This device combines the functions of a KNX/EIB bus coupling unit, a single-room temperature
controller with setpoint specification, and a push-button sensor, in just one bus subscriber. The
combination of these functions makes it possible, for example, to control the light, the blinds,
and the room temperature centrally from the entry area of a room. The room temperature
controller and pushbutton sensor functions are each independent function sections of the device
with their own parameter blocks in the ETS.
The device has 3 control surfaces that can be used to operate the integrated room temperature
controller and the pushbutton sensor. The functions can be configured in the ETS. Optionally,
the number of control surfaces can be expanded to include up to 4 additional ones by
connecting an expansion module to the basic unit. Configuration and commissioning of the
expansion module is clearly structured and easy to perform using the application program of the
basic unit.
Pushbutton sensor functionality:
When a rocker or button is pressed, the device transmits telegrams to the KNX/EIB, depending
on the ETS parameter settings. These can be, for instance, telegrams for switching or
pushbutton control, for dimming or for controlling blinds. It is also possible to program value
transmitter functions, such as dimming value transmitters, light scene extensions, temperature
value transmitters or brightness value transmitters.
In connection with a room temperature controller equipped with a 1-byte object for change-over
of operating modes, the device can be used as a full-featured controller extension. The device
can also be used for presence detection or for setpoint shifting purposes and to indicate
different controller states.
The operation concept of a control surface can be configured in the ETS either as a rocker
function or alternatively as a push-button function. With the rocker function, one control surface
is divided into two actuation pressure points with the same basic function. In the push-button
function either a control surface is divided into 2 functionally separate actuation pressure points
(2 buttons), or a control surface is evaluated as single-surface operation (only one button).
With the rocker function and the double-surface push-button function, the button arrangement
can be set either as "vertical" (top-bottom operation) or as "horizontal" (left-right operation) for
each control surface. With the rocker function it is also possible to trigger special functions using
full-surface operation.
The device has two status LEDs for each of the lower control surfaces and for the control
surfaces of the expansion module, which, according to the function of the rocker or button can
be internally connected to the operating function. Each status LEDs can then also signal
completely independent display information, operating states of room temperature controllers or
indicate the results of logic value comparisons, flash or be permanently switched on or off. The
control surface next to the display does not have status LEDs.
Room temperature controller functionality
The device can be used for single-room temperature control. Depending on the operating mode,
the current temperature setpoint and on the room temperature, a command value for heating or
cooling control can be sent to the KNX/EIB for the control circuit. In addition to the heating or
cooling basic level, activating an additional heater and/or cooling unit means that an additional
heating or cooling unit can be used. In this connection, you can set the temperature setpoint
difference between the basic and the additional level by a parameter in the ETS. For major
deviations between the temperature setpoint and the actual temperature, you can activate this
additional level to heat up or cool down the room faster. You can assign different control
Art.-No.: 4093 KRM TS D
Page 4 of 241
Product definition
algorithms to the basic and additional levels.
For heating and cooling functions, you can select continuous or switching PI or switching 2-point
feedback control algorithms.
The room temperature can be recorded either by the internal or by an external temperature
sensor. Combined temperature recording by both sensors can also be configured.
The controller distinguishes between different operating modes (comfort, standby, night, frost/
heat protection) each with their own temperature setpoints for heating or cooling.
General:
A bus coupling unit is already permanently integrated in the device, allowing the device to be
connected directly to the bus cable during commissioning.
When used, an operation LED can either serve as an orientation light (also flashing), or can be
activated via a separate communication object. When the device is in the programming mode,
the operation LED flashes with a frequency of about 8 Hz. The same flashing rate is also used
for indicating that a rocker has been actuated by a press on the full surface. In this case the
LED returns to the programmed behaviour after the operation. If no or a wrong application has
been loaded into the pushbutton sensor, the operation LED flashes with a frequency of about
0.75 Hz to indicate an error. The device does not then work.
2 Installation, electrical connection and operation
2.1 Safety instructions
Electrical devices may only be fitted and installed by electrically skilled persons. The
applicable accident prevention regulations must be observed.
Failure to observe the instructions may cause damage to the device and result in fire and
other hazards.
