Jung TR UD 231 Series Operating Instructions Manual

Safety instructions
GB
The unit may only be opened by an electrician and installed according to the circuit diagram on the unit or in these instructions. Observe existing safety instructions. To satisfy the requirements of protection class II, corresponding installation measures are required. This independently installable electronic device is exclusively for controlling the temperature in dry, enclosed rooms with normal surroundings. This device is in conformance with EN 60730 and functions according to operating mode 1C.
Damage to the device, re or other hazards may
arise if these instructions are not followed. These instructions are a component part of the product and must remain with the end customer.
Structure of the device
(1) (2) (3)
(4)
(5)
(6)
(7)
Fig. 1: Layout of the temperature controller
(1) Controls (2) Display (3) Control buttons (4) Plug-in contacts (5) Design frame (not including delivery) (6) Socket for the plug-in contacts (7) Use
Function
Correct use
– Measuring and controlling the room temperature – Measuring and controlling the oor temperatureRoom temperature control via oor heating with
a limiting function (for example in conjunction
with tiled stoves) – Can be used for “heating only” or “cooling only” – Installable in a box in conformance with
DIN 49073 – Only for use in dry, enclosed rooms
Product characteristics
– Large display with backlighting – Text display for self-explanatory operation – Programmable even when the controls are
removed – Di󰀨erent user languages can be selected – Real-time clock with automatic switchover to/
from daylight savings time – Internal temperature sensor – An external remote sensor can be connected – Three selectable and adjustable time
temperature programs for automatic mode – A maximum of nine operating times per day (the
setting can also be terminated after a specic
operating time) – Can be individually programmed every day, or a
block of operating times can be set: workdays/
non-workdays, all days the same – Can be manually adjusted at any time – “Vacation” mode with the entered date (from/to) – “At-home” mode (present) – Short-time timer (“party function”) – Optimum start” function (the temperature is
reached at the set time) – Protection against frost
– Display of energy consumption for electric
heating systems
– Pulse width modulation (PWM) or two-point
control system
– Adjustable cycle time (PWM), hysteresis and
minimum on/o󰀨 time (two-point)
– Switch on delay, such as for burners (with two-
point control) – Adaptation to valves normally open or closed – Valve protection (as a room temperature
controller with and without a limiting function) – Resetting separate from user and installer settings
Description of functions
The programmable temperature controller
automatically controls the room or oor temperature
depending on the time and day of the week. The automated program can be interrupted at any time by manual entries. The temperature controller has three selectable programs for heating which can be adapted to your individual comfort. The controller is equipped with an internal sensor for measuring the room temperature. In addition, an external remote sensor
can be connected, for example to measure the oor
temperature. The temperature controller compares the measured temperature with set values. If the temperature falls below the current setting, the heating system is turned on. The control method depends on the type of heating and is determined by the installer:
Room temperature controller: The heating is
turned on when the room temperature falls below
the set target temperature (measured with an
internal sensor or external remote sensor).
– Floor temperature controller: The oor heating
is turned on when the oor temperature falls
below the set target temperature (measured
using an external remote sensor). – Room temperature controller with a limiter
(in conjunction with oor heaters):
The room temperature is measured and
regulated using the internal sensor. An additional
external remote sensor is connected to measure
the oor temperature, and a target temperature
range for the oor is set. The room temperature
control is deactivated when the oor temperature
is outside of this range. If temperature falls
below this range, the heater is turned on, and if
the temperature is above this range, the heater
is turned o󰀨 independent of the current room
temperature.
Operation
(10)
(9)
(11)
(8)
(16)
Fig. 2: Default display
(8) Function display (such as the mode) (9) Large display (such as the current temperature) (10) Day of the week display
(1 = Monday ... 7 = Sunday)
(11) Heating mode display (12) Display (such as the current time) (13)
O
(14)
+ button
(15)
- button
(16) M button (menu)
button
(info/OK)
(13)(14)(15)
(12)
Universal room temperature controller with display
Ref.-no.: TR UD .. 231 ..
