Jung TRDA523028 Series, TRDLS923028 Series, TRDA523048 Series, TRDLS923048 Series Operating Instructions Manual

Temperature controller fan coil, 2-/4-pipe
Temperature controller fan coil, 2-pipe
Art. No. : TRDA523028..
Temperature controller fan coil, 2-pipe
Art. No. : TRDLS923028..
Temperature controller fan coil, 4-pipe
Art. No. : TRDA523048..
Temperature controller fan coil, 4-pipe
Art. No. : TRDLS923048..
Operating instructions

1 Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.
These instructions are an integral part of the product, and must remain with the end customer.

2 Function

Intended use
- Switching and operating electrical fan coil units with electrothermically actuated heating/cooling valves
- Measurement and feedback control of the room temperature
- Installation in appliance box according to DIN 49073
Product characteristics
- Connection of one fan coil unit with up to 3 fan stages
- Operating modes for heating, cooling or combined heating/cooling operation
- Variants for 2-pipe or 4-pipe operation
- 8 capacitive sensor buttons
- Internal temperature sensor
- Room temperature controller function
- Preselection of the current energy level through the option of 5 temperature profiles for use in hotels or similar sites
- Display for indication of temperature (°C or °F), fan level, operating mode/profile
- Menu levels blockable
- 1 status LED (red/green/blue)
- Brightness and contrast adjustable
- Switch-off time of the display illumination up to 120 seconds
- Extension input to the connection of, e.g. hotel card switch (see accessories)