Make sure during the installation that there is always sufficient insulation between the
mains voltage and the bus. A minimum distance of at least 4 mm must be maintained
between bus conductors and mains voltage cores.
The device may not be opened or operated outside the technical specifications.
Art.-No.: 4093 KRM TS D
Page 7 of 241
2.2 Device components
Installation, electrical connection and operation
picture 1: Device components, front side
(1) LCD with backlighting
(2) Control surfaces (rockers 1...2)
(3) Display control surface (rocker 3)
(4) Status LEDs (2 x per control surface for rockers 1...2)
(5) Operation LED
picture 2: Device components, rear side
(6) Connection for KNX/EIB bus cable
(7) Connection for pushbutton sensor expansion module
Art.-No.: 4093 KRM TS D
Page 8 of 241
Installation, electrical connection and operation
2.3 Fitting and electrical connection
DANGER!
Electrical shock on contact with live parts in the installation environment.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
DANGER!
When mounting with 230 V devices under a common cover, e.g. socket outlets,
there is a danger of electrical shocks in the event of a fault!
Electrical shocks can be fatal.
Do not install any 230 V devices in combination with a pushbutton expansion
module under a common cover!
Snapping on the adapter frame
An adapter frame is required for the CD design. The adapter frame must be snapped onto the
continuous controller module before the device is connected and fastened to the wall.
o With the adapter frame (10) in the correct orientation, snap it from the front onto the
i Recommended installation height: 1.50 m.
i The installation of the supporting frame depends on the design used.
Supporting frame side "A" to the front for switch design ranges A, CD and FD.
Supporting frame side "B" to the front for switch design range LS.
o Mount supporting frame (8) in the right orientation on an appliance box. Note marking TOP;
marking "A" or "B" in front. Use the enclosed box screws (12).
o Position the design frame (9) on the supporting frame.
o Connect the continuous controller module (11) with KNX connection terminal (14), which is
connected to the KNX bus cable, on the rear side of the module. Run the connecting cable
downwards from the continuous controller module and then into the appliance box from the
rear.
o Push continuous controller module onto the supporting frame.
o Fasten the continuous controller module to supporting frame using the enclosed plastic
screws (13). Tighten the plastic screws only lightly.
o Before mounting the control surfaces (15), load the physical address into the device (see
chapter 2.4. Commissioning).
Art.-No.: 4093 KRM TS D
Page 10 of 241
Installation, electrical connection and operation
Fitting and connecting continuous controller module with pushbutton sensor expansion
module
picture 4: Fitting the pushbutton sensor expansion module (example of combined fitting)
(7) Connection point in continuous controller module for connecting cable of the expansion
module
(9) Design frame
(11) Continuous controller module
(12) Box screws
(13) Fastening screws
(15) Design control surfaces for the continuous controller module
(16) Design control surfaces for the expansion module
(17) Large supporting frame for combined fitting of continuous controller module and expansion
module
(18) Pushbutton sensor expansion module
(19) Connecting cable for pushbutton sensor expansion module with plug
Art.-No.: 4093 KRM TS D
Page 11 of 241
Installation, electrical connection and operation
i The installation of the supporting frame depends on the design used.
Supporting frame side "A" to the front for switch design ranges A, CD and FD.
Supporting frame side "B" to the front for switch design range LS.
One pushbutton sensor expansion module can be connected to each continuous controller
module. For combined fitting of an expansion module directly underneath the continuous
controller module, the large supporting frame (17) must be fitted (picture 4). The large
supporting frame is contained in the scope of supply of the pushbutton sensor expansion
module.
For combined fitting on just a single appliance box, fit the continuous controller module with the
KNX bus connection in the appliance box and countersink the fixing screws of the expansion
module in the wall, for example using Ø 6 x 10 mm boreholes. The large supporting frame can
be used as a template for this.
i Recommended installation height for the continuous controller module: 1.50 m.
The expansion module can be installed in a separate box with the extension (see
accessories) at a height of 1.10 m. The extension must be routed through a pipe. In this
installation a separate small supporting frame is used for the expansion module (included
in the scope of supply for the extension).
o For combined fitting underneath the continuous controller module: Fit large supporting
frame (17) in the right orientation on an appliance box. Note marking TOP; marking "A" or
"B" in front. Use the enclosed box screws (12).
