 95% RH NC Max. Altitude: 6500’ (2000 m) Power Supply: Two “D” Cell Alkaline Batteries Battery Life: Approximately 16 hours Pollution Degree: 2 Overvoltage Category: 2 Weight (with power cells): 1.28 lb. (0.58 kg)
*may be operated for a limited time in lower temperature environments.
LD-2500 HUNTER Features
JB’s HUNTER combines sophisticated technology with durability for an instrument with outstanding sensitivity.
Electrochemical heated-diode sensor
“No-reset” detection of CFCs, HCFCs, and HFCs
Automatic adjustment (zeroing) to refrigerants in leak test area
• Rugged, fl exible probe with a foam fi lter for sensor protection
High/Low sensitivity and power in one switch
To get the best performance from your HUNTER leak detector, please read this manual carefully before use. If you have any questions or need additional assistance, please call 800-323-0811.
Filter
Sensor Cover
Power/Low Battery LED
Power/Sensitivity Setting Switch
High Sensitivity LED
Low Sensitivity LED
Battery Cover Release Latch
Getting Started
1. Install the batteries (See next page)
2. Install the sensor (See next page) NOTE: Installation of the batteries and sensor is required before use.
3. Press the control button to power on the LD-2500 HUNTER
4. Wait for the unit to warm up. All three LEDs will illuminate during warm up. When the High Sensitivity LED starts fl ashing and a chirp- ing sound is heard, the HUNTER is ready to hunt for leaks.
The LD-2500 HUNTER Refrigerant Leak Detector provides similar re­sponses to all CFCs, HCFCs, and HFCs and refrigerant blends (R410A, R407C) as well as SF6.