Operating instructions
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1 58579 Schalksmühle GERMANY
Tel. +49 2355 806-0 Fax +49 2355 806-204 kundencenter@jung.de www.jung.de
08/2015
0024073501
Basic information
6:00
14
16
18
20
22
24
26
27
28
°C
8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00
h
25
23
21
19
17
15
6:00
14
16
18
20
22
24
26
27
28
°C
8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00
h
25
23
21
19
17
15
14
16
18
20
22
24
26
27
28
°C
25
23
21
19
17
15
Four buttons below the display are used to operate the temperature controller (Fig. 2, items (13) to (16)). In the menu, you can activate operating modes, adapt programs and make settings. If a button is not pressed for more than three minutes, the unit automatically switches back to the previous function and the default display (Fig. 2). Program 1 and AUTO mode are the preselected defaults; see “Default programs” and “Modes and setting menus (overview 1)”.
Programming when the controls are removed
The unit can also be programmed when the controls are removed. The current temperature is
not displayed, the “heating mode” display ashes,
and the display is not illuminated. If a button is not pressed for more than three minutes, the display goes dark.
Display information on the current mode
To go to the default display when the controls
W
are removed and the display is dark, press any button.
• Press O in the default display. Information on the current mode/setting is displayed in the form of a marquee.
• Return to the default display by pressing O.
Selecting modes and setting menus
• Press M in the default display.
MENU briey appears in the function display (8).
A help text as a marquee appears at the bottom edge of the display.
Use the + / - buttons to switch to the desired mode/setting.
• Select the desired mode/setting by pressing O. Another menu opens depending on the mode/ setting.
• Go back to the last display/setting by
pressing M.
• Return to the default display by pressing
several times.
M
Manually adapting the target temperature
You can always adapt the target temperature in modes AUTO, MAN and TIMER.
• In the default display, press + or -.
The current target temperature ashes.
• Set the desired temperature by pressing + / -.
• Accept the displayed temperature by pressing O. The device returns to the default display.
Turning o󰀨 the controls
• In the default display, press the M button for
10 seconds.
First “MENU” appears in the display. After 10 seconds, the device switches to the default display and “OFF” appears.
• Turn the controls back on by selecting a mode.
Default programs
The controller o󰀨ers three default time/temperature
programs (full-day settings). These full-day settings depend on the selected heating mode (installer settings, H1) and can be selected by the user and adapted to individual heating preferences (user settings, G1 and G2). The factory setting is program 1. The default time/temperature programs are illustrated in the following in sections in graphs and tables.
A specic example is used (room temperature
controller) for program 1 to explain the full-day settings.
Programs for room temperature controller with and without a limiting function
Program 1
Switching time
Mon – Fri Time of day
T°C Time of day T°C
Sat – Sun
1 06:00 21.0 07:00 21.0 2 08:30 18.0 10:00 18.0 3 12:00 21.0 12:00 21.0 4 14:00 18.0 14:00 21.0 5 17:00 21.0 17:00 21.0 6 22:00 15.0 Sat, 23:00
Sun, 22:00
Table 1: Full-day settings for program 1, room temperature controller
Program with six switching times. “Comfortable temperature” 21 °C, temperature lowered to 18 °C in the morning and afternoon of work days (absent) and lowered daily at night to 15°C.
Program 2
Switching time
Mon – Fri Time of day
T°C Time of day T°C
Sat – Sun
1 06:00 21.0 07:00 21.0 2 08:30 18.0 Sat: 23:00
Sun: 22:00 3 12:00 21.0 4 14:00 18.0 5 17:00 21.0 6 22:00 15.0
Table 2: Full-day settings for program 2, room temperature controller
Program 3
Switching time
Mon – Fri Time of day
T°C Time of day T°C
Sat – Sun
1 06:00 21.0 07:00 21.0 2 08:30 18.0 10:00 18.0 3 17:00 21.0 12:00 21.0 4 22:00 15.0 Sat, 23:00
Sun, 22:00
Table 3: Full-day settings for program 3, room temperature controller
15.0
15.0
15.0
Programs for the oor temperature controller
Program 1
Switching time
Mon – Fri Time of day
Sat – Sun
T°C Time of day T°C
1 06:00 28.0 08:00 28.0 2 08:00 18.0 10:00 18.0 3 19:00 28.0 19:00 28.0 4 22:00 15.0 22:00 15.0
Table 4: Full-day settings for program 1, oor
temperature controller
Program 2
Switching time
Mon – Fri Time of day
Sat – Sun
T°C Time of day T°C
1 06:00 28.0 08:00 28.0 2 08:00 18.0 10:00 18.0 3 12:00 28.0 12:00 28.0 4 14:00 18.0 14:00 18.0 5 19:00 28.0 19:00 28.0 6 22:00 15.0 22:00 15.0
Table 5: Full-day settings for program 2, oor
temperature controller
Program 3
6:00
8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00
Switching time
Mon – Fri Time of day
Sat – Sun
T°C Time of day T°C
1 11:00 28.0 08:00 28.0 2 13:00 18.0 10:00 18.0 3 22:00 15.0 19:00 28.0 4 22:00 15.0
Table 6: Full-day settings for program 3, oor
temperature controller
h
Select program (G1)
The factory setting is program 1.
