Joslyn Hi-Voltage JSP – 160 Data Sheet

SURGE PROTECTIVE DEVICES
JSP – 160
HEAVY DUTY FOR SERVICE ENTRANCE APPLICATIONS
FEATURE S AND BENEFITS
Listed to UL 1449 3rd Edition for a Type 1 and Type 2 SPD application.
Fail-safe design with individually fused Metal Oxide Varistors (MOVs)
eliminating single point failure, protecting against both overcurrent and overvoltage events.
200kAIC short circuit rating permits direct bus connection to most
electrical services.
Low let through voltage ensured by the lowest possible impedance path
to ground and equal current sharing during surge events.
All weather sealed, powder-coated NEMA 4/IP65 housing is designed
for any orientation and indoor/outdoor applications.
10-year standard warranty with optional 15-year extended warranty.
Model Number Voltage Configuration
JSP160-1P120 120V 1-Phase, 2-Wire + Ground JSP160-1P240 240V 1-Phase, 2-Wire + Ground JSP160-1S240 120/240V 2-Phase, 3-Wire + Ground JSP160-3Y208 120/208V 3-Phase Wye, 4-Wire + Ground JSP160-3Y380 220/380V 3-Phase Wye, 4-Wire + Ground JSP160-3Y415 240/415V 3-Phase Wye, 4-Wire + Ground JSP160-3Y480 277/480V 3-Phase Wye, 4-Wire + Ground JSP160-3Y600 347/600V 3-Phase Wye, 4-Wire + Ground JSP160-3H240 120/240V 3-Phase High-Leg, 4-Wire + Ground JSP160-3D240 240V 3-Phase Delta, 3-Wire + Ground JSP160-3D380 380V 3-Phase Delta, 3-Wire + Ground JSP160-3D480 480V 3-Phase Delta, 3-Wire + Ground JSP160-3D600 600V 3-Phase Delta, 3-Wire + Ground
Units suitable for TT and IT grounded power systems available upon request. Consult factory for model number.
10-years (Optional 15-years)
Available Options
Surge Counter Add suffix -B Transient Filter Add suffix -F (Meets UL 1283*) Stainless Steel Enclosure Add suffix -S
*Not recommended when using telecommunication rectifiers.
EMI/RFI Filter Attenuation
Max. Attenuation Frequency 41dB @ 106kHz
PRODUCT SPECIFICATIONSAVAILABLE CONFIGUR ATIONS
Electrical
Maximum Surge Current Rating 160kA per phase, 80kA per mode Nominal Discharge Current Rating (I-n) 20kA Operating Frequency 47–63Hz Connection Method Parallel to electrical distribution system Modes of Protection All Modes (L-N, L-G, N-G, L-L) Fault Rating (SCCR) 200kAIC – no upstream over-current protection
device (breaker or fuse) required Response Time Less than 1 nanosecond Standard Monitoring Status indicator lights (one per phase)
Standard Dry (From C) Relay Contacts
Audible Alarm with Silence Button
Mechanical
Weight 20 lbs. (9 kg) Enclosure Type Powder coated, impact-resistance steel,
weather-proof NEMA 4 Installation Location Indoor / Outdoor Mounting Method Dual mounting flanges Operating Environment -40° to +185°F (-40° to +70°C) Altitude Up to 13,000 ft. (4000 m) Product Design Parallel design with individually fused MOVs
Regulatory
UL 1449 3rd Edition Type Type 1 UL 1283 Yes IEEE C62.41.1, .2, C62.45 Yes Listed By UL CE Yes
JSP 160 PERFOR MANCE DATA
ANSI/IEEE C62.41.1-2002, C62.41.2-2002, & C62.45-2002 Measured Limiting Voltage
Model Voltage Protection B3 Ring Wave B3/C1 Combo C3 Combo UL 1449 3rd Edition Number Configuration Mode MCOV 6kV, 500A Wave 6kV, 3kA Wave 20kV, 10kA 6kV, 3kA VPR
L-N 150V 440V 629V 1413V 700V JSP160-1P120 1P120 L-G 150V 496V 640V 1360V 700V N-G 150V 464V 624V 1360V 700V L-N 320V 347V 525V 1069V 1000V JSP160-1P240 1P240 L-G 320V 1145V 565V 1117V 1000V N-G 320V 1090V 507V 930V 1000V L-N 150V 440V 629V 1413V 700V
JSP160-1S240 1S240 L-L 300V 544V 971V 1707V 1200V
N-G 150V 464V 624V 1360V 700V L-N 150V 440V 629V 1413V 700V
JSP160-3Y208 3Y208 L-L 300V 544V 971V 1707V 1200V
N-G 150V 464V 624V 1360V 700V L-N 320V 347V 525V 1069V 1000V
JSP160-3Y380 3Y380 L-L 640V 491V 860V 1443V 1800V
N-G 320V 1090V 507V 930V 1000V L-N 320V 347V 525V 1069V 1000V
JSP160-3Y415 3Y415 L-L 640V 491V 860V 1443V 1800V
N-G 320V 1090V 507V 930V 1000V L-N 320V 347V 525V 1069V 1000V
JSP160-3Y480 3Y480 L-L 640V 491V 860V 1443V 1800V
N-G 320V 1090V 507V 930V 1000V L-N 420V 715V 1250V 1910V 1500V
JSP160-3Y600 3Y600 L-L 840V 1130V 2300V 2910V 2500V
N-G 420V 670V 1230V 1880V 1500V L-N 150V 440V 629V 1413V 700V H-N 320V 347V 525V 1069V 1000V L-G 150V 496V 640V 1360V 700V JSP160-3H240 3H240 H-G 320V 1145V 565V 1117V 1000V L-L 300V 544V 971V 1707V 1000V H-L 470V 980V 1250V 1640V 1500V N-G 150V 512V 568V 1090V 800V
JSP160-3D240 3D240 L-L 320V 640V 1070V 1550V 1000V
JSP160-3D380 3D380 L-L 550V 860V 1720V 2340V 1800V
JSP160-3D480 3D480 L-L 550V 860V 1720V 2340V 1800V
JSP160-3D600 3D600 L-L 750V 1070V 2260V 2950V 2500V
L-G 150V 496V 640V 1360V 700V
L-G 150V 496V 640V 1360V 700V
L-G 320V 1145V 565V 1117V 1000V
L-G 320V 1145V 565V 1117V 1000V
L-G 320V 1145V 565V 1117V 1000V
L-G 420V 829V 1340V 1960V 1500V
L-G 320V 759V 982V 1630V 1000V
L-G 550V 1050V 1500V 2260V 1800V
L-G 550V 1050V 1500V 2260V 1800V
L-G 750V 1260V 1960V 2760V 2500V
All JSPTM systems measured limited voltages are peak values (±10%) measured from the zero reference point and are in compliance with test and evaluation procedures outlined in NEMA LS1-1992 (2000), paragraphs 2.210 and 3.10.
(D)
3.20"
(83.8 mm)
1.36"
(34.5 mm)
(W1)
(W2)
Allowable Area For Conduit Entry
(H1)
ø0.31 (7.87)
(H2)
(H3)
DIMENSIONS
Dim Inches (mm)
H1 10.00 (254.0)
H2 10.75 (273.1)
H3 11.50 (292.1)
W1 8.00 (203.2)
W2 6.00 (152.4)
D 6.20 (157.5)
© 2014 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 12/03/14