Jung FM 1701 Series Operating Instructions Manual

LB management
eNet radio centre plate
eNet radio centre plate Art. no.: FM..1701..
Operating instructions

1 Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully. Danger of electric shock. Always disconnect before carrying out work on the device or load. In
The radio communication takes place via a non-exclusively available transmission path, and is therefore not suitable for safety-related applications, such as emergency stop and emergency call.
These instructions are an integral part of the product, and must remain with the end customer.

2 Device components

Figure1: Device components
(1) Insert (2) Frame (3a) Blind/shutter up / light on, brighter (3b) Blind/shutter down / light off, darker (4a) Disabling function (4b) Memory function (5) Function LED
Red = Disabling function active Green = Memory function active
(6) Status LED
Green = Blind/shutter activated / light switched on red = sending status red flashing = error message, programming mode or resetting to the default setting
32597903 07.08.2019 J0082597903
1 / 29
LB management
eNet radio centre plate

3 Intended use

Manual, radio- and time-controlled operation of e.g. Venetian blinds, shutters, awnings,
lighting or fans
Transmitter for radio communication of switching, dimming and blind movement com-
mands
Operation of switching, dimming or Venetian blind insert or 3-wire extension from LB man-
agement
When operating with the eNet Server, operation and signalling could vary from what is de­scribed here.

4 Product characteristics

2 switching times can be saved, which are repeated in a 24-hour cycle – Disabling function – Status feedback to radio transmitter – Status indication with LED – Night mode – Evaluation of extension inputs
Functions in combination with Venetian blind insert – Positioning of the blind/shutter via scene request – Position for sun protection and twilight – Running time and ventilation position of the blind/shutter can be saved
Functions in combination with light insert – Scene operation possible – Switch-on brightness can be saved permanently when combined with flush-mounted in-
serts for dimming
Can be set with eNet Server from version 2.2 (depending on application) – Repeater function – Slat change-over time/fabric-stretching time – Change-over-time for direction change – Running direction invertible – Operation locks – Deactivating extension evaluation – Position for sun protection, twilight, lock-out protection and wind alarm – Maximum brightness – Minimum brightness – Dimming speed – Switch-on delay / switch-off delay – Dim up/dim down ramp – Switch-off warning – Continuous on, Continuous off – Hotel function – Run-on time – Light control
Supplementary functions with eNet Server: – Fully encrypted radio transmission (AES-CCM) – Update of the device software – Reading of error memory
Behaviour after mains voltage return – The switching times saved in memory operation have been deleted.
32597903 07.08.2019 J0082597903
2 / 29
LB management
eNet radio centre plate
The response after mains voltage return can be configured with the eNet server.

5 Operation of Venetian blind and shutters

Moving the blind/shutter ■ Press button (3a) or (3b) for longer than one second.
The blind/shutter moves in the desired direction to the end position or stops when the but­ton is pressed again.
If a ventilation position has been saved, the blind stops in the ventilation position when moving down (see Saving the ventilation position).
Adjusting the slats ■ Press the button (3a) or (3b) for less than one second.
Saving blind/shutter running time
To perform positioning movements, the blind/shutter running time has to be saved beforehand. To save blind/shutter running time, the Venetian blind must be moved to the upper end position
and the status LED (6) switch off automatically. ■ From the top end position, press the button (3b) for longer than second.
The blind/shutter moves in the lower end position direction.
Press and hold down the button (3a) and (3b).
The blind/shutter remains stopped, but continues to move after 4 seconds.
As soon as the blind/shutter has reached the lower end position, release the buttons and
press button (3b) within the next 4 seconds. The running time is saved. The blind/shutter moves back to the upper end position.
The change-over-time of the slats for the venetian blind and time/fabric-stretching time for awnings can only be saved using the eNet server.
Saving the ventilation position To save the ventilation position, the Venetian blind must be moved to the upper end position
and the status LED (6) switch off automatically. ■ From the top end position, press the button (3b) for longer than second.
The blind/shutter moves in the lower end position direction.
Press and hold down the button (3a) and (3b).
The blind/shutter remains stopped, but continues to move after 4 seconds.
As soon as the desired ventilation position has been reached, release the buttons and
press the button (3a) within the next 4 seconds. The ventilation position is saved. The blind/shutter moves back to the upper end position.
If the ventilation position is saved again, the old value is overwritten.

6 Operation of lighting

Switch light ■ Press button (3a) or (3b) for less than 0.4 seconds.
With a dimming insert, the light switches to the brightness that was last set or a saved brightness.
Switch light on with minimum brightness ■ Press the button (3b) for longer than 0.4 seconds.
Adjust the brightness ■ Press button (3a) or (3b) for longer than 0.4 seconds.
32597903 07.08.2019 J0082597903
3 / 29
LB management
eNet radio centre plate
Save switch-on brightness ■ Adjust the brightness.
Press the buttons (3a) and (3b) for longer than 4 seconds.
Switch-on brightness is saved. For confirmation, the light is switched off briefly and switched on again.
Delete switch-on brightness ■ Press button (3) briefly: Light switches on at the saved switch-on brightness.
Press the buttons (3a) and (3b) for longer than 4 seconds.
The switch-on brightness has been deleted.
Switching on takes place at the last brightness value set. For confirmation, the light is switched off briefly and switched on again.

7 Transmitter function of the attachment

In addition to operating its own insert, the attachment also sends radio telegrams to remote eNet actuators. In this way, a comprehensive central control system can be implemented. Irre­spective of local use, the attachment can be used for switching, dimming and operating Vene­tian blinds of remote actuators.
Signalling of the status LED
As soon as the button (3a) or (3b) is pressed or released, the red status LED first signals radio transmission.
The status LED lights up red for 3 seconds. The actuator status/group status is then displayed (see Query group status).
Polling sum status ■ Press buttons (3a) and (3b) for 1 to 4 seconds.
If there is no status message from at least one remote actuator, a transmission error is signaled. Status LED flashes red quickly for 5 seconds.
Signalling of the group status: – Status LED turns green for 3 seconds:
At least one actuator is switched on, or one Venetian blind is not in the top end position.
Status LED remains off:
All the actuators are switched off or the Venetian blinds are all in the upper end position.