W
The device is in the default display.
Press the M button.
The help text “MENU...” appears at the bottom edge of the display.
• Press + / - to select the settings menu USER
SETTINGS and conrm with O.
G1 - PROGRAM SELECT ONE appears.
Press the O button.
The number of the active program ashes.
• Press + / - to select the desired program
(1 ... 3) and conrm with O.
G1 - PROGRAM SELECT ONE appears. The selected program is now active.
Adapting the program (G2)
The default programs can be adapted to individual heating comfort. A maximum of 9 switching times/ intervals per day are possible. All adaptations
a󰀨ect the active program. When you switch to new
program, the adaptations are not saved; that is, any adaptations made to a default program must be
recongured.
The desired program is active (G1), and G1 ­PROGRAM SELECT ONE appears.
• Press the + button. G2 - EVENT SETTING appears.
• Press O to select menu item G2. DAY is displayed, and the day of the week
display (10) ashes.
The numbers correspond as follows: 1 Monday, 2 Tuesday... 7 Sunday.
With the exception of individual weekdays,
W
switching times can also be set for blocks of days 1-5, 6-7, 1-7.
• Press + / - to select the desired day/block of
days, and conrm with O.
The temperature display (9) for the rst switching interval of the day ashes.
• Press + / - to set the desired temperature and
conrm with O.
The starting time of the switching interval
ashes.
• Press + / - to set the desired start time and
conrm with O.
The ending time of the switching interval ashes.
• Press + / - to set the desired ending time and
conrm with O.
The rst switching interval is now set. The
temperature display for the second switching
interval ashes.
If needed, additional temperatures and switching times can be set using the same procedure. The number of the switching interval is displayed in the bottom line of the display in front of the switching times. The respective end time in the display is becomes the start time of the next interval. Each switching time can be decreased to the previous time or to 00:00, and increased to a maximum of 23:50.
If ->>> ashes in the display, the following switching
time falls within the next weekday.
• Press O to go to the rst start time of the next
day of the week.
• Press + / - to create a di󰀨erent switching
interval. If all 9 switching times of the day are already assigned, the program automatically jumps to the next day of the week. You can delete a switching interval indirectly by increasing the previous interval. Repeatedly press M to leave menu item G2 - EVENT
SETTING. The settings take e󰀨ect.
Main menu
Modes and setting menus (overview 1).
To follow is an overview of the modes and setting menus within the main menu.
AUTO Automatically control the room temperature ac-
cording to the time and temperature settings of the selected program. Adapt the temperature to the next to switching time (see "Manually adapt the target temperature"). A minus sign following the "AUTO–" mode in the display indicates that the target temperature has been adapted and that it deviates from the tempera­ture saved in the time/temperature program until the next switching time.
MAN Manually control the room temperature independent
of the time to the value set here (see "Manually adapt target temperature".)
TIMER Short-time timer to specify the room temperature for
a set number of hours ("Party function").
• Press + / - to set the hours and conrm with .
O
• Press + / - to set the temperature and con-
rm with O.
The display (12) shows the number of remain­ing hours.
Subsequently adapt the temperature for the remaining hours (see "Manually adapt the target temperature").
HOLIDAY Specify a room temperature for a set time interval
with the start and end date of vacation. Until vaca­tion starts, the currently set mode is active: AUTO, MAN, TIMER, AT HOME. Start HOLIDAY when the start date is reached.
Set the year, month, day for the rst and last
day of vacation with + / - and conrm with O.
• Press + / - to set the temperature and con-
rm with O.
"V." and the date of the last day of vacation is shown in the displays (8) and (12).
AT HOME Control the temperature independent of the day of
the week according to the time and temperature in­formation in the selected program (full-day setting). The program defaults correspond to the current day program of Monday.
• Set the temperature and switching times with
USER SETTINGS Open the menu for the user settings.
• To select the desired submenu, see "User
INSTALLER SETTINGS Open the setting menu for the installer.