For individual fitting of the expansion module at 1.10 m: Fit small supporting frames for the
continuous controller module and for the expansion module in the right orientation on two
appliance boxes. Note marking TOP; marking "A" or "B" in front. Use the enclosed box
screws (12).
o Position the design frame (9) on the supporting frame(s).
o For combined fitting underneath the continuous controller module: Fit pushbutton sensor
expansion module (18) in the large supporting frame. Route connecting cable (19) between
supporting frame and intermediate web.
For individual fitting of the expansion module at 1.10 m: Fit pushbutton sensor expansion
module (18) in separate small supporting frame. Guide connecting cable (19) through a
pipe into the box of the continuous controller module.
o With the plug of the connecting cable in the right orientation, insert it into the connection
point in the continuous controller module (7). When doing so, ensure that the connecting
cable is not pinched.
o Connect the continuous controller module (11) with KNX connection terminal, which is
connected to the KNX bus cable, on the rear side of the module. Run the connecting cable
downwards from the continuous controller module and then into the appliance box from the
rear.
o Push continuous controller module onto the supporting frame.
o Fasten module to supporting frame using the enclosed plastic screws (13). Tighten the
plastic screws only lightly.
o Mount the control surfaces on the pushbutton sensor expansion module (16). Before
mounting the control surfaces on the continuous controller module (15), load the physical
address into the device (see chapter 2.4. Commissioning).
Art.-No.: 4093 KRM TS D
Page 12 of 241
Installation, electrical connection and operation
2.4 Commissioning
After the device has been connected to the bus and mounted on the wall, it can be put into
operation. Commissioning is basically confined to programming with the ETS and attaching the
decorative control surfaces.
Assignment of the physical address
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
The device has an integrated bus coupling unit. It has no separate programming button or LED.
Programming mode is activated by a defined and time-delayed press on the first rocker and
signalled by the operation LED. To program the physical address, the decorative control
surfaces must not be in place on the device.
The physical address is programmed as described below...
picture 5: Buttons for activating Programming mode
o Activate Programming mode. Press button at the top left of rocker 1 (20) and keep it
depressed (picture 5). Then press the second button at the bottom right of rocker 1 (21).
Programming mode is activated. The operation LED (5) flashes quickly (approx. 8 Hz).
"Prog" is shown on the display of the device.
i Use suitable objects to push the buttons (e.g. thin screwdriver, tip of a ballpoint pen, etc.)
i To exclude any inadvertent activation of Programming mode during a 'normal' use of the
control surface in later operation, the time between the first and the second button
actuation must be at least 200 ms. Pressing both buttons simultaneously (time between
first and second actuation < 200 ms) will not result in an activation of Programming mode.
i It should be noted that the operation LED also flashes quickly in the case of a full-surface
operation of rocker 1 (see functional description). The difference from quick flashing in
programming mode is that with a full-surface operation the rocker of the LED returns to the
parameterized basic state when the buttons are released. In programming mode, flashing
continues until the operating mode is ended. The state of the LED defined by Programming
mode will always prevail.
o Program the physical address with the help of the ETS.
Art.-No.: 4093 KRM TS D
Page 13 of 241
Installation, electrical connection and operation
The operation LED switches back to the previous status (off, on or flashing slowly).
i If Programming mode is to be activated or deactivated in a device which is already
programmed with a valid application, there is the possibility that telegrams will be
transmitted to the bus at the time the button is pressed. The telegram transmitted depends
on the push-button function programmed.
i The expansion module does not receive any physical address of its own. It is activated by
the application program loaded in the continuous controller module.
Programming the application
The application must then be programmed into the device with the help of the ETS. The ETS3.0
from version "d" onwards detects automatically whether a valid application has already been
programmed into the device before. To reduce the programming time, the ETS3 downloads the
whole application only if the device was programmed beforehand with another application or
with no application at all. In all other cases, the ETS makes a time-optimised partial download in
which only the modified data is loaded into the device. For commissioning. it is recommended to
use the ETS3.0 from Version d Patch A onwards.
i The expansion module does not receive any physical address of its own. It is activated by
the application program loaded in the continuous controller module.
