Joslyn Hi-Voltage 1265-85-MN, 1265-85-M Data Sheet

SURGE PROTECTIVE DEVICES
Surgitron® I 1265-85-M
1265-85-MN
HEAVY DUTY SERVICE ENTRANCE APPLICATIONS MODULAR DESIGN
FEATURE S AND BENEFITS
Listed by ETL to UL 1449 3rd Edition for a Type 1 SPD application.
Matrix of individually fused Metal Oxide Varistors (MOVs) housed
in replaceable modules.
Cover lights indicate status of modules.
Model Number kA Per Phase Voltage Configuration
1265-85-M 240kA 120/240V 1-Phase, 3-Wire + Ground 1265-85-MN 240kA 120/240V 1-Phase, 3-Wire + Ground
Warranty
5-years
Available Options
Surge Counter Add suffix -S
Stainless Steel NEMA 4X enclosure Add suffix -4X
Stand Alone Option
Remote Monitor 1260-97
PRODUCT SPECIFICATIONSAVAILABLE CONFIGUR ATIONS
Electrical
Nominal Discharge Current Rating (I-n) 20kA Operating Frequency 50–60Hz Connection Methods Parallel to load (shunt)
Lugs #14–#2 Directly connect or through 60A (min) breaker
Modes of Protection 1265-85-M L-N 1265-85-MN L-N, N-G
Fault Rating (SCCR) 100kAIC Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights (one per phase)
Mechanical
Weight 24.3 lbs. (11 kg) Enclosure Type NEMA 4, 4X Installation Location Indoor/Outdoor Mounting Method Dual mounting flanges Operating Environment -40° to +185°F (-40° to +85°C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs
Overcurrent fusing
Regulatory
UL 1449 3rd Edition Type Type 1 UL 1283 No IEEE C62.41.1, .2, C62.45 Yes Listed By ETL
SURGITRON I PE RFORMANC E DATA
Model Number kA Per Phase Voltage Configuration Protection Modes MCOV 6kV 3000A VPR
1265-85-M 240kA 120/240 L-N 150V 1000V 1265-85-MN 240kA 120/240 L-N 150V 1000V N-G 150V 500V
UL 1449 3rd Edition
DIMENSIONAL SPECIFICATIONS
Dim Inches (mm)
H1 12.75 (323.85)
H2
H1
H2 13.5 (342.9)
W1 10.9 (276.86)
W2 8.0 (203.2)
D 5.2 (132.08)
D
W2 W1
© 2014 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 10/22/14