• To select the desired submenu, see "Installer
Overview 1: Modes and setting menus
Select the desired mode/setting menu
The device is in the default display.
• Press the M button.
• Press the buttons + / - until the desired menu
Conrm with O.
and conrm with O.
+ / -
Activate the mode "AT HOME" by conrming
the last switching time. The function display (8) shows "HOME".
The display (9) shows the menu ID G1.
settings".
The display (8) shows the menu ID H1.
settings".
The help text “MENU...” appears at the bottom edge of the display.
item (mode or setting menu) appears.
The function is activated in modes AUTO and MAN.
With the other menu items, the device jumps to additional settings (see overview 1).
User settings
Overview 2
A marquee at the bottom of the display shows
information for an individual menu items identied
with G1 to G16.
Depending on the set control procedure, the
W
menu items G11 and G12 are not available.
(The menu displays and set all values are in UPPERCASE, and the settings are
G1 PROGRAM SELECT ONE Choose one of the default time/temperature pro­grams (see "Select program"):
1
, 2, 3. Select the program number with + / -, conrm with O.
G2 EVENT SETTING Adjust a default time/temperature program (see "Adapt program"): Adjust the days of the week, temperatures, switch­ing times with + / -, conrm with O.
G3 CLOCK SETTING Set the date and time. Set the YEAR, MONTH, DAY, HOUR, MINUTE with
/ - and conrm with O.
+
G4 OFF HEATING PERMANENT
Turn o󰀨 the temperature control:
– YES = Control o󰀨
–NO = Control on Select YES/NO with + / -, conrm with O. If OFF HEATING PERMANENT = YES is selected, the frost protection is active provided that it has been set by the installer, see also Installer settings
H6 - FROST PROTECTION ≠ OFF
Display function (8): OFF Turn on the control: Select a function using the menu, or hold M for 10 s.
G5 SUMMER/WINTER TIME CHANGE Set whether the switchover from/to daylight savings is automated.
YES
= automated
– NO = not automated Select YES/NO with + / -, conrm with O.
G6 KEY LOCK Protect the controller from unauthorized use. Use is not possible when access protection is enabled.
– YES = access protection on
–NO = no access protection Select YES/NO with + / -, conrm with O. Remove access protection: Press any button, and when CODE is displayed, set 93 with + / - and
conrm with O.
G7 TEMP LIMIT MIN/MAX TEMP Set the bottom and top temperature to be regulated:
– LOWER TEMP LIMIT:
For the room temperature controller (H1 = ROOM or LIMITER):
5.0°C
, 5.5°C … 30.0°C
For the oor temperature controller
(H1 = FLOOR):
10.0°C
– UPPER TEMP LIMIT:
For the room temperature controller (H1 = ROOM or LIMITER):
5.0°C, 5.5°C …
For the oor temperature controller
(H1 = FLOOR):
10.0°C, 10.5°C … Set the temperatures with + / - and conrm with O. The controls in the modes AUTO, MAN, TIMER etc. are limited to the temperature range set here.
G8 COSTS /HR OF ENERGY Enter the estimated energy costs per hour for the room in which the temperature is being controlled: 1, 2, ...
W
Set COST/HR with + / -, conrm with O. The determined use is displayed under G9.
, 10.5°C … 40.0°C
30.0°C
40.0°C
100
... 999 CENT/HR
If the energy cost meter is to serve as an oper­ating hour meter, set the value COST/h to 100.
bold
)
G9 ENERGY CONSUMTION TO DATE
230 V~, 50 Hz
Display of the approximate energy consumption in euros (or operating hours) per time period. The current day is included up to the displayed time. Calculation: Time heat turned on x COST/HR (G8). EURO/2DAYS, EURO/WEEK, EURO/30DAYS, EURO/YEAR. Select the period for calculating the energy con­sumption, display it with + / -, go back to the menu with O. Reset using INSTALLER SETTINGS (H9)
G10 SET TEMP TO READ Setting for the target temperature to be shown in the display instead of the current room temperature:
– YES = Target temperature –NO = Room temperature
Select YES/NO with + / -, conrm with O.
G11 ADJUST TEMP
This menu item is not available when used as a
W
oor temperature controller.
Specify a correction value to be displayed and regulated:
-5.0°C, -4.9°C …
Useful adaptations are for example matching
W
calibrated thermometers, or adapting to instal­lation heights or locations that are problematic.
Adjust the correction value with + / - and conrm with O.
