JUMO AQUIS 500 RS, 202569 Operating Manual

JUMO AQUIS 500 RS
Display unit/controller for digital sensors with
Modbus protocol
Type 202569
B 202569.0
Operating Manual
V3.00/EN/00598864
WARNING!
NOTE!
Please read these operating instructions before commissioning the device. Keep the manual in a place which is accessible to all users at all times.
NOTE! Resetting the contrast of the LCD display:
If the contrast/brightness setting has been adjusted so that the display text is no longer legible, the basic setting can be restored as follows:
Versorgungsspannung ausschalten.Die Tasten und gleichzeitig gedrückt halten, dann die Versorgungsspan-
nung einschalten.
Reset the language to "English":
If the language has been adjusted so that the display text is no longer comprehen­sible, use the Administrator password, 7485, to reset the language to "English":
Press the key for longer than 3 seconds.Press the key once.Briefly press the key.Enter 7485.Briefly press the key.
The required language can then be set in
A
DMINISTR.LEVEL > PASSWORD > PARAMETER LEVEL > DISPLAY > LANGUAGE .
Contents
1 Typographical conventions ...................................................... 5
1.1 Warning symbols .........................................................................................5
1.2 Note symbols ...............................................................................................5
2 Description ................................................................................ 6
3 Identifying the device ............................................................... 8
3.1 Nameplate ....................................................................................................8
3.2 Order details .................................................................................................9
3.3 Accessories (in scope of delivery) ..............................................................10
3.4 Accessories (optional) ................................................................................10
4 Mounting .................................................................................. 11
4.1 General information ....................................................................................11
4.2 Surface mounting .......................................................................................11
4.3 Pipe-mounted kit / weather protection canopy .........................................12
4.4 DIN-rail mounting kit ..................................................................................12
4.5 Mounting in a panel ....................................................................................13
5 Installation ............................................................................... 15
5.1 Installation notes ........................................................................................15
5.2 Galvanic isolation .......................................................................................16
5.3 Opening and closing the device ................................................................17
5.4 Connecting the cables ...............................................................................18
5.5 Terminal assignment ..................................................................................19
5.6 Pin configuration ........................................................................................20
6 Operation ................................................................................. 22
6.1 Control elements ........................................................................................22
6.2 Display .......................................................................................................23
6.3 Operating principle .....................................................................................24
6.4 Measurement mode ...................................................................................25
6.5 Input/output information ............................................................................25
6.6 Operator level .............................................................................................27
6.7 Administrator level .....................................................................................27
6.8 Device info .................................................................................................33
6.9 Controller functions ....................................................................................34
6.10 MANUAL mode / simulation mode ............................................................35
6.11 HOLD mode ...............................................................................................39
Contents
7 Startup ..................................................................................... 40
7.1 Quick introduction ......................................................................................40
7.2 Examples of settings ..................................................................................41
8 Calibrating sensors ................................................................. 56
8.1 Calibrating sensor type 202613/... .............................................................56
8.2 Calibrating sensor type 20263x .................................................................63
8.3 Calibrating sensor type 202670/... .............................................................69
9 Setup program ........................................................................ 74
9.1 Function .....................................................................................................74
10 Overcoming errors and malfunctions ................................... 75
11 Technical data ......................................................................... 77
11.1 Digital interface ..........................................................................................77
11.2 Analog temperature input ..........................................................................77
11.3 Sampling rate .............................................................................................77
11.4 Measuring circuit monitoring .....................................................................77
11.5 Binary input ................................................................................................77
11.6 Controller ...................................................................................................77
11.7 Analog outputs (maximum 2) .....................................................................78
11.8 Switching outputs (maximum 2 changeover contacts) ..............................78
11.9 Voltage supply for sensors .........................................................................78
11.10 Setup interface ...........................................................................................78
11.11 Electrical data ............................................................................................78
11.12 Display .......................................................................................................79
11.13 Case ...........................................................................................................79
11.14 Approvals/marks of conformity ..................................................................79
12 Appendix .................................................................................. 80
12.1 Operator level parameters .........................................................................80
12.2 Parameter explanation ...............................................................................89
12.3 Term definition ...........................................................................................93
12.4 Flow diagram of the basic setting wizard ..................................................95
12.5 Template for panel cut-out ........................................................................98
13 Index ......................................................................................... 99

1.1 Warning symbols

DANGER!
This symbol indicates that personal injury from electrocution may occur if the appropriate precautionary measures are not taken.
WARNING!
This symbol in connection with the signal word indicates that personal injury may occur if the appropriate precautionary measures are not taken.
CAUTION! This symbol in connection with the signal word indicates that damage to
assets or data loss will occur if the appropriate precautionary measures are
not taken.

1.2 Note symbols

1 Typographical conventions

NOTE!
This symbol refers to important information about the product, its handling, or additional use.
1
abc
Action instructions
Footnote
Footnotes are remarks that refer to specific parts of the text. Footnotes con­sist of two parts:
An identification marking in the text and the footnote text. The identification markings in the text are arranged as sequential superscript
numbers.
This symbol indicates that an action to be performed is described. The individual steps are marked by this asterisk. Example: Undo recessed head screws.
5

2 Description

General infor­mation
The device has a total of 1 digital interface, 1 analog temperature input, and 1 binary input. The digital interface is suitable for connecting sensors that have a Modbus-RS485 interface. If the connected sensor does not have an integrated temperature sensor, an RTD temperature probe Pt100, Pt1000, or NTC/PTC (up to 4 kΩ) can be connected to the analog temperature input. The voltage supply for the digital sensor is integrated into the device.
The LCD graphic display allows input signals to be displayed as digits or as a bar graph. Displaying parameters in plain text ensures that operation is easily understandable and safe.
Two optional relay changeover contacts are used to implement simple switch­ing or alarm functions as well as demanding control tasks with P, PI, PD, and PID behavior. Upon request, the device can also be supplied with two analog outputs (0 to 10 V or 0(4) to 20 mA) that can be freely parameterized and scaled.
The device is suitable for tasks such as display, measurement, and control of:
Dissolved oxygen in conjunction with sensors acc. to data sheet 202613
Free chlorine in conjunction with sensors acc. to data sheet 202630
Tot al chlor in e in conjunction with sensors acc. to data sheet 202631
Ozone in conjunction with sensors acc. to data sheet 202634
Hydrogen Peroxide and Peracetic Acid in conjunction with sensors
acc. to data sheet 202636
Turb id it y in conjunction with sensors acc. to data sheet 202670
Special features • Display: mg/l, ppm, % SAT, %, ‰, g/l, ppb, µg/l, NTU, FNU, etc.
Others possible with use of the setup program (option)
• Large LCD graphic display with backlight
• Display can be selected: large digits, bar graph, or trend display
• Integrated calibration routines (depending on sensor): zero point, end value, and 2-point
• Calib. logfile
• Protection type IP67 for surface mounting Protection type IP65 for control cabinet mounting
• User languages (possible to switch): English, German, French
• With setup program (option): easy-to-use programming, plant documenta­tion, download of additional user languages
6
Block diagram
2 Description
7

3 Identifying the device

Typ: 20256 / 0- - - - - 2 /0009 2 654 888 000 310 000- 3
TN: 00602276
JUMO AQUIS 500 RS
Fulda, Germany www.jumo.net
AC 110..240V -15/+10% 48..63Hz
14VA
F-Nr.: 0168122901016010001

3.1 Nameplate

Position
The nameplate is affixed to the right-hand side of the case.
Contents
The nameplate shows important information. This includes:
Description Designation on
Device type Typ 202569/20-654-888-000-310-000-23/000 Parts no. TN 00602276 Fabrication
number Voltage supply AC 110 to 240 V -15/+10 % 48 to 63 Hz
Device (type)
Compare the specifications on the nameplate with your order documents. The supplied device version can be identified using the order code in (See chapter
3.2 "Order details", page 9).
Part no. (PN)
The part no. clearly identifies an article in the catalog. It is important for com­munication between the customer and the sales department.
Fabrication number (F-Nr.)
Among other things, the fabrication number indicates the production date (year/week) and the hardware version number.
Example
the nameplate
F-Nr. 0168122901016010001
<14 VA
Production date
Example: F-Nr. = 0168122901016010001 The figures in question are in positions 12 to 15 (from the left). In this example, the device was produced in the 01st week of 2016.
8

3.2 Order details

(1) Basic type
202569 JUMO AQUIS 500 RS
Display unit/controller for digital sensors with Modbus protocol
(2) Basic type extension
10 For panel installation 20 Surface-mounted case
(3) Input
654 RS422/485 Modbus master
(4) Output 1 (for main value or continuous controller)
000 No output 888 Analog output 0(4) to 20 mA or 0 to 10 V
(5) Output 2 (for temperature or continuous controller)
000 No output 888 Analog output 0(4) to 20 mA or 0 to 10 V
(6) Output 3
000 No output 310 Relay with changeover contact
(7) Output 4
000 No output 310 Relay with changeover contact
3 Identifying the device
(8) Voltage supply
23 AC 110 to 240 V, -15/+10 %, 48 to 63 Hz 25 AC/DC20to30V, 48to63Hz 30 DC 12 to 24 V, ±15 %
(9) Extra code
000 Without
(1) (2) (3) (4) (5) (6) (7) (8) (9)
Order code /- -----/ Order example 202569 / 20 - 654 - 888 - 000 - 310 - 000 - 23 / 000
9
3 Identifying the device

3.3 Accessories (in scope of delivery)

4 × pluggable screw terminal 1 × small insertable jumper 1 × large insertable jumper 1 × mounting clip for cable diameter > 5 mm 2 × mounting clip for cable diameter < 5 mm 1 × mounting clip for cable diameter < 3 mm 2 × lens head screw 3.5 × 6.5 4 × spacing for panel installation 4 × hex nut for panel installation 4 × flat head screw M6 × 10 4 × mount 1 × cable gland M12 × 1.5 1 × flat gasket for cable gland M12 × 1.5 1 × reduction sealing ring M12 × 1.5 2 × cable gland M16 × 1.5 2 × flat gasket for cable gland M16 × 1.5 1 × multiple seal insert for cable gland M16 × 1.5 1 x stranded wire, PVC-insulated

3.4 Accessories (optional)

Type Parts no.
Protective roof for JUMO AQUIS 500 Pipe mounting kit for JUMO AQUIS 500 DIN-rail mounting kit for JUMO AQUIS 500 Support pillar with pedestal base, cantilever arm, and chain 00398163 Holder for suspended fitting 00453191 Rear case wall kit 20256x 00506351 PC setup program 00483602 PC interface cable with USB/TTL converter and two adapters
(USB transmitter cable)
a
The pipe mounting kit is required for installation of the protective roof.
b
The JUMO AQUIS 500 can be fitted to a pipe (such as a support pillar or rail) with the pipe mounted kit.
c
The JUMO AQUIS 500 can be fitted to a DIN-rail of 35 mm × 7.5 mm (acc. to DIN EN 60715 A.1) with the DIN-rail mounting kit.
a
b
c
00398161 00483664 00477842
00456352
10

4 Mounting

30
60
149
134
120
161
140
77
94
94
23
(1)

4.1 General information

Mounting site Ensure that the device is easily accessible for later calibration.
It must be mounted securely and with minimum exposure to vibration. Avoid direct sunlight! Admissible ambient temperature at installation location: -10 to 55 °C at max.
95 % rel. humidity without condensation.
Installation
The device can be installed in any position.
position

4.2 Surface mounting

n
NOTE!
Mounting brackets (1) are included in the scope of delivery.
Screw the four mounting brackets (1) onto the case.
The mounting brackets can be rotated in stages of 90°.
Mount the case onto the mounting brackets (with screws, anchors, or simi-
lar) on a surface or board.
11
4 Mounting
ø30-50
(2)
(1)
(1)

4.3 Pipe-mounted kit / weather protection canopy

The pipe-mounted kit for the JUMO AQUIS 500 (part no.: 00483664) can be used to mount the device (and, if applicable, the protective roof for the JUMO AQUIS 500, part no.: 00398161) on pipes or rails with a diameter of 30 to 50 mm.
The M5 × 30 screws (1) are for pipe diameters of 30 to 40 mm. The M5 × 40 screws (2) are for pipe diameters of 40 to 50 mm. The pipe-mounted kit is also suitable for horizontal pipes.

