SURGE PROTECTIVE DEVICES
available configur ationS
Model Number kA Per Phase Voltage Configuration
1261-21-xx 40kA 230V 1-Phase, 2-Wire + Ground
xx = -TNG, -TMS, -TT, -IT, -IT-L
Warranty
3-years
Available Options
Mounting Bracket Add suffix -B
Surgitron® III 1261-21 Series
MEDIUM DUTY FOR RESIDENTIAL
OR INDUSTRIAL APPLICATIONS
feature S and benefitS
• Listed to UL 1449 3rd Edition for a Type 2 SPD application.
• Individual fusing for each Metal Oxide Varistors (MOVs).
• There is a 1261 model for each power system configuration (neutral
grounding practice) as defined in EN60950:
TNC – Neutral and PE (protected earth conductor) are combined
throughout the system while TNCS splits the combined PEN into a
separate neutral and PE at the service entry; the U.S. practice is a
variation of this. The neutral is earthed at the transformer for both types.
The model 1261-21-TNC is suited for both TNC and TNCS systems.
TNS – Neutral is earthed at the transformer; however, is not bonded to
earth or the PE elsewhere. The PE is carried to the site from the
transformer and bonded to site earth. Model 1261-21-TNS is intended
for use on this system; it can also be used on TNCS as well as on U.S.
120/240V services without the neutral.
TT – Neutral is earthed at the transformer. The PE originates at site;
however, is not bonded to the neutral. There is no interconnection
between the PE and transformer earth. The 1261-21-TT is for use on this
system; it can also be employed upon TNS, TNCS and U.S. services
without neutral.
IT and IT-L – The transformer is unearthed or earthed through high
impedance. The PE originates at site; however, is not bonded to a service
conductor. No conductor in this system is designated as neutral. The
1261-21-IT is suited for this application; it can also be used on TT, TNS,
TNCS and U.S. services without neutral power systems.
Product SPecificationS
Electrical
Nominal Discharge Current Rating (I-n) 20kA
Operating Frequency 50–60Hz
Connection Methods Parallel to Load (shunt)
#14 AWG wires
30A Max Breaker
Modes of Protection Model Dependent
Fault Rating (SCCR) 100kAIC
Response Time Less than 1 nanosecond (one per phase)
Standard Monitoring LED status indicator lights
Mechanical
Weight 2 lbs. (.9 kg)
Enclosure Type NEMA 1, Non-metallic
Installation Location Indoor
Mechanical (Continued)
Mounting Method 1/2" – 14 NPS Thread
(Aluminum Bracket Optional)
Operating Environment -40° to +176°F (-40° to +80°C)
Altitude Up to 16,400 ft. (5000 m)
Product Design Individually fused MOVs
Overcurrent Fusing
Thermal Fusing
Regulatory
UL 1449 3rd Edition Type Type 2
UL 1283 No
IEEE C62.41.1, .2, C62.45 Yes
Listed By UL
Surgitron iii PerforMa nce data
Model Number Voltage Configuration Protection Modes MCOV
6kV 3000A VPR
1261-21-TNC 230 L-N 300 1200
N-G 0 1200
1261-21-TNS 230 L-N 300 1200
L-G 300 1200
N-G 0 1200
1261-21-TT 230 L-N 300 1800
L-G 300 1200
N-G 0 1800
1261-21-IT 230 L-N 300 1200
L-G 480 1800
N-G 0 1800
1261-21-IT-L 230 L-N 300 1200
L-G 480 1800
N-G 0 1800
UL 1449 3rd Edition
diMenSional SPecificationS
2.93"
(75mm)
3.56"
(90mm)
ø .21" (5.5mm)
2 HOLES
1.26"
(32mm)
1.37"
(35mm)
2.52"
(64mm)
BRACKET DETAIL
2.93"
(75mm)
.75" (19mm)
1/2–14 NPT Thread
#14 AWG (2mm
STRANDED WIRE
600V PVC INSULATION
18" (450mm) LONG