Installing the decorative control surfaces
The decorative control surfaces are available as a complete set of buttons. Individual buttons or
the complete set of buttons can be replaced using buttons with symbols.
The design control surfaces are not included in the scope of supply of the continuous controller
module or the pushbutton sensor expansion module. These must be ordered specially
according to the required design.
The physical address of the continuous controller module must be programmed in the device in
advance.
o Place control surfaces on the continuous controller module in the right orientation and also
on the pushbutton sensor expansion module (if used), and snap in with a short push. Note
marking TOP.
i To simplify installation, a complete set of buttons is fitted with a mounting spider at the
factory. This mounting spider is not essential for installing the decorative control surfaces,
meaning that it is not required when adding symbol buttons to the button panel.
Art.-No.: 4093 KRM TS D
Page 14 of 241
Installation, electrical connection and operation
2.5 Operation
The device consists of three mechanically separate control surfaces. The control surfaces are
the design covers attached to the device with push-button elements underneath. A distinction is
made between the display control surface (23) and the control surfaces of the pushbutton
sensor function (22) (picture 6).
picture 6: Arrangement of the control surfaces on the front of the device
(22) Pushbutton sensor control surfaces (rocker 1 left / rocker 2 right) incl. 4 status LEDs
Function: Any desired pushbutton sensor function or controller operation, operation of the
second display operating level
(23) Display control surface (rocker 3)
Function: Any desired pushbutton sensor function or controller operation
The lower control surfaces (rockers 1 & 2) are allocated to the pushbutton sensor function. The
function of these rockers can also be configured in the ETS to any desired pushbutton sensor
function. Alternatively it is possible to set operation of the integrated room temperature
controller. It is also possible to activate and operate the second display operating level via
button evaluation of these surfaces (see chapter 2.5.2. Second operating level).
The display is surrounded by the upper display control surface (rocker 3). The function of this
surface can also be configured in the ETS to any desired pushbutton sensor function.
Alternatively the room temperature controller can be operated.
The pushbutton sensor function is an independent function section of the device with its own
parameter blocks in the ETS. Insofar as the control surfaces are to operate the integrated room
temperature controller, the following functions can be parameterised in the pushbutton
configuration: setpoint shift, presence button, operating mode change-over, fan control. For a
more detailed description of the operating functions, please see Chapter 4. of this
documentation.
The operation concept of a control surface can be configured in the ETS either as a rocker
function or alternatively as a push-button function. With the rocker function, one control surface
is divided into two actuation pressure points with the same basic function. In the push-button
function either a control surface is divided into 2 functionally separate actuation pressure points
(2 buttons), or a control surface is evaluated as single-surface operation (only one large button).
If a control surface is used as a single rocker function, then it is also possible to trigger special
functions using full-surface operation.
With the rocker function and the double-surface push-button function, the button arrangement
can be set either as "vertical" or as "horizontal" for each control surface. The variable
specification of the button arrangement does not, however, apply to operation of the second
display operating level via rockers 1 & 2. There the button arrangement is fixed (see chapter
2.5.2. Second operating level).
Art.-No.: 4093 KRM TS D
Page 15 of 241
Installation, electrical connection and operation
Optionally, the number of control surfaces can be expanded to include up to 4 additional ones
by connecting an expansion module to the continuous controller module. Configuration and
commissioning of the expansion module is clearly structured and easy to perform using the
application program of the continuous controller module. The control surfaces of the expansion
module can be set in the ETS to any desired pushbutton sensor function, or also to controller
operation.
Between the lower control surfaces of the continuous controller module (rockers 1 & 2) there
are 4 red status LEDs, 2 for each rocker. These status LEDs can be internally connected to the
operating function according to the function of the rocker or pushbuttons, thus indicating the
operating status directly. They may, however, also be used for signalling completely
independent functions or be permanently on or off.
The operation LED can also signal the switching state of its own object, flash or be permanently
on or off. Besides functions that can be set using the ETS, the operation LED also indicates that
the device is in the programming mode for commissioning or diagnosis purposes.