8 Activate functions

Saving switching times - Memory operation ■ In addition to normal operation with the button (3a) or (3b), press the button (4b) for
longer than one second. The insert switches and the switching time is saved.
The device switches to memory operation. The function LED (5) turns continuously green.
Saved switching operations are repeated in a 24-hour cycle.
An upward and downward movement time, or on and off time, can be saved. The old switching time will be replaced if a new one is saved.
To delete all times, press button (4b) for longer than 20 seconds until the function LED (5) lights up green for a second time.
After programming with the eNet Server or
eNet SMART HOME app
, the switching times
saved in memory operation have been deleted.
Activating / deactivating memory operation ■ Press the button (4b) for longer than 4 seconds.
32597903 07.08.2019 J0082597903
4 / 29
LB management
eNet radio centre plate
In memory operation, the function LED (5) turns continuously green.
It is only possible to switch to memory operation if at least one switching time has been saved.
Activating / deactivating the disabling function
The disabling function disables extension operation and operation via radio and deactivates all automatic functions. Manual operation using buttons (3a) and (3b) continues to be possible.
With Venetian blinds, extension operation in the "UP" direction (wind alarm) continuous to be possible.
Press the button (4a) for longer than 4 seconds.
The function LED (5) is red for as long as the disabling function is active.
Activating / deactivating night mode
In night mode, the status and function LEDs are not permanently lit, but only for 5 seconds after a button is pressed.
Press the buttons (4a) and (4b) for longer than 4 seconds.
Night mode is activated: The function LED turns red for 3 seconds. Night mode is deactivated: The function LED turns green for 3 seconds.
Resetting the device to the factory setting
All connections to radio transmitters and radio actuators are disconnected and parameters are reset to the default setting.
The connections in the radio transmitters and radio actuators are preserved and must be deleted separately.
Load is switched off. ■ Press buttons (3a) and (3b) for longer than 20 seconds until the red status LED flashes
quickly.
Release buttons (3a) and (3b) and press briefly once again within 10 seconds.
The red status LED flashes more slowly for approx. 5 seconds.
The attachment is reset to the default setting.
On a Venetian blind insert, a reference run to the upper end position is performed.

9 Information for electrically skilled persons

DANGER!
Mortal danger of electric shock
Disconnect the device. Cover up live parts.
Fitting the device Switching, dimming or Venetian blind insert or 3-wire extension are mounted and connected
properly (see instructions of the relevant inserts). ■ Fit the cover with frame on the insert. ■ Switch on mains voltage.
If the status LED (6) flashes red three times at repeated intervals, the cover was previ­ously connected to another insert. To enable operation again, either place the cover onto the respective insert or press buttons (3a) and (3b) for longer than 4 seconds. When switching to another application, the device should always be reset to the default setting and then reprogrammed.
32597903 07.08.2019 J0082597903
5 / 29
LB management
eNet radio centre plate

10 Commissioning

DANGER!
Mortal danger of electric shock.
During commissioning, cover the parts carrying voltage on radio transmitters and ac­tuators and in their surrounding area.
The attachment can also be commissioned with eNet Server as an alternative to the com­missioning described here.
The prerequisite for scenes and positioning movements is that the moving times of the connected blind/shutter in the attachment are saved.
Connecting attachment with radio transmitter
Load is switched off. ■ Press buttons (3a) and (3b) for longer than 4 seconds.
When operating on a switching or dimming insert, the load is switched on.
The status LED flashes after 4 seconds. The attachment is in programming mode for approx. 1 minute.
Switch radio transmitter to programming mode (see radio transmitter instructions). ■ Trigger telegram on the radio transmitter.
The status LED lights up for 5 seconds.
The attachment is connected to the radio transmitter. The attachment and radio transmit­ter exit the programming mode automatically.
If the status LED of the attachment flashes 3 times for approx. 5 seconds, then the pro­gramming procedure was not successful. All the memory locations in the attachment or radio transmitter are occupied.
Connecting attachment to radio actuator
Up to 10 radio actuators can be connected to a transmitter in a single step.
Press buttons (3a) and (3b) simultaneously for longer than 4 seconds.
The red status LED flashes. The attachment is in programming mode for approx. 1 minute.
Switch radio actuator to programming mode (see radio actuator instructions). ■ Press button (3a) briefly.
The red status LED lights up for approx. 5 seconds. The attachment and actuator exit the programming mode automatically.
If the red status LED of the attachment flashes 3 times for approx. 5 seconds, then the programming procedure was not successful. The radio actuator is outside the radio range, not in programming mode or there are radio faults.
If the red status LED of the radio actuator flashes 3 times for approx. 5 seconds, then the programming procedure was not successful. All the memory locations in the attachment or radio actuator are occupied.
Press buttons (3a) and (3b) once again simultaneously for longer than 4 seconds to ter­minate the programming mode prematurely.
Disconnecting connection to a radio transmitter or radio actuator ■ Carry out the same steps as when connecting (see Connecting attachment to radio trans-
mitter or Connecting attachment to radio actuator).
32597903 07.08.2019 J0082597903
6 / 29
LB management
eNet radio centre plate
The status LED flashes quickly for 5 seconds. The attachment is disconnected from the radio transmitter or radio actuator. The attachment and radio transmitter or radio actuator exit the programming mode automatically.
If there several connections or scene buttons for a radio transmitter, all connections must be disconnected individually.
All On and All Off buttons of a radio transmitter are disconnected automatically as soon as the last connection of the corresponding output to the radio transmitter is disconnected. Manual disconnection is not possible.

11 Technical data

Ambient temperature -5 ... +45 °C Storage/transport temperature -20 ... +70 °C Transmitting range in free field typ. 100 m Radio frequency 868.0 ... 868.6 MHz Transmission capacity max. 20 mW Receiver category 2