G12 NUMBER FOR FLOOR TEMP
This menu item is not available when used as
W
a room temperature controller with/without a limiting function.
Activate the oor temperature display for informa­tion (without the unit °C).
YES = Display the oor temperature –NO = Display the room temperature
Select YES/NO with + / -, conrm with O.
G13 BACKLIGHT Set the display lighting:
SHORT
– OFF = always o󰀨 – PERMANENT (only when using a remote sensor)
Select SHORT/OFF or PERMANENT with + / -,
conrm with
G14 LANGUAGE Select the languages shown in the display: GER­MAN, ENGLISH, DUTCH, FRENCH Select the LANGUAGE with + / -, conrm with O.
G15 INFO Display controller type and controller version: TR UD ... Display the controller version with + / -, go back to menu with M or O.
G16 RESET USER SETTINGS ONLY Reset the user settings to the defaults.
The counter ENERGY CONSUMTION TO
W
DATE is not reset. This is reset by the installer in the menu H9.
– YES = reset –
NO
Select YES/NO with + / -, conrm with O.
Overview 2: User settings
Open the settings menu and make settings
The menu ID G1 appears in the display (9), and PROGRAM SELECT ONE appears at the bottom as a marquee.
• Press + / - o select the desired menu. The menu ID and a help text appear at the bottom edge of the display (8) and (12).
Conrm with O.
The rst settable value ashes in the display.
• Set the desired value by pressing + / -.
Conrm with O.
The next settable value ashes in the display.
Once all the values are set, the display returns to higher-level and displays the menu ID.
0.0°C
... 4.9°C, 5.0°C
= short time after pressing the button
O.
Information for electrically skilled persons
Installation and electrical connection
DANGER! Electric shock from touching live parts.
V
Electric shock can be fatal. Before working on the device, disconnect the connecting lines and cover surrounding live parts.
Installation site
The controller should be installed at a location in the room which is easily accessible for use. When using the internal temperature sensor, the chosen installation site should:
– Enable free circulation of air – Not be in a draft (such as an open window or doors) – Not be located behind curtains, cabinets, shelves,
etc. – Not be exposed to direct sunlight – Not be directly inuenced by sources of heat – Not be adjacent to external walls – Be 1.5 m above the oor.
Connecting and installing the controller
(1)
(7)
Fig. 3: Remove the controls from the insert
• Remove the controls (1) from the insert (7).
• Remove a maximum of 8 mm of the insulation from the connecting lines.
N L
(17)
(18)
(19)
(24)
(20)
Fig. 4: Connection diagram
The terminals (18) before the power supply and
switching current are designed for solid or exible
lines with a cross-section of 1 to 2,5 mm2.
• Connect the controller according to the connection diagram (Fig. 4).
• If necessary, connect an external remote sensor (20) (see “Connecting the external remote senso”).
(21)
(22)
(23)
(7)
Fig. 5: Installation
Only install the temperature controller in non-
W
conductive plastic ush-mounted boxes with a
diameter of 60 mm.
• Align the insert (7) in the receptacle (22).
• Fix the insert with fastening screws (23). Install the insert so that the plastic tongue (21) functions as insulation against the fastening screw (Fig. 5).
(1)
(5)
(7)
Fig. 6: Mounting the controls
• Mount the design frame (5) and secure by attaching the controls (1).
Connecting the remote sensor
An external remote sensor is necessary for the modes “Floor temperature controller” and “Room temperature controller with limiter”. The remote sensor line carries mains voltage and can be extended to 50 m with appropriate wires. In order to prevent signal faults, do not run the remote sensor line together with power lines. It is recommendable to run the remote sensor in ducting.
• Connect the remote sensor according to the connection diagram (Fig. 4, item (20)).
• When inserting and removing the connecting line using an appropriate tool, press the release button (Fig. 4/7, item (24)).
(24)
Fig. 7: Terminal for connecting the remote sensor
Start-up
CAUTION! The heating system will malfunction if the
V
controls are incorrectly set. This can damage the heating system. Only a technician may adjust the settings.
Set the heating mode when starting the controller.
• Press M in the default display. MENU briey appears in the function display (8). A help text as a marquee appears at the bottom edge of the display.
• Press the + / - buttons until INSTALLER
SETTINGS appears.
• Select INSTALLER SETTINGS with O.
CODE is displayed, and code number 0 ashes.
