Joslyn Hi-Voltage 49 Series Data Sheet

SURGE PROTECTIVE DEVICES
Surgitron® III -49 Series
Type 1
MEDIUM DUTY FOR RESIDENTIAL OR INDUSTRIAL APPLICATIONS
FEATURE S AND BENEFITS
Listed to UL 1449 3rd Edition for a Type 1 SPD application.
Individual fusing for each Metal Oxide Varistors (MOVs).
LED indicates proper function of individual MOVs
PRODUCT SPECIFICATIONS
AVAILABLE CONFIGUR ATIONS
Model Number kA Per Phase Voltage Configuration
1260-49 40kA 120V 1-Phase, 2-Wire +Ground 1260-49-C 40kA 120V 1-Phase, 2-Wire +Ground 1261-49-C 40kA 240V 1-Phase, 2-Wire +Ground 1265-49 40kA 120/240V 2-Phase, 3-Wire + Ground 1265-49-C 40kA 120/240V 2-Phase, 3-Wire + Ground 1450-49 40kA 240V 3-Phase Delta, 4-Wire + Ground 1455-49 40kA 120/208V 3-Phase Delta, 4-Wire + Ground
Warranty
3-years
Available Options
1 set of Dry Relay Contacts + Mounting Bracket (only on1265-49 model) Add suffix -RB
Electrical
Nominal Discharge Current Rating (I-n) 20kA Operating Frequency 47–63Hz Connection Methods Parallel to Load (shunt)
#14 AWG wires
Modes of Protection 1260-49 L-N, L-G, N-G
1260-49-C L-N, L-G, N-G 1261-49-C L-N, L-G, N-G 1265-49 L-N, L-G, N-G 1265-49-C L-N, L-G, N-G, L-L 1450-49 L-G, L-L
1455-49 L-N, L-G, N-G, L-L Fault Rating (SCCR) 100kAIC Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights
Mechanical
Weight 2 lbs. (.9 kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor Mounting Method 1/2" – 14 NPS Thread
(Aluminum Bracket Optional) Operating Environment -40° to +176°F (-40° to +80°C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs
Regulatory
UL 1449 3rd Edition Type Type 1 UL 1283 No IEEE C62.41.1, .2, C62.45 Yes Listed By UL
SURGITRON III PERFORMA NCE DATA
2.90"
(73mm)
2.00"
(51mm)
1.60"
(41mm)
5.6"
(142 mm)
2.30"
(58mm)
.75" (19mm)
.136 DIA. BLIND HOLES, .40 DEEP FOR #8 SELF-TAPPING SCREWS (2)
0.25" (6mm)
#14 AWG (2mm
2
)
STRANDED WIRE 600V PVC INSULATION 18" (450mm) LONG
REMOTE MONITORING TERMINALS, -R ONLY
LED
1/2–14 NPT Thread
RE M OT
E AL AR M
1
2
3
1
2
3
Model Number Voltage Configuration Protection Modes MCOV 6kV 3000A VPR
1260-49 120 L-N 150 800 L-G 260 1000 N-G 150 800 1260-49-C 120 L-N 150 800 L-G 150 800 N-G 150 800 1261-49-C 240 L-N 320 1000 L-G 320 1200 N-G 320 1000 1265-49 120/240 L-N 150 800 L-G 260 1000 N-G 150 800 L-L 260 1000 1265-49-C 120/240 L-N 150 800 L-G 150 800 N-G 150 800 L-L 260 1000 1450-49 240 L-G 260 1000 L-L 260 1000 1455-49 120/208 L-N 150 800 L-G 260 1000 N-G 150 800 L-L 260 1000
UL 1449 3rd Edition
DIMENSIONAL SPECIFICATIONS
Alarm Relay Contacts Shown with Power On
© 2015 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 01/06/15