Joslyn Hi-Voltage TransEnd - 25 Data Sheet

SURGE PROTECTIVE DEVICES
TransEnd® – 25
MEDIUM DUTY FOR DISTRIBUTION APPLICATIONS
FEATURES AND BENEFITS
Listed to UL 1449 4th Edition for a Type 2 SPD application.
Protects facilities and equipment against the harmful effects of
lightning strikes and internally generated electrical transients.
Includes pre-wired pigtail conductors to streamline installation.
Features internal copper bus conduction path to minimize system
impedances, lowering clamping voltage and increasing protection.
AVAILABLE CONFIGURATIONS
Model Number Voltage Configuration
XN25-120/240-2G 120/240V 1-Phase, 3-Wire + Ground XN25-120/208-3GY 120/208V 3-Phase Wye, 4-Wire + Ground XN25-220/380-3GY 220/380V 3-Phase Wye, 4-Wire + Ground XN25-120/240-3GHD 120/240V 3-Phase High-Leg Delta, 4-Wire
Warranty
5-years
Available Option
Dry Form "C" Relay Contacts Add suffix -FC
Stand Alone Options (To be ordered as a Seperate Item)
Option A
XN Metallic Conduit Kit Metallic conduit installation kit has a 3/4" (.019 m) x
3" (.076 m) metallic nipple and all associated hardware required to complete the TransEnd installation
Option B
XN Plastic Conduit Kit Flexible plastic conduit installation kit, including 18"
(.457 m) flexible conduit and all associated hardware required to complete the TransEnd installation
EMI/RFI Filter Attenuation
Max. Attenuation Frequency 50dB @ 100kHz
PRODUCT SPECIFICATIONS
Electrical
Maximum Surge Current Rating 50kA per phase, 25kA per mode Nominal Discharge Current Rating (I-n) 20kA Operating Frequency 47–63Hz Connection Methods Parallel to Load (shunt)
24" #10AWG wires
Through 20A (max) breaker Modes of Protection L-N, L-G, N-G, L-L Fault Rating (SCCR) 65kAIC – upstream over-current protection device
(breaker or fuse required) Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED Status Indicator lights
Mechanical
Weight 12.7 lbs. (5.8 kg) Enclosure Type NEMA 4X fiberglass-reinforced polyester (FRP)
surface-mount, non-removable cover Installation Location Indoor/Outdoor Mounting Methods Dual Mounting Flanges Operating Environment -40° to +140°F (-40° to +60°C) Altitude Up to 16,400 ft. (5000 m) Product Design No internal fusing
Regulatory
UL 1449 4th Edition Type Type 2 UL 1283 Yes IEEE C62.41.1, .2, C62.45 Yes Listed By UL
TRANSEND 25 PERFORMANCE DATA
Model Number Voltage Configuration Protection Mode MCOV
L-L 300V 1000V
XN25-120/240-2G 1S240
XN25-120/208-3GY 3Y208
XN25-220/380-3GY 3Y380
XN25-277/480-3GY 3Y480
XN25-120/240-3GHD 3H240
XN25-240-3DG 3D240
XN25-380-3DG 3D380
XN25-480-3DG 3D480
All TransEnd® systems’ Voltage Protection Ratings (VPRs) are peak values taken at the 90° point on the sine wave. Ring Wave values are taken at the 180° point on the sine wave. All data collection is in compliance with testing and evaluation procedures as outlined in ANSI/IEEE C62.45
L-N 150V 600V L-G 150V 600V
N-G 150V 600V
L-L 300V 1000V L-N 150V 600V L-G 150V 600V N-G 150V 600V
L-L 550V 1500V L-N 275V 900V L-G 275V 900V N-G 275V 900V
L-L 552V 1800V L-N 320V 900V L-G 320V 1000V N-G 320V 1000V
L-L 300V 1000V L-N 150V 600V L-G 150V 600V N-G 150V 600V H-L 425V 1500V H-N 275V 900V H-G 275V 900V
L-L 275V 1000V L-G 550V 900V
L-L 550V 1800V L-G 400V 1500V
L-L 640V 1800V L-G 550V 1800V
UL 1449 4th Edition
6kV, 3kA VPR
DIMENSIONS
Dim Inches (mm)
H1 6.17 (156.7)
H2 6.75 (171.5)
H3 7.50 (190.4)
W1 4.01 (101.9)
W2 6.12 (155.4)
D 5.01 (127.5)