4.4 DIN-rail mounting kit

The DIN-rail mounting kit for the JUMO AQUIS 500 (part no.: 00477842) can be used to mount the device on a DIN-rail of 35 mm × 7.5 mm acc. to DIN EN 60715 A.1.
12

4.5 Mounting in a panel

(1)
(2)
(4)
(5)
(3)
NOTE!
For drilling template, see chapter 12.5 "Template for panel cut-out", page 98. To achieve the specified protection type of IP65, the panel must have the cor-
rect thickness.
4 Mounting
Make the panel cut-out and holes according to the drilling template.Place the control panel (1) with gasket (2) in the panel cut-out and fasten it
with screws (2) spacing rollers (4) and nuts (5).
CAUTION!
To guarantee electrical safety, the cable cover must be mounted, see next page!
13
4 Mounting
(1)
(2)
(3)
44
Depth behind panel
Make the electrical connection.Break off the required flap(s) (3) from the cable cover (2) so that the cable
can be laid in the cable path.
Attach the cable cover (2) onto the control panel (1).
14

5.1 Installation notes

DANGER! The electrical connection must only be carried out by qualified personnel.
The choice of cable, the installation and the electrical connection must conform to the requirements of VDE 0100 “Regulations on the Installation of Power Circuits with Nominal Voltages below 1000 V” or the appropriate local regulations. Only flexible cables and wires shall be used!
If contact with live parts is possible while working on the device, it must be completely disconnected from the electrical supply.
Load circuits must be fused for the maximum relay current in each case, in order to prevent welding of the relay contacts in the event of a short circuit.
The electromagnetic compatibility conforms to EN 61326. Run input, output and supply cables separately and not parallel to one
another. Use shielded sensor cables with twisted conductors. Do not run these cables
close to current-carrying components or cables. Ground shielding at one end. Sensor leads should be implemented as uninterrupted cables (not routed via
terminal blocks etc.). Do not connect any additional loads to the supply terminals of the device. The device is not suitable for use in areas with an explosion hazard (Ex areas). Apart from faulty installation, incorrect settings on the device may also affect
the proper functioning of the subsequent process or lead to damage. Safety devices independent of the device should therefore always be provided and should only be capable of adjustment by specialist personnel.

5 Installation

Conductor cross sections and ferrules
Mounting notes
Minimum
cross section without ferrule 0.34 mm Ferrule without lip 0.25 mm Wire ferrule with lip up to 1.5 mm Wire ferrule with lip over 1.5 mm Twin ferrule with lip 0.25 mm
2
0.25 mm
2
1.5 mm
2
2
2
2
2
Maximum cross section
2.5 mm² 10 mm (stripped)
2.5 mm² 10 mm
1.5 mm
2.5 mm² 12 mm
1.5 mm
2
2
Minimum length of ferrule
10 mm
12 mm
CAUTION!
The protection type specified for the device (IP67) can only be achieved if not more than one cable runs into the device through each cable gland.
15
5 Installation

5.2 Galvanic isolation

16
1
not for protective extra-low voltage of voltage supply 30 (DC 12 to 24 V)

5.3 Opening and closing the device

(1)
(2)
5 Installation
Opening the device
Closing the device
Prior to opening, loosen all cable fittings (2) so that the cables are
moveable.
Push connection cable a little into the case so that enough cable reserve is
available for opening.
Loosen the 4 front-panel screws (1) of the case lid and pull them out as
much as possible.
Pull the lid to the front and then fold to the front. The user needs to be able
to easily open the lid. Do not use force while opening!
When closing the device, pull the connecting cables to the outside while
the cable fittings are in a released state and make sure that the lines in the inside of the device run properly. Pay attention to the corresponding sheathing measurement to ensure strain relief and protection type (IP67) of the cable fitting.
The user must be able to close the lid with the 4 screws without a high
degree of pressure.
Tighten cable fittings.
17
5 Installation
(1)

5.4 Connecting the cables

The electrical connection for the surface-mountable housing is easily accessible when the device is folded out.
The device contains a guide plate that ensures an optimum cable path. After
laying the cables, the cable cover (1) must be attached until it clicks, like shown above. This is important to ensure the electrical safety!
To connect the individual core wires, remove pluggable screw terminals from the control panel.
Run the connecting cables through the cable glands.
18
Interior view
987654103
NL1
(L-) (L+)
11 12 13 14 15
13 14 15 16
9876541032
1
11 12
(3)
(1)
(2)
figure without cable cover and without sensor cable
987654103
11 12 13 14 15
9876541032
1
(L-)
NL1
(L+)
13 14 15 16
11 1 2
Row 1
Row 2
5 Installation
Lead the connecting cables in through the cable fittings.Use the cable clip (3) to clamp the signal cable to the shielding.
The clip (3) must only be attached by a 3.5 x 6.5 pan head screw! If the screw is any longer, dangerous voltage could be directed to the cable shielding!
Break off the required flap(s) from the cable cover so that the cable can be
laid in the cable path. Attach the cable cover.
Connect the cores as assigned below, and see chapter 5.6 "Pin
configuration", page 20.
Push the plug-in terminals for row 1 (1) and row 2 (2) into the sockets in the
device.

5.5 Terminal assignment

19
5 Installation
ϑ
9
8
10

5.6 Pin configuration

Connection Terminal Row Voltage supply for transmitter/controller
Voltage supply (23): AC 110 to 240 V; -15/+10 %; 48 to 63 Hz
Voltage supply (25): AC/DC 20 to 30 V; 48 to 63 Hz
Voltage supply (30): DC 12 to 24 V; +/-15 % (connection only admissible to SELV/PELV circuits)
NC 3
Voltage supply for proximity switch
DC 12 V (10 to 20 V) 11 +
Voltage supply 24 V for digital sensors type 20263x/... (connection see chapter "Electrical connection of sensor type 202630/50... or /
51... and the flow monitor", page 47) DC 24 V (20.4 to 28.8 V) 14 +
Voltage supply of 5 V for digital sensors type 202613/... and type 202670/... (connection see chapter "Electrical connection of sensor type 202613/...", page 42 and see chapter "Electrical connection of sensor type 202670/...", page 52)
DC 5 V (5.1 to 5.25 V) 1 -
Inputs
NC 5
Modbus RS485 interface 3 data -
RTD temperature probe in 2-wire circuit 8
1 N (L-)
2 L1 (L+)
12 -
15 -
2 +
6
4 data +
7 shielding
9
10
1
1
1
2
2
20
5 Installation
11
12
6
4
5
10
8
9
Connection Terminal Row
RTD temperature probe in 3-wire circuit 8
9
10
Binary input 11
12
Outputs
Analog output 1 0to20mA or 20to0mA or 4to20mA or
13 +
14 -
20 to 4 mA or 0to10V or 10to0V
(galvanically isolated) Analog output 2
0to20mA or 20to 0mA or 4to20mA or 20to
15 +
16 -
4mA or 0to10V or 10to 0V
(galvanically isolated) Switching output K1
(floating)
4 Pole 5 N/C contact 6 N/O contact
2
2
Switching output K2 (floating)
1NC 7
8 Pole 9 N/C contact 10 N/O contact
21

6 Operation

(2)
(1)
(4)
(6)
(5)
(3)
NOTE!
For operation of the device using the optional setup program, see chapter 9 "Setup program", page 74.
This section describes how to operate the device using the keypad.

6.1 Control elements

(1) Display Background lighting (during operation)
(2) key Start calibration
(3) key Cancel entry / exit level
(4) key Change level
Scroll through selection Confirm selection
(5) key Reduce value
Scroll through selection
(6) key Increase value
Scroll through selection
22

6.2 Display

(1) (2) (3) (5)(4) (6)
(7)
(8)(9)
(10)
(11)

6.2.1 Measuring mode (normal display)

Example
6 Operation
Relay K1 is active
(1)
Relay K2 is active
(2)
Binary input 1 is
(3)
controlled Keypad is locked
(4)
Device status (notes)
(5)
- Alarm (e.g. overrange)
- Calib flashing (calibration timer expired)
- Calib (customer calibration active)
Output mode
(6)
- Manual (manual mode)
- Hold (hold mode)
NOTE!
To return to measurement mode (MEASURING): Press the key or wait for timeout.
Measured value
(7)
Unit of measured value
(8)
Medium temperature
(9)
Device status e.g.
(10)
- Measuring (normal)
- Status of calibration AL R1 = alarm controller 1
(11)
AL R2 = alarm controller 2 AL R12 = alarm controller 1 and 2
23
6 Operation

6.3 Operating principle

6.3.1 Operation in levels

(1) see chapter 6.4 "Measurement mode", page 25 (6) see chapter 6.7 "Administrator level", page 27 (2) see chapter 6.5.1 "Min./max. values", page 25 (7) see chapter 6.7.2 "Parameter level", page 29 (3) see chapter 6.5.2 "Output level display", page 26 (8) see chapter 6.7.3 "Enable level", page 29 (4) see chapter 6.10.4 "MANUAL/simulation overview",
page 38
(5) see chapter 6.6 "Operator level", page 27 (10) see chapter 6.7.5 "Calibration level", page 32
(9) see chapter 6.7.4 "Basic settings", page 32
24

6.4 Measurement mode

(3)
(1)
(2)

6.4.1 Normal display

Display
The following items are displayed in measurement mode:
• Signal of digital interface
• Unit (configurable mg/l, ppm, % Sat., etc.)
6 Operation
•Temperature of medium
(1) MEASURING -> measurement mode (2) 23.7 °C -> temperature of medium (3) 1.58 ppm -> measured value calculated from the digital main input
NOTE!
In measurement mode, the "trend display" or "bar graph" can also be selected – see "MEAS. DISPLAY TYPE", page 90.

6.5 Input/output information

.

6.5.1 Min./max. values

Activating the display of min./max. values
The device is in measurement mode (normal display). Press the key for less than 2 seconds.
The minimum and maximum values of the main value (mg/l, ppm, % Sat., etc.) and temperature are displayed.
25
6 Operation
NOTE!
The extremes of the main measurands and temperature are not assigned to each other (e.g. not 1.16 ppm at 15.3 °C).
To return to measurement mode: Press the key or wait for timeout.
Measurements with overrange are ignored. Press the button again briefly to go to the "output level" display. The min./max. value memory can be reset:
OPERATOR LEVEL > DISPLAY > MIN/MAX RESET. The min. and max. values are deleted when the basic settings are changed
and when the voltage supply is lost.

6.5.2 Output level display

The device is in measurement mode (normal display). Press the key twice for less than 2 seconds.
The output level for the two controller contacts (if present) is displayed.
NOTE!
The output level of an output can only be displayed if the relevant output has been configured: For example: ADMINISTRATOR LEVEL > PARAMETER LEVEL > CTRL. CHAN. 1 OR 2.
To return to the normal display: Press the key or wait for timeout.
Press the key again to go to the "Manual mode overview".
26

6.6 Operator level

All parameters that have been approved by the administrator (see chapter 6.7 "Administrator level", page 27) can be edited in this level. All other parameters (indicated by a key ) can only be read.
Press the key for more than 2 seconds.Select "OPERATOR LEVEL".

6.7 Administrator level

• All parameters can be edited in this level.
• This level can also be used to define which parameters a "normal" operator can edit, and which calibrations may be performed.
6 Operation
To access the administrator level:
Press the key for more than 2 seconds.Use the or key to select "ADMINISTR. LEVEL".Use the and keys to enter the password 300.Confirm with the key.
27
6 Operation

6.7.1 Levels of the administrator level

Timeout and return to mea­surement mode from all menu items after 60 s
28
1
Not available for freely configurable sensor..
1 Only available for freely configurable sensor.
3
Only available for sensors type 202613/... and 202670/...