12 Parameter list

The device parameters can be changed with the eNet Server. Device and channels
Parameters Setting options
Basic setting
Sensor channel function
Actuator channel function
Rocker, Unused Basic setting: Rocker
Switch insert, Dimming insert, Extension insert, Venetian blind insert, Switch insert 2-channel, Unknown insert Unused
"Switching" oper­ating mode
Switching operation Push-button operation Flashing Continuous on Continuous off Basic setting: Switching operation
Explanations
Rocker The channel works as a channel button.
Unused The channel is not displayed in the HOME app
and is disabled for use in the com-
missioning interface.
The attachment function depends on the applica­tion. For catalogue devices, the insert on which the attachment is operated must be selected at this point.
For devices from the device search, the existing insert is displayed. This setting cannot be altered.
Switching operation After switch-on, the device remains stable in the "On" state, and stable in the "Off" state after switch-off.
Push-button operation The device switches "On" when the channel but­ton of a radio transmitter is pressed, if the attach­ment is pressed directly or via an extension and "Off" when the button is released. It is irrelevant whether the "On" or "Off" button is pressed.
eNet SMART
Flashing Switch-on starts flashing and switch-off stops flashing. The default flash frequency is 1 Hz. This frequency is also the maximum flash frequency.
32597903 07.08.2019 J0082597903
7 / 29
LB management
eNet radio centre plate
Parameters Setting options
Basic setting
"Switching" func­tion
Light (switching), Switching, Unused Basic setting: Light (switching)
Explanations
The flash frequency can be changed using para­meters. The parameter "Switch-off delay" is used for the pulse time and the parameter "Switch-on delay" for the pause time.
Continuous on The output switches to continuously "On". All op­erations of radio transmitters, via an extension or directly on the attachment are ignored.
Continuous off The output switches to continuously "Off". All op­erations of radio transmitters, via an extension or directly on the attachment are ignored.
Light (switching) The channel is integrated for the "Lighting" cent­ral function in the
eNet SMART HOME app
.
Switching The channel is not integrated in any central func­tion.
Operating mode "Dimming"
"Dimming" func­tion
Normal operation Continuous on Continuous off Basic setting: Normal operation
Light (dimming), Unused Basic setting: Light (dimming)
Unused The channel is not displayed in the HOME app
and is disabled for use in the com-
eNet SMART
missioning interface.
Normal operation The insert can be operated with radio transmit­ters, via an extension or directly on the attach­ment.
Continuous on The output switches to continuously "On". All op­erations of radio transmitters, via an extension or directly on the attachment are ignored.
Continuous off The output switches to continuously "Off". All op­erations of radio transmitters, via an extension or directly on the attachment are ignored.
Light (dimming) The channel is integrated for the "Lighting" cent­ral function in the
eNet SMART HOME app
.
Unused The channel is not displayed in the HOME app
and is disabled for use in the com-
eNet SMART
missioning interface.
Operating mode "Extension opera­tion"
Normal operation Continuous on Continuous off Basic setting:
Normal operation The attachment is located on a 3-wire extension and can operate the main device via radio trans­mitter or directly on the attachment.
Normal operation
Continuous on
32597903 07.08.2019 J0082597903
8 / 29
LB management
eNet radio centre plate
Parameters Setting options
Basic setting
Function "Exten­sion operation"
Light (dimming), light (switching), switching, unused Basic setting: Light (dimming)
Explanations
The output switches to continuously "On". All op­erations of radio transmitters or directly on the at­tachment are ignored.
Continuous off The output switches to continuously "Off". All op­erations of radio transmitters or directly on the at­tachment are ignored.
The attachment is located on a 3-wire extension. The function of the main device can be entered here.
Light (dimming) The channel is integrated for the "Lighting" cent­ral function in the
eNet SMART HOME app
.
Light (switching) The channel is integrated for the "Lighting" cent­ral function in the
eNet SMART HOME app
.
Switching The channel is not integrated in any central func­tion.
"Venetian blind" operating mode
Operating mode "2-channel switch insert"
Roller shutter Venetian blind Awning Basic setting: Roller shutter
Switching operation Push-button operation Flashing Continuous on Continuous off Basic setting: Switching operation
Unused The channel is not displayed in the HOME app
and is disabled for use in the com-
eNet SMART
missioning interface.
Roller shutter A shutter is controlled. The channel is integrated for the "Venetian blind" central function in the
eNet SMART HOME app
.
Venetian blind A Venetian blind is controlled. The channel is integrated for the "Venetian blind" central function in the
eNet SMART HOME app
.
Awning An awning is controlled. The channel is not integrated into the "Venetian blind" central function in the app
.
eNet SMART HOME
Switching operation After switch-on, the device remains stable in the "On" state, and stable in the "Off" state after switch-off.
Push-button operation The device switches "On" when the channel but­ton of a radio transmitter is pressed, if the attach­ment is pressed directly or via an extension and "Off" when the button is released. It is irrelevant whether the "On" or "Off" button is pressed.
32597903 07.08.2019 J0082597903
9 / 29
LB management
eNet radio centre plate
Parameters Setting options
Basic setting
Function "2-channel switch insert"
Light (switching) + fan Switching + fan Light (switching) Switching Unused Basic setting: Light (switching) + fan
Explanations
Flashing Switch-on starts flashing and switch-off stops flashing. The default flash frequency is 1 Hz. This frequency is also the maximum flash frequency. The flash frequency can be changed using para­meters. The parameter "Switch-off delay" is used for the pulse time and the parameter "Switch-on delay" for the pause time.
Continuous on The output switches to continuously "On". All op­erations of radio transmitters, via an extension or directly on the attachment are ignored.
Continuous off The output switches to continuously "Off". All op­erations of radio transmitters, via an extension or directly on the attachment are ignored.
Light (switching) + fan The light channel is integrated into the "Lighting" central function in the
eNet SMART HOME app
. The fan channel switches on and off with a delay depending on the set parameters.
Switching + fan The switching channel is not integrated in any central function. The fan channel switches on and off with a delay depending on the set parameters.
Advanced device settings
Parameters Setting options, Basic
setting
Manual commis­sioning
On, Off Basic setting: On
Repeater mode On, Off
Basic setting: Off
Light (switching) The channel is integrated for the "Lighting" cent­ral function in the
eNet SMART HOME app
. Both
channels of the switch insert switch in parallel.
Switching The channel is not integrated in any central func­tion. Both channels of the switch insert switch in parallel.
Unused The channel is not displayed in the HOME app
and is disabled for use in the com-
eNet SMART
missioning interface.
Explanations
Disables manual commissioning for all device channels. In the "Off" setting, the device cannot be reset to the factory setting.
In addition to its other functions, the device can be used as a repeater. In the "On" setting, the device repeats all the received telegrams.
32597903 07.08.2019 J0082597903
10 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Allow extension unit operation
On, Off Basic setting: On
Extended channel settings Sensor channel
Parameters Setting options, Basic
setting
Manual commis­sioning
On, Off Basic setting: On
Local Operation On, Off
Basic setting: On
Channel settings "switching"
Parameters Setting options, Basic
setting
Switch-on delay 0 s … 24 h
Basic setting: 0 s
Explanations
Allows operation via wired extensions.
Explanations
Blocks manual commissioning for the sensor channel. In the "Off" setting, the device cannot be reset to the factory setting.
Blocks the sensor operation of the button. Tele­grams are no longer transmitted to remote actu­ators.
Explanations
The load switches on after a delay. Repeated switch-on commands restart the delay time. If the load has not yet been switched on due to the delay when a switch-off command comes, then the load will remain off. In Flashing operating mode, the pause time is set using this parameter.
