Joslyn Hi-Voltage 1265-22-80, 1265-22-60, 1265-22-40 Data Sheet

SURGE PROTECTIVE DEVICES
Surgitron® III 1265-22-80
1265-22-60 1265-22-40
MEDIUM DUTY FOR RESIDENTIAL OR INDUSTRIAL APPLICATIONS
feature S and benefitS
Listed to UL 1449 3rd Edition for Type 2 SPD application.
Multiple Metal Oxide Varistors (MOVs) with individual and
overcurrent protection.
LED indicates proper function of individual MOVs.
Product SPecificationS
available configur ationS
Model Number kA Per Phase Voltage Configuration
1265-22-80-F1 80kA 120/240V 1-Phase, 3-Wire + Ground 1265-22-60-F1 60kA 120/240V 1-Phase, 3-Wire + Ground 1265-22-40-F1 40kA 120/240V 1-Phase, 3-Wire + Ground
Warranty
3-years
Stand Alone Option (To be ordered as a Separate Item)
Flush-Mount Plate Kit 22-FMP-KIT
Electrical
30A Max Breaker Modes of Protection L-L, L-N, L-G, N-G Fault Rating (SCCR) 100kAIC Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights
Mechanical
Weight 2 lbs. (.9 kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor Mounting Method 1/2" – 14 NPS Thread
(Aluminum Bracket Optional) Operating Environment -40° to +176°F (-40° to +80°C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs
Regulatory
UL 1449 3rd Edition Type Type 2 UL 1283 No IEEE C62.41.1, .2, C62.45 Yes Listed By UL
Surgitron iii PerforMa nce data
Model Number Voltage Configuration Protection Modes MCOV 6kV 3000A VPR
1265-22-80-F1 120/240 L-L 300 1000 L-N 150 600 L-G 150 600 N-G 0 900 1265-22-60-F1 120/240 L-L 300 1000 L-N 150 600 L-G 150 600 N-G 0 900 1265-22-40-F1 120/240 L-L 300 1000 L-N 150 600 L-G 150 600 N-G 0 900
UL 1449 3rd Edition
diMenSional SPecificationS
H1 .75 (19.1)
D3
D2
D1
W
1/2–14 NPT Thread
H2 .25 (6.4)
H3 2.93 (74.4)
W 3.56 (90.4)
D1 .32 (8.1)
H1
H2
D2 2.78 (70.6)
D3 3.10 (78.7)
All measurements in
H3
Schematic shown in horizontal position. (Photo shown in vertical position)
inches (mm)
© 2015 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 07/09/15