6.7.2 Parameter level

The same settings can be made here as in the operator level – see chapter 6.6 "Operator level", page 27. As the operator has administrator rights here, he/she can also change param­eters that are locked in the operator level.

6.7.3 Enable level

In this level, all parameters can be enabled (changes possible) or locked (changes not possible) for editing in the operator level.
To access the enable level:
ADMINISTR. LEVEL > PASSWORD > ENABLE LEVEL.
RS485 INPUT
ZERO POINT SLOPE NULL SPAN BAUD RATE PARITY STOPBITS DEVICE ADDRESS ADDR. TEMPERATURE ADDR. MAIN VALUE ADDR. UNCOMP. MAIN UNIT MAIN VALUE UNIT UNCOMP. BYTEORDER FLOAT UNIT TEMP. COMP. SOURCE SALINITY PRESSURE SAMPLING RATE FILTER TIME CONST. CALIB. INTERVAL
6 Operation
TEMPERATURE INPUT
TEMPERATURE SENSOR UNIT MAN. TEMPERATURE FILTER TIME CONST. OFFSET
BINARY INPUT
FUNCTION SWITCH-ON DELAY.
1
When using the type 202613/... sensor, the temperature offset setting affects the displayed temperature, the analogue outputs and the limit values. It, however, does not affect the tem­perature compensation inside the sensor.
1
29
6 Operation
CONTROLLER CHANNEL 1 or CONTROLLER CHANNEL 2
CONTROLLER TYPE SETPOINT SETPOINT 2 MIN/MAX CONTACT PROPORTIONAL BAND RESET TIME DERIVATIVE TIME PULSE PERIOD ACTR.STROKE TIME HYSTERESIS MIN. ON TIME MAX. PULSE FREQ. OUTPUT LEVEL LIMIT PULL-IN DELAY DROP-OUT DELAY CONTROLLER ALARM ALARM TOLERANCE ALARM DELAY IN HOLD MODE HOLD OUTPUT LEVEL ON ERROR MAX. SETPOINT MIN. SETPOINT
CONTROLLER SPEC. FUNCT. (controller special function)
I SWITCH-OFF SEPARATE CNTRLR: MANUAL MODE
SWITCHING OUTPUT 1 or SWITCHING OUTPUT 2
FUNCTION SWITCHING POINT PRE-ALARM SPACING HYSTERESIS SWITCH-ON DELAY. SWITCH-OFF DELAY. PULSE TIME FOR CALIBRATION IN CASE OF FAULT IN HOLD MODE MANUAL MODE NC / NO CONTACT
ANALOG OUTPUT 1 or ANALOG OUTPUT 2
SIGNAL SELECTOR SIGNAL TYPE SCALING START SCALING END DURING CALIBRATION ON ERROR
30
DISPLAY
WASHTIMER
6 Operation
IN HOLD MODE SAFETY VALUE SIMULATION SIMULATION VALUE
LANGUAGE LIGHTING LCD INVERSE MEAS. DISPLAY TYPE LOWER DISPLAY UPPER DISPLAY BAR GR. SCALE START BAR GR. SCALE END MIN/MAX RESET OP. TIMEOUT CONTRAST
CLEANING INTERVAL CLEANING DURATION
31
6 Operation

6.7.4 Basic settings

To make it easier for users to configure a digital sensor with Modbus protocol and prevent configuration conflicts, the JUMO AQUIS 500 RS has a basic setup wizard.
To access the basic settings:
ADMINISTR. LEVEL > PASSWORD > BASIC SETTINGS.
NOTE!
For an overview on the process for the basic setup wizard (flow diagram) see chapter 12.4 "Flow diagram of the basic setting wizard", page 95.
For a detailed description of the configuration of digital sensors on the device using the basic setup wizard see chapter 7.2 "Examples of settings", page 41 ff.

6.7.5 Calibration level

You can start a calibration procedure directly from this menu item. To access the calibration level:
ADMINISTR. LEVEL > PASSWORD > CALIB. LEVEL.
Depending on the connected sensor, one or more of the following calibration options may be available:
•Zero point
•Final value
• Two-point calibration

6.7.6 Calibration enable

Settings can be made here to define which calibration procedures can or can­not be conducted following the start of calibration in the operating level or using the "CAL" key.
To access the calibration level: ADMINISTR. LEVEL > PASSWORD > CALIBR. ENABLE.
Depending on the connected sensor, one or more of the following calibration options may be disabled or enabled:
•Zero point
•Final value
• Two-point calibration

6.7.7 Searching for sensors

This function searches for a connected sensor of type 202613/..., 20263x/... or 202670/... on the RS485 interface, lists its settings for the values baud rate, parity and device address and saves them in the device after confirmation using the "PGM" key.
32
The function is helpful atter replacing a sensor. If the new sensor, e.g. is con­figured on another device address, all other settings, however, are to be retained.
6 Operation

6.7.8 Deleting the logbook

The five most recent calibration procedures are archived in the calibration log­book.
If necessary, the logbook can be deleted following a security prompt.

6.7.9 Resetting the sensor calibrations

In case a calibration procedure yields impermissible values, this function
restores the factory calibration of the sensors of type 202613/... and 20670/....
The function does not affect the calibration logbook of the sensors.
1
2

6.8 Device info

The current configuration of all important parameters (from the basic settings menu) is listed here.
Example TEMPERATUR SENSOR -> MODBUS
SENSOR TYPE -> 202613 DEVICE ADDRESS -> 255 SALINITY -> 10.0 g/kg PRESSURE -> 1013 hPa UNIT -> % Sat. SAMPLE RATE -> 5 sec
1
Only available for freely configurable sensor.
2
Only available for sensors type 202613/... and 202670/...
33
6 Operation

6.9 Controller functions

Simple switching functions
In the JUMO AQUIS 500, simple switching functions such as alarm contact, limit value monitoring, or calibration timer signaling are configured in the parameter level using the "Switching output 1" or "Switching output 2" para­meters.
Higher order control functions
Higher order control functions (P, PI, PD, and PID behavior) are configured in the parameter level using the "Controller 1" or "Controller 2" parameters.
If the limit value, pulse length, pulse frequency, and three-step controller types are used, the switching outputs must be configured; if the continuous control­ler is used, the analog outputs must be configured.
Example of parameters in the operator level
Switching output 1 or 2 Explanation
None Neither switching nor control function required Controller 1 The device should use "higher order" control Controller 2 The device should use "higher order" control Controller alarm 1 or 2 "Simple" switching function Controller alarm "Simple" switching function
main value (Alarm function 1) main value main value (Alarm function 2) main value main value (Alarm function 7) main value main value (Alarm function 8) main value temperat. (Alarm function 1) temperature temperat. (Alarm function 2) temperature temperat. (Alarm function 7) temperature
temperat. (Alarm function 8) temperature Sensor error Washtimer Calib. timer
Controller channel 1 or 2
Limit Pulse width Pulse frequency Continuous Modulating
"Higher order" control functions
34

6.10 MANUAL mode / simulation mode

This function can be used to set the switching outputs and the analog outputs of the device to a defined status manually. The makes dry startup, trouble­shooting, and servicing easier, for example.
6 Operation
Simulation mode accesses switching outputs K1/K2 and analog outputs A1/ A2 directly. If simulation mode has been selected, MANUAL mode cannot be used.
In MANUAL mode, the settings of the "higher order controllers" are taken into account.

6.10.1 MANUAL mode using "higher order control functions"

Higher order switching functions
The JUMO AQUIS 500 is configured to higher order controller functions if the following settings are made:
OPERATOR LEVEL > CTRL. CHAN. 1 OR 2 > CONTROLLER TYPE: LIMIT or PULSE WIDTH or PULSE FREQ. or CONTINUOUS or MODULATING
Depending on the configured controller type, manual mode affects the analog outputs and/or switching outputs. For recommended procedure, see chapter
6.10.3 "Simulation of analog outputs using MANUAL mode", page 38.
Selecting manual mode
NOTE!
The MANUAL mode parameter is locked in the device per default, which means that it can only be activated by an administrator. For other operators, the parameter must be enabled first – see chapter 6.7.3 "Enable level", page 29.
35
6 Operation
ADMINISTRATOR LEVEL > PASSWORD > PARAMETER LEVEL > CTRL.
SPEC. FUNCT. > MANUAL MODE: set LOCKED or PULSED or SWITCH-
ING.
LOCKED= No manual mode; the JUMO AQUIS 500 is in control PULSED The outputs are active for as long as the or key is
SWITCHING The outputs become active when the or key is
Activating manual mode
The device is in measurement mode. Press the and keys for less than 2 seconds.
"MAN." appears in the status line of the LCD display. The device outputs then behave according to the pre-settings.
NOTE!
pressed
pressed; when the relevant key is pressed again, the corre­sponding output is deactivated again
If the and keys are pressed for more than 3 seconds, the device enters HOLD mode.
To exit HOLD mode, press the and keys again for more than 3 seconds.
The JUMO AQUIS 500 is no longer in control. The output level at the output of the controller channel is 0 %.
To select controller channel 1, use the key; the output level at the output of the controller channel 1 is set to 100 %.
To select controller channel 2, use the key; the output level at the output of controller channel 2 is set to 100 %.
MANUAL/simulation overview
It is possible to display which outputs or controllers are in MANUAL mode. Requirement: the device is in measurement mode.
Press the key several times for less than 2 seconds (number varies
according to the features and configuration of the device).
36
Output level of controller channels
It is possible to display the output levels of the controllers in manual mode in the output level overview. Requirement: the device is in measurement mode.
Press the key several times for less than 2 seconds (number varies
according to the features and configuration of the device).
The display changes when the or key is pressed.
NOTE!
To return to measurement mode: Press the key or wait for timeout.
6 Operation
Deactivating manual mode
Press the key. The outputs of the device are in control again. The "MAN" text disappears
from the status line of the LCD display.

6.10.2 Switching output simulation

Simple switching functions
Switching outputs are configured if the following settings are made: SWITCH OUTPUT 1 OR 2 > FUNCTION:
or or or .
Activating simulation
NOTE!
The MANUAL mode parameter in the device is set to "NO SIMULATION" per default. MANUAL mode can only be activated by the operator if this has been enabled in the enable level – see chapter 6.7.3 "Enable level", page 29.
37
6 Operation
ADMINISTR. LEVEL > PASSWORD > PARAMETER LEVEL > SWITCH
OUTPUT 1 OR 2/MANUAL MODE: set INACTIVE or ACTIVE.
INACTIVE => Relay K1 or K2 drops out ACTIVE => Relay K1 or K2 picks up
Deactivating simulation
ADMINISTR. LEVEL > PASSWORD > PARAMETER LEVEL > SWITCH
OUTPUT 1 OR 2/MANUAL MODE: set NO SIMUL.
No simulation = No MANUAL mode; the JUMO AQUIS 500 is in control.

6.10.3 Simulation of analog outputs using MANUAL mode

Enabling and activating
Deactivating ADMINISTR. LEVEL > PASSWORD > PARAMETER LEVEL > ANALOG
Select activation for simulation of the actual value output:
ADMINISTR. LEVEL > PASSWORD > PARAMETER LEVEL > ANALOG OUTPUT 1 OR 2 > SIMULATION: OFF or ON.
If "ON" is selected, the output adopts the value of the "SIMULATION VALUE" parameter.
If the device is back in measurement mode, "MAN." appears at the top right of the LCD display in the status line.
OUTPUT 1 OR 2 > SIMULATION > Off.
The relevant output of the JUMO AQUIS 500 resumes operation. If the device is back in measurement mode and no other output or controller is
in MANUAL mode, "MAN." disappears from the top right of the LCD display in the status bar.

