Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Function
Intended use
-Switching and operating electrical fan coil units with electrothermically actuated
heating/cooling valves
-Measurement and feedback control of the room temperature
-Installation in appliance box according to DIN 49073
Product characteristics
-Connection of one fan coil unit with up to 3 fan stages
-Operating modes for heating, cooling or combined heating/cooling operation
-Variants for 2-pipe or 4-pipe operation
-8 capacitive sensor buttons
-Internal temperature sensor
-Room temperature controller function
-Preselection of the current energy level through the option of 5 temperature profiles for use
in hotels or similar sites
-Display for indication of temperature (°C or °F), fan level, operating mode/profile
-Menu levels blockable
-1 status LED (red/green/blue)
-Brightness and contrast adjustable
-Switch-off time of the display illumination up to 120 seconds
-Extension input to the connection of, e.g. hotel card switch (see accessories)
3 Operation
Setpoints for room temperature and fan stage – Profiles
The selection of the current setpoints for room temperature and fan stage is based on so-called
profiles that are specified by the user on site. The following situations are covered, e.g.:
32598503
j0082598503
1/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 1: Temperature setpoints for heating and cooling for the individual profiles
-"Comfort" profile:
The hotel room is occupied, the hotel guest is present. The room temperature is set to a
comfortable value.
-"Comfort–" profile ƕ (if a hotel card switch is installed):
The hotel guest is not present. The setpoints are set to an energy saving level; the values
of the "Comfort" profile can be reached quickly.
As soon as a hotel guest inserts the hotel card into the available hotel card switch, the
controller switches to the "Comfort" profile.
-"Eco" profile Ɣ:
It is night, the controller controls the connected fan coil units and puts them into an energysaving and silent operation.
-"Standby" profile Ɠ:
Currently the room is not in use. The energy level is set such that only minimum heating/air
conditioning costs are incurred by the owner.
-"Building Protection" profile Ɩ:
When the environment raises or lowers the room temperature to a level that could damage
the building, the controller automatically activates the building protection operation. The
setpoint temperatures are permanently set (heating: + 7 °C; cooling: +45 °C).
32598503
j0082598503
2/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Operating elements
Figure 2: View
(1) Temperature setpoint adjustment ‰ƞ / ‰Ɵ
(2) Manual setting of the fan stage şƞ / şƟ
(3) Status LED
(4) Switchover to the Eco Ɣ profile
(5) Fan stage automatic mode ƪ
(6) Switchover to the Standby Ɠ profile
(7) Switchover of the temperature display Celsius/Fahrenheit °C/°F
Operating modes and display icons
The device compares the current room temperature with the setpoint temperature and controls
heating or cooling devices according to the current demand. The setpoint temperature depends
on the currently set profile and can be changed by the user, depending on the setting. The
current operating state is displayed.
IconMeaning
No iconComfort profile
ƕComfort– profile
ƔEco profile
ƓStandby profile
32598503
j0082598503
3/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
ƖBuilding Protection profile
ŤHeating
ŵCooling
‰Setpoint temperature
şManual fan level
ƪAutomatic fan level
Status LED
The status LED shows the current operating mode of the controller or the actuation of the
sensor buttons or both.
LED colourProfile
Green or offComfort, comfort–, eco
Red or offStandby, building protection
Green flashing signals actuation of the sensor buttons.
Operating level and menu levels
The current profile with setpoints for room temperature and fan stage is preselected on the
operating level. In addition, for the "Comfort" profile the setpoints can be manually corrected
temporarily.
The menu levels define the setpoints for the individual profiles and further settings for operation.
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
4.1 Fitting and electrical connection
Mounting and connecting the device
Recommended installation height: 1.50 m.
32598503
j0082598503
6/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 3: Fitting the device
(8) Power supply unit
(9) Frame
(10) Cover
oFan coil unit for 2-pipe operation at 2-pipe power supply unit variant(figure 4)or 4-pipe
connection(figure 5)Connecting .
oFan coil unit for 4-pipe operation at 4-pipe power supply unit variant(figure 5)Connecting .
oInstall the power supply unit (8) in the right orientation in an appliance box. Note marking
TOP .
oFit the frame (9) onto the insert.
oFit the cover (10) onto the insert
32598503
j0082598503
7/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 4: Connection of a 2-pipe fan coil unit with hotel card switch
32598503
j0082598503
8/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 5: Connection of a 4-pipe fan coil unit with hotel card switch
32598503
j0082598503
9/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 6: Connection of a 2-pipe fan coil unit at a 4-pipe fan coil controller
4.2 Commissioning
First steps – Configuration menu
After mounting the device has to be adapted to the system.
The configuration menu is only available on first commissioning and after resetting to factory
settings.
i Exception: Project-specific devices are preconfigured in the factory. The settings of the
configuration menu are not available for this devices.
oSwitch on voltage.
The device displays the software version for 5 seconds. The device subsequently changes
into the configuration menu.
oSet the properties of input 1 for the hotel card switch:
OFF not connected
OPEN for NO contact
CLOSE for NC contact
oSet the fan coil unit type:
2 Pipes for 2-pipe system
4 Pipes for 4-pipe system
i The variants TRD..23028.. are permanently set to 2 Pipes.
oSet the function:
MODE Ť HEATING: The device only actuates heating units.
MODE ŵ COOLING: The device only actuates climate control units.
MODE ŵŤ MANUAL: The device actuates heating and climate control units. The
switchover between heating and cooling mode is carried out manually on the device.
MODE ŵŤ AUTO: The device actuates heating and climate control units and automatically
switches between heating and cooling mode.
i The Mode ŵŤ AUTO setting is only available for the TRD..23048.. variants.
32598503
j0082598503
10/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
oSet the properties of the actuators to be controlled:
VALVE OPEN for de-energised open actuators
VALVE CLOSE for de-energised closed actuators
When the settings are saved, the device exits the configuration menu. The system parameters
set there can only be changed after resetting to factory settings.
i Following the first steps it is convenient to compare the temperature measurement and to
set the cycle time if necessary. Both settings can be found on the second menu level.
Set offset for temperature measurement
By setting this parameter differences between the measured temperature value at the
installation location and the actual room temperature are offset.
oMeasure the temperature in the room and note down as value T1 .
oRead the temperature measured by the device and note down as value T2 .
oCalculate the difference between both values ΔT = T1 – T2 and note it down.
oOpen menu level 2.
oOpen the menu page TEMPERATURE OFFSET.
oSet the difference value on the device.
5 Appendix
5.1 Technical data
Rated voltageAC 110 ... 230V~
Mains frequency50 / 60Hz
Total power loss0.18 ... 0.52W
Storage temperature-5 ... +45 °C
Transport temperature-25 ... +70 °C
Ambient temperature-5 ... +45 °C
Relative humidity5 ... 95% (No moisture condensation)
Connection
single stranded1.5mm²
Finely stranded with conductor sleeve1.5mm²