D3.1.10
Low Voltage Systems
Project:
Fixture Type:
Location:
REMOTE MOUNT CLASS 2
MAGNETIC TRANSFORMER
Contact/Phone:
PRODUCT SPECIFICATIONS
Description
TL576-10-BL: 12V-10VA remote magnetic transformer Class 2
• Rated for 0.5-10 watts total load • 120VAC input
• Ideally suited for driving Juno Mini LED Downlight/Gimbal
and Solo-Task fixtures • May also be used to operate other low
wattage LED or incandescent loads.
TL576-25-BL: 12V-25VA remote magnetic transformer Class 2
• Rated for 0.5-25 watts total load • 120VAC input • Ideally
suited for driving Juno Mini LED Downlight/Gimbal and Solo-Task
fixtures • May also be used to operate other low wattage LED or
incandescent loads.
TL576-60-BL: 12V-60VA remote magnetic transformer Class 2
• Rated for 0.5-60 watts total load • 120VAC input • Ideally
suited for driving Juno Mini LED Downlight/Gimbal and Solo-Task
fixtures • May also be used to operate other low wattage LED or
incandescent loads.
Construction Potted core and coil • 13 volt boost tap • Thermally
protected primary • Manually resettable, fast-acting magnetic circuit
breaker on secondary • Primary and secondary circuits physically
and electrically isolated.
Circuit Breaker Resettable magnetic circuit breaker • Provides
faster short circuit protection than standard thermal circuit breakers
• Provides overload protection which is unaffected by ambient
operating conditions • Eliminates false overload failures due to
elevated ambient temperatures which can occur with thermal circuit
breakers • Enables transformer to be mounted in any position.
Dimming 120V installations only – consult factory for 277V
dimming applications • Incandescent loads can be dimmed with
high quality dimmers designed specifically for use with magnetic
transformer • LED loads may be dimmed using only dimmers that
have been tested and qualified by Juno for use with Juno LED fixtures
referenced on the following pages – consult factory to confirm
compatibility of other dimmers prior to installation with Juno LED
fixtures.
Installation Easy access front located wiring compartment • Wire
nut terminations for input and output circuits • Operate in accessible
locations with ambient temperatures below 140˚ F.
Labels UL/CUL listed • New York City Approved.
Product specifications subject to change without notice.
12V AC LED-COMPATIBLE
TL576
DIMENSIONS
3 1/2”
3”
9”
PRODUCT CODES
Catalog Number Finish Description
TL576-10-BL Black
TL576-25-BL Black
TL576-60-BL Black
ENGINEERING DATA
TL576-10 TL576-25 TL576-60
Input Voltage 120V 120V 120V
Input Current Typ. 0.21A 0.31A 0.51A
Nominal Output 11.9V 11.6V 11.2V
Max. Load 10W 25W 60W
Operating Frequency 60Hz 60Hz 60Hz
Power Factor 0.70 0.85 0.92
T.H.D.I. 37% 30% 27%
10W 12V AC Magnetic Transformer
25W 12V AC Magnetic Transformer
60W 12V AC Magnetic Transformer
REV-1/13
D3.1.10
Low Voltage Systems
12V AC LED-COMPATIBLE REMOTE MOUNT
CLASS 2 MAGNETIC TRANSFORMER
TL576
APPLICATION
Consideration 12V Electronic Driver/Transformer 12V Magnetic Transformer
• Length • Use for short to medium fixture run lengths and • Use for medium to long run lengths and medium to
low to medium wattage systems higher wattage systems
• Dimming
designed for use with electronic transformers; designed for use with magnetic transformers;
transformers used with Juno LED fixtures should transformers used with Juno LED fixtures should
only be operated with dimmers pre-qualified for only be operated with dimmers pre-qualified for
suitability by Juno Lighting Group suitability by Juno Lighting Group
• Transformer Location • For best performance, transformer should be • Install in well ventilated locations where ambient
• Can be surface mounted or installed in insulation.
• Install where ambient temperature will not exceed
120
• Distance to First Fixture • For best results, should be mounted within 4’ • Suitable for remote mounting at long distances
• For optimal results, use dimmers specifically • For optimal results, use dimmers specifically
located close to fixture run.
°
F (50°C); transformer must be accessible
to first fixture in run.
temperature will not exceed 140°F (60°C);
transformer must be accessible
VOLTAGE DROP CALCULATIONS (FOR MAGNETIC TRANSFORMERS)
Voltage drop is a function of the following factors:
Wire Length:
As the wire length from the supply to the fixture becomes longer,
voltage drop increases.
Wire Diameter:
As the wire cross-sectional area becomes smaller, voltage drop
increases (this is related to the resistance per foot of wire).
Amperage of the Electrical Load:
As the amperage of the electrical load increases, voltage drop
also increases.
Voltage drop in 12 volt systems is 10 times greater
than in 120 volt systems.
This is because a load of the same wattage has 10 times greater
amperage in 12 volts as compared to 120 volts.
This is illustrated by the formula:
WATTS = VOLTS x AMPS
Assuming a 120 watt electrical load:
120 WATTS = 12 VOLTS x 10 AMPS
120 WATTS = 120 VOLTS x 1 AMP
Voltage drop from a magnetic transformer to the
first lampholder on 12V Trac 12 can be
calculated as follows:
TRANSFORMER
VOLTAGE DROP = 2D x A x Ω
WHERE:
D = Distance in feet from transformer to 1st lamp
A = Total amperage load of all lampholders on the trac
Ω = Resistance per foot of wire per the following chart:
Wire Gauge Resistance Per Foot of Wire (OHMS)
#8 .00065
#10 .00104
#12 .00166
(A =
D
WATTS
______
VOLTS
=
A
WATTS
______
12
)
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone (847) 827-9880 • Fax (847) 827-2925
220 Chrysler Drive • Brampton, Ontario • Canada L6S 6B6 • Phone (905) 792-7335 • Fax (905) 792-0064
Visit us at www.junolightinggroup.com