6.10.4 MANUAL/simulation overview

It is possible to display which outputs or controllers are in MANUAL mode. The device is in "normal display" mode.
Press the key several times for less than 2 seconds (number varies
according to the features and configuration of the device).
38
.
NOTE!
To return to measurement mode: Press the key or wait for timeout.

6.11 HOLD mode

In HOLD state, the outputs take the states programmed in the corresponding parameters (controller channel, switching output, analog output).
This function can be used to "hold" the switching outputs and the analog out­puts of the device, which means that the current state of the output is main­tained even if the measured value changes. The device is not in control.
NOTE!
If MANUAL mode is activated while HOLD mode is active, MANUAL mode has priority and "MAN."is displayed in the status bar. The key can be used to exit MANUAL mode. If HOLD mode is still active (via binary input or keypad), the device returns to HOLD mode.
6 Operation
HOLD mode can be activated using the keypad or via binary input. When this mode is activated via the binary input, a delay time of up to 60 s
can be entered in the parameter level of the device. This function, for example, is useful for monitoring the minimum inflow of sensors. It prevents the unwanted activation of HOLD mode, due to small flow disturbances in the measurement medium, e.g. due to air bubbles.
Activating HOLD mode via keypad
Press the and keys for more than 3 seconds. The device outputs behave according to the pre-settings. "HOLD" appears in
the status line of the LCD display.
NOTE!
If the and keys are pressed for less than 3 seconds, the device enters MANUAL mode.
Deactivating HOLD mode via keypad
Press the and keys for more than 3 seconds.
NOTE!
If the and keys are pressed for less than 3 seconds, the device enters MANUAL mode.
The device outputs are in control again and the HOLD test disappears.
39

7 Startup

7.1 Quick introduction

NOTE!
The suggestion below can be used to configure the device quickly and reliably.
✱ Mount the device – See chapter 4 "Mounting", page 11. ✱ Install the device – See chapter 5 "Installation", page 15 ff. ✱ Call up the administrator level (ADMINISTR. LEVEL). ✱ Enter the password 300. ✱ Call up PARAMETER LEVEL > DISPLAY > OPERATION TIMEOUT. ✱ Set OPERATION TIMEOUT to 0 minutes (no timeout). ✱ Exit parameter level. ✱ Call up the administrator level (ADMINISTR. LEVEL). ✱ Enter the password 300. ✱ Select BASIC SETTINGS and work through all menu items. ✱ Answer the question "Reinitialize device?" with "YES". ✱ Configure the necessary parameters. ✱ Calibrate device for sensor and medium. ✱ Set OPERATION TIMEOUT back to a value between 1 and 10 minutes.
40

7.2 Examples of settings

Voltage supply
Digital sensor signal
(RS422/485 Modbus)
Option:
1 or 2 relays
Option: Main output value Dissolved oxygen 0(4) to 20 mA or 0 to 10 V Galvanically isolated
Option:
Temperature output 0(4) to 20 mA or 0 to 10 V Galvanically isolated
(1)
(2)
For digital sensor

7.2.1 Measuring dissolved oxygen in aqueous solutions

NOTE!
Optical sensor with digital interface for dissolved oxygen, see data sheet
202613.
Ta sk Measuring range: 0to20mg/l
Output signal: 4 to 20 mA (main value)
4to20mA (temperature) Temperature measurement Inside sensor Control function: off
Measurement configuration
7 Startup
(1) JUMO AQUIS 500 RS (2) JUMO ecoLine O-DO (sensor for dissolved oxygen), type 202613/...
41
7 Startup
(3)
(4)
Terminal assignment of sensor connection cable
Wire color Function Connection
Black GND Row 2, terminal 1 Red DC 5 V + Row 2, terminal 2 Green RS485 - Row 2, terminal 3 White RS485 + Row 2, terminal 4
Electrical connection of sensor type 202613/...
(1)
(2)
(1) Terminal block 1 (2) Terminal block 2 (3) 4-wire connection cable (fixed cable on the sensor) (4) JUMO ecoLine O-DO (sensor for dissolved oxygen), type 202613/...
42
7 Startup
"Step-by-step" instructions for sensor startup using automatic sensor configuration
NOTE!
If you do not know where the device display is in the menu structure, use the
key to navigate to the next menu level up. Pressing several times will take
you back to measurement mode (normal display).
Accessing the administrator level
The device is in measurement mode (normal display).
Press the key for more than 2 seconds.Use the key to select "ADMINISTR. LEVEL".Confirm with the key.
Entering the password
Use the key to set the flashing value on the display under "PASS-
WORD" to "300" (holding down the key increases the value continuously; pressing the key decreases the value).
Confirm with the key.
Accessing the basic settings
Use the key to select "BASIC SETTINGS".Confirm with the key.
Use the or key to respond to "AUTOMATIC CONFIG. OF THE SEN-
SOR" with "YES" (flashing). Confirm with the key. The JUMO AQUIS 500 now scans the Modbus RS485 interface. If it is con-
nected correctly, the following display appears after a short time:
Confirm with the key.
43
7 Startup
Implementing the basic settings
Use the and keys to enter the value for "SALINITY" and confirm with
the key. Enter the values for "AIR PRESSURE", "UNIT" (select "mg/l"), and "SAM-
PLING RATE" using the and keys and confirm each using the
key. For the "TEMPERATURE SENSOR" request, select "MODBUS" and con-
firm with the key.
Initializing the device
Use the or key to respond to the next question "REINITIALIZE
DEVICE?" with "YES" and confirm with the key.
Accessing the parameter level
In the same way as the "BASIC SETTINGS", the "PARAMETER LEVEL" is a submenu in the administrator level. After successful sensor initialization, the device display will already be in this level, or you can navigate to it as described above.
Final device settings / inspections
RS485 input Device address: 255
Salinity: as entered in "Basic settings" Air pressure: as entered in "Basic settings" Sampling rate: as entered in "Basic settings" Filter time constant: as needed Calibration interval: as needed Zero point: calibration value Slope: calibration value
Te mp er at ur e input
Temperature sensor: Modbus Unit: °C Filter time constant: 2 s Offset: 0.0 °C
NOTE!
When using the type 202613/... sensor, the temperature offset setting affects the displayed temperature, the analog outputs and the limit values. It, however, does not affect the temperature compensation inside the sensor.
Analog output 1
44
Signal selector: Main value Signal type: 4 to 20 mA Scaling start: 0.00 mg/l Scale end: 20.00 mg/l For calibration: As required
In case of fault: As required In hold mode: As required Safety value: As required Simulation: As required Simulation value: As required
7 Startup
Analog output 2
Display Language: As required
Signal selector: Temperature Signal type: 4 to 20 mA Scaling start: 0 °C Scaling end: 50 °C For calibration: As required In case of fault: As required In hold mode: As required Safety value: As required Simulation: As required Simulation value: As required
Lighting: As required LCD inversion: As required Measured value display type: As required Display on bottom: As required Display on top: As required Max./min. reset: As required Operation timeout: As required Contrast: As required
45
7 Startup
Voltage supply
Digital sensor signal
(RS485 Modbus)
Option:
1 or 2 relays
Option:
Calibrated analog output Chlorine concentration 0(4)...20 mA or 0...10 V, galvanically isolated
Option:
Temperature output 0(4)...20 mA or 0...10 V, galvanically isolated
(1)
(2)
for digital sensor
(3)

7.2.2 Measuring the concentration of free chlorine

HINWEIS!
Sensor with digital interface for free chlorine, see data sheet 202630 and optional flow monitor, see data sheet 202811.
Ta sk Measuring range: 0 ... 2 ppm
Output signal: 4 ... 20 mA (main value)
4 ... 20 mA (temperature) Temperature measurement: Inside sensor Control function: off
Measurement configuration
46
(1) JUMO AQUIS 500 RS (2) JUMO tecLine Cl2 (sensor for free chlorine),
type 202630/50... or /51...
(3) Individual fitting flow monitor, part no.: 00605507
7 Startup
(3)
(4)
Terminal assignment of sensor connection cable
Pin M12 (Wire color)
Function Connection
5 (Green) RS485 + Row 2, terminal 3 4 (White) RS485 - Row 2, terminal 4 2 (Brown) +24 V Row 1, terminal 14 3 (Yellow) GND Row 2, terminal 1 (Black) Screen Row 2, terminal 7
Terminal assignment of flow monitor
Wire color Function Anschluss
Brown +12 V Row 1, terminal 11 Black Contact
(NPN N/O contact)
Row 2, terminal 12
Blue GND Row 1, terminal 12
(5)
Electrical connection of sensor type 202630/50... or /51... and the flow monitor
(1)
(2)
(1) Terminal block1 (2) Terminal block 2 (3) Sensor connection cable, part no. 00638337 (5 m) (4) JUMO tecLine Cl2 (sensor for free chlorine), type 202630/50 or /51... (5) JUMO individual fitting flow monitor, type 202811/10...
47
7 Startup
"Step-by-step" instructions for sensor startup using automatic sensor configuration
NOTE!
If you do not know where the device display is in the menu structure, use the
key to navigate to the next menu level up. Pressing several times will take
you back to measurement mode (normal display).
Accessing the administrator level
The device is in measurement mode (normal display).
Press the key for more than 2 seconds.Use the key to select "ADMINISTR. LEVEL".Confirm with the key.
Entering the password
Use the key to set the flashing value on the display under "PASS-
WORD" to "300" (holding down the key increases the value continuously; pressing the key decreases the value).
Confirm with the key.
Accessing the basic settings
Use the key to select "BASIC SETTINGS".Confirm with the key.
Use the or key to respond to "AUTOMATIC CONFIG. OF THE SEN-
SOR" with "YES" (flashing). Confirm with the key. The JUMO AQUIS 500 now scans the Modbus RS485 interface. If it is con-
nected correctly, the following display appears after a short time:
48
Confirm with the key.
Implement the basic settings
Use the and keys to enter the value for „UNIT“ („ppm“ in this
example) and confirm with the key. Enter the value for the decimal point of the main value („DEC. POINT MAIN
VAL.“) using the and keys („X.xxx“ in this example) and confirm with
the key. For the "TEMPERATURE SENSOR" request, select "MODBUS" and con-
firm with the key.
Initializing the device
Use the or key to respond to the next question "REINITIALIZE
DEVICE?" with "YES" and confirm with the key.
Accessing the parameter level
In the same way as the "BASIC SETTINGS", the "PARAMETER LEVEL" is a submenu in the administrator level. After successful sensor initialization, the device display will already be in this level, or you can navigate to it as described above.
Final device settings / inspections
7 Startup
RS485 input Null: Calibration value
Span: Calibration value Baudrate 9600 Parity None Measures variable Free chlorine Unit ppm Filter time const.: As needed Calib.interval As needed
Temperature input
Binary input Function: Hold mode
Analog output 1
Temperature sensor: Modbus Unit: °C Filter time const.: As needed Offset: 0,0 °C
Signal selector: Main variable Signal type: 4 ... 20 mA Scaling start: 0.000 ppm Scaling end: 2.000 ppm During calibration: As needed On error: As needed In hold mode: As needed Safe value: As needed
49
7 Startup
Simulation: As needed Simulation value: As needed
Analogausgang 2
Anzeige Language: As needed
Signal selector: Temperature Signal type: 4 ... 20 mA Scaling start: 0 °C Scaling end: 50 °C During calibration: As needed On error: As needed In hold mode: As needed Safe value: As needed Simulation: As needed Simulation value: As needed
Lighting: As needed LCD inverse: As needed Meas. display type: As needed Lower display: As needed Upper display: As needed Min/Max reset: As needed Op. timeout: As needed Contrast: As needed
50

