Joslyn Hi-Voltage 1000 Series Data Sheet

SURGE PROTECTIVE DEVICES
1000 Series
LIGHT DUTY FOR DC APPLICATIONS
featureS and benefitS
Full weather permanently connected.
Individually fused Metal Oxide Varistors (MOVs).
May be used on grounded (+ or -) or floating power systems,
LED indicates proper functioning of L-L and L-G MOVs.
Model Number kA Per Phase DC Voltage AC Voltage
1020-30 25kA 30Vdc 25Vac 1020-60 50kA 60Vdc 45Vac 1020-90 50kA 90Vdc 65Vac 1020-150* 50kA 150Vdc 110Vac
*Model 1020-150 is not intended for use on 110/120 Vac power system.
Warranty
3-years
dimenSional SPecificationS
2.80"
2.91"
(73.9 mm)
3.54"
(89.9 mm)
Schematic shown in vertical position. (Photo shown in horizontal position)
(96.5 mm)
2.10"
(78.7 mm)
1.25"
#14 AWG (2 mm 600V PVC INSULATION 18" (450 mm) LONG
1/2–14 NPS THD.
LOCKNUT
ALUMINUM BRACKET
ø .218" Hole, 2 Pl.
1.37"
.25"
2.50"
2
) STRANDED WIRE
Product SPecificationSavailable configurationS
Electrical
Nominal Discharge Current Rating (I-n) None Operating Frequency AC/DC 0–400 Hz Connection Methods Mounts through 1/2" knockout or
Modes of Protection L-L, L-G Response Time Less than 1 nanosecond Standard Monitoring LED status indicator lights (one per line)
Mechanical
Weight 1.5 lbs. (.7kg) Enclosure Type NEMA 1 Installation Location Indoor Operating Environment -40° to +176°F (-40° to +80°C) Altitude Up to 16,400 ft. (5000 m)
.75"
Product Design Individually fused MOVs
Regulatory
Requirements are discretionary and respective to the product application
by its bracket Connects in parallel with load
Overcurrent Fusing Thermal Fusing
© 2015 Thomas & Betts Corporation. All rights reserved. Printed in the U.S.A. 01/06/15
SURGE PROTECTIVE DEVICES
Surgitron® III -21 Series
Type 2
MEDIUM DUTY FOR RESIDENTIAL OR INDUSTRIAL APPLICATIONS
featureS and benefitS
Listed to UL 1449 3rd Edition for a Type 2 SPD application.
Individual fusing for each Metal Oxide Varistors (MOVs).
LED indicates proper functioning of L-N and N-G MOVs
Product SPecificationS
available configurationS
Model Number kA Per Phase Voltage Configuration
1261-21 40kA 277V 1-Phase, 2-Wire + Ground 1263-21 40kA 480V 1-Phase, 2-Wire 1452-21 40kA 120/240V 3-Phase High-Leg Delta,
4-Wire + Ground 1456-21 40kA 277/480V 3-Phase, 4-Wire + Ground 1456-21-D 40kA 480V 3-Phase, 3-Wire + Ground 1457-21 40kA 230/400V 3-Phase, 4-Wire + Ground
Warranty
3-years
Available Options
Mounting Bracket Add suffix -B
Electrical
Nominal Discharge Current Rating (I-n) 20kA Operating Frequency 47–63Hz Connection Methods Parallel to Load (shunt)
#14 AWG wires
Modes of Protection 1261-21 L-N, L-G, N-G
1263-21 L-L 1452-21 L-N, L-G, N-G, L-L 1456-21 L-N, L-G, N-G, L-L 1456-21-D LG, L-L
1457-21 L-N, L-G, N-G, L-L Fault Rating (SCCR) 100kAIC Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights
Mechanical
Weight 2 lbs. (.9 kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor Mounting Method 1/2" – 14 NPS Thread
(Aluminum Bracket Optional) Operating Environment -40° to +176°F (-40° to +80°C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs
Regulatory
UL 1449 3rd Edition Type Type 2 UL 1283 No IEEE C62.41.1, .2, C62.45 Yes Listed By UL