2.5.1 Basic display
During device operation, the basic display of the display can show up to four different display
functions. This means that is possible to display the time, the setpoint temperature, the actual
temperature (room temperature) or the outdoor temperature (picture 7). The information is
shown separately on the display. It is possible to change over between the information
automatically after set times or in a controlled manner by pressing a button on the device.
These properties, and the actually visible display information, are configured in the ETS before
the device is commissioned (see chapter 4.2.4.5. Display).
picture 7: Possible display information of the basic display
(24) Time display (with flashing seconds mark ":")
(25) Actual temperature display (room temperature)
(26) Setpoint temperature display
(27) Outdoor temperature display
i The temperatures can be displayed in °C or alternately in °F. The display format can be
configured in common for all temperature values in the ETS.
Art.-No.: 4093 KRM TS D
Page 16 of 241
Installation, electrical connection and operation
2.5.2 Second operating level
The second operating level makes it possible to make various basic settings on the unit locally
without using the ETS. In order to avoid the unintentional disruption of essential functions,
access to individual settings or to the entire second operating level can be prevented via the
parameterisation in the ETS. An active button disable also disables access to the second
operating level.
Calling up the second operating level
The second operating level is called up by pressing buttons 1 and 3 on the device
simultaneously(picture 8). It must be ensured here that the control surfaces are pressed at the
upper left corner in order to be independent of the configured button arrangement.
The device leaves the second operating level again when buttons 1 and 3 are pressed again
simultaneously. Depending on the setting of the ETS parameter "Save changes after manual
exit?" all settings that have been made are saved or discarded in this case. The parameters
"Automatic exit of the second operating level", "Time until automatic exit" and "Save changes?"
define whether the device terminates the second operating level automatically if no entries are
made, and whether in this case all of the changed settings are saved or discarded (see "Exiting
the second operating level").
picture 8: Button combination to call up the second operating level
Operation in the second operating level
The settings in the second operating level are organised in a ring-shaped menu. This is shown
in the display. Selection and settings are performed using the 1...4 buttons of the device
(picture 9). Within the second operating level the button arrangement of the control surfaces is
preset to "top / bottom" independently of the ETS configuration, and cannot be changed.
Moreover, buttons 1...4 are always available for operation of the second operating level,
independently of any single-surface operation configured in the ETS.
The four buttons have the following functions...
Button 1: + change-over or value change in positive direction
Button 2: - change-over or value change in negative direction
Button 3: n Jump to the previous menu entry
Button 4: o Jump to the next menu entry
Art.-No.: 4093 KRM TS D
Page 17 of 241
Installation, electrical connection and operation
i Continuous adjustment of the value settings is possible if buttons 1 or 2 are held in the
depressed position.
picture 9: Button assignment for operation in the second operating level
Configuration in the ETS offers various options for influencing the entries that are visible and
changeable in the menu...
1. If entries are configured via parameterisation as "hidden", they do not appear in the menu.
This setting is performed in the ETS separately for various menu entries in the parameter node
"General -> Second operating level" Some entries are always visible and can thus not be
configured as invisible in the ETS. When the device functions as a controller extension,
controller settings (setpoint temperatures, setpoint shifting, operating mode, fan control) are
fundamentally not accessible in the second operating level.
2. The setpoint temperatures of the continuous controller can either be changeable, or can
alternatively only show the current value and thus not be editable. This setting is performed in
the ETS in the parameter node "Room temperature control -> Controller general -> Second
operating level".
The menu entry that is shown as the first entry when the second operating level is called up can
be selected in the ETS using the parameter "First menu item in second operating level". The
sequence of the subsequent entries is then fixed as shown below.
The following menu functions can be called up in the second operating level, if not explicitly
disabled in the ETS. The symbols shown in the display indicated which function or which
temperature value is displayed or set.
Setting the basic temperature ("Continuous controller" menu):
picture 10: Setting the basic temperature
The + and - buttons can be used to adjust the basic temperature in increments of +/- 1 K. The
symbols ó and ÿ light up in the display. The basic temperature is displayed flashing as an
absolute value in °C or °F (parameter-dependent).