7.2.3 Turbidity measurement

Voltage supply
Digital sensor signal
(RS422/485 Modbus)
Option:
1 or 2 relays
Option:
Main output value Turb id it y 0(4) to 20 mA or 0 to 10 V Galvanically isolated
Option:
Temperature output 0(4) to 20 mA or 0 to 10 V Galvanically isolated
(1)
(2)
For digital sensor
NOTE!
Optical sensor with digital interface for turbidity measurements, see data sheet
202670.
Ta sk Measuring range: 0 to 200 NTU
Output signal: 4 to 20 mA (main value)
4to20mA (temperature)
Control function: off
Measurement configuration
7 Startup
(1) JUMO AQUIS 500 RS (2) JUMO ecoLine NTU (sensor for turbidity measurements),
type 202670/...
51
7 Startup
(3)
Terminal assignment of sensor connection cable
Wire color Function Connection
Black GND Row 2, terminal 1 Red DC 5 V + Row 2, terminal 2 Green RS485 - Row 2, terminal 3 White RS485 + Row 2, terminal 4
(4)
Electrical connection of sensor type 202670/...
(1)
(2)
52
(1) Terminal block 1 (2) Terminal block 2 (3) 4-wire connection cable (fixed cable on the sensor) (4) JUMO ecoLine NTU (sensor for turbidity measurements), type 202670/...
7 Startup
"Step-by-step" instructions for sensor startup using automatic sensor configuration
If you do not know where the device display is in the menu structure, use the
key to navigate to the next menu level up. Pressing several times will take
you back to measurement mode (normal display).
Accessing the administrator level
The device is in measurement mode (normal display).
Press the key for more than 2 seconds.Use the key to select "ADMINISTR. LEVEL".Confirm with the key.
Entering the password
Use the key to set the flashing value on the display under "PASS-
WORD" to "300" (holding down the key increases the value continuously;
pressing the key decreases the value). Confirm with the key.
Accessing the basic settings
Use the key to select "BASIC SETTINGS".Confirm with the key.
Use the or key to respond to "AUTOMATIC CONFIG. OF THE SEN-
SOR" with "YES" (flashing). Confirm with the key. The JUMO AQUIS 500 now scans the Modbus RS485 interface. If it is con-
nected correctly, the following display appears after a short time:
Confirm with the key.
53
7 Startup
Implementing the basic settings
Use the or keys to select the measuring range "0 to 200" and con-
firm with the key. Use the or keys to select the "NTU" unit for the display and confirm
with the key. For the "TEMPERATURE SENSOR" request, select "MODBUS" and con-
firm with the key.
Initializing the device
Use the or key to respond to the next question "REINITIALIZE
DEVICE?" with "YES" and confirm with the key.
Accessing the parameter level
In the same way as the "BASIC SETTINGS", the "PARAMETER LEVEL" is a submenu in the administrator level. After successful sensor initialization, the device display will already be in this level, or you can navigate to it as described above.
Final device settings / inspections
RS485 input Unit: NTU
Device address: 255 Filter time constant: as needed Calibration interval: as needed Zero point measuring range 1: calibration value Slope measuring range 1: calibration value Zero point measuring range 2: calibration value Slope measuring range 2: calibration value Zero point measuring range 3: calibration value Slope measuring range 3: calibration value Zero point measuring range 4: calibration value Slope measuring range 4: calibration value
Te mp er at ur e input
Temperature sensor: Modbus Unit: °C Filter time constant: 2 s Offset: 0.0 °C
Analog output 1
54
Signal selector: Main value Signal type: 4 to 20 mA Scale start: 0.0 NTU Scale end: 200.0 NTU For calibration: As required
In case of fault: As required In hold mode: As required Safety value: As required Simulation: As required Simulation value: As required
Display Language: As required
Lighting: As required LCD inversion: As required Measured value display type: As required Display on bottom: As required Display on top: As required Max./min. reset: As required Operation timeout: As required Contrast: As required
7 Startup
55

8 Calibrating sensors

8.1 Calibrating sensor type 202613/...

8.1.1 General information

The JUMO ecoLine O-DO (type 202613/...) is an optical sensor designed to measure dissolved oxygen in aqueous solutions. Its measuring method, accredited according to ASTM D888-05 is based on the principle of lumines­cence quenching. As with all optical sensors, the JUMO ecoLine O-DO is sub­ject to sensor aging and sensor drift during operation. The effects of these fac­tors are compensated for by calibration.
Calibrating methods
The JUMO AQUIS 500 RS provides two calibration methods for the JUMO ecoLine O-DO sensor:
• For end value calibration (typical method), the slope of the sensor is cali-
brated – see chapter 8.1.2 "End value calibration", page 57
• For 2-point calibration, the zero point and slope of the sensor are cali-
brated – see chapter 8.1.3 "Two-point calibration", page 59. This calibration
method offers the greatest possible level of accuracy and is particularly rec-
ommended for measurements of small oxygen concentrations.
When to calibrate?
Preparatory work
The JUMO ecoLine O-DO (type 202613/...) sensor is calibrated ex works, meaning that no calibration is required before initial startup. During operation, the sensor should be calibrated at least once a year and should also be cleaned regularly (depending on the extent of contamination by the process medium).
The sensor and membrane should be rinsed with clean water before each cal­ibration. Organic deposits left on the membrane, such as a biofilm or silt, may cause measurement errors. These deposits should be removed carefully with warm soapy water and a soft sponge. Never use abrasive agents (e.g. scour­ing sponge).
CAUTION!
During the calibration, the relays and analog output signals assume the config­ured states.
Basic procedures for starting calibration:
• Press the key if this has been enabled in
ADMINISTR: LEVEL > PASSWORD > CALIB. ENABLE
56
•Via ADMINISTR: LEVEL > PASSWORD > CALIB. LEVEL
•Via CALIBR. LEVEL in the main menu, if this has been enabled in
ADMINISTR. LEVEL > PASSWORD > CALIB. ENABLE

8.1.2 End value calibration

Prerequisite
• The device must be supplied with voltage –
see chapter 5 "Installation", page 15 ff.
• The sensor must be connected
• Sensor startup must be complete
• Calibration must be enabled – see chapter 6.7 "Administrator level", page
27
• The device must be in "Measurement mode"
8 Calibrating sensors
Selecting calibration methods
Initiate calibration using the key (or via the administrator level).
Select "FINAL VALUE" and start with the key.
CAUTION!
The response of the outputs during calibration depends on their configuration.
Calibration for 100 % saturation (final value)
Bring the sensor to the defined 100 % saturation state by placing it in
water vapor-saturated air.
57
8 Calibrating sensors
NOTE!
Water vapor-saturated air occurs, for example, directly above the water sur­face in a half-full glass of water at room temperature.
Make sure there are no drops of water on the bottom of the membrane. The sensor must stay dry during the measurement. It is safest to use a holding device (such as a test tube stand) to prevent the sensor from entering the water.
Wait until the displayed value is stable at "100.0%Sat" or has stabilized
near this value.
Confirm with the key. The slope determined by the device (deviation from the factory calibration) is
displayed along with the corrected measured value, which should be 100.0 % Sat. immediately after acknowledgement.
Use the key to apply the calibration or the key to reject the calibra-
tion. The device returns to measurement mode.
58

8.1.3 Two-point calibration

Prerequisite
• The device must be supplied with voltage
(see chapter 5 "Installation", page 15 ff).
• The sensor must be connected.
• Sensor startup must be complete.
• Calibration must be enabled (see chapter 6.7 "Administrator level", page
27).
• The transmitter must be in "Measurement mode".
8 Calibrating sensors
Selecting calibration methods
Initiate calibration using the key (or via the administrator level).
Select "2-POINT CALIB." and start calibration with the key.
CAUTION!
The response of the outputs during calibration depends on their configuration.
Calibration for 0 % saturation (zero point)
Bring the sensor to the defined 0 % saturation state by submerging it in an
aqueous sodium sulfite solution (concentration < 2 %).
59
8 Calibrating sensors
CAUTION!
Do not leave the sensor in contact with the sodium sulfite solution for more than 1 hour.
NOTE!
For flawless measurement, make sure that there are no air bubbles on the bottom of the membrane of the submerged sensor.
Wait until the displayed value is stable at "0.00%Sat" or has stabilized near
this value.
Confirm with the key; the display switches to "MEAS. END VAL."
Calibration for 100 % saturation (final value)
Remove the sensor from the sodium sulfite solution and dry with a paper
towel, being careful to only dab the membrane. Rinse the sensor with clean water and dry with a paper towel, being careful
to only dab the membrane. Next bring the sensor to the second defined state by placing it in water
vapor-saturated air.
NOTE!
Water vapor-saturated air occurs, for example, directly above the water sur­face in a half-full glass of water at room temperature.
60
Make sure there are no drops of water on the bottom of the membrane. The sensor must stay dry during the measurement. It is safest to use a holding device (such as a test tube stand) to prevent the sensor from entering the water.
Wait until the displayed value is stable at "100.0%Sat" or has stabilized
near this value.
8 Calibrating sensors
Confirm with the key. The zero point and slope determined by the device (deviation from the factory
calibration) are displayed along with the corrected measured value, which should now be 100.0 % Sat.
Use the key to apply the calibration or the key to reject the calibra-
tion. The device returns to measurement mode.
61
8 Calibrating sensors

8.1.4 Calibration logbook

The data records for the last 10 successful calibrations are saved in the con­nected sensor, are extracted by the JUMO AQUIS 500 RS, and can be viewed in the calibration logbook.
Accessing the calibration logbook
The device is in measurement mode.
Press the key for more than 2 seconds.Use the key to select the "CALIBR. LOGBOOK" entry.Confirm with the key.
The data for the last successful calibration is displayed; in the example described the values for zero point and slope (deviation from the factory cali­bration) of a 2-point calibration:
As not all of the data for the 2-point calibration fits on one page in the display, you can use the key to access further data from the calibration data record for the 2-point calibration:
Use the and keys to access all other stored calibration data records.
NOTE!
Irrespective of the unit selected in the basic settings, calibrations are always conducted in % Sat. The last determined calibration data record is always the top entry in the list.
62

8.2 Calibrating sensor type 20263x

8.2.1 General information

The JUMO tecLine 20263x type sensors are membrane-covered amperome­tric sensors with digital interface. They are made for measuring the the follo­wing disinfectants:
• Free chlorine (Type 202630/...)
• Total chlorine (Type 202631/...)
• Ozone (Type 202634/...)
• Hydrogen peroxide and (Type 202636/...)
peracetic acid
Calibrating methods
The JUMO AQUIS 500 RS provides two calibration methods for the JUMO tecLine 20263x type sensors:
• For end value calibration (typical method), the slope of the sensor is cali-
brated, see chapter 8.2.2 "End value calibration", page 64.
• For two-point calibration, the zero point and slope of the sensor are cali-
brated, see chapter 8.2.3 "Two-point calibration", page 66.
8 Calibrating sensors
Preparatory work
When to calibrate?
The membrane caps of the JUMO tecLine 20263x type sensors must be filled with electrolyte prior to the initial operation. This process is described in detail in the operating manuals (BTA) of the sensors.
For the initial operation, the JUMO tecLine 20263x sensors mus be calibrated after filling the membrane caps. One day after the initial operation, calibration should be repeated. During operation, the sensors should be calibrated on a weekly basis, and more often if required. After each change of electrolyte and after each loss of power the sensors must be calibrated.
CAUTION!
During the calibration, the relays and analog output signals assume the config­ured states.
Basic procedures for starting calibration:
• Press the key if this has been enabled in
ADMINISTR: LEVEL > PASSWORD > CALIB. ENABLE
•Via ADMINISTR: LEVEL > PASSWORD > CALIB. LEVEL
•Via CALIBR. LEVEL in the main menu, if this has been enabled in
ADMINISTR. LEVEL > PASSWORD > CALIB. ENABLE
63
8 Calibrating sensors