Switch-off delay 0 s … 24 h
Basic setting: 0 s
Run-on time 0 s … 24 h
Basic setting: 0 s
Use run-on time On, Off
Basic setting: Off
The load switches off after a delay. Repeated switch-off commands restart the delay time. If the load has not yet been switched off due to the delay when a switch-on command comes, then the load will remain on. In Flashing operating mode, the pulse times are set using this para­meter.
If a run-on time is entered and the "Use run-on time" parameter is activated, the actuator no longer remains permanently switched on, but only for the duration of the run-on time entered here or transmitted by a motion detector. The run-on time is restarted if actuation is repeated.
A motion detector command without transmitted run-on time (e.g. from an extension) leads to switching on for the duration of the run-on time entered here. If no run-on time is entered here, the default run-on time of 2 minutes is applied.
On: If a run-on time is configured (≠ 0 s), in addition to motion detector commands, all switching or dimming commands also lead to switching on for the duration of the run-on time.
If no run-on time is configured (= 0 s), all switch­ing or dimming commands result in permanent switching of the load. As soon as the attachment receives a motion de­tector command, the transmitted run-on time is
32597903 07.08.2019 J0082597903
11 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Manual switch-off of the run-on time
On, Off Basic setting: Off
Operating hours 0 ... 65535
Basic setting: Current value
Extended channel settings "switching"
Explanations
automatically entered in the "Run-on time" para­meter and this then also applies to all switching and dimming commands.
Off: Only motion detector commands lead to switch­ing on for the duration of the transmitted or set run-on time. The load is permanently switched for switching and dimming commands.
Allows manual switch-off of a running run-on time. If the parameter is switched off, then a switch-off command will also switch the actuator on. Only visible if a run-on time was set.
The time is counted during which the load is switched on (relay contact closed). This para­meter can be reset to "0", for example after ex­changing the load. The Reset button is used to reset the counter to "0". The device must be pro­grammed to apply the change.
Parameters Setting options, Basic
setting
Operating mode Switching operation
Push-button operation Flashing Continuous on Continuous off Basic setting: Switching operation
Manual commis­sioning
On, Off Basic setting: On
Local Operation On, Off
Basic setting: On
Behaviour on voltage return
On Off Last value Basic setting: Off
Timer behaviour, voltage return
Off Restart Basic setting: Off
Explanations
See Device and channels.
Blocks manual commissioning for the device channel. In the "Off" setting, the device cannot be reset to the factory setting.
Blocks the output for operation using the button.
Defines the behaviour of the output after voltage return.
Specifies whether an active switch-on delay, switch-off delay or run-on time remains off or re­starts after voltage return. Directly connected to the parameters "Switch-on delay", "Switch-off delay" and "Run-on time".
Behaviour after the end of the disabling function
On Off no change
Behaviour of the output when a block is removed.
Last value Basic setting: No change
32597903 07.08.2019 J0082597903
12 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Manual saving of the scene values
Switch-off warn­ing
Priority, lock-out protection
Activate lock-out protection switch-
On, Off Basic setting: On
On, Off Basic setting: Off
0...4 Basic setting: 1
On, Off Basic setting: Off
ing state
Deactivate lock­out protection
On, Off Basic setting: Off
switching state
Priority, restraint 0...4
Basic setting: 2
Explanations
Disables the saving of the current actuator state (On/Off) as scene value in an actuator for a com­mand via a transmitter.
If the switch-off warning is active, the light is not switched off directly. The light briefly goes off 30, 20 and 10 seconds before permanent switch-off. During the switch-off warning, a switch-on com­mand activates direct switch-on. It is not possible to terminate the time using a switch-off com­mand.
Specifies the priority for recalling and removing a scene of type Lock-out protection for the channel.
Defines the behaviour of the output on activating the lock-out protection.
Defines the behaviour of the output on deactivat­ing the lock-out protection. Only visible when the priority for the lock-out protection is 0.
Specifies the priority for recalling and removing a scene of type Restraint for the channel.
Activate forced operation switch­ing state
Deactivate forced operation switch­ing state
Priority, wind alarm
Activate wind alarm switching state
Deactivate wind alarm switching state
Priority, sun pro­tection
Activate sun pro­tection switching state
Deactivate sun protection switch­ing state
On, Off Basic setting: On
On, Off Basic setting: Off
0...4 Basic setting: 3
On, Off Basic setting: Off
On, Off Basic setting: Off
0...4 Basic setting: 0
On, Off Basic setting: On
On, Off Basic setting: Off
Defines the behaviour of the output on activating the forced operation.
Defines the behaviour of the output on deactivat­ing the forced operation. Only visible when the priority for the forced operation is 0.
Specifies the priority for recalling and removing a scene of type Wind alarm for the channel.
Defines the behaviour of the output on activating the wind alarm.
Defines the behaviour of the output on deactivat­ing the wind alarm. Only visible when the priority for the wind alarm is 0.
Specifies the priority for recalling and removing a scene of type Sun protection for the channel.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Priority, twilight 0...4
Basic setting: 0
Activate twilight switching state
32597903 07.08.2019 J0082597903
On, Off Basic setting: On
Specifies the priority for recalling and removing a scene of type Twilight for the channel.
Defines the behaviour of the output on activating the twilight function.
13 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Deactivate twi­light switching
On, Off Basic setting: Off
state
Invert switching output
Minimum switch­ing repeat time
On, Off Basic setting: Off
100 ms ... 10 sec Basic setting: 100 ms
Channel settings "dimming"
Parameters Setting options, Basic
setting
Switch-on bright­ness
1...100 % Basic setting: 100 %
Explanations
Defines the behaviour of the output on deactivat­ing the twilight function. Only visible when the pri­ority for the twilight function is 0.
Inverts the switching output from NO contact function (factory setting) to NC contact function
Limits the switching speed of the device by in­creasing the value, in order to protect the load, for example. Only when the set time has elapsed is switching possible again. The last command during the blocking time is executed after a delay. The switching repeat time starts after each switching operation.
Explanations
During brief operation, the output switches on at the set switch-on brightness. Note: If the value is above the set maximum brightness or below the minimum brightness, then the system will switch to the appropriate limit value.
Minimum bright­ness
Maximum bright­ness
Dimming adjust­ment time
1...67 % Basic setting: 5 %
75...100 % Basic setting: 100 %
1…60 s Basic setting: 4 s
Switch-on delay 0 s … 24 h
Basic setting: 0 s
Switch-off delay 0 s … 24 h
Basic setting: 0 s
Dim up ramp 0 s … 24 h
Basic setting: 0 s
Specifies the minimum settable brightness. Note: If parameters or scene values are set to a level lower than the minimum brightness, then the sys­tem will dim to minimum brightness.
Specifies the maximum settable brightness. Note: If parameters or scene values are set to a level higher than the maximum brightness, then the system will dim to maximum brightness.
Time from minimum brightness until reaching maximum brightness (dimming speed).
The load switches on after a delay. Repeated switch-on commands restart the delay time. If the load has not yet been switched on due to the delay when a switch-off command comes, then the load will remain off.
The load switches off after a delay. Repeated switch-off commands restart the delay time. If the load has not yet been switched off due to the delay when a switch-on command comes, then the load will remain on.
Time between switch-on and reaching switch-on brightness. The light is switched on at minimum brightness and then dimmed to the switch-on brightness. Only applies to switch-on with trans­mitters (short operation). If scenes are recalled or switching uses logic modules, the switch-on brightness is approached using so-called soft dimming (not configurable).
