Joslyn JSP Series, JSP-120, JSPR Series, JSP-160, JSP-200 Installation, Operation And Maintenance Manual

...
TM TM
JSP JSPR
SURGE
PROTECTION
SURGE
PROTECTION
Installation, Operation and Maintenance Manual
PN 750-0100-001 C00
Joslyn
Surge Protective Devices
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
2
Table of Contents
Guide to Installation and Assistance ............................. 3
Pre-Installation Checklist ..................................... 4
Service Configurations ....................................... 5
Conductor Sizing and Routing .................................. 6
Upstream Overcurrent Protection Device .......................... 7
Mounting ................................................. 8
Indoor vs. Outdoor Installation .................................. 8
Conduit Openings .......................................... 8
Electrical Connections ...................................... 10
Connecting Form “C” Dry Contacts ............................. 11
Remote Monitoring ........................................ 11
Verification and Power Up .................................... 12
Troubleshooting ........................................... 13
Installation Assistance ...................................... 13
Standards and Listings ...................................... 13
Return and Warranty Procedures ............................... 13
Warranty Statement ........................................ 14
tnbpowersolutions.com/joslynsurge
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Thank you for choosing the Joslyn
Guide to Installation and Assistance
We look forward to fulfilling your facilitywide surge protection needs.
®
TM
JSP
Series Surge Protective Device (SPD).
3
Should you have questions about installing the JSP Series please call Joslyn
®
Technical Support at 800.238.5000 or 804.236.3300 Monday through Friday, 8:00 a.m. to 5 p.m. (EST). Or, email us at joslyn@tnbpowersolutions.com.
This manual provides guidelines for the proper installation of the JSP Series of devices. Proper product selection and compliance with these guidelines will help your new suppression system provide years of reliable service. If installers are unsure about the facility electrical configuration or have other installation-related questions, it is recommended they consult with a master electrician or other qualified electrical professional.
When shortcuts are taken or installation procedures are not followed, the JSP Series may become damaged or may not provide adequate protection. It is extremely important to follow these installation procedures carefully.
W A R N I N G !
THE JSP SERIES WARRANTY IS VOIDED if the unit is damaged as a result of improper installation or the installer’s failure to verify the following conditions prior to installation.
W A R N I N G ! HAZARDOUS VOLTAGES PRESENT: Improper installation or misapplication may result in serious personal injury or damage to the electrical system. Read the complete installation instructions before proceeding with installation. Remove all power to the electrical panel before installing or servicing the SPD.
W A R N I N G ! IMPORTANT SAFETY INSTRUCTIONS: All work must be performed by licensed and qualified personnel. The electrical system must be properly grounded in accordance with the U.S. National Electrical Code, state and local codes or other applicable codes for this SPD to function properly. This device is suitable for installation where the available short circuit current is 200,000 rms symmetrical amperes up to 600VAC or less. For countries outside of the US follow applicable electrical specifications for the country the unit is being used in.
W A R N I N G ! Check to ensure that a proper bond is installed between neutral and ground at the transformer upstream from all 3-Phase Wye, 3-Phase High-Leg Delta or Split-Phase JSP Series device (See NEC Article 250). If the transformer is not accessible, check the main service disconnect/panel for the NG bond. Lack of a proper bond will damage JSP Series and void the warranty.
W A R N I N G ! Do not HIPOT the JSP Series units or the electrical system to which the JSP Series unit is connected without disconnecting the JSP Series units conductors including phases, neutral and ground.
