1 Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
For parallel connection of several motors to an output it is essential to observe the corresponding instructions of the manufacturers, and to use a cut-off relay if necessary. The motors may be destroyed.
Risk of injury. Use the device only for controlling Venetian blind and roller shutter motors or awnings. Do not use it to switch other loads.
Use only venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct adjustment. Observe the specifications of the motor manufacturers. Device can be damaged.
These instructions are an integral part of the product, and must remain with the end customer.

2 Device components

Figure 1: Front view
(1) Operating mode switch (2) Button Prog (3) Status LED (4) Measuring points for voltage measurement, terminals rear-mounted

3 Function

Intended use
- Controlling electrically driven Venetian blinds, rolling shutters and awnings
82581443 J0082581443
1/11
24.03.2017
eNet radio blinds actuator 1-gang mini
- Operation with suitable eNet radio transmitters
- Mounting in appliance box according to DIN 49073 with a suitable cover
- Installation in surface-mounted housing or panel-mounted housing (accessories) for suspended ceilings
Product characteristics
- Operating mode switch for switch-over to blind actuator, shutter actuator or parameterisation via eNet server
- Positioning of the blind/shutter via scene request
- Positions for sun protection and twilight can be saved
- Status feedback to radio transmitter
- Switchable output with Prog button
- Blind/shutter running time can be saved
- Slat change-over time can be saved
- Fabric-stretching for awnings
- Status indicator via LED
Can be set with eNet server:
- Change-over-time for direction change
- Running direction invertible
- Operation locks
- Position for sun protection, twilight, lock-out protection and wind alarm
i When operating with the eNet Server, operation and signalling could vary from what is
described here.
Supplementary functions with eNet Server:
- Fully encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
- Repeater function
- Reading of error memory
Behaviour after mains voltage return
The response after mains voltage return can be configured with the eNet server. Default setting: no action.

4 Operation

Operation is with radio transmitters, please observe the radio transmitter instructions.

5 Information for electrically skilled persons

5.1 Fitting and electrical connection

DANGER! Electrical shock when live parts are touched. Electrical shocks can be fatal. Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.
Mounting and connecting actuator
To ensure good transmission quality, keep a sufficient distance from any possible sources of interference, e.g. metallic surfaces, microwave ovens, hi-fi and TV systems, ballasts or transformers.
82581443 J0082581443
2/11
24.03.2017
eNet radio blinds actuator 1-gang mini
Figure 2: Connection example
o Connect load as shown in the connection example (figure 2). o Insert the actuator in the appliance box in such a way that the Prog button and status LED
are visible.
Figure 3: Operating mode switch
Switch position Function
PC Operating mode and parameter set with eNet
server.*)
Ht Commissioning - determine running time
It Commissioning - determine slat time
O Blind operating mode
P Operating mode rolling shutter, awning
*) If the operating mode switch is turned from the position PC to another operating mode, the
parameters are set to the default setting. The settings made with the eNet Server will be lost.
o Set the operating mode switch. o Switch on mains voltage. i The load can be switched by briefly pressing the Prog button.
Status LED lights up: output switched on Status LED off: output switched off
o Perform commissioning.
82581443 J0082581443
3/11
24.03.2017
eNet radio blinds actuator 1-gang mini
i In installation positions that are not easily accessible, turn the operating mode switch to
position PC after commissioning and performing a function test. Subsequent changes to the device settings can thus be carried out with the aid of the eNet Server without involving excessive installation work.
o Mount the cover.

5.2 Commissioning

DANGER! Electrical shock when live parts are touched. Electrical shocks can be fatal. During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.
i The actuator can also be commissioned with eNet Server as an alternative to the
commissioning described here.
i Prerequisite for scenes and positioning movements is that the moving times of the
connected blind/shutter in the actuator are saved.
Saving blind/shutter running time for rolling shutters
The operating mode switch (figure 3) is in the Venetian blind O or rolling shutter P position. o Turn the operating mode switch (1) to the I t position until the blind/shutter reaches the
upper end position.
o Turn operating mode switch to the Ht position.
The blind/shutter moves downwards.
o When the lower end position is reached, turn the operating mode switch to the P position.
The running time is saved and the blind/shutter moves to the upper end position.
Saving blind/shutter running time for blind
The operating mode switch (figure 3) is in the Venetian blind O or rolling shutter P position. o Turn the operating mode switch (1) to the I t position until the blind/shutter reaches the
upper end position.
o Turn operating mode switch to the Ht position.
The blind/shutter moves downwards.
o When the lower end position is reached, turn the operating mode switch to the I t
position.
o When the slats have been fully changed over, turn the operating mode switch to the O
position. The running times are saved and the blind/shutter moves to the upper end position.
Saving the awning running time
The operating mode switch (figure 3) is in the Venetian blind O or rolling shutter P position. o Turn the operating mode switch (1) to the I t position until the blind/shutter reaches the
upper end position.
o Turn operating mode switch to the Ht position. o For awnings without fabric-stretching function: When the extended lower end position is
reached, turn the operating mode switch to the It position. As soon the fabric is hanging taut, turn the operating mode switch to the P position.
o For awnings with their own fabric-stretching function: When the extended lower end
position is reached, turn the operating mode switch to the P position. The running times are saved and the blind/shutter moves to the upper end position.
Connecting actuator to radio transmitters
Load is switched off. o Press the Prog button for longer than 4 seconds.
82581443 J0082581443