32597903 07.08.2019 J0082597903
14 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Dim down ramp 0 s … 24 h
Basic setting: 0 s
Run-on time 0 s … 24 h
Basic setting: 0 s
Use run-on time On, Off
Basic setting: Off
Explanations
Time until reaching minimum brightness. The light is dimmed to minimum brightness and then switched off. Only applies to switch-off with trans­mitters (short operation). If scenes are recalled or switching uses logic modules, the system switches off directly.
If a run-on time is entered and the "Use run-on time" parameter is activated, the actuator no longer remains permanently switched on, but only for the duration of the run-on time entered here or transmitted by a motion detector. The run-on time is restarted if actuation is repeated.
A motion detector command without transmitted run-on time (e.g. from an extension) leads to switching on for the duration of the run-on time entered here. If no run-on time is entered here, the default run-on time of 2 minutes is applied.
On: If a run-on time is configured (≠ 0 s), in addition to motion detector commands, all switching or dimming commands also lead to switching on for the duration of the run-on time.
Manual switch-off of the run-on time
Switch on to last brightness
On, Off Basic setting: Off
On, Off Basic setting: Off
If no run-on time is configured (= 0 s), all switch­ing or dimming commands result in permanent switching of the load. As soon as the attachment receives a motion de­tector command, the transmitted run-on time is automatically entered in the "Run-on time" para­meter and this then also applies to all switching and dimming commands.
Off: Only motion detector commands lead to switch­ing on for the duration of the transmitted or set run-on time. The load is permanently switched for switching and dimming commands.
Allows manual switch-off of a running run-on time. If the parameter is switched off, then a switch-off command will also switch the actuator on. Only visible if a run-on time was set.
Allows you to switch the lighting on at the same brightness value that was used before it was last switched off. With the "Off" setting, the lighting is switched on with the brightness saved in the "Switch-on brightness" parameter.
32597903 07.08.2019 J0082597903
15 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Operating hours 0...65535
Basic setting: Current value
Extended channel settings "dimming"
Parameters Setting options, Basic
setting
Operating mode Normal operation
Continuous on Continuous off Basic setting: Normal Operation
Manual commis­sioning
On, Off Basic setting: On
Local Operation On, Off
Basic setting: On
Behaviour on voltage return
On Off Last value Configured brightness Basic setting: Off
Explanations
The time is counted during which the load is switched on. This parameter can be reset to "0", for example after exchanging the load. The Reset button is used to reset the counter to "0". The device must be programmed to apply the change.
Explanations
see Device and channels
Blocks manual commissioning for the device channel. Note: In the "Off" setting, the device cannot be reset to the factory setting.
Blocks the output for operation using the button.
Defines the behaviour of the output after voltage return.
Brightness on voltage return
Behaviour after the end of the disabling function
Manual saving of the scene values
Switch-off warn­ing
0...100 % Basic setting: 100 %
On Off no change Last value Basic setting: No change
On, Off Basic setting: On
On, Off Basic setting: Off
Brightness value, set by the output after voltage return (mains voltage). The parameter "Beha­viour after voltage return" must be set to "Con­figured brightness". Note: If the value is above the set maximum brightness or below the min­imum brightness, then the system will switch to the appropriate limit value.
Behaviour of the output when a block is removed.
Disables the saving of the current brightness value as scene value in an actuator for a com­mand via a transmitter.
If the switch-off warning is active, then, during switch-off, the system dims to minimum bright­ness within 30 seconds and only then switches off. If the parameter "Dim down ramp" is con­figured as longer than 30 seconds, then the dura­tion of the dim down ramp is applied. If, during the dim down operation, another command is given, e.g. switch on or scene recall, then the switch-off warning stops and the command is ex­ecuted. A switch-off command restarts the time for the switch-off warning.
32597903 07.08.2019 J0082597903
16 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Priority, lock-out protection
Activate lock-out protection bright-
0...4 Basic setting: 1
0…100 % Basic setting: 0 %
ness value
Deactivate lock­out protection
0…100 % Basic setting: 0 %
brightness value
Priority, restraint 0...4
Basic setting: 2
Activate forced operation bright-
0…100 % Basic setting: 100 %
ness value
Deactivate forced operation bright-
0…100 % Basic setting: 0 %
ness value
Priority, wind alarm
0...4 Basic setting: 3
Explanations
Specifies the priority for recalling and removing a scene of type Lock-out protection for the channel. Note: 1 is the highest priority and 4 the lowest. 0 means no priority.
Defines the behaviour of the output on activating the lock-out protection.
Defines the behaviour of the output on deactivat­ing the lock-out protection. Only visible when the priority for the lock-out protection is 0.
Specifies the priority for recalling and removing a scene of type Restraint for the channel.
Defines the behaviour of the output on activating the forced operation.
Defines the behaviour of the output on deactivat­ing the forced operation. Only visible when the priority for the forced operation is 0.
Specifies the priority for recalling and removing a scene of Wind alarm type for the channel.
Activate wind alarm brightness
0…100 % Basic setting: 0 %
value
Deactivate wind alarm brightness
0…100 % Basic setting: 0 %
value
Priority, sun pro­tection
Activate sun pro­tection brightness
0...4 Basic setting: 0
0…100 % Basic setting: 100 %
value
Deactivate sun protection bright-
0…100 % Basic setting: 0 %
ness value
Priority, twilight 0...4
Basic setting: 0
Activate twilight brightness value
Deactivate twi­light brightness
0…100 % Basic setting: 100 %
0…100 % Basic setting: 0 %
value
Defines the behaviour of the output on activating the wind alarm.
Defines the behaviour of the output on deactivat­ing the wind alarm. Only visible when the priority for the wind alarm is 0.
Specifies the priority for recalling and removing a scene of type Sun protection for the channel.
Defines the behaviour of the output on activating the sun protection.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Specifies the priority for recalling and removing a scene of type Twilight for the channel.
Defines the behaviour of the output on activating the twilight function.
Defines the behaviour of the output on deactivat­ing the twilight function. Only visible when the pri­ority for the twilight function is 0.
Basic light func­tion
Hotel function, Off Basic setting: Off
If the hotel function is activated, the system will dim to "Hotel function brightness" when a switch­off command is made. Switch-off is only possible with a forced position command. Note: If the min­imum brightness is set to greater than "Hotel
32597903 07.08.2019 J0082597903
17 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Brightness hotel function
0.4 ... 100 % Basic setting: 20 %
Channel settings "3-wire extension"
Parameters Setting options, Basic
setting
Switch-on delay 0 s … 24 h
Basic setting: 0 s
Switch-off delay 0 s … 24 h
Basic setting: 0 s
Explanations
function brightness", then the system dims to the set minimum brightness when the hotel function is activated.
Brightness to which the light is switched when the hotel function is activated, if switched off. The percentage value refers to the maximum bright­ness.
Explanations
The load switches on after a delay. Repeated switch-on commands restart the delay time. If the load has not yet been switched on due to the delay when a switch-off command comes, then the load will remain off.
The load switches off after a delay. Repeated switch-off commands restart the delay time. If the load has not yet been switched off due to the delay when a switch-on command comes, then the load will remain on.
Extended channel settings "3-wire extension"
Parameters Setting options, Basic
setting
Operating mode Normal operation
Continuous on Continuous off Basic setting: Normal Operation
Manual commis­sioning
On, Off Basic setting: On
Local Operation On, Off
Basic setting: On
Channel settings "Venetian blind"
Parameters Setting options, Basic
setting
Venetian blind ventilation posi-
0 ... 100 % Basic setting: 0 %
tion
Slats ventilation position
