Jung KNX 2116.10 REG Operating Instructions Manual

KNX Switching actuator / shutter actuator Ref.-no.: 2116.10 REG
Operating Instructions Switching actuator / shutter actuator
This unit is a product of the instabus-EIB-System and corresponds to the EIBA Guidelines. Detailed technical knowledge acquired in instabus training courses is a prerequisite for the understanding of the system. The functions of the device are software-dependent. Detailed information on the software and the functions implemented and the software itself are available from the manufacturer’s product data bank.
Planning, installation and commissionning of the device are effected with the help of EIBA-certified software.
For the productdatabase and technical descriptions please refer to the internet at www.jung.de offering up-to-date information.
2. Safety warnings
Attention: Electrical equipment must be installed and fitted only by qualified electricians and in observance of the applicable accident prevention regulations. To prevent electric shocks, disconnect the power supply before working on the device (by cutting out the circuit breaker). Any non-observance of the fitting instructions may cause fire or other hazards. Shutter actuator applications: Connect only shutter motors to the device. Appropriate safety measures must be taken to exclude any hazards deriving from motor-operated components.
Stand: Jun-08 825 238 13
KNX Switching actuator / shutter actuator Ref.-no.: 2116.10 REG
3. Function
Depending on parameterization, the actuator can either be used as switching actuator (max. 16 channels) or as shutter actuator (max. 8 channels). Functions can also be mixed, e.g. outputs A1 – A6 as switching actuator with 6 channels, outputs A7 – A16 as shutter actuator with 5 channels. In the shutter actuator mode, two outputs must be combined for each motor. The device needs an additional power supply.
By means of the control and display elements, the actuator – if parameterized accordingly - can also be readily operated by hand without bus voltage. This includes also the possibility of central shutoff by hand. Cf. also the chapter on manual operation.
4. Important
Switching operation:
The relay outputs of an actuator switch with a slight time delay when controlled by a central telegram.
Do not connect tri-phase AC motors.
The connection of 230 V and SELV voltages to different outputs of
an actuator is not permitted.
Shutter operation:
For shutter operation, 2 neighbouring relay outputs are used as one shutter output. The left (1, 3, 5, …) relay outputs are reserved for the UP movements and the right ones (2, 4, 6, …) for the the DOWN movements.
If motors are to be connected in parallel, it is absolutely necessary to observe the instructions of the motor manufacturers. The motors can otherwise be irreparably damaged.
Use only shutters with limit switches (mechanical or electronic). The limit switches of the motors connected must be checked for proper adjustment.
Activation of the manual operation mode terminates all time delays and the safety shutdown function in stormy weather. The safety shutdown during stroms is reactivated when the manual operation mode is ended.
The manual mode permits only continuous movements (long press) and stop (short press).