The basic temperature designates the comfort setpoint temperatures for heating and cooling,
depending on the configured operating mode. With "Heating only" it sets the setpoint
Art.-No.: 4093 KRM TS D
Page 18 of 241
Installation, electrical connection and operation
temperature for comfort heating directly. With "Cooling only", on the other hand, it sets the
setpoint temperature for comfort cooling. With "Heating and cooling" the basic setpoint sets the
setpoint temperature for heating directly or indirectly depending on the deadband position. The
setpoint temperature for cooling is then derived from this, taking the deadband into account.
(see chapter 4.2.4.2.5. Temperature setpoints)
The menu entry "Basic temperature" is visible as an option as a component of the "Continuous
controller" menu. The editing function can be disabled separately. This menu is not accessible
in controller extensions.
Setting the setpoint temperature "Lowering for standby mode, heating" ("Continuous controller"
menu):
picture 11: Setting the setpoint temperature "Lowering for standby mode, heating"
The + and - buttons can be used to adjust the temperature decrease for standby mode for
heating with an increment of +/- 0.1 K. The symbols ô and â light up in the display. The
temperature decrease is displayed flashing as a relative value in K.
The menu entry "Setpoint temperature lowering standby" is visible as an option as a component
of the "Continuous controller" menu. The editing function can be disabled separately. This menu
is not accessible in controller extensions.
Setting the setpoint temperature "Raising for standby mode, cooling" ("Continuous controller"
menu):
picture 12: Setting the setpoint temperature "Raising for standby mode, cooling"
The + and - buttons can be used to adjust the temperature increase for standby mode for
cooling with an increment of +/- 0.1 K. The symbols ô and è light up in the display. The
temperature increase is displayed flashing as a relative value in K.
The menu entry "Setpoint temperature raising standby" is visible as an option as a component
of the "Continuous controller" menu. The editing function can be disabled separately. This menu
is not accessible in controller extensions.
Setting the setpoint temperature "Lowering for night mode, heating" ("Continuous controller"
menu):
picture 13: Setting the setpoint temperature "Lowering for night mode, heating"
Art.-No.: 4093 KRM TS D
Page 19 of 241
Installation, electrical connection and operation
The + and - buttons can be used to adjust the temperature decrease for night mode for heating
with an increment of +/- 0.1 K. The symbols õ and â light up in the display. The temperature
decrease is displayed flashing as a relative value in K.
The menu entry "Setpoint temperature lowering night" is visible as an option as a component of
the "Continuous controller" menu. The editing function can be disabled separately. This menu is
not accessible in controller extensions.
Setting the setpoint temperature "Raising for night mode, cooling" ("Continuous controller"
menu):
picture 14: Setting the setpoint temperature "Raising for night mode, cooling"
The + and - buttons can be used to adjust the temperature increase for night mode for cooling
with an increment of +/- 0.1 K. The symbols õ and è are illuminated in the display. The
temperature increase is displayed flashing as a relative value in K.
The menu entry "Setpoint temperature raising night" is visible as an option as a component of
the "Continuous controller" menu. The editing function can be disabled separately. This menu is
not accessible in controller extensions.
Setting presence mode ("Presence" menu):
picture 15: Setting presence mode
A "P" is shown in the display to indicate that the presence mode can be edited. The symbols
additionally shown in the display identify the active operating mode of the internal room
temperature controller. Depending on this, presence mode can be adjusted as follows using the
+ and - buttons...
"Comfort" operating mode active:
No setting of presence mode is possible. The ó symbol lights up statically.
"Standby" operating mode active:
The buttons + or - can be used to change over the operating mode between Comfort ó and
Standby ô. In each case, the symbols activated by the Presence operating mode flash.
"Night" operating mode active:
The buttons + or - can be used to change over the operating mode between Night õ and
Comfort extension óõ. In each case, the symbols activated by the Presence operating mode
flash.
"Frost/heat protection" operating mode active:
The buttons + or - can be used to change over the operating mode between Frost/heat
protection ö and Comfort extension óö. In each case, the symbols activated by the Presence
operating mode flash.
i The comfort extension cannot be activated using the presence function in the second
operating level if the frost/heat protection has been activated via the window status!