• Select code 7 with + / -, conrm with O. H1 and the marquee text APPLICATION is displayed.
Press O.
ROOM
is the default. When switching the heating mode, all of the user and installer settings are reset to the default.
• Press + / - to set the desired heating mode and
conrm with O.
The heating mode is set.
Additional settings are available under “Installer settings”.
Installer settings
Overview 3
A marquee at the bottom of the display shows
information for an individual menu items identied
with H1 to H11.
Some menu items are not available under the
W
control modes set under H1.
The abbreviations for the relevant control mode for each menu item are indicated in the table. The abbreviations have the following meaning:
R = Room temperature controller F = Floor temperature controller L = Room temperature controller with a limiting
function (The menu displays and set all values are in UPPERCASE, and the settings are bold)
H1 APPLICATION R F L Selection of the control method depending on the
heating mode:
ROOM
= Room temperature controller with the setting of whether or not a remote sensor is connected: EXTERN SENSOR = YES/
– FLOOR = Floor temperature controller – LIMITER = Room temperature controller with
limiter
Select with + / -, conrm with O.
H2 CONTROL MODE R F L Select the control mode:
PWM
= Pulse width modulation with the cycle
time set in minutes: 10, 15 ... 30.
For fast heating systems, select a short cycle
W
time, for slow heating systems, select a long
cycle time. The minimum on/o time is 10% of
the cycle time.
– ON/OFF= two-point control with adjustable
hysteresis ( minimum relay on/o󰀨 time in minutes (1, 2 … 10 ... 30).
If the hysteresis is not set, the relay switches
W
with the minimum on/o time even when the temperature dierences are very small.
Select with + / -, conrm with O.
OFF
, 0.1°C, 0.2°C … 5.0°C) and
NO
H3 MIN/MAX FLOOR TEMP L
Setting the top and bottom limit for the oor temper­ature:
LOWER TEMP LIMIT: The oor should not be
colder than the set temperature (
10.5°C … 35.0°C).
UPPER TEMP LIMIT: The oor should not be
warmer than the set temperature (OFF, 10.0°C,
10.5°C …
Set the temperatures with + / - and conrm with O.
W
H4 HEATING OR COOLING R Switching the controller between heating and
cooling mode:
HEATING
– COOLING
W
W
W
Select with + / -, conrm with O.
H5 VALVE PROTECTION R L Protection of the valve from seizing after long pe-
riods of nonuse. The valve is opened at 10 o'clock every day for the time in minutes set here: OFF, 1, 2, 3 … 10. Set the opening time with + / - and conrm with O.
H6 FROST PROTECTION R F L Setting the frost protection temperature:
– For H1 = ROOM or LIMITER:
OFF,
– For H1 = FLOOR:
OFF, Press + / - to set the temperature and conrm with O. If the temperature falls below the set frost protection temperature, heating is turned on.
W
W
H7 OPTIMUM START R F L This setting causes the system to go to the set
target temperature upon starting:
YES
– NO AUTO_ is displayed in the required preheating time. Select YES/NO with + / -, conrm with O.
H8 VALVES NORMALLY OPEN R L Reverse of the relay switching behaviour for using
actuators that are normally open:
– YES = activated
–NO = deactivated Select YES/NO with + / -, conrm with O.
H9 ENERGY COUNTER RESET R F L Reset to zero the energy cost meter set under G8/
G9 (see user settings).
– YES = reset
NO
Select YES/NO with + / -, conrm with O.
H10 FLOOR TEMPERATURE DISPLAY L
Display the current oor temperature for service
purposes.
H11 RESET ALL R F L Reset to the defaults all of the settings made in the
menus for the installer and user.
– YES = reset
NO
Select YES/NO with + / -, conrm with O.
W
Overview 3: Installer settings
35.0°C
... 40.0°C, OFF).
To deactivate the top or bottom limit, set the bottom temperature limit < 10°C, or the top temperature limit > 40°C with + / - . OFF is displayed.
Precondition for switching to cooling mode: H2 - CONTROL MODE = ON/OFF
When switching to cooling mode, H6 - FROST PROTECTION is automatically set to OFF, and H7 - OPTIMUM START is set to NO.
The switching times and temperatures of heat­ing mode are used.
5.0°C
, 5.5°C … 30.0°C
10.0°C
, 10.5°C … 40.0°C
To deactivate the frost protection with a button
select the OFF setting under the lowest
-
temperature.