3 Operation

Setpoints for room temperature and fan stage – Profiles
The selection of the current setpoints for room temperature and fan stage is based on so-called profiles that are specified by the user on site. The following situations are covered, e.g.:
32598503 j0082598503
1/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 1: Temperature setpoints for heating and cooling for the individual profiles
- "Comfort" profile: The hotel room is occupied, the hotel guest is present. The room temperature is set to a comfortable value.
- "Comfort–" profile ƕ (if a hotel card switch is installed): The hotel guest is not present. The setpoints are set to an energy saving level; the values of the "Comfort" profile can be reached quickly. As soon as a hotel guest inserts the hotel card into the available hotel card switch, the controller switches to the "Comfort" profile.
- "Eco" profile Ɣ: It is night, the controller controls the connected fan coil units and puts them into an energy­saving and silent operation.
- "Standby" profile Ɠ: Currently the room is not in use. The energy level is set such that only minimum heating/air conditioning costs are incurred by the owner.
- "Building Protection" profile Ɩ: When the environment raises or lowers the room temperature to a level that could damage the building, the controller automatically activates the building protection operation. The setpoint temperatures are permanently set (heating: + 7 °C; cooling: +45 °C).
32598503 j0082598503
2/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Operating elements
Figure 2: View
(1) Temperature setpoint adjustment ‰ƞ / ‰Ɵ (2) Manual setting of the fan stage şƞ / şƟ (3) Status LED (4) Switchover to the Eco Ɣ profile (5) Fan stage automatic mode ƪ (6) Switchover to the Standby Ɠ profile (7) Switchover of the temperature display Celsius/Fahrenheit °C/°F
Operating modes and display icons
The device compares the current room temperature with the setpoint temperature and controls heating or cooling devices according to the current demand. The setpoint temperature depends on the currently set profile and can be changed by the user, depending on the setting. The current operating state is displayed.
Icon Meaning
No icon Comfort profile
ƕ Comfort– profile
Ɣ Eco profile
Ɠ Standby profile
32598503 j0082598503
3/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Ɩ Building Protection profile
Ť Heating
ŵ Cooling
Setpoint temperature
ş Manual fan level
ƪ Automatic fan level
Status LED
The status LED shows the current operating mode of the controller or the actuation of the sensor buttons or both.
LED colour Profile
Green or off Comfort, comfort–, eco
Red or off Standby, building protection
Green flashing signals actuation of the sensor buttons.
Operating level and menu levels
The current profile with setpoints for room temperature and fan stage is preselected on the operating level. In addition, for the "Comfort" profile the setpoints can be manually corrected temporarily.
The menu levels define the setpoints for the individual profiles and further settings for operation.
Operating level
- Increase setpoint temperature: press sensor button ‰ƞ.
- Reduce setpoint temperature: press sensor button ‰Ɵ.
- Increase fan stage: press sensor button şƞ.
- Reduce fan stage: press sensor button şƟ.
- Set automatic fan stage: press sensor button ƪ.
- Switchover to Eco profile: press sensor button Ɣ.
- Switchover to Standby profile: press sensor button Ɠ.
i The profiles Eco and Standby are exited by pressing again the sensor buttons Ɣ or Ɠ.
The follow-on condition depends on whether or not the presence of persons was reported to the controller.
Operating in the menu
o Increase value: press sensor button ‰ƞ. o Reduce value: press sensor button ‰Ɵ. o Select previous menu item: press şƞ sensor button. o Select next menu item: press şƟ sensor button. o Exit menu without saving: press sensor button ƪ (ŏ) o Save settings and exit menu: press °C/°F sensor button (Ŏ)
Open menu level 1
Only for heating and cooling mode with manual switchover. In systems that are intended solely for heating or cooling menu level 1 is not available.
o Press the sensor buttons ĸƟ and Ɣ between 2 and 4 seconds.
Menu level 1:
- Switchover heating mode/cooling mode
Open menu level 2
o Press the sensor buttons ĸƟ and Ɣ longer than 5 seconds.
32598503 j0082598503
4/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Menu level 2:
- Setpoint temperature Comfort heating
- Setpoint temperature Comfort cooling
- Lowering the setpoint temperature Comfort– heating
- Raising the setpoint temperature Comfort– cooling
- Setting fan stage Comfort–
- Lowering the setpoint temperature Eco heating
- Raising the setpoint temperature Eco cooling
- Setting fan stage Eco
- Lowering the setpoint temperature Standby heating
- Raising the setpoint temperature Standby cooling
- Setting fan stage Standby
- Set offset for temperature measurement
- Set display brightness
- Set display contrast
- Set display illumination duration
- Status LED: button-press indicator
- Status LED: operation indicator
- PWM cycle time
- Disable controller
- Resetting to factory setting
Setting Display Range [step width]
Setpoint temperature Comfort heating
COMFORT
+7 ... +45 °C [0.5 K] +45 ... +110 °F [1 °F]
HEATING
Setpoint temperature Comfort cooling
COMFORT
+7 ... +45 °C [0.5 K] +45 ... +110 °F [1 °F]
COOLING
Comfort fan stage Is permanently set to Auto
Lowering the setpoint temperature Comfort– heating
Raising the setpoint temperature Comfort– cooling
Setting fan stage Comfort– COMFORT
COMFORT–
HEATING
COMFORT–
COOLING
ş
Lowering by 0 ... 10 K [0.5 K] 0 ... 18 °F [1 °F]
Raising by 0 ... 10 K [0.5 K] 0 ... 18 °F [1 °F]
AUTO AUTO-1 AUTO-1-2 0 1 2 3
Lowering the setpoint temperature Eco heating
ECO
HEATING
Lowering by 0…10 K [0.5 K] 0 ... 18 °F [1 °F]
Raising the setpoint temperature Eco cooling
ECO
COOLING
Setting fan stage Eco ECO
ş
32598503 j0082598503
5/11
Raising by 0…10 K [0.5 K] 0 ... 18 °F [1 °F]
AUTO AUTO-1 AUTO-1-2 0 1 2 3
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Lowering the setpoint temperature Standby heating
STANDBY
HEATING
Raising the setpoint temperature Standby cooling
STANDBY
COOLING
Setting fan stage Standby STANDBY
ş
Set offset for temperature measurement
TEMPERATURE
OFFSET
Set display brightness DISPLAY
BRIGHTNESS
Set display contrast DISPLAY
CONTRAST
Set display illumination duration
DISPLAY TIMEOUT
Lowering by 0…10 K [0.5 K] 0 ... 18 °F [1 °F]
Raising by 0…10 K [0.5 K] 0 ... 18 °F [1 °F]
AUTO AUTO-1 AUTO-1-2 0 1 2 3
–12.8 ... +12.7 K [0.1 K] –23.0 ... +22.8 °F [0.2 °F]
1 – 2 – 3
1 – 2 – 3
15 ... 120 s [1 s]
Status LED: button-press indicator
Status LED: operation indicator
PWM cycle time CYCLE TIME
STATUS LED Activate the function: ON
Deactivate the function: OFF
OPERATION LED Activate the function: ON
Deactivate the function: OFF
5 ... 255 min [5 min]
INTERVAL
Disable controller ACTUATOR Disable: UNLOCK
Enable: LOCK
Resetting to factory setting FACTORY RESET
CONFIRM
Cancel: ŏ Confirm: Ŏ

4 Information for electrically skilled persons

Mortal danger of electric shock. Disconnect the device. Cover up live parts.

