Joslyn Hi-Voltage 1261-45, 1261-85 Data Sheet

SURGE PROTECTIVE DEVICES
Surgitron® I 1261-45
1261-85
HEAVY DUTY SERVICE ENTRANCE APPLICATIONS MODULAR DESIGN
FEATURE S AND BENEFITS
Listed by ETL to UL 1449 3rd Edition for a Type 1 SPD application.
Matrix of individually fused Metal Oxide Varistors (MOVs) housed
in replaceable modules.
Suitable for use on types TN-C, TNS, TN-C-S, and TT neutral
grounding schemes.
Cover lights indicate status of modules.
Model Number kA Per Phase Voltage Configuration
1261-45 120kA 230V 1-Phase, 2-Wire + Ground 1261-85 120kA 230V 1-Phase, 2-Wire + Ground
Warranty
5-years
Available Options
Surge Counter Add suffix -S
Dry Relay Contacts come standard with 1261-85 model only
Remote Monitor 1260-97
PRODUCT SPECIFICATIONSAVAILABLE CONFIGUR ATIONS
Electrical
Nominal Discharge Current Rating (I-n) 20kA Operating Frequency 50–60Hz Connection Methods Parallel to load (shunt)
Lugs #14–#2
Directly connect or through 60A (min) breaker Modes of Protection L-N, L-G, N-G Fault Rating (SCCR) 100kAIC Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights (one per phase)
Mechanical
Weight 15.4 lbs (7 kg) Enclosure Type NEMA 12 Installation Location Indoor/Outdoor Mounting Method Dual mounting flanges Operating Environment -40° to +185°F (-40° to +85°C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs
Overcurrent fusing
Regulatory
UL 1449 3rd Edition Type Type 1 UL 1283 No IEEE C62.41.1, .2, C62.45 Yes Listed By ETL
SURGITRON I PE RFORMANC E DATA
Model Number kA Per Phase Voltage Configuration Protection Modes MCOV 6kV 3000A VPR
1261-45 120kA 230V L-N 320 1000V L-G 320 1000V N-G 320 1000V 1261-85 120kA 230V L-N 320 1000V L-G 320 1000V N-G 320 1000V
UL 1449 3rd Edition
DIMENSIONAL SPECIFICATIONS
Dim Inches (mm)
H1 10.75 (273.05)
H2
H1
H2 11.5 (292.1)
W1 8.9 (226.06)
W2 6.0 (152.4)
D 4.2 (106.68)
D
W2 W1
© 2014 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 10/22/14
Thomas & Betts Corporation
Loading...