SURGE PROTECTIVE DEVICES
JSP – 80
HEAVY DUTY FOR SERVICE ENTRANCE APPLICATIONS
feature S and benefitS
• Listed to UL 1449 3rd Edition for a Type 1 and Type 2 SPD application.
• Fail-safe design with individually fused Metal Oxide Varistors (MOVs)
eliminating single point failure, protecting against both overcurrent and
overvoltage events.
• 200kAIC short circuit rating permits direct bus connection to most
electrical services.
• Low let through voltage ensured by the lowest possible impedance path
to ground and equal current sharing during surge events.
• All weather sealed, powder-coated NEMA 4/IP65 housing is designed
for any orientation and indoor/outdoor applications.
• 10-year standard warranty with optional 15-year extended warranty.
Model Number Voltage Configuration
JSP080-1P120 120V 1-Phase, 2-Wire + Ground
JSP080-1P240 240V 1-Phase, 2-Wire + Ground
JSP080-1S240 120/240V 2-Phase, 3-Wire + Ground
JSP080-3Y208 120/208V 3-Phase, 4-Wire + Ground
JSP080-3Y380 220/380V 3-Phase, 4-Wire + Ground
JSP080-3Y415 240/415V 3-Phase, 4-Wire + Ground
JSP080-3Y480 277/480V 3-Phase, 4-Wire + Ground
JSP080-3H240 120/240V 3-Phase, High-Leg, 4-Wire + Ground
JSP080-3D240 240 (Delta) 3-Phase, 3-Wire + Ground
Warranty
10-years (Optional 15-years)
Available Options
Advanced Monitoring Add suffix -M (Includes Dry Relay Contacts,
Audible Alarm, Alarm Silence Button, Fault Light)
Transient Filter Add suffix -F (Meets UL 1283*)
Stainless Steel Enclosure Add suffix -S
*Not recommended when using telecommunication rectifiers.
Stand Alone Option (To be ordered as a Seperate Item)
JSP-FMP Flush-Mount Plate Kit
EMI/RFI Filter Attenuation
Max. Attenuation Frequency 41dB @ 106kHz
Product SPecificationSavailable configur ationS
Electrical
Maximum Surge Current Rating 80kA per phase, 40kA per mode
Nominal Discharge Current Rating (I-n) 10kA
Operating Frequency 47–63Hz
Connection Method Parallel to electrical distribution system
Modes of Protection All Modes (L-N, L-G, N-G, L-L)
Fault Rating (SCCR) 200kAIC – no upstream over-current protection
device (breaker or fuse) required
Response Time Less than 1 nanosecond
Standard Monitoring Status indicator lights (one per phase)
Mechanical
Weight 10 lbs. (4.5 kg)
Enclosure Type Powder coated, impact-resistance steel,
weather-proof NEMA 4
Installation Location Indoor / Outdoor
Mounting Method Dual mounting flanges
Operating Environment -40° to +185°F (-40° to +70°C)
Altitude Up to 13,000 ft. (4000 m)
Product Design Parallel design with individually fused MOVs
Regulatory
UL 1449 3rd Edition Type Type 1
UL 1283 Yes
IEEE C62.41.1, .2, C62.45 Yes
Listed By ETL
JSP 80 PerforM ance data
ANSI/IEEE C62.41.1-2002, C62.41.2-2002, & C62.45-2002 Measured Limiting Voltage
Model Voltage Protection B3 Ring Wave B3/C1 Combo C3 Combo UL 1449 3rd Edition
Number Configuration Mode MCOV 6kV, 500A Wave 6kV, 3kA Wave 20kV, 10kA 6kV, 3kA VPR
L-N 150V 202V 587V 1078V 600V
JSP080-1P120 1P120 L-G 150V 529V 564V 1157V 600V
N-G 150V 548V 594V 1180V 600V
L-N 320V 180V 1036V 1553V 1200V
JSP080-1P240 1P240 L-G 320V 855V 989V 1483V 1200V
N-G 150V 840V 989V 1470V 1200V
L-N 150V 202V 587V 1078V 600V
JSP080-1S240 1S240
L-L 300V 290V 1029V 1667V 1000V
N-G 150V 548V 594V 1180V 600V
L-N 150V 202V 587V 1078V 600V
JSP080-3Y208 3Y208
L-L 300V 290V 1029V 1667V 1000V
N-G 150V 548V 594V 1180V 600V
L-N 320V 180V 1036V 1553V 600V
JSP080-3Y380 3Y380
L-L 600V 261V 1847V 2520V 1000V
N-G 150V 840V 989V 1470V 600V
L-N 320V 180V 1036V 1553V 1200V
JSP080-3Y415 3Y415
L-L 600V 261V 1847V 2520V 2000V
N-G 150V 840V 989V 1470V 1200V
L-N 320V 180V 1036V 1553V 1200V
JSP080-3Y480 3Y480
L-L 600V 261V 1847V 2520V 2000V
N-G 150V 840V 989V 1470V 1200V
L-N 150V 202V 587V 1078V 600V
H-N 320V 180V 1036V 1553V 1200V
L-G 150V 529V 564V 1157V 600V
JSP080-3H240 3H240 H-G 320V 855V 989V 1483V 1200V
L-L 300V 290V 1029V 1667V 1000V
H-L 470V 840V 1250V 1640V 1500V
N-G 150V 548V 594V 1180V 600V
JSP080-3D240 3D240
L-L 300V 855V 989V 1553V 1000V
All JSPTM systems measured limited voltages are peak values (±10%) measured from the zero reference point and are
in compliance with test and evaluation procedures outlined in NEMA LS1-1992 (2000), paragraphs 2.210 and 3.10.
L-G 150V 529V 564V 1157V 600V
L-G 150V 529V 564V 1157V 600V
L-G 320V 855V 989V 1483V 600V
L-G 320V 855V 989V 1483V 1200V
L-G 320V 855V 989V 1483V 1200V
L-G 320V 855V 989V 1553V 1200V
3/4” MYERS HUB
(D2)
(D1)
© 2014 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A.
12/03/14
(W1)
(W2)
(H1)
ø0.31 (7.87)
(H2)
(H3)
diMenSionS
Dim Inches (mm)
H1 6.00 (152.4)
H2 6.75 (171.5)
H3 7.50 (190.5)
W1 6.00 (152.4)
W2 4.00 (101.6)
D1 4.16 (105.7)
D2 2.00 (50.8)