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
4
Pre-Installation Checklist
Confirm that the voltage(s) and service configuration shown on the JSP Series product label are consistent with the voltage and service configuration of the facility. A model number is on the right side of the JSP Series unit. Each model number corresponds to the configurations printed in Table 1:
Example of a SPD model number: JSP(R)160-3Y208-F
Sample Model Number Scheme
JSP(R) 160 — 3Y 208 — F
Model
kA Rating
Configuration
Voltage
Options
Table 1: Configuration Table
MODEL NOMINAL L-N L-L CONFIGURATION VOLTAGE VOLTAGE VOLTAGE RANGE RANGE
JSP(R)xxx-1P1201 120 108-132 N/A 1-Phase, 2-Wire + Ground
JSP(R)xxx-1P240
JSP(R)xxx-1S240
JSP(R)xxx-3Y208
JSP(R)xxx-3Y380
JSP(R)xxx-3Y415
JSP(R)xxx-3Y480
JSP(R)xxx-3H240 187-229 (B) 4-Wire + Ground
JSP(R)xxx-3Y600 347/600 312-382 540-660 3-Phase Wye, 4-Wire + Ground
JSP(R)xxx-3D240
JSP(R)xxx-3D380 380 N/A 342-418 3-Phase Delta, 3-Wire + Ground
JSP(R)xxx-3D480 480 N/A 432-528 3-Phase Delta, 3-Wire + Ground
JSP(R)xxx-3D600 600 N/A 540-660 3-Phase Delta, 3-Wire + Ground
1
240 216-264 N/A 1-Phase, 2-Wire + Ground
1
120/240 108-132 216-204 Split-Phase, 3-Wire + Ground
1
120/208 108-132 187-229 3-Phase, 4-Wire + Ground
1
220/380 198-242 342-418 3-Phase, 4-Wire + Ground
1
240/415 216-264 374-457 3-Phase, 4-Wire + Ground
1
277/480 249-305 432-528 3-Phase, 4-Wire + Ground
1
120/240
1
240 N/A 216-264 3-Phase Delta, 3-Wire + Ground
108-132 (A, C)
216-264
3-Phase, High-Leg
tnbpowersolutions.com/joslynsurge
JSP Series Options
F Transient filter that meets UL 1283 (Not recommended when using telecommunication rectifiers)
B Surge Counter (not available on JSP 60–100kA units or the JSPR series)
S NEMA 4X stainless steel enclosure
M Advanced monitoring (available in 60–100kA units only)
1
These are the only voltages available on the 60, 80, and 100kA systems.
NOTES:
xxx denotes surge rating per phase (60, 80, 100, 120, 160, 200, 240, 300, 400)
JSPR units are only available in 120 and 160kA.
The power system operation frequency is between 47–63Hz.
Confirm that the environmental conditions are consistent with the following ranges:
• Ambient Temperatures: Between -40° and +158°F (-40º to 70º C).
• Relative Humidity: Between 5% and 95% non-condensing.
• Altitude: Less than 13,000 feet (4000 m).
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
5
Service Configurations
L1
L1
N
NG
Xo BOND
N
G
EARTH
GROUND
Figure 1 1-Phase, 2-Wire
30–200 AMP, 1-POLE
CIRCUIT BREAKER
L
G
N
CONDUCTORS
FURNISHED WITH
JSP SERIES
Figures 1–5 show the electrical relationship between JSP Series unit and these five basic service configurations: 1-Phase, 2-Wire; 2-Phase, 3-Wire; 3-Phase Wye, 4-Wire; 3-Phase Delta, 3-Wire and 3-Phase High-Leg Delta, 4-Wire.
1
30–200 AMP, 2-POLE
CIRCUIT BREAKER
JSP SERIES
2
L2
Xo BOND
N
G
EARTH
GROUND
L1NL2
NG
L1
CONDUCTORS
FURNISHED WITH
Figure 2 2-Phase, 3-Wire
1
JSP SERIES
L1
L2
G
N
2
JSP SERIES
B
N
CA
Xo BOND
N G
EARTH
GROUND
ABC
NG
Figure 3 3-Phase Wye, 4-Wire
30–200 AMP, 3-POLE
CIRCUIT BREAKER
A
B C
G
N
CONDUCTORS
FURNISHED WITH
JSP SERIES
1
JSP SERIES
2
30–200 AMP, 3-POLE
CIRCUIT BREAKER
B
CA
G
EARTH
GROUND
ABC
NG
Figure 4 3-Phase Delta, 3-Wire
1
A
B C
G
CONDUCTORS
FURNISHED WITH
JSP SERIES
JSP SERIES
2
Continued
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Note: High-Leg Orange must be B Phase
C
Xo BOND
N
N
G
EARTH
GROUND
A
30–200 AMP, 3-POLE
CIRCUIT BREAKER
ABBC
NG
A B C
G
N
CONDUCTORS
FURNISHED WITH
JSP SERIES
1
JSP SERIES
2
Figure 5 3-Phase High-Leg Delta, 4-Wire
6
1
All JSP Series units can be connected without an upstream breaker/fuse.
2 JSP 60 through 100kA and all JSPR units are furnished
with #10AWG leads.
Conductor Sizing & Routing
CAUTION: The JSP Series unit’s performance will be limited severely if the conductors are (a) too long, (b) are of too small a wire gauge, (c) have too many bends or (d) have sharp bends. For optimum performance never exceed 10' conductor lengths.
The factors listed above should be addressed during the design of an installation to reserve a suitable place for the JSP Series unit next to its point of connection to the electrical system. The selected mounting location should allow for the shortest possible conductor runs and a direct route with a minimum of bends. If bends are required, they should be sweeping bends. Do not make sharp 90° bends for appearance purposes because they will severely decrease the effectiveness of JSP Series unit.