Art.-No.: 4093 KRM TS D
Page 20 of 241
Installation, electrical connection and operation
i In the second operating level, presence mode and operating mode (see "Setting the
operating mode" below) may never be changed at the same time before a "save"
command. Otherwise the presence status is always reset, and thus the manual setting may
not be applied. If the controller operating mode and the presence mode have to be
changed, first the operating mode has to be changed and the setting has to be saved. Only
after that is it possible to change the presence mode and save this setting by calling up the
second operating level again.
The menu entry "Presence" is visible as an option. This menu is not accessible in controller
extensions.
Setting the setpoint shift ("Setpoint shift" menu):
picture 16: Setting the setpoint shift
The menu entry for setpoint shifting is indicated in the display by the bar scale "- - - - 0 - - - -".
The buttons + and - can be used to adjust the basic setpoint shift by up to 4 levels. Here the
shift is shown in the display as a relative numeric value in kelvin (K)
The increment of the shift depends on the ETS parameter "Increment of the 4-level setpoint
shift" in the parameter branch "Room temperature controller -> Controller general -> Setpoints".
i A setpoint shift cannot be saved when the second operating level is exited if the frost/heat
protection is activated in the controller! In this case the settings of the setpoint shift in the
second operating level are lost.
The menu entry "Setpoint shift" is visible as an option. This menu is not accessible in controller
extensions.
Setting the operating mode ("Operating mode" menu):
picture 17: Setting the operating mode
The buttons + and - can be used to adjust the controller operating mode. The symbol for the
active operating mode flashes in the display. The modes that can be set are "Comfort" ó,
"Standby" ô, "Night" õ and "Frost/heat protection" ö.
It should be noted that a set operating mode with a low priority cannot be activated immediately
when the second operating level is exited if an operating mode with a higher priority (e.g. frost
protection via window status) has been specified by the controller (see chapter 4.2.4.2.4.
Operating mode change-over). The operating mode set in the second operating level is only
accepted by the controller when the operating mode with a higher priority has been terminated
and in the meantime no other operating mode specification with a higher priority has been
performed (e.g. via operation of a pushbutton sensor or via communication objects).
The menu entry "Operating mode" is visible as an option. This menu is not accessible in
controller extensions.
Art.-No.: 4093 KRM TS D
Page 21 of 241
Installation, electrical connection and operation
Fan control ("Fan levels" menu):
picture 18: Fan controller
The + and - buttons can be used to influence the fan operating mode (automatic / manual
mode). In manual mode it is possible to change over the fan level independently of the
controller command values (see chapter 4.2.4.2.8. Fan controller).
When the menu entry "Fan levels" is called up, the fan symbol in the display flashes, and
indicates the current fan level by means of the illuminated arc segments ( ì, í, î etc.). If no
arc segment is illuminated, the fan is switched off. The display also shows whether the fan
controller is in automatic or manual operation. In manual operation the Ü symbol is also
illuminated. The number of illuminated arc segments depends on the number of fan levels
configured.
i In fan control in the second operating level the fan level and automatic mode can be set
directly without taking into account the specific settings of the fan controller (Parameter
"Fan level on change-over to manual", the switch-on level or fan run-on times).
The menu item "Fan levels" is visible as an option, but only if the fan control is also enabled in
the controller for the ETS. This menu is not accessible in controller extensions.
Indicating the time:
picture 19: Indicating the time
Only indication of the current time. No adjustment possibility.
The menu entry "Time" is visible as an option.
Indication of actual temperature:
picture 20: Indication of actual temperature
Only Indication of the current room temperature No adjustment possibility.
The menu entry "Actual temperature" is visible as an option.
Indication of setpoint temperature:
Art.-No.: 4093 KRM TS D
Page 22 of 241
Installation, electrical connection and operation
picture 21: Indication of setpoint temperature
Only indication of the current setpoint temperature. No adjustment possibility.
The menu entry "Setpoint temperature" is visible as an option.
Indicating the outdoor temperature:
picture 22: Indicating the outdoor temperature
Only indication of the current outdoor temperature No adjustment possibility.
The menu entry "Outdoor temperature" is visible as an option.