4.1 Fitting and electrical connection

Mounting and connecting the device
Recommended installation height: 1.50 m.
32598503 j0082598503
6/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 3: Fitting the device
(8) Power supply unit (9) Frame (10) Cover o Fan coil unit for 2-pipe operation at 2-pipe power supply unit variant(figure 4)or 4-pipe
connection(figure 5)Connecting .
o Fan coil unit for 4-pipe operation at 4-pipe power supply unit variant(figure 5)Connecting . o Install the power supply unit (8) in the right orientation in an appliance box. Note marking
TOP .
o Fit the frame (9) onto the insert. o Fit the cover (10) onto the insert
32598503 j0082598503
7/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 4: Connection of a 2-pipe fan coil unit with hotel card switch
32598503 j0082598503
8/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 5: Connection of a 4-pipe fan coil unit with hotel card switch
32598503 j0082598503
9/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
Figure 6: Connection of a 2-pipe fan coil unit at a 4-pipe fan coil controller

4.2 Commissioning

First steps – Configuration menu
After mounting the device has to be adapted to the system. The configuration menu is only available on first commissioning and after resetting to factory
settings. i Exception: Project-specific devices are preconfigured in the factory. The settings of the
configuration menu are not available for this devices.
o Switch on voltage.
The device displays the software version for 5 seconds. The device subsequently changes into the configuration menu.
o Set the properties of input 1 for the hotel card switch:
OFF not connected OPEN for NO contact CLOSE for NC contact
o Set the fan coil unit type:
2 Pipes for 2-pipe system 4 Pipes for 4-pipe system
i The variants TRD..23028.. are permanently set to 2 Pipes. o Set the function:
MODE Ť HEATING: The device only actuates heating units. MODE ŵ COOLING: The device only actuates climate control units. MODE ŵŤ MANUAL: The device actuates heating and climate control units. The
switchover between heating and cooling mode is carried out manually on the device. MODE ŵŤ AUTO: The device actuates heating and climate control units and automatically switches between heating and cooling mode.
i The Mode ŵŤ AUTO setting is only available for the TRD..23048.. variants.
32598503 j0082598503
10/11
09.11.2017
Temperature controller fan coil, 2-/4-pipe
o Set the properties of the actuators to be controlled:
VALVE OPEN for de-energised open actuators VALVE CLOSE for de-energised closed actuators
When the settings are saved, the device exits the configuration menu. The system parameters set there can only be changed after resetting to factory settings.
i Following the first steps it is convenient to compare the temperature measurement and to
set the cycle time if necessary. Both settings can be found on the second menu level.
Set offset for temperature measurement
By setting this parameter differences between the measured temperature value at the installation location and the actual room temperature are offset.
o Measure the temperature in the room and note down as value T1 . o Read the temperature measured by the device and note down as value T2 . o Calculate the difference between both values ΔT = T1 – T2 and note it down. o Open menu level 2. o Open the menu page TEMPERATURE OFFSET. o Set the difference value on the device.

5 Appendix

5.1 Technical data

Rated voltage AC 110 ... 230V~ Mains frequency 50 / 60Hz Total power loss 0.18 ... 0.52W
Fan output ş Output current max. 3A Motors 230 V 690VA Motors 110 V 300VA
Valve outputs 7 Switching current max. 250mA
Storage temperature -5 ... +45 °C Transport temperature -25 ... +70 °C Ambient temperature -5 ... +45 °C Relative humidity 5 ... 95% (No moisture condensation)
Connection single stranded 1.5mm² Finely stranded with conductor sleeve 1.5mm²

5.2 Accessories

Key card holder RFID Art. No. ..CARDRFID.. Energy saving unit Art. No. ESU230-2