Binding or twisting conductors together using tie-wraps or electrical tape increases the protection performance of the device.
The conductor length should be as short as possible to ensure the maximum level of protection. Wires are marked with (Phase A, B, C, Line 1, Line 2, Neutral or Ground) depending on the model.
tnbpowersolutions.com/joslynsurge
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Joslyn recommends installing the JSP unit by following conductor size for
Conductor Sizing & Routing (JSP)
phase, ground and neutral connections. The conductor length should be as short as possible to ensure the maximum level of protection.
Table 2: Maximum Recommended Conductor Size
JSP Models Conductor size
JSP-120 #6AWG
JSP-160 #6AWG
JSP-200 #4AWG
JSP-240 #4AWG
JSP-300 #4AWG
JSP-400 #4AWG
• 60 through 100kA units are shipped with #10AWG leads. Leads should be
shortened during installation in order to minimize conductor length.
• 120 through 400kA units are shipped with compression box lugs.
The set screws on the box lugs should be torqued to 20 in-lbs.
• Terminals are identified with markers (Phase A, B, C, Line 1, Line 2,
Neutral or Ground)
7
Upstream Overcurrent Protection Device
The JSP Series unit is a Type 1 SPD which is suitable for use in both Type 1 and Type 2 SPD applications. The JSP Series unit is a one-port SPD and is to be connected in parallel with the electrical system. It may be connected via a circuit breaker, molded case switch, fused switch, or connected directly to the bus of the panelboard or switchboard it is protecting. If direct bus connection is used, Joslyn
®
recommends installing the JSP Series unit behind
a disconnect switch or other disconnecting means for ease of serviceability.
If the SPD is connected to a dedicated OCPD, a 60A breaker is recommended (30A minimum, 200A maximum).
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
8
Mounting
JSP)
(
Mounting
JSPR)
(
Mount the JSP to the building structure using construction methods and hardware appropriate for your site. Install the conduit and pull the conductors as specified in Table 2.
Mount the JSPR to the building structure using construction methods and hardware appropriate for your site.
Mount the JSPR into the wall. Electrician can mount to the back wall, if the back wall is made of structural material such as masonry or plywood. (Drywall is not a structural material). If back wall is not made of structural material, the electrician can create brackets to hold the SPD to the adjacent studs.
After the drywall has been installed, install Flush Mounting Plate (FMP) by first removing the JSPR enclosure lid. Place the FMP over enclosed body. Attached the FMP to the wall using the enclosed hardware kit. Screw the lid back on to the enclosure body.
Indoor vs. Outdoor Installations
Conduit Openings (JSP)
13"
11"
JSPR 120, 160 Weight: 30 lbs. (13.6 kg)
NEMA 4 enclosures are suitable for indoor or outdoor use. NEMA 4X (stainless steel) enclosures are suitable for corrosive environments as well. For direct sunlight applications, Joslyn suggests shading the monitoring components. All conduits and fittings must be rated and properly installed so that the final installation maintains the NEMA rating.
If desired, punch holes at this time for the conduit or nipple or wait until the JSP unit is mounted to the building structure. Punch holes only in the designated areas as shown in the following illustration.
tnbpowersolutions.com/joslynsurge
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
3/4" MYERS HUB
9
Conduit Openings (continued)
Figure 6A Conduit Openings and Enclosure Mounting Dimensions (JSP)
(W1)
(D1)
(D2)
(W2)
(H1)
(H2)
ø0.31 (7.87)
(H3)
1.36"
(34.5 mm)
(D)
3.20"
(83.8 mm)
CAUTION: Careful consideration must be made when selecting an area for conduit entry. There are several components inside the enclosure that may interfere with the conduit entry path, therefore, ensure the path is clear of all objects before drilling. Damages caused by installation errors are not covered under the product warranty. See Figures 6A and 6B for conduit openings and enclosure dimensions.