8.2.2 End value calibration

Prerequisite
• The device must be supplied with voltage –
see chapter 5 "Installation", page 15 ff.
• The sensor must be connected
• Sensor startup must be complete
• Calibration must be enabled – see chapter 6.7 "Administrator level", page
27
• The device must be in "Measurement mode"
Selecting calibration method
Initiate calibration using the key (or via the administrator level).
Select "FINAL VALUE" and start with the key.
CAUTION!
The response of the outputs during calibration depends on their configuration.
The display changes to the reference value (final value) measurement mode).
64
8 Calibrating sensors
Calibration for the desired chlorine concentration (final value)
Bring the process to the defined chlorine concentration state.Immerse the sensor into the process solution.Determine the chlorine concentration of the process solution by using the
DPD-1 method. When the displayed value is stable, confirm with the key. The display changes for the input of the previously determined reference
value, the input value „flashes“.
Enter the determined reference value by using the and keys.
Confirm with the key.
The display shows the slope determined by the device.
Use the key to apply the calibration or the key to reject the calibra-
tion. The device returns to measurement mode.
65
8 Calibrating sensors

8.2.3 Two-point calibration

Prerequisite
• The device must be supplied with voltage –
see chapter 5 "Installation", page 15 ff.
• The sensor must be connected
• Sensor startup must be complete
• Calibration must be enabled – see chapter 6.7 "Administrator level", page
27
• The device must be in "Measurement mode".
Selecting calibration method
1
Initiate calibration using the key (or via the administrator level).
Select "2-POINT CALIB." and start with the key.
CAUTION!
The response of the outputs during calibration depends on their configuration.
The display changes for the measurement of the zero point.
1. Shown at the example of the sensor for free chlorine, type 202630/51...
66
Calibrating the zero point
Immerse the sensor into chlorine-free process water.When the display value is stable around the zero point, confirm with
the key. The display changes for the measurement of the reference value.
Calibrating the reference value
Bring the process to the defined chlorine concentration state.Determine the chlorine concentration of the process solution by using the
DPD-1 method.
8 Calibrating sensors
When the displayed value is stable, confirm with the key.The display changes for the input of the previously determined reference
value, the input value „flashes“.
Enter the determined reference value by using the and keys.
Confirm with the key.
The display shows the slope and the zero point determined by the device.
67
8 Calibrating sensors
Use the key to apply the calibration or the key to reject the calibra-
tion. The device returns to measurement mode.

8.2.4 Calibration logbook

The data records for the last 5 successful calibrations are saved in the con­nected sensor, are extracted by the JUMO AQUIS 500 RS, and can be viewed in the calibration logbook.
Accessing the calibration logbook
The device is in measurement mode.
Press the key for more than 2 seconds.Use the key to select the "CALIBR. LOGBOOK" entry.Confirm with the key.
The data for the last successful calibration is displayed; in the example described the values for zero point and slope:
Use the and keys to access all other stored calibration data records.
NOTE!
When displaying the calibration data in the calibration logbook, the sensor does not distinguish between end value calibration and two-point calibration. The last determined calibration data record is always the top entry in the list.
68
8 Calibrating sensors

8.3 Calibrating sensor type 202670/...

8.3.1 General information

The JUMO ecoLine NTU sensor (type 202670/...) is an optical sensor for mea­suring turbidity according to DIN EN ISO 7027. The measuring principle of the sensor is based on an infrared light measurement according to the 90° scat­tered light method. As with all optical sensors, the JUMO ecoLine NTU is sub­ject to sensor aging and sensor drift during operation. The effects of these fac­tors are compensated for by calibration.
Calibrating methods
The JUMO AQUIS 500 RS offers the JUMO ecoLine NTU sensor the 2-point calibration method for each 4 measuring ranges of the sensor.
NOTE!
If the JUMO ecoLine NTU sensor is to be operated in the automatic measur­ing range switchover mode, all 4 measuring ranges must be calibrated.
When to calibrate?
Preparatory work
The sensor is calibrated ex works, meaning that no calibration is required before initial startup. During operation, the sensor should be calibrated in case of deviating measured values and should also be cleaned regularly (depending on the extent of contamination by the process medium).
The sensor should be rinsed with clean water before each calibration. Organic deposits left on the sensor optics, such as a biofilm or silt, may cause mea­surement errors. These deposits should be removed carefully with warm soapy water and a soft sponge. Never use abrasive agents (e.g. scouring sponge).
Calcium deposits can be removed by submersing the sensors in a diluted hydrochloric acid solution (concentration max. 5 %) for several minutes.
CAUTION!
The response of the outputs during calibration depends on their configuration.
Basic procedures for starting calibration:
• Press the key if this has been enabled in
ADMINISTR: LEVEL > PASSWORD > CALIB. ENABLE
•Via ADMINISTR: LEVEL > PASSWORD > CALIB. LEVEL
•Via CALIBR. LEVEL in the main menu, if this has been enabled in
ADMINISTR. LEVEL > PASSWORD > CALIB. ENABLE
69
8 Calibrating sensors

8.3.2 Two-point calibration

Prerequisite
• The device must be supplied with voltage
(see chapter 5 "Installation", page 15 ff).
• The sensor must be connected.
• Sensor startup must be complete.
• Calibration must be enabled (see chapter 6.7 "Administrator level", page
27).
• The transmitter must be in "Measurement mode".
Selecting calibration methods
Initiate calibration using the key (or via the administrator level).
Select "2-POINT CALIB." and start calibration with the key.
Selecting the measuring range
Select the measuring range to be calibrated (0 to 200 in the following exam-
ple) using the and keys.
CAUTION!
The response of the outputs during calibration depends on their configuration.
Start calibrating the zero point using the key.
70
Calibrating the zero point
Bring the sensor to the defined state 0 NTU by submersing it in distilled
water. To avoid measuring errors, the distance to the vessel wall must not
be below the minimum distance of 20 mm.
NOTE!
For flawless measurements, make sure that there are no air bubbles on the optics of the submerged sensor. In addition, it must ensured that the sensor is protected against ambient light, above all sunlight, during the measurements.
Wait until the displayed value is stable at "0 NTU" or has stabilized near this
value.
8 Calibrating sensors
Confirm with the key; the display switches to "MEAS. SLOPE".
Calibrating the slope
To calibrate the slope, a formazine reference solution is created according to ISO 7027 with the known turbidity value according to the following table:
Remove the sensor from the distilled water and submerge it in the for-
Measuring range Reference solution
0to50NTU 0to200NTU 0to1000NTU 0to4000NTU
mazine reference solution with the known turbidity value. To avoid measur-
40 NTU
100 NTU
500 NTU
2000 NTU
71
8 Calibrating sensors
ing errors, the distance to the vessel wall must not be below the minimum
distance of 20 mm.
The device suggests the reference value "100.0 NTU" (flashing) for the calibra­tion of the measuring range (0 to 200 NTU) selected in this example.
Set the exact reference value (in this example 112.0 NTU) using the and
keys.
Wait until the measured value (MEASUREMENT) has stabilized.Confirm with the key.
The values determined for the zero point comparison and the slope deviation from the factory calibration along with the corrected measured value are dis­played.
Use the key to apply the calibration or the key to reject the calibra-
tion. The device returns to measurement mode.
NOTE!
The calibration process can be interrupted at any time (e.g. in case of fault messages of the device) with the key and then restarted.
72

8.3.3 Calibration logbook

The data records for the last 10 successful calibrations are saved in the con­nected sensor, are extracted by the JUMO AQUIS 500 RS, and can be viewed in the calibration logbook.
Accessing the calibration logbook
The device is in measurement mode.
Press the key for more than 2 seconds.Use the key to select the "CALIBR. LOGBOOK" entry.Confirm with the key.
The data for the last successful calibration is displayed; in the example described the values for zero point and slope (deviation from the factory cali­bration) and the selected measuring range of the 2-point calibration:
8 Calibrating sensors
As not all of the data for the 2-point calibration fits on one page in the display, you can use the key to access further data from the calibration data record for the 2-point calibration:
Use the and keys to access all other stored calibration data records.
NOTE!
Irrespective of the unit selected in the basic settings, calibrations are always conducted in NTU. The last determined calibration data record is always the top entry in the list.
73

9 Setup program

(1)
(2)
(3)

9.1 Function

Configurable parameters
The optionally available setup program (part no.: 00483602) and optionally available PC interface cable with USB/TTL converter (part no.: 00456352) can be used for convenient adjustment of the transmitter to the requirements:
• Setting the measuring range
• Setting the behavior of outputs in the event of an overrange
• Setting the functions of the switching outputs K1 and K2
• Setting the functions of the binary input E1
• Setting the controller functions
• Setting the password
• Setting a customer-specific characteristic line
•etc.
NOTE!
Data transfer from or to the transmitter can only take place if it is supplied with voltage – See chapter 5 "Installation", page 15 ff.
Connection
74
(1) JUMO AQUIS 500 RS (2) PC interface cable with USB/TTL converter, part no.: 00456352 (3) PC or notebook

10 Overcoming errors and malfunctions

Problem Possible causes Measures
No measured value dis­play or no current output
Measured value display 0000 or current output 4 mA
Incorrect or unstable measured value display
Measured value display 8888, Temperature display "ok", flashing
No voltage supply Check voltage supply
Sensor not submerged in medium Container level too low
Flow fitting blocked Clean flow fitting Sensor measurand
unsuitable or sensor faulty
Sensor measurand unsuitable
Sensor not positioned correctly Select different installation loca-
No through-mixing Ensure homogeneous medium.
Air bubbles disrupt the measure­ment
Overrange Select suitable measuring range Connected sensor faulty Replace connected
Top up container
Clean sensor Replace sensor
Clean sensor Calibrate sensor Replace sensor
tion
Ensure sensor has rinsing flow on all sides
Optimize mounting
sensor
Measured value display 8888, Temperature display 8888 flashing
Problem Possible causes Measures
Temperature overrange or under­range
Temperature probe short-circuit or open circuit
Open circuit Replace sensor or cable No sensor connected Connect sensor
Short circuit
- Cable
- Sensor
- Terminals Temperature too high Keep within admissible range
The temperature of the medium must be within the admissible range.
Replace sensor Replace sensor or cable
Configure sensor on device Check cables and connections.
Replace sensor.
75
10 Overcoming errors and malfunctions
Temperature too low Keep within admissible range
Input signal too low Check configuration
Concentration outside of admissi­ble range
Input signal too high Check configuration
Temperature is above or below the compensation range
Parameter is not enabled Enable parameter in the enable
Password incorrect Correct password read-out using
Key lock was activated by the binary input
Check concentration
Check temperature
level
the setup program
Revoke binary input control
Modbus communication to sen­sor impaired
A sensor other than the configured sensor was found on the bus (e.g. type 202670/... instead of type 202613/...)
The sensor has indicated a fault to the JUMO AQUIS 500; sensor is not operating within its specified measuring range
1.Ex factory, the device is pre-configured for the connection of a type 202613/... sensor. If e.g. a type 202670/ ... sensor ist connected, the device has to be configured for this sensor, see chapter 7.2.3 "Turbidity mea­surement", page 51.
Check for disconnected/broken/ short-circuited cables
Check for incorrect baud rates or parity settings
Check for incorrectly configured sensor address
Connect suitable sensor type or configure suitable sensor
type on the device
Perform calibration
1
76

11.1 Digital interface

11 Technical data

Main input Display range Accuracy Temperature influ-
ence
RS485 interface with Mod­bus master function
0.000 to 9.999
00.00 to 99.99
000.0 to 999.9 0000 to 9999
Depends on the sensor used
Depends on the sensor used
Baud rate
2400 Bd 4800 Bd 9600 Bd 19200 Bd 38400 Bd

11.2 Analog temperature input

Auxiliary input Measuring range Accuracy Temperature influence Temperature Pt100
(automatic detection) Temperature Pt1000
(automatic detection) Temperature NTC/PTC Max. 4 kOhm
a
Can be changed to °F.
b
Depending on the supporting points.
-50to+250°C
Input via table with 20 pairs of values via setup program
a
± 0,5_K (up to 100 °C) ± 0,8_K (as of 100 °C)
± 0,5_K (up to 100 °C) ± 1,0_K (as of 100 °C)
0.3 %
b
0.05 %/10 K
0.05 %/10 K

