Jung FMAS816REG Operating Instructions Manual

eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
Art. No. : FMAS816REG
Operating instructions
1 Safety instructions
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the devise or load. In so doing, take all the circuit breakers into account, which support dangerous voltages to the device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
Do not connect any three-phase motors. Device can be damaged.
Danger of electric shock. During installation and cable routing, comply with the regulations and standards which apply for SELV circuits.
Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains voltage and SELV/PELV together on a single switch actuator.
For parallel connection of several motors to an output it is essential to observe the corresponding instructions of the manufacturers, and to use a cut-off relay if necessary. The motors may be destroyed.
Use only venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct adjustment. Observe the specifications of the motor manufacturers. Device can be damaged.
Fire hazard! Operation exclusively with the power supplies listed under accessories
These instructions are an integral part of the product, and must remain with the end customer.
2 Device components
Figure 1
(1) Load connection A1...A8 (2) Operating mode switch for outputs A1+A5, A2+A6, A3+A7, A4+A8
1/20
82581933 J0082581933
23.03.2017
(3) Button Prog A1...A8 (4) Status LED A1...A8 (5) Teach Switch for commissioning in the operating mode Venetian blind/rolling shutter (6) Bus line connection
3 Function
Intended use
- Switching of lighting
- Switching of single-phase fan motors
- Controlling electrically driven Venetian blinds, rolling shutters and awnings
- Operation with suitable eNet radio transmitters
- Operation with power supply RMD and receiver module RMD cover or eNet server (see accessories)Operation with power supply RMD and receiver module RMD cover or eNet server (see accessories)
- Installation in distribution boxes on DIN rail according to EN 60715
Product characteristics
- Operating mode switch for switch-over of switching actuator, push-button actuator, blind actuator, shutter actuator or configuration via eNet server
- Status feedback to radio transmitter
- Scene operation possible
- Outputs switchable with Prog button
- Status indicator of the outputs via LED
Switching operation:
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
Operating mode Venetian blind/rolling shutter
- Positioning of the Venetian blind and slats via scene recall
- Position for sun protection and twilight
- Blind/shutter running time can be saved
- Slat change-over time can be saved
- Fabric-stretching for awnings
Can be set with eNet server in switching/push-button operation:
- Operating mode for each output can be set separately
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as NO or NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operation locks
- Continuous on, Continuous off
Can be set in the operating mode Venetian blind/rolling shutter with eNet server:
- Change-over-time for direction change
- Running direction invertible
- Operation locks
- Position for sun protection, twilight, lock-out protection and wind alarm
Supplementary functions with eNet Server:
- Fully encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
- Reading of error memory
2/20
82581933 J0082581933
23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
Behaviour in case of bus voltage failure and return
If the bus voltage fails, the actuator switches off. The response to bus voltage return can be parameterised with the eNet server. Default setting operating mode Venetian blind/rolling shutter: no action. Switching operation/bush-button operation default setting: Off.
4 Operation
i When operating with the eNet Server, operation and signalling could vary from what is
described here.
Operation with radio transmitters
Operation is with radio transmitters, please observe the radio transmitter instructions.
Operation with Prog button in switching or push-button operation
o Press button Prog (3) briefly.
The light switches on or off. Status LED A1..A8 (4) lights up: output is switched on.
Status LED A1..A8 off: output is switched off.
Operation with Prog button in the operating mode Venetian blind/rolling shutter
In this operating mode, two neighbouring outputs are combined respectively into a single venetian blind output. Both Prog buttons have the same function.
o Press Prog button briefly.
A moving blind/shutter is stopped and a stationary blind/shutter is briefly activated, e.g. for slat change-over.
The control direction is changed when the button is pressed again.
o Press the Prog button for longer than one second but shorter than four seconds.
The motor moves to the end position. The control direction is changed when the button is pressed again. The upper status LED indicates the upward movement and the lower status LED indicates
the downward movement.
5 Information for electrically skilled persons
5.1 Fitting and electrical connection
DANGER! Electrical shock when live parts are touched. Electrical shocks can be fatal. Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
Fitting the device
o Mount device on DIN rail. Output terminals must be at the top.
3/20
82581933 J0082581933
23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
Connect bus line
Figure 2: Connection diagram of bus line
Labelling / Colour Connection
DC– / GY dark grey Power supply –
DC+ / RD red Power supply +
Bus– / WH white Data cable –
Bus+ / YE yellow Data cable +
As bus line, use e.g. J-Y(St)Y 2x2x0.8 o Connect the device with bus line (figure 2) to the RMD reception module and power supply
(see instructions of RMD reception module and power supply).
CAUTION! Overloading the device leads to excessive heating. Damage to the device and the connected cables may result. Do not exceed the maximum current carrying capacity. Load neighbouring outputs only until the sum of their output currents is a max.
of 20 A.
4/20
82581933 J0082581933
23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
Figure 3: Current carrying capacity of neighbouring outputs
Connecting loads in switching/push-button operation
Figure 4: Connection example of switching loads A1...A4
o Connect loads as shown in the connection example of switching loads (figure 4).
5/20
82581933 J0082581933
23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
Connecting loads in operating mode Venetian blind/rolling shutter
Figure 5: Connection example of Venetian blind loads
o Connect loads as shown in the connection example of Venetian blind loads (figure 5).
Presetting the operating mode
CAUTION! Danger of destruction from wrong operating mode. Simultaneous current feed in both directions of travel can destroy the device
and connected blind motors. Before setting the operating mode, check what loads are connected.
One operating mode switch applies to two outputs each.
Figure 6: Operating mode switch
Switch position Function
6/20
82581933 J0082581933
23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang, for rail mounting
Loading...