(D)
(W1)
(W2)
ø0.31 (7.87)
(H1)
(H2)
(W1)
(W2)
(H1)
ø0.31 (7.87)
(H2)
(H3)
1.36"
(34.5 mm)
3.20"
(83.8 mm)
(H3)
JSP 60–100
JSP 120–160
Allowable Area For Conduit Entry
DIMENSIONAL SPECIFICATIONS
Dim JSP 60, 80, 100 JSP 120, 160 JSP 200, 240, 300, 400
H1 6.00 (152.4) 10.00 (254.0) 14.00 (355.6)
H2 6.75 (171.5) 10.75 (273.1) 14.75 (374.7)
H3 7.50 (190.5) 11.50 (292.1) 15.50 (393.7)
W1 6.00 (152.4) 8.00 (203.2) 12.00 (304.8)
W2 4.00 (101.6) 6.00 (152.4) 10.00 (254.0)
D 6.20 (157.5) 6.20 (157.5)
D1 4.16 (105.7)
D2 2.00 (50.8)
All measurements in inches (mm)
Allowable Area For Conduit Entry
JSP 200–400
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Figure 6B Enclosure Mounting Dimensions (JSPR)
(D1)
(D2)
10
(W1)
(W2)
3/4"
MYERS
HUB
Dim JSPR 120, 160
H1 10.00 (254.0)
H2 10.75 (273.1)
H3 11.50 (292.1)
W1 8.00 (203.2)
W2 6.00 (152.4)
D1 4.20 (106.9)
D2 2.00 (50.8)
Weight 30 (13.6)
Ø 0.31 (7.87)
(H1)
(H2)
(H3)
Electrical Connections
tnbpowersolutions.com/joslynsurge
All measurements in inches (mm) and pounds (kg)
CAUTION: Prior to installation ensure the system configuration and voltage is equivalent to the JSP Series unit being installed.
Following all applicable National Electrical Code standards as well as state and local codes, connect phase, neutral* (white wires) and ground (green wires) to the JSP Series unit.
JSPR units come with 36" of #10AWG conductors. Each phase conductor is labeled (Phase A, B or C). Ensure that the conductor lengths are kept as short and straight as possible. On all high-leg delta systems, the high-leg (208V LN) must be connected to the Phase B of the SPD. (Color coded orange according to NEC).
*The 3-Wire + Ground Delta JSP Series units do not have a neutral conductor.
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
11
Connecting Form “C” Dry Contacts
Remote Monitoring
Figure 7 Wire Connections
Contacts shown in de-energized state (alarm condition).
Units that come with Form “C” dry relay contacts provide status of the surge protective device. These contacts are for connection to a user-provided remote alarm and monitoring circuit. The relay contacts are rated 65VDC/150VAC with maximum switching power of 30WDC/60VA AC. The Form “C” contacts come pre-wired with 36" of #20AWG conductors on the JSP 60 to 100kA models and on all JSPR models.
When input power is present on all phases, terminals “NO” (Normally Open) and “COM” (Common) are an open circuit and terminals “NC” (Normally Closed) and “COM” are a closed circuit. The contacts change state when the unit has encountered failure to one or more phases.
The installer must provide the appropriate raceway and wiring for the monitoring circuit, observing the restrictions and conduit openings illustrated in an earlier section of this manual.
Models: JSP60kA to JSP100kA with -M option and JSPR Series
For these models, the Form “C” contacts come pre-wired with 36" of #20AWG conductors.
See Figure 7 for the Form “C” wiring and contact configuration.
FORM C RELAY
N.O. • BLK
COM. • WHITE
N.C. • RED
N.O.
COM.
N.C.
SHOWN IN ALARM
CONDITION
Figure 8 Terminal Block
Contacts shown in energized normal state (no fault condition).
Use butt splices within the panelboard to connect the Form “C” leads to the user’s monitoring circuits. Alternatively, install a junction box between the JSP Series and the panelboard to connect Form “C” leads to user’s monitoring circuits. If the Form “C” contacts are not used, user has the option of either cutting off the leads or coiling up the leads and saving them for potential future use. Consult applicable local codes to ensure proper installation.
Models: JSP120kA to JSP400kA
For these models, the Form “C” contacts must be wired by the installer.
See Figure 8 for the Form “C” contact configuration and terminal location on the monitor board. The annotations on the diagram match the markings on the terminal block.
The installer must route the monitoring conductors to the terminal blocks on the door mounted main monitoring board. Route the wires to allow the door to be opened and closed properly. Tighten screws on terminals to 3.5 in-lbs. (0.4 Nm). This terminal block will accept wire sizes #28AWG–#16AWG. #18–#20AWG is recommended.
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
R
R
12
Verification and Power Up
Figure 9 JSP Diagnostics
R
W A R N I N G ! It is recommended that the cover of the JSP Series unit along with its associated cabling be installed prior to applying power. The monitoring harness, which exits the epoxy and connects to the input connector on the monitor board, contains line voltage when power is applied to the unit.
Apply Power to the JSP Series unit by closing the overcurrent protection device or switch feeding the suppressor.
For Compact JSP units (60, 80, and 100kA)
Verify that all “Protection Available” indicating lights are illuminated. The “Protection Available” indicating lights extinguish only upon failure