11.3 Sampling rate

Analog temperature input
500 ms Adjustable,
Digital interface with JUMO ecoLine O-DO
1to60s
Digital interface with JUMO tecLine 20263x
500 ms 1 s Adjustable,
Digital interface with JUMO ecoLine NTU
Digital interface with freely config­urable sensor
1to60s

11.4 Measuring circuit monitoring

Input Underrange/
overrange
Temperature Yes Yes Yes
Short-circuit Open circuit

11.5 Binary input

Activation Via potential-free contact Function Key lock/HOLD/alarm stop

11.6 Controller

Controller type Limit value controller, pulse length controller, pulse frequency controller,
three-step controller, continuous controller
Controller structure P/PI/PD/PID
77
11 Technical data

11.7 Analog outputs (maximum 2)

Output type Signal range Accuracy Temperature
influence
Current signal 0(4) to 20 mA ≤ 0.25 % 0.08 %/10 K ≤ 500 Ω Voltage signal 0 to 10 V ≤ 0.25 % 0.08 %/10 K ≥ 500 Ω The analog outputs behave according the NAMUR NE43 recommendation.
They are galvanically isolated: AC 30 V/DC 50 V.
Admissible load resistance

11.8 Switching outputs (maximum 2 changeover contacts)

Rated load 3 A / AC 250 V (resistive load) Contact life > 2 × 10
5
switching operations at rated load

11.9 Voltage supply for sensors

Voltage supply for digital sensors
Voltage supply for inductive proximity switch
a
for example type EI1808 NPOSS
a
DC 24 V (20.4 to 28.8 V), max. 30 mA DC 5 V (5.1 to 5.25 V), max. 100 mA; max. pulse load 500 mA for 20 ms
ED 5 %, not short-circuit proof DC 12 V (10 to 20 V), max. 10 mA

11.10 Setup interface

Interface for configuration of the device with optional setup program (for device configuration only)

11.11 Electrical data

voltage supply AC 110 to 240 V; -15/+10 %; 48 to 63 Hz
AC/DC 20 to 30 V, 48 to 63 Hz DC 12 to 24 V; +/-15 %
(connection only admissible to SELV/PELV circuits) Power consumption approx. 14 VA Electrical safety DIN EN 61010, Part 1
Overvoltage category III Electrical connection Screw terminals
Conductor cross section max. 2.5 mm
(voltage supply, relay outputs, sensor inputs)
Conductor cross section max. 1.5 mm
(analog outputs, voltage supply for sensors) Electromagnetic
compatibility (EMC)
Interference emission Class B Interference immunity Industrial requirements
a
Not valid for protective extra-low voltage of power supply unit variants DC 12 to 24 V.
EN 61326-1
a
, pollution degree 2
2
2
78
11 Technical data

11.12 Display

LCD display 120 × 32 pixels Background lighting Programmable:
•Off
• 60 seconds "ON" during operation

11.13 Case

Material ABS Cable inlet Cable glands, max. 3× M16 and 2× M12 Special feature Ventilation element for prevent of condensation
(on IP 67 surface-mounted case version) Ambient temperature range -10 to +50 °C (accuracy figures are adhered to in this range) Operating temperature
range Storage temperature range -30 to +70 °C Resistance to climatic con-
ditions Protection types
acc. to EN 60529 Resistant to vibration Acc to. DIN EN 60068-2-6
Weight Approx. 900 g
-15 to +65 °C (device functioning)
Rel. humidity 90 % annual average, no condensation
(derived from DIN EN 60721 3-3 3K3)
Surface-mounted case: IP67
Panel installation: front IP65, rear IP20

11.14 Approvals/marks of conformity

Mark of conformity
c UL us Underwriters Laboratories E 201387 UL 61010-1
Testing laboratory Certificates/certification
numbers
Test basis valid for
CAN/CSA C22.2 No. 61010-1
all types
79

12 Appendix

12.1 Operator level parameters

If a large number of device parameters are to be configured, it is advisable to make a note of all the parameters to be changed in the following table and to work through the parameters in the order specified.
NOTE!
The following list shows the maximum number of changeable parameters. Depending on the configuration, some parameters may not be visible or edit-
able on your device.
Parameter Selection/value range
per default
RS485 input
Zero point -9999 to 0 to +9999 Slope 50 to 100 to 200 % Zero -999.9 to +999.9 nA Span 0.00001 to +999.9 nA/ppm or pA/ppm Baud rate 2400
4800
9600
19200 38400
Parity None
Odd Even
Stop bits 1
2
Device address 1 to 255 Address temperature 0 to 1 to 65535 Address main value 0 to 1 to 65535 Address of uncompen­sated main value
0to1 to 65535
New
setting
80
12 Appendix
Parameter Selection/value range
per default
Main value unit (only for freely configurable sensor)
Uncompensated main value unit (only for freely configurable sensor)
Byte order float mixed endian
Unit for sensor type 202613/... (only via basic setting)
Unit for sensor type 202670/...
None
‰ % %Sat ppb ppm µg/l mg/l g/l µs/cm ms/cm kΩ MΩ nA µA mA mV pH Customer-specific
None
‰ % %Sat ppb ppm µg/l mg/l g/l µs/cm ms/cm kΩ MΩ nA µA mA mV pH Customer-specific
little endian big endian
%Sat
mg/l ppm
NTU
FNU
New
setting
81
12 Appendix
Parameter Selection/value range
per default
Measurand for sensor type 20263x/...
Unit for sensor type 20263x/...
Temperature compensa­tion source
Salinity 0 to 100 g/kg Air pressure 500 to 1013 to 1500 hPa Sampling rate 1 to 10 to 60 s Filter time constant 0 to 2 to 25 s Calibration interval 0 to 999 days (0 = deactivated)
Temperature input
Sensor type Modbus
Unit °C
Filter time constant 0 to 2 to 25 s Manual temperature entry Offset -20.0 to 0.0 to +20.0 °C
Binary input Function No function
Controller channel 1
Controller type No function
Setpoint value Depending on device variant Second setpoint value (only for three-step control-
ler for controller 1)
Free chlorine
Tot al chlorine Ozone Hydrogen peroxide Peracetic acid
ppm
mg/l ppb µg/l
%
‰ g/l
Internal
External
No sensor Pt100/Pt1000 Customer-specific
°F
-50.0 to +25.0 to +250.0 °C
Key lock Hold mode Alarm stop (only for controller)
Limit value controller Pulse frequency output Pulse length output Continuous controller Three-step controller
Depending on device variant
New
setting
82
12 Appendix
Parameter Selection/value range
per default
Min./max. contact (falling/rising characteristic line) Proportional band 0 to 9999 (decimal places configurable) Reset time 0 to 9999
Derivative time 0 to 9999 Pulse period 2.5 to 20 to 999.5 Actuator time (only for three-step control­ler for controller 1) Hysteresis (of limit value controller) Minimum start time 0.5 to 999.5 maximum pulse frequency 0 to 60 rpm Output level limit 0 to 100 % ON-delay 0.00 to 999.5 s OFF-delay 0.00 to 999.5 s Limit value controller
monitoring Alarm tolerance 0 to 1 to measuring range end Alarm delay 0 to 9999 s Response at hold LOW
Hold value 0 to 100 % Response in case of error 0%
Min. setpoint limit 0 to 9999 (decimal places configurable) Max. setpoint limit 0 to 9999 (decimal places configurable)
Controller channel 2
Controller type No function
Setpoint value Depending on device variant Second setpoint value (only for three-step control-
ler for controller 1) Min./max. contact
(falling/rising characteristic line) Proportional band 0 to 9999 (decimal places configurable)
Reset time 0 to 9999 Derivative time 0 to 9999
Min. contact
Max. contact
15 to 60 to 3000 s
0to200 to 9999 (decimal places configurable)
OFF
ON
HIGH
FROZEN
SAFE VALUE
100% Frozen Hold value
Limit value controller Pulse frequency output Pulse length output Continuous controller
Depending on device variant
Min contact
Max. contact
New
setting
83
12 Appendix
Parameter Selection/value range
per default
Pulse period 2.5 to 20 to 999.5 Actuator time
(only for three-step control­ler for controller 1) Hysteresis (of limit value controller) Minimum start time 0.5 to 999.5
maximum pulse frequency 0 to 60 rpm Output level limit 0 to 100 % ON-delay 0.00 to 999.5 s OFF-delay 0.00 to 999.5 s Limit value controller monitoring Alarm tolerance 0 to 1 to measuring range end Alarm delay 0 to 9999 s Response at hold 0 %
Hold value 0 to 100 % Response in case of error 0%
Min. setpoint limit 0 to 9999 (decimal places configurable) Max. setpoint limit 0 to 9999 (decimal places configurable)
Special controller functions
Manual mode No manual mode admissible
Isolated controller OFF
I-proportion switch-off Yes
15 to 60 to 3000 s
0to200 to 9999 (decimal places configurable)
OFF
ON
100 %
Frozen
Hold value
100% Frozen Hold value
Momentary Permanently
ON
No
New
setting
84
12 Appendix
Parameter Selection/value range
per default
Switching output 1
Function No function
Controller output 1 Controller output 2 Controller alarm 1 Controller alarm 2 Controller alarm
AF1 main value AF2 main value
AF7 main value
AF8 main value
AF1 temperature
AF2 temperature
AF7 temperature
AF8 temperature
New
setting
Sensor error Wash timer expired Calibration timer expired
Switching point 0 to 9999 Margin to switching point Window range for AF1 / AF2 Hysteresis 0 to 100 % of MR or
switch-on delay 00:00:00 to 01:00:00 H:M:S Switch-off delay 00:00:00 to 01:00:00 H:M:S Pulse time For calibration Inactive
In case of fault Inactive
In hold mode Inactive
Manual mode No simulation
a
0 to 50 % of MR or 0 to 150 °C
-50 to +250 °C
00:00:00 to 01:00:00 H:M:S
Active Status retained
Active Status retained
Active Status retained
Inactive Active
a
For pulse times greater than 0 seconds, the OFF-delay is automatically deactivated.
85
12 Appendix
Parameter Selection/value range
per default
Switching output 2
Function No function
Controller output 1 Controller output 2 Controller alarm 1 Controller alarm 2 Controller alarm
AF1 main value AF2 main value
AF7 main value
AF8 main value
AF1 temperature
AF2 temperature
AF7 temperature
AF8 temperature
New
setting
Sensor error Wash timer expired Calibration timer expired
Switching point 0 to 9999 Margin to switching point Window range for AF1 / AF2 Hysteresis 0 to 100 % of MR or
switch-on delay 00:00:00 to 01:00:00 H:M:S Switch-off delay 00:00:00 to 01:00:00 H:M:S Pulse time For calibration Inactive
In case of fault Inactive
In hold mode Inactive
Manual mode No simulation
a
0 to 50 % of MR or 0 to 150 °C
-50 to +250 °C
00:00:00 to 01:00:00 H:M:S
Active Status retained
Active Status retained
Active Status retained
Inactive Active
a
For pulse times greater than 0 seconds, the OFF-delay is automatically deactivated.
86
12 Appendix
Parameter Selection/value range
per default
Analog output 1
Signal selector Actual value for main value / temperature
Continuous controller output 1 Continuous controller output 2
Signal type 0 to 10 V
0to20mA
4to20mA
10 to 0 V 20 to 0 mA
20 to 4 mA Scaling start of main value Depending on measurand and measuring range Scaling end of main value Depending on measurand and measuring range Response during calibra-
tion
Response in case of error Low (0V/0mA/3.4mA)
Response in hold mode Low (0V/0mA/3.4mA)
Safety value 0 to 10.7 V
Simulation OFF
Simulation value 0 to 10.7 V
Moving
Frozen
Safe value
High (10.7 V/22 mA)
Frozen
Safe value
High (10.7 V/22 mA)
Frozen
Safe value
Moving
0 to 22 mA
ON
New
setting
0 to 22 mA Analog output 2
Signal selector Actual value for main value / temperature
Continuous controller output 1
Continuous controller output 2 Signal type 0 to 10 V
0to20mA
4to20mA
10 to 0 V
20 to 0 mA
20 to 4 mA Scaling start of main value Depending on measurand and measuring range Scaling end of main value Depending on measurand and measuring range Response during calibra-
tion
Moving
Frozen
Safe value
87
12 Appendix
Parameter Selection/value range
per default
Response in case of error Low (0V/0mA/3.4mA)
High (10.7 V/22 mA)
Frozen
Safe value Response in hold mode Low (0V/0mA/3.4mA)
High (10.7 V/22 mA)
Frozen
Safe value
Moving Safety value 0 to 10.7 V
0 to 22 mA Simulation OFF
ON Simulation value 0 to 10.7 V
0 to 22 mA Display
Language German
English
French
Customer-specific Lighting During operation
Off LCD inversion OFF
ON Measured value display
type
Display on bottom Tem pe ra tu re
Display on top Compensated
Max./min. reset No
Operation timeout 0 to 1 to 10 min (the operation timeout is deacti-
Contrast 0 to 8 to 20
Normal
Tren d
Bar graph
Output level 1
Output level 2
Setpoint value 1
Setpoint value 2
None
Compensated
Uncompensated
Uncompensated
Temperature
Output level 1
Output level 2
Setpoint 1
Setpoint 2
None
Ye s
vated when the setting is "0")
New
setting
88