Frost protection mode is only possible when the control is shut o; see user settings: G4 - OFF HEATING PERMANENT = YES
= OPTIMUM START
For safety reasons settings among H1 and the selected language will not be changed with a RESET.
OFF
, 10.0°C,
Open the settings menu and make settings
The menu ID H1 appears in the display (8), and APPLICATION appears at the bottom as a marquee.
• Press + / - o select the desired menu. The menu ID and a help text appear at the bottom edge of the display (7) and (11).
Conrm with O.
The rst settable value ashes in the display.
• Set the desired value by pressing + / -.
Conrm with O.
The second settable value ashes.
• Repeat the aforementioned steps until all the
values are set.
The display returns to higher-level and displays the menu ID.
Appendix
Do not dispose of this product in household garbage. Dispose of the device in a facility designated for electronics waste. Consult the local recycling authorities.
This symbol conrms that the product is in
conformance with the relevant guidelines.
C
Technical data
Operating voltage: AC 230 V ~ Rated frequency: 50 Hz
Output: Make contact relay, non-oating
Switching current: 10 mA ... 16 (4) A, 230 V~ Power consumption: ~ 1.2 W Degree of protection: IP 30 Protection class: II (with corresponding installation) Pollution category: 2 Ambient temperature:
- operation: 0°C to 40 °C (without thawing)
- Storage: -20°C to 70°C (without thawing)
Temperature setting range (in increments of 0.5 °C):
- as a room temperature controller: 5°C ... 30 °C
- as a oor temperature controller 10°C ... 40 °C
Temperature display: in increments of 0.1°C Output signal: Pulse width modulation (PWM)
or two-point control ( on/o󰀨)
PWM cycle time: adjustable (10 ... 30 min) Hysteresis: adjustable (with two-point control) Minimum switching time adjustable (1 ... 30 min) Rated impulse voltage: 4 kV Temperature for the ball thrust test: 75 ± 2°C Voltage and current for the EMC emitted interference test: 230 V, 0.1 A Software class: A Accuracy: < 4 min/year Reserve power: ~ 10 years (lithium cell)
Help in case of problems
Overviews 4 and 5 describe a few error messages and problems as well as probable causes and solutions.
Error message/problem Possible cause
– Suggestions for troubleshooting
Display of device faults
Errors in the hardware conguration can be shown on
the display. In this case, ERR and an error type are displayed as marquee text.
ERR CONFIGURATION The controls and insert do not match.
– Only use matching components. – Turn the power o󰀨 and on.
ERR COMMUNICATION Communication problem between the controls and
insert.
– Remove the controls and put them back on. – Turn the power o󰀨 and on.
ERR EXT SENSOR External remote sensor broken/shorted/missing.
– Check whether the remote sensor is connected.
The limits of the display range are exceeded.
– Determine the cause and eliminate it.
Overview 4: Display of device faults
Other problems and operating errors
Heating takes too long. The programmed switching times or time are incorrect.
– Adapt programming (G1, G2).
The time switched to/from daylight savings.
– Adapt the time (G3, G5). The optimum start is deactivated or does not run long enough (a few days) in order to determine the optimum preheating time.
– Select the optimum start (H7) and give the con-
troller time to adjust to the surrounding conditions.
The room is heating up too slowly.
The oor temperature is limited by the maximum
limiter.
– Deactivate the upper limit (H3).
The room temperature is too hot.
The oor temperature is limited by the minimum
limiter.
– Deactivate the bottom limit (H3).
No entries can be made. Access protection is enabled.
– Disable access protection (G6).
The desired temperature cannot be set. The temperature limitation prevents the desired setting.
– Reset the temperature limitation (G7).
The temperature display does not change. The target temperature display is activated.
– Enable the display of the room temperature
(G10).
Overview 5: Other problems and operating errors
ACCESSORIES
Remote sensor (not included in the delivery)
The external sensor must meet the requirements of protection class II. Please use sensor cable H03VV-F for installation in protection tube or H05VV-F without protection tube. Type: FF 7.8 Length: 4 m (can be extended up to 50 m)
Wire: exible, nely stranded
Stripped end: 8 mm
Fig. 8: External remote sensor
Resistance/temperature table for remote sensor FF 7.8
Temperature [°C] Resistance [kW]
10 66.8 20 41.3 25 33 30 26.3 40 17.0 50 11.3
Table 7: Resistance/temperature table for remote sensor FF 7.8
Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
Loading...