0 ... 100 % Basic setting: 0 %
Explanations
See Device and channels.
Blocks manual commissioning for the device channel. In the "Off" setting, the device cannot be reset to the factory setting.
Blocks the output for operation using the button.
Explanations
Position, in which the curtain stops as a ventila­tion position when moving down.
Slat position set by a Venetian blind in the ventil­ation position.
Operating hours,Up0...65535
Basic setting: Current value
The time is counted during which the load is switched on (relay contact closed). This para­meter can be reset to "0", for example after ex­changing the load.
32597903 07.08.2019 J0082597903
18 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Operating hours, Down
0...65535 Basic setting: Current value
Extended channel settings "Venetian blind"
Parameters Setting options, Basic
setting
Operating mode Roller shutter
Venetian blind Awning Basic setting: Roller shutter
Manual commis­sioning
On, Off Basic setting: On
Explanations
The Reset button is used to reset the counter to "0". The device must be programmed to apply the change.
The time is counted during which the load is switched on (relay contact closed). This para­meter can be reset to "0", for example after ex­changing the load. The Reset button is used to reset the counter to "0". The device must be programmed to apply the change.
Explanations
See Device and channels.
Blocks manual commissioning for the device channel. In the "Off" setting, the device cannot be reset to the factory setting.
Local Operation On, Off
Basic setting: On
Running time 1 ... 600 sec
Basic setting: 120 s
Slat change-over time/fabric­stretching time
0 ms ... 10 sec 300 ms … 10 s Basic setting: 0 ms / 300 ms
Minimum change-over-time
Invert movement direction
Behaviour on voltage return
300 ms ... 10 sec Basic setting: 1 s
On, Off Basic setting: Off
No change Configured value Basic setting: No change
Configured vene­tian blind position
0 ... 100 % Basic setting: 0 %
Blocks the output for operation using the button.
Absolute time which the blind/shutter requires from the top to the bottom end position. The entry is essential if scene or position movements are to occur.
Absolute time for changing-over Venetian blind slats. The fabric stretching time can also be set here for the Awning operating mode.
Minimum interruption time when changing direc­tions. Increasing the minimum change-over time will cause less wear on the motors.
Inverts the activation of the relay outputs. During inverted operation, the relay outputs "Up" and "Down" should be activated in reverse. This is re­quired, for example, for controlling skylights.
Defines the behaviour of the output after voltage return. RMD design: Bus voltage return.
If the "Configured position" value is entered for the parameter "Behaviour after voltage return", then the blind/shutter position set here is ap­proached.
Configured slat position
0 ... 100 % basic setting: 0 %
If the "Configured position" value is entered for the parameter "Behaviour after voltage return", then the slat position set here is approached.
32597903 07.08.2019 J0082597903
19 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Behaviour after the end of the disabling function
no change Last value Down up Basic setting: No change
Manual saving of the scene values
Disable wind alarm via exten-
On, Off Basic setting: On
On, Off Basic setting: Off
sion
Priority, lock-out protection
Activate lock-out protection blind
0...4 Basic setting: 1
0 ... 100 % Basic setting: 0 %
position
Explanations
Behaviour of the output when a block is removed.
Disables the saving of the current Venetian blind position as scene value in an actuator for a com­mand via a transmitter.
If the function is switched on, the UP signal no longer has increased priority via an extension and can be stopped via local control or radio con­trol.
Note: In order to be able to use the wind alarm function via the extension, this function must be switched on.
Specifies the priority for recalling and removing a scene of type Lock-out protection for the channel.
Defines the behaviour of the output on activating the lock-out protection.
Activate lock-out protection slat
0 ... 100 % Basic setting: 0 %
position
Deactivate lock­out protection
0 ... 100 % Basic setting: 0 %
blind position
Deacitvate lock­out protection slat
0 ... 100 % Basic setting: 0 %
position
Priority, restraint 0...4
Basic setting: 2
Activate force op­eration blind posi-
0 ... 100 % Basic setting: 0 %
tion
Recall forced op­eration slat posi-
0 ... 100 % Basic setting: 0 %
tion
Deactivate force operation blind
0 ... 100 % Basic setting: 0 %
position
Defines the slat position of the output on activat­ing the lock-out protection. Only visible when the Venetian blind operating mode is set.
Defines the behaviour of the output on deactivat­ing the lock-out protection. Only visible when the priority for the lock-out protection is 0.
Defines the behaviour of the output on deactivat­ing the lock-out protection. Only visible when the priority for the lock-out protection is 0 and the Venetian blind operating mode is set.
Specifies the priority for recalling and removing a scene of type Restraint for the channel.
Defines the behaviour of the output on activating the forced operation.
Defines the slat position of the output on activat­ing forced operation. Only visible when the Vene­tian blind operating mode is set.
Defines the behaviour of the output on deactivat­ing the forced operation. Only visible when the priority for the forced operation is 0.
Deacitvate forced operation slat po­sition
0 ... 100 % Basic setting: 0 %
Defines the slat position of the output on deactiv­ating forced operation. Only visible when the pri­ority for the forced operation is 0 and the Vene­tian blind operating mode is set.
Priority, wind alarm
32597903 07.08.2019 J0082597903
0...4 Basic setting: 3
Specifies the priority for recalling and removing a scene of type Wind alarm for the channel.
20 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Activate wind alarm blind posi-
0 ... 100 % Basic setting: 0 %
tion
Recall wind alarm slat position
Deactivate wind alarm blind posi-
0 ... 100 % Basic setting: 0 %
0 ... 100 % Basic setting: 0 %
tion
Deacitvate wind alarm slat posi-
0 ... 100 % Basic setting: 0 %
tion
Priority, sun pro­tection
Activate sun pro­tection blind posi-
0...4 Basic setting: 0
0 ... 100 % Basic setting: 100 %
tion
Recall sun pro­tection slat posi-
0 ... 100 % Basic setting: 100 %
tion
Explanations
Defines the behaviour of the output on activating the wind alarm.
Defines the slat position of the output on activat­ing the wind alarm. Only visible when the Vene­tian blind operating mode is set.
Defines the behaviour of the output on deactivat­ing the wind alarm. Only visible when the priority for the wind alarm is 0.
Defines the slat position of the output on deactiv­ating the wind alarm. Only visible when the prior­ity for the wind alarm is 0 and the Venetian blind operating mode is set.
Specifies the priority for recalling and removing a scene of type Sun protection for the channel.
Defines the behaviour of the output on activating the sun protection.
Defines the slat position of the output on activat­ing the sun protection. Only visible when the Venetian blind operating mode is set.
Deactivate sun protection blind
0 ... 100 % Basic setting: 0 %
position
Deacitvate sun protection slat
0 ... 100 % Basic setting: 0 %
position
Priority, twilight 0...4
Basic setting: 0
Activate twilight blind position
Activate twilight slat position
Deactivate twi­light blind posi-
0 ... 100 % Basic setting: 100 %
0 ... 100 % Basic setting: 100 %
0 ... 100 % Basic setting: 0 %
tion
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Defines the slat position of the output on deactiv­ating the sun protection. Only visible when the priority for the sun protection is 0 and the Vene­tian blind operating mode is set.
Specifies the priority for recalling and removing a scene of type Twilight for the channel.
Defines the behaviour of the output on activating the twilight function.
Defines the slat position of the output on activat­ing the twilight function. Only visible when the Venetian blind operating mode is set.
Defines the behaviour of the output on deactivat­ing the twilight function. Only visible when the pri­ority for the twilight function is 0.
32597903 07.08.2019 J0082597903
21 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Deacitvate twi­light slat position
0 ... 100 % Basic setting: 0 %
Channel settings "Switching + fan"
Parameters Setting options, Basic
setting
Switch-off delay 0 s … 24 h
Basic setting: 0 s
Run-on time 0 s … 24 h
Basic setting: 0 s
Explanations
Defines the slat position of the output on deactiv­ating the twilight function. Only visible when the priority for the twilight function is 0 and the Vene­tian blind operating mode is set.
