Indoor, outdoor and channel RTD
temperature probe
■ For temperatures from -50 ... +90 °C (200 °C)
■ For application in the air conditioning technology
■ Protection class IP20 to IP65
■ Connection: in 2-wire, 3-wire or 4-wire circuit
■ Available with 4 ... 20 mA or 0 ... 10 V transmitter
Indoor, outdoor and channel RTD temperature probes for air conditioning technology are mainly
used for temperature measurement in rooms, in air channels and outdoors.
Various device versions made of plastic with different protection classes are available for the
respective measuring task.
The measuring insert is normally fitted with a Pt 100 temperature probe as per DIN EN 60751,
Class B in 2-wire circuit, versions with Pt500, Pt1000 or Ni1000 can also be supplied. From the
connection terminals, wiring in 3-wire and 4-wire circuit is also possible.
A transmitter can be optionally integrated.
Data sheet 90.2520 (90.2523) Page 1/7
Technical Data
Connection case Plastic case PC (basic type 902520/11 material PP), IP20 to IP65,
basic type 902524/25 protection class IP54 and IP65
Sheath Stainless steel 1.4571; Ø 5.4 mm, Ø 6 mm
Measuring insert Pt100 temperature probe, DIN EN 60751, class B, 2-wire circuit
Transmitter Analog transmitters, output signal 4 ... 20 mA or 0 ... 10 V
Pt1000 temperature probe, DIN EN 60751, class B, 2-wire circuit,
For further probes, refer to the order details
2011-05-20/00311507
Data sheet 90.2520 (90.2523) Page 2/7
JUMO GmbH & Co. KG
Delivery address:Mackenrodtstraße 14,
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
e-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
e-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone: 315-697-JUMO
1-800-554-JUMO
Fax: 315-697-5867
e-mail: info@jumo.us
Internet: www.jumo.us
- ++-
+
-
+
-
4 - 20mA
IndicatorController
2-wire
transmitter
Supply unit
7.5 - 30V DC
+ --+
+
-
-
+
0 - 10V
IndicatorController
3-wire
transmitter
Supply unit
15 - 30V DC
+
0 - 10V
L1
N
81
8382
15 - 30V DC
Supply voltage
TerminalConnection for
Voltage output
0 - 10V
+ 81
- 82
- 82
+ 83
81+83
+
Load 10k≥Ω
Output 0 - 10V
82
-
Output 4 - 20mA
22mA
- 7.5V
b
U
B
R =
R
B
= burden resistance
b
= supply voltage
U
-
82
+
81
- 82
+ 81
Current output
4 - 20mA
Supply voltage
7.5 - 30V DC
TerminalConnection for
Transmitter Output 4 ... 20 mA Output 0 ... 10 V
Input
Measuring input Pt100 (DIN EN 60751)
Probe current ≤ 0.5 mA
Measuring range Permanent measurement due to analog signal path
Measuring circuit monitoring
Underrange dropping to ≤ 3.6 mA 0 V
Overrange increasing to ÷ 22 mA ... < 28 mA (typical
24 mA)
increasing to ÷ 11 V... < 14 V
(typical 12 V)
Probe short-circuit ≤ 3.6 mA 0 V
Probe and wire break ÷ 22 mA ... < 28 mA (typical 24 mA) ÷ 11 V... < 14 V (typical 12 V)
Output
Output signal load-independent direct current 4 ... 20 mA Direct current 0 ... 10 V
Transmission behavior temperature linear
Transmission accuracy ≤ ±0.1% ≤ ±0.2%
Damping of the residual ripple
of a voltage supply of 24 V,
amplitude 10 V/50 Hz,
burden 470 Ω/Load 10MΩ
37 dB 40 dB
Burden (Rb) Rb = (Ub - 7.5 V) / 22 mA Burden influence
≤ ± 0.02 % / 100 Ω
1
-
Load/load influence - ÷ 10 kΩ / ≤ ±0.1%
Setting time for temperature changes ≤ 10 ms
Adjustment conditions DC 24 V / approx. 22 °C
Calibration accuracy
≤ ±0.2%
1,2
or ≤ ±0.2K
Overall accuracy, probe/calibration ± 0.4 K (typical) at 20 °C / 24 V voltage supply
Voltage supply
Voltage supply (Ub) DC 7.5 ... 30 V DC 15 ... 30 V
Reverse voltage protection yes
Voltage supply influence
≤ ± 0.01 %/V deviation from 24 V
1
Environmental influences
Operating temperature range -40 ...+ 85 °C
Storage temperature range -40 ... +100 °C
Temperature coefficient
Ambient conditions
similar to DIN EN 60654 Kl. C1
EMC Interference emission/
resistance
1. All specifications referring to the measuring range limit value of 20mA. 2. The higher value is valid.
relative humidity ≤ 95 % annual average, no condensation
EN 61326 class B/Industrial requirements
≤ ± 0.01 %/K deviation from 22 °C
1
Connection example with power pack, output 4 ... 20 mAConnection example with power pack, output 0 ... 10 V
Connection diagram
2011-05-20/00311507
JUMO GmbH & Co. KG
Delivery address:Mackenrodtstraße 14,
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
e-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
e-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone: 315-697-JUMO
1-800-554-JUMO
Fax: 315-697-5867
e-mail: info@jumo.us
Internet: www.jumo.us
Dimensions
Data sheet 90.2520 (90.2523) Page 3/7
Basic type 902520/10 Basic type 902520/11 Basic type 902520/12
Basic type 902520/13 Basic type 902520/15 Basic type 902524/20
2011-05-20/00311507