12.2 Parameter explanation

HySt
x
0
w
AF
1
HySt
0
w
AF
x
1
HySt
x
w
0
1
HySt
w
x
0
1
FUNCTION
NO FUNCT.
Alarm window AF1 MAIN VALUE
Alarm window AF2 MAIN VALUE
Limit value controller AF7 MAIN VALUE
Limit value controller AF8 MAIN VALUE
Alarm window AF1 TEMPERAT.
Alarm window AF2 TEMPERAT.
Limit value controller AF7 TEMPERAT.
Limit value controller AF8 TEMPERAT
SENSOR ERROR
CALIB. TIMER
12 Appendix
Alarm window AF1 Alarm window AF2
Limit value function AF7 Limit value function AF8
89
12 Appendix
t
0
t
P
Pulse contact
t
Trigger condition
1
0
1
t
t
P
Pulse contact
t
Trigger condition
0
1
0
1
(3)
(1)
(2)
Alarm pulse contact Trigger condition longer than pulse duration
Alarm pulse contact Trigger condition shorter than pulse duration
0Off t Time 1On t
P
Pulse duration AF Spacing w Setpoint value / limit value HySt Hysteresis x Actual value / measured
value
MEAS. DISPLAY TYPE
NORMAL
TREND BAR GRAPH
NORMAL In the normal display, the measured value, measurand, and temperature of the
medium are displayed.
(1)
Operation mode
(2)
Display on bottom (temperature)
(3)
Display on top (measured value of main input)
TREND The operator can quickly identify in which direction the measured value is
changing.
90
12 Appendix
Rising
Stable
Sharp Medium Slight Slight Medium Sharp
NOTE!
The measured value trend is calculated from the last 10 measured values. At a sampling rate of 10 s, the last 100 seconds are taken into account.
BAR GRAPH • The measured value for the digital input (main input variable) is shown as
a variable bar
• There is no temperature display
• For devices with configured control contact(s), the setpoint values are marked above the bar graph with arrows
Falling
Scaling the bar
Activate the "BAR GRAPH" measured value display typeUse to select "BARGR. SCALE START"Use to confirm selectionUse or to enter the lower limit of the range for displayUse to confirm selectionUse to select "BARGR. SCALE END"Use or to enter the upper limit of the range for displayUse to confirm selection
NOTE!
To return to measurement mode: Press the key several times or wait for timeout.
91
12 Appendix
(3)
(1)
(2)
DISPLAY ON BOTTOM
NOTE!
The "DISPLAY ON BOTTOM" and "DISPLAY ON TOP" parameters are only available for the "NORMAL" or "TREND" measured value display types, but not for the "BAR GRAPH" measured value display type.
(1) (2) (3)
Operation mode Display on bottom Display on top
DISPAY ON TOP
The "bottom" display can be assigned the following values: This parameter is only available with the "NORMAL" or
"TREND" measurement display type.
TEMPERATURE
OUTP. LEVEL 1 OUTP. LEVEL 2 SETPOINT 1 SETPOINT 2 NONE COMPENSATED UNCOMPENSATED
The "top" display can be assigned the following values:
COMPENSATED
UNCOMPENSATED TEMPERATURE OUTPUT LEVEL 1 OUTPUT LEVEL 2 SETPOINT VALUE 1 SETPOINT VALUE 2 NONE
92
12 Appendix
Process value X
Setpoint W
Proportional band X
P
100%
50%
0%
Output level y
Switching period
10%
90%
90%
10%
t
On
50%
50%
t
Off
10%
90%
X
P
X - W
0
1
100%
50%
0%
No pulses
50% of pulse frequency
Maximum pulse frequency
Setpoint W
Proportional band X
P
X
P
X - W
0
1
Output level y
Process value X

12.3 Term definition

Pulse length controller (output active when x > w and control structure P)
Pulse frequency controller (output active when x > w and control structure P)
Calibration timers
If the actual value x exceeds the setpoint value w, the P-controller controls in proportion to the control deviation. When the proportional band is exceeded, the controller operates with an output level of 100 % (100 % cycle ratio).
If the actual value x exceeds the setpoint value w, the P-controller controls in proportion to the control deviation. When the proportional band is exceeded, the controller operates with an output level of 100 % (maximum switching fre­quency).
The calibration time can (optionally) notify of the need to conduct routine cali­bration. The calibration timer is activated by entering the number of days after which recalibration should be scheduled (plant or operator-specified).
93
12 Appendix
Customer-specific table
In this mode, you can use the optionally available setup program (no entry can be made on the device) to create a customer-specific characteristic line in the form of a table with up to 20 pairs of resistance/temperature values for the analog temperature input. NTC and PTC characteristic lines are possible; they must be monotonous.
Max./min. value memory
This memory stores the minimum and maximum input values. This information can be used to evaluate whether the connected sensor is designed for the actually occurring values, for example.
The max./min. value memory can be reset: Operator level / Display / MIN/MAX RESET / Yes, see "Operator level parameters", page 80ff.
Special controller functions:
The following functions can be activated in this menu:
• Manual mode (activate controller outputs manually) – See chapter 6.10.4 "MANUAL/simulation overview", page 38
• Isolated controller (see below)
• I-proportion switch-off (see below)
Isolated controller
This function is normally deactivated (default settings or "no" selected). In the deactivated state, the software prevents two controller outputs from
working "against each other". This means that simultaneous dosing of acid and lye is not possible.
If the controllers are isolated ("yes" selected), both controllers are freely con­figurable.
I-proportion switch-off
This function is normally deactivated (default settings or "no" selected). In the deactivated state, the controller operates according to the general con-
troller theory. If I-proportion switch-off is activated ("yes" selected), the share of the output
level to which the I-proportion is attributed is set to zero when the setpoint value is reached.
This may beneficial for mutual neutralization (acid and lye dosing possible) in one treatment tank.
94

12.4 Flow diagram of the basic setting wizard

initialize
?
initialize
device
cancel
settings
yesyesnono
Start of the
basic setup wizard
configure
sensor
automatically
?
nono
sensor
found
?
yesyes
M
yesyes
nono
M
type 202613type 202613type 202670type 202670
unit,
decimal place,
temperature sensor
type 20263xtype 20263x
salinity,
air pressure,
unit,
sampling rate,
temperature sensor
MODBUS NO SENSOR PT100/PT1000 CUSTOMIZED
set set
select
temperature
compensation
source
NO SENSOR
MODBUS
PT100/PT1000
CUSTOMIZED
set
temperature
measuring range,
unit,
temperature sensor
set
NO SENSOR
MODBUS PT100/PT1000 CUSTOMIZED
set
temperature
set
temperature
select
temperature
compensation
source

12.4.1 Automatic configuration of a sensor

12 Appendix
95
12 Appendix
M
NO SENSOR
MODBUS PT100/PT1000 CUSTOMIZED
set
temperature
select sensor type
baud rate,
parity,
stop bits,
device address,
byte order,
sampling rate,
main value decimal point,
main value unit,
main value address,
uncomp. main value dec. point,
uncomp. main value unit,
uncomp. main value address,
temperature address
1
set
measuring range,
unit
set
device address,
salinity,
air pressure,
unit,
sampling rate,
compensation source
1
set
baud rate,
parity
measurand,
unit,
decimal place
set
type 202670type 202670 type 202613type 202613
type 20263xtype 20263x
otherother
initialize
?
initialize
device
cancel
settings
yesyesnono
set
temperature sensor
1
Only for temperature sensor = MODBUS

12.4.2 Manual configuration of a sensor

96
12 Appendix
97
12 Appendix

12.5 Template for panel cut-out

98

13 Index

A
Accessories 10 Administrator level 27 Analog output 30
B
Basic settings 32 Binary input 74 Block diagram 7
C
Cable routing 18 CAL key 32 Calib. logfile 62, 73 Calibrating sensor type 202613/... 56
2-point calibration 59 End (final) value calibration 57
Calibrating sensor type 20263x 63
End value calibration 64
Calibrating sensor type 202670/...
2-point calibration
Calibrating the sensor type 202670/... 69 Calibration 56 Calibration enable 32 Calibration level 32 Calibration logbook 68 Calibration timers 93 Calibrationg sensor type 20263x
Two-point calibration
Conductor cross sections 15 Configurable parameters 74 Controller channel 30 Controller functions 34, 74 Customer-specific characteristic line 74 Customer-specific table 94
70
66
D
Data transmission 74 Deleting the logbook 33 Device information 33 Device status 23 Direct sunlight 11 Display 23, 31
bar graph 91 bottom 92 normal 90 top 92 trend 90
E
Electrical connection
Flow monitor Type 202613/... 42 Type 20263x/50... or /51... 47 Type 202670/... 52
Enable level 29 Example setting
Measuring dissolved oxygen Measuring free chlorine 46 Turbidity measurement 51
Examples of settings 41
47
41
G
Galvanic isolation 16
H
Higher order switching functions 34 HOLD mode 39
delay time 39
I
Input
binary RS485 29
temperature 29 Inputs 20 Installation position 11 I-proportion switch-off 94
29
M
MANUAL mode for analog outputs 38 MANUAL mode for switching outputs 35 MANUAL mode overview 36 Max./min. value memory 94 Measurement mode 25 Measuring range 74 Min./max. values 25 Mounting brackets 11 Mounting in a panel 13 Mounting site 11
N
Nameplate 8 Note symbols 5
O
Offset 29, 44, 82
Note: This index is not intended to be exhaustive! Please read the operating instructions before starting up the device!
99
13 Index
Opening the device 17 Operating principle 24 Operator 27 Operator level 27 operator level parameters 80 Order details 9 Output 26 Output level display 26 Outputs 21 Overcoming errors and malfunctions 75 Overrange 7475
P
Panel installation 13 Parameter explanation 89 Parameter level 29 Parameter table 80 Password 27, 74, 76 Pin configuration 20 Pipe mounting 12 Pulse frequency controller 93 Pulse length controller 93
Q
Quick introduction 40
R
Resetting the sensor calibrations 33
S
Scaling 30 Searching for sensors 32 Sensor replacement 32 Setup program 74 Simple switching functions 34 Simulation mode 35 Special controller function 94 Surface mounting 11 Switching functions
higher order
simple 34 Switching output 30, 74 Switching output simulation 37
34
V
Voltage supply 20
W
Warning symbols 5 Washtimer 31 Weather protection canopy 12
100
Loading...