Setting the display contrast:
picture 23: Setting the display contrast
Illuminate all elements of the display. The buttons + and - can be used to adjust the display
contrast.
The menu item "Display contrast" is always visible.
Setting the display brightness:
picture 24: Setting the display brightness
"H" and the brightness value of the backlighting are displayed in the backlighting. The buttons +
and - can be used to adjust the brightness of the display in the range from 10 to 100%. For
additional notes about control of the backlighting, via the second operating level, please see the
chapter "Display control" (see page 165-166).
The menu item "Display brightness" is always visible.
Exiting the second operating level by pressing Save:
Art.-No.: 4093 KRM TS D
Page 23 of 241
Installation, electrical connection and operation
picture 25: Exiting the second operating level by pressing Save:
"OK" is displayed. The buttons + or - can be used to exit the second operating level with a
"save" command (see "Exiting the second operating level").
This option is always visible.
Exiting the second operating level without saving:
picture 26: Exiting the second operating level without saving
"ESC" is shown on the display. The buttons + or - can be used to exit the second operating level
without saving the settings (see "Exiting the second operating level").
This option is always visible.
i All menu entries are displayed or not depending on the configuration of the ETS. If, for
example, the controller is parameterised only for heating, no setpoints for cooling can be
displayed or set in the menu. When the device functions as a controller extension,
controller settings (setpoint temperatures, setpoint shifting, operating mode, fan control) are
fundamentally not accessible in the second operating level.
If an entry has been parameterised as the first menu item in the ETS that is not accessible
at all due to the other settings, the first possible entry is displayed according to the defined
menu sequence (see above).
i When a menu entry is shown on the display, the setting currently valid in the controller is
identified using the symbols or the display value, if the setting has not already been
changed previously in the second operating level. If the setting has already been changed
and not yet accepted validly (see "Exiting the second operating level"), the last manual
setting will be shown on the display, and not the real state of the controller.
Exiting the second operating level
Settings that have been made in the second operating level are only accepted validly in the
device when the operating level is exited with a "Save" command. It is possible to discard
settings by exiting the second operating level without a "Save" process. When exiting the
second operating level, a distinction is made among the following cases...
- Exiting by means of button combination: The second operating level is exited by pressing
buttons 1 and 3 on the device simultaneously (picture 8). Here the parameter "Save
changes after exiting with button combination?" defines whether the settings are saved or
not when the second operating level is exited using the button combination.
Art.-No.: 4093 KRM TS D
Page 24 of 241
Installation, electrical connection and operation
- Automatic exiting: Automatic exiting of the second operating level can optionally be
configured in the ETS using the parameter of the same name in the parameter branch
"General -> Second operating level". In this case the device leaves the second operating
level when no additional operation takes place after the last push-button operation within
the "Time until automatic exit" configured in the ETS. With automatic exiting it is also
possible to define with the parameter "Save changes after automatic exiting?" whether the
settings are saved or not.
- Exiting with "OK": In the second operating level the menu item "OK" can be selected with
the n or o buttons. The buttons + or - can then be used to exit the second operating level.
All settings are always saved in this case!
- Exiting with "ESC": In the second operating level the menu item "ESC" can be selected
with the n or o buttons. The buttons + or - can then be used to exit the second operating
level. In this case the settings are not saved and are discarded!
Art.-No.: 4093 KRM TS D
Page 25 of 241
Technical data
3 Technical data
General
Safety class III
Mark of approval KNX
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
KNX/EIB supply
KNX medium TP 1
Commissioning mode S mode
Rated voltage KNX DC 21 V ... 32 V SELV
Power consumption KNX typical 150 mW
Connection mode KNX Connection terminal
BAU used: FZE 1066 + µC
KNX/EIB type class: 3b device with cert. Physical layer + stack
Configuration: S mode standard
PEI type: "00"
PEI connector: No connector
Application program:
No. Short description Name Version from mask
Hex
/ "0"
Dec
version
1 Multifunctional room temperature
controller / pushbutton sensor
application:
Up to 3 control surfaces on the
continuous controller module for the
pushbutton sensor function and for
operation of the integrated room
temperature controller. Can be
expanded to include 4 additional
control surfaces using an expansion
module.