Explanations
The load switches off after a delay. Repeated switch-off commands restart the delay time. If the load has not yet been switched off due to the delay when a switch-on command comes, then the load will remain on.
If a run-on time is entered and the "Use run-on time" parameter is activated, the actuator no longer remains permanently switched on, but only for the duration of the run-on time entered here or transmitted by a motion detector. The run-on time is restarted if actuation is repeated.
A motion detector command without transmitted run-on time (e.g. from an extension) leads to switching on for the duration of the run-on time entered here. If no run-on time is entered here, the default run-on time of 2 minutes is applied.
Use run-on time On, Off
Basic setting: Off
Manual switch-off of the run-on time
On, Off Basic setting: Off
On: If a run-on time is configured (≠ 0 s), in addition to motion detector commands, all switching or dimming commands also lead to switching on for the duration of the run-on time.
If no run-on time is configured (= 0 s), all switch­ing or dimming commands result in permanent switching of the load. As soon as the attachment receives a motion de­tector command, the transmitted run-on time is automatically entered in the "Run-on time" para­meter and this then also applies to all switching and dimming commands.
Off: Only motion detector commands lead to switch­ing on for the duration of the transmitted or set run-on time. The load is permanently switched for switching and dimming commands.
Allows manual switch-off of a running run-on time. If the parameter is switched off, then a switch-off command will also switch the actuator on. Only visible if a run-on time was set.
Switch off switch­on delay, output 2
On, Off Basic setting: On
With 2-channel inserts, this allows you to switch off the switch-on delay of output 2. If this is switched off, output 2 is simultaneously switched on with output 1.
32597903 07.08.2019 J0082597903
22 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Switch-on delay, output 2
Switch-off delay, output 2
Operating hours, output 1
0 s … 24 h Basic setting: 2 min
0 s … 24 h Basic setting: 5 min
0...65535 Basic setting: Current value
Operating hours, output 2
0...65535 Basic setting: Current value
Extended channel settings "Switching + fan"
Parameters Setting options, Basic
setting
Explanations
Switch-on delay for output 2 of a 2-channel in­sert, e.g. for fan control in sanitary facilities.
Switch-off delay for output 2 of a 2-channel in­sert, e.g. for fan control in sanitary facilities.
The time is counted during which the load is switched on (relay contact closed). This para­meter can be reset to "0", for example after ex­changing the load. The Reset button is used to reset the counter to "0". The device must be pro­grammed to apply the change.
The time is counted during which the load is switched on (relay contact closed). This para­meter can be reset to "0", for example after ex­changing the load. The Reset button is used to reset the counter to "0". The device must be pro­grammed to apply the change.
Explanations
Operating mode Switching operation
Push-button operation Flashing Continuous on Continuous off Basic setting: Switching operation
Manual commis­sioning
On, Off Basic setting: On
Local Operation On, Off
Basic setting: On
Behaviour on voltage return
On Off Last value Basic setting: Off
Timer behaviour, voltage return
Off Restart Basic setting: Off
Behaviour after the end of the disabling function
On Off no change Last value Basic setting: No change
See Device and channels.
Blocks manual commissioning for the device channel. In the "Off" setting, the device cannot be reset to the factory setting.
Blocks the output for operation using the button.
Defines the behaviour of the output after voltage return.
Specifies whether an active switch-on delay, switch-off delay or run-on time remains off or re­starts after voltage return. Directly connected to the parameters "Switch-on delay", "Switch-off delay" and "Run-on time".
Behaviour of the output when a block is removed.
Manual saving of the scene values
On, Off Basic setting: On
Disables the saving of the current actuator state (On/Off) as scene value in an actuator for a com­mand via a transmitter.
32597903 07.08.2019 J0082597903
23 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Switch-off warn­ing
Priority, lock-out protection
Activate lock-out protection switch-
On, Off Basic setting: Off
0...4 Basic setting: 1
On, Off Basic setting: Off
ing state
Deactivate lock­out protection
On, Off Basic setting: Off
switching state
Priority, restraint 0...4
Basic setting: 2
Activate forced operation switch-
On, Off Basic setting: On
ing state
Explanations
If the switch-off warning is active, the light is not switched off directly. The light briefly goes off 30, 20 and 10 seconds before permanent switch-off. During the switch-off warning, a switch-on com­mand activates direct switch-on. It is not possible to terminate the time by using a switch-off com­mand.
Specifies the priority for recalling and removing a scene of type Lock-out protection for the channel.
Defines the behaviour of the output on activating the lock-out protection.
Defines the behaviour of the output on deactivat­ing the lock-out protection. Only visible when the priority for the lock-out protection is 0.
Specifies the priority for recalling and removing a scene of type Restraint for the channel.
Defines the behaviour of the output on activating the forced operation.
Deactivate forced operation switch-
On, Off Basic setting: Off
ing state
Priority, wind alarm
Activate wind alarm switching
0...4 Basic setting: 3
On, Off Basic setting: Off
state
Deactivate wind alarm switching
On, Off Basic setting: Off
state
Priority, sun pro­tection
Activate sun pro­tection switching
0...4 Basic setting: 0
On, Off Basic setting: On
state
Deactivate sun protection switch-
On, Off Basic setting: Off
ing state
Priority, twilight 0...4
Basic setting: 0
Defines the behaviour of the output on deactivat­ing the forced operation. Only visible when the priority for the forced operation is 0.
Specifies the priority for recalling and removing a scene of type Wind alarm for the channel.
Defines the behaviour of the output on activating the wind alarm.
Defines the behaviour of the output on deactivat­ing the wind alarm. Only visible when the priority for the wind alarm is 0.
Specifies the priority for recalling and removing a scene of type Sun protection for the channel.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Specifies the priority for recalling and removing a scene of type Twilight for the channel.
Activate twilight switching state
Deactivate twi­light switching state
Invert switching output
32597903 07.08.2019 J0082597903
On, Off Basic setting: On
On, Off Basic setting: Off
On, Off Basic setting: Off
Defines the behaviour of the output on activating the twilight function.
Defines the behaviour of the output on deactivat­ing the twilight function. Only visible when the pri­ority for the twilight function is 0.
Inverts the switching output from NO contact function (factory setting) to NC contact function
24 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Minimum switch­ing repeat time
100 ms ... 10 sec Basic setting: 100 ms
Channel settings "2-wire switching"
Parameters Setting options, Basic
setting
Switch-on delay 0 s … 24 h
Basic setting: 0 s
Switch-off delay 0 s … 24 h
Basic setting: 0 s
Explanations
Limits the switching speed of the device by in­creasing the value, in order to protect the load, for example. Only when the set time has elapsed is switching possible again. The last command during the blocking time is executed after a delay. The switching repeat time starts after each switching operation.
Explanations
The load switches on after a delay. Repeated switch-on commands restart the delay time. If the load has not yet been switched on due to the delay when a switch-off command comes, then the load will remain off.
The load switches off after a delay. Repeated switch-off commands restart the delay time. If the load has not yet been switched off due to the delay when a switch-on command comes, then the load will remain on.
Run-on time 0 s … 24 h
Basic setting: 0 s
Use run-on time On, Off
Basic setting: Off
If a run-on time is entered and the "Use run-on time" parameter is activated, the actuator no longer remains permanently switched on, but only for the duration of the run-on time entered here or transmitted by a motion detector. The run-on time is restarted if actuation is repeated.
