Jung 1180 Series, 1180-1 Series Operation Manual

Automatic switch 180° 1.10 m
Light Management
Standard automatic switch 180° 1.10 m
Art.-No.: ..1180..
Universal automatic switch 180° 1.10 m
Art.-No.: ..1180-1..
Operationsmanual
Electrical equipment may only be installed and fitted by electrically skilled persons.
Failure to observe the instructions may cause damage to the device and result in fire and other hazards.
Danger of electric shock. Always disconnect before carrying out work on the devise or load. At the same time, take into account all circuit breakers that supply dangerous voltage to the device or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load is not electrically isolated from the mains even when the device is switched off.
Do not press on the sensor window. Device can be damaged.
The device is not suitable for use as a burglar alarm or other alarm.
These instructions are an integral part of the product, and must remain with the end customer.
2 Device components
picture 1
(1) Flush-mounted insert (2) Frame (3) Motion detector cover (4) Cover plate / slide switch
1/14
32540233 J:0082540233
26.07.2010
Automatic switch standard
picture 2: Automatic switch standard
Automatic switch universal
picture 3: Automatic switch universal
(5) Adjuster, sensitivity (6) Adjuster, brightness (7) Operating mode switch (8) Adjuster, run-on time
3 Function
Intended use
- Automatic switching of lighting depending on the heat motion and ambient brightness.
- Operation with concealed insert for dimming, switching or extension insert, 3-wire
- Interior mounting on flush-mounted insert at a height of 1.1 m.
2/14
32540233 J:0082540233
26.07.2010
Light Management
Automatic switch 180° 1.10 m
Product characteristics
Automatic switch standard
- Sensitivity and brightness threshold settable
- Manual switch-on possible via extension insert, 2-wire, or installation button
- 18 lens segments in 2 recording levels
- Extension of the detection area in combination with the 3-wire extension insert
- Detection area can be limited using cover plate
i Dimming inserts can only execute switching functions. Automatic switch universal
- Run-on time, sensitivity and brightness threshold settable
- Teach function to save the current brightness as the new brightness threshold.
- Operating mode switch for Automatic operation, Continuous on or Continuous off
- Short-time operation, e.g. to control acoustic signal encoders
- Manual switch-on possible via extension insert, 2-wire, or installation button
- With the dimmer insert, it is possible to change the brightness using a 2-wire extension
insert
- Switch-on brightness can be saved with the dimmer insert
- With the dimmer insert, the dim-down function is possible at the end of the run-on time
- 18 lens segments in 2 recording levels
- Extension of the detection area in combination with the 3-wire extension insert
- Detection area can be limited using cover plate
- High protection against ambient light
Automatic operation
The controller detects heat motions of people, animals and objects.
- The light is switched on if a person enters the monitored detection area and the brightness
is below the set threshold. Each detected movement restarts the run-on time.
- The light is switched off if no more movement is detected in the detection area and the run-
on time has elapsed.
Light oscillations e.g. due to the cooling of bulbs are prevented via interlock times in the automatic switch. No switching commands are performed during the interlock. Automatic switch standard approx. 3 seconds Automatic switch universal: 0.2 to 3 seconds, dynamic.
Automatic switch universal: The day/night and night/day switch-over is performed only after the brightness is above or below the threshold for approx. 10 seconds. This prevents the motion detector from switching to Night mode is there is brief shadow or to Day mode if there is brief light.
Behaviour in case of mains failure for automatic switch standard
- Less than 0.2 seconds: the old switching position is restored after mains return.
- 0.2 seconds to approx. 1 seconds: when the power returns, the lighting is switched on
again for the run-on time.
- Longer than 1 second: when the power returns, the motion detector carries out a self test
for approx. 60 seconds. The lighting is switched on during the self test. Then the lighting switches off for the length of the run-on time.
Behaviour in case of mains failure for automatic switch universal
- Less than 0.2 seconds: the old switching position is restored after mains return.
- 0.2 seconds to approx. 2 seconds: when the power returns, the lighting is switched on
again for the run-on time.
- Longer than 2 seconds: when the power returns, the motion detector carries out a self test
for approx. 90 seconds. The lighting is switched on during the self test. Then the lighting switches off briefly, and then on again for the length of the run-on time.
i In the Continuous on and Continuous off operating modes, the light is switched on or off
after the self-test.
i A power failure of longer than 2 seconds causes the loss of the switch-on brightness and
the brightness threshold saved via the Teach function.
3/14
32540233 J:0082540233
26.07.2010
Light Management
Automatic switch 180° 1.10 m
4 Automatic switch standard operation
Switch on the light via extension
A 2-wire extension or an installation button, NO contact is connected. o Press extension or installation button.
Light is switched on independently of the brightness. Automatic mode is active.
i Manual switch-on is not possible.
Setting the brightness threshold
The brightness threshold is infinitely adjustable in a range from approx. 0 to 80 lux and day operation3. In so doing, the 3symbol stands for brightness-independent switching and the 2symbol for switching in case of darkness.
o Remove plate (4) (picture 1). o Turn the adjuster (6) to the required position (picture 2). i Should the motion detector no longer react to detected movements in Night mode,
2setting, turn the adjuster back somewhat towards 3.
o Snap cover on.
Setting the sensitivity The sensitivity of the cover is infinitely adjustable using the adjuster Sens. (5).
o Remove plate (4) (picture 1). o Set the sensitivity using the adjuster Sens. (5). o Snap cover on.
5 Automatic switch universal operation
Switch on the light via extension
A 2-wire extension or an installation button, NO contact is connected. o Press button for less than 0.4 seconds.
The Light is switched on independently of the brightness for the run-on time.
i If the run-on time setting dial (5) is set to M, Short-time operation (picture 6), then the light
is switched on for approx. 0.5 seconds, even if the button is pressed for longer.
i Manual switch-on is not possible.
Switch light on with minimum brightness
Motion detector cover is combined with a dimmer insert. A 2-wire extension is connected. Light is switched off o Press button at bottom for longer than 0.4 seconds.
Light is switched on at minimum brightness and stays at this brightness for as long as motion is detected.
Adjusting brightness via extension
Motion detector cover is combined with a dimmer insert. A 2-wire extension is connected. o Press top button for a long time.
The light gets brighter up to maximum brightness.
o Long press on bottom of button.
Light gets darker to minimum brightness.
4/14
32540233 J:0082540233
26.07.2010
Light Management
Automatic switch 180° 1.10 m
Save switch-on brightness
The light is switched to this brightness value on each switch-on. In the as-delivered state, the switch-on brightness is set to the maximum brightness.
Motion detector cover is combined with a dimmer insert. A 2-wire extension is connected.
o Set light to the required brightness. o Press extension over entire surface for at least 3 seconds.
For confirmation the lighting switches off briefly and then on again to the saved switch-on brightness.
i The saved switch-on brightness is deleted after a power failure.
Setting the operating modes
picture 4: Slide switch
The motion detector has three operating modes that can be set using the slide switch (4) (picture 4). In the as-delivered state, the centre position is set and locked. The slide switch must be unlocked before a different operating mode can be set.
picture 5: Locking screw
5/14
32540233 J:0082540233
26.07.2010
Light Management
Automatic switch 180° 1.10 m
Loading...
+ 9 hidden pages