A motion detector command without transmitted run-on time (e.g. from an extension) leads to switching on for the duration of the run-on time entered here. If no run-on time is entered here, the default run-on time of 2 minutes is applied.
On: If a run-on time is configured (≠ 0 s), in addition to motion detector commands, all switching or dimming commands also lead to switching on for the duration of the run-on time.
If no run-on time is configured (= 0 s), all switch­ing or dimming commands result in permanent switching of the load. As soon as the attachment receives a motion de­tector command, the transmitted run-on time is automatically entered in the "Run-on time" para­meter and this then also applies to all switching and dimming commands.
Off: Only motion detector commands lead to switch­ing on for the duration of the transmitted or set run-on time. The load is permanently switched for switching and dimming commands.
32597903 07.08.2019 J0082597903
25 / 29
LB management
eNet radio centre plate
Parameters Setting options, Basic
setting
Manual switch-off of the run-on time
On, Off Basic setting: Off
Operating hours 0...65535
Basic setting: Current value
Extended channel settings "2-wire switching"
Operating mode Switching operation
Push-button operation Flashing Continuous on Continuous off Basic setting: Switching operation
Manual commis­sioning
On, Off Basic setting: On
Explanations
Allows manual switch-off of a running run-on time. If the parameter is switched off, then a switch-off command will also switch the actuator on. Only visible if a run-on time was set.
The time is counted during which the load is switched on (relay contact closed). This para­meter can be reset to "0", for example after ex­changing the load. The Reset button is used to reset the counter to "0". The device must be pro­grammed to apply the change.
See Device and channels.
Blocks manual commissioning for the device channel. In the "Off" setting, the device cannot be reset to the factory setting.
Local Operation On, Off
Basic setting: On
Behaviour on voltage return
On Off Last value Basic setting: Off
Timer behaviour, voltage return
Off Restart Basic setting: Off
Behaviour after the end of the disabling function
On Off no change Last value Basic setting: No change
Manual saving of the scene values
Switch-off warn­ing
On, Off Basic setting: On
On, Off Basic setting: Off
Blocks the output for operation using the button.
Defines the behaviour of the output after voltage return.
Specifies whether an active switch-on delay, switch-off delay or run-on time remains off or re­starts after voltage return. Directly connected to the parameters "Switch-on delay", "Switch-off delay" and "Run-on time".
Behaviour of the output when a block is removed.
Disables the saving of the current actuator state (On/Off) as scene value in an actuator for a com­mand via a transmitter.
If the switch-off warning is active, the light is not switched off directly. The light briefly goes off 30, 20 and 10 seconds before permanent switch-off. During the switch-off warning, a switch-on com­mand activates direct switch-on. It is not possible to terminate the time by using a switch-off com­mand.
Priority, lock-out protection
32597903 07.08.2019 J0082597903
0...4 Basic setting: 1
Specifies the priority for recalling and removing a scene of type Lock-out protection for the channel.
26 / 29
LB management
eNet radio centre plate
Activate lock-out protection switch-
On, Off Basic setting: Off
ing state
Deactivate lock­out protection
On, Off Basic setting: Off
switching state
Priority, restraint 0...4
Basic setting: 2
Activate forced operation switch-
On, Off Basic setting: On
ing state
Deactivate forced operation switch-
On, Off Basic setting: Off
ing state
Priority, wind alarm
Activate wind alarm switching
0...4 Basic setting: 3
On, Off Basic setting: Off
state
Deactivate wind alarm switching
On, Off Basic setting: Off
state
Defines the behaviour of the output on activating the lock-out protection.
Defines the behaviour of the output on deactivat­ing the lock-out protection. Only visible when the priority for the lock-out protection is 0.
Specifies the priority for recalling and removing a scene of type Restraint for the channel.
Defines the behaviour of the output on activating the forced operation.
Defines the behaviour of the output on deactivat­ing the forced operation. Only visible when the priority for the forced operation is 0.
Specifies the priority for recalling and removing a scene of type Wind alarm for the channel.
Defines the behaviour of the output on activating the wind alarm.
Defines the behaviour of the output on deactivat­ing the wind alarm. Only visible when the priority for the wind alarm is 0.
Priority, sun pro­tection
Activate sun pro­tection switching
0...4 Basic setting: 0
On, Off Basic setting: On
state
Deactivate sun protection switch-
On, Off Basic setting: Off
ing state
Priority, twilight 0...4
Basic setting: 0
Activate twilight switching state
Deactivate twi­light switching
On, Off Basic setting: On
On, Off Basic setting: Off
state
Invert switching output
Minimum switch­ing repeat time
On, Off Basic setting: Off
100 ms ... 10 sec Basic setting: 100 ms
Specifies the priority for recalling and removing a scene of type Sun protection for the channel.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Defines the behaviour of the output on deactivat­ing the sun protection. Only visible when the pri­ority for the sun protection is 0.
Specifies the priority for recalling and removing a scene of type Twilight for the channel.
Defines the behaviour of the output on activating the twilight function.
Defines the behaviour of the output on deactivat­ing the twilight function. Only visible when the pri­ority for the twilight function is 0.
Inverts the switching output from NO contact function (factory setting) to NC contact function
Limits the switching speed of the device by in­creasing the value, in order to protect the load, for example. Only when the set time has elapsed is switching possible again. The last command during the blocking time is executed after a delay. The switching repeat time starts after each switching operation.
32597903 07.08.2019 J0082597903
27 / 29
LB management
eNet radio centre plate
Information window
During channel selection in the Information window, the following settings can be made or val­ues displayed.
"Switching"
Display value Explanations
Load state The load can be switched on or off.
Restraint Display of forced position status.
Local disabling function Shows whether the disabling function has been activated on the
attachment
Operating hours Display of the operating hours since the last restart in the
Settings
window.
"Dimming"
Display value Explanations
Dim brightness value The load can be dimmed using the slider or a brightness value
entry. Only when "Function" is set to "Light (Dimming)".
Load state The load can be switched on or off.
Restraint Display of forced position status.
Local disabling function Shows whether the disabling function has been activated on the
attachment
Operating hours Display of the operating hours since the last restart in the
Settings
window.
"Venetian blind"
Display value Explanations
Position value, venetian
The position value of the Venetian blind can be changed.
blind
Position value, slat The position value of the slat can be changed.
Restraint Display of forced position status.
Lock-out protection Display of the lock-out protection status
Operating hours UP Display of the operating hours in the UP direction since the last
restart in the
Settings
window.
Operating hours DOWN Display of the operating hours in the DOWN direction since the
last restart in the
Settings
window.
"2-wire switching", "Switching + fan"
Display value Explanations
Load state The load can be switched on or off.
Restraint Display of forced position status.
Local disabling function Shows whether the disabling function has been activated on the
attachment
Operating hours Display of the operating hours since the last restart in the
Settings
window.
32597903 07.08.2019 J0082597903
28 / 29
LB management
eNet radio centre plate
Display value Explanations
Operating hours Fan chan­nel
Display of the operating hours since the last restart in the window.
Settings
Only displayed if the fan channel has been configured.

13 Conformity

Albrecht Jung GmbH & Co. KG hereby declares that the radio system type art. no. FM..1701.. meets the directive 2014/53/EU. You can find the full article number on the device. The com­plete text of the EU Declaration of Conformity is available under the Internet address: www.jung.de/ce

14 Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.
ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle GERMANY
Telefon: +49 2355 806-0 Telefax: +49 2355 806-204 kundencenter@jung.de www.jung.de
32597903 07.08.2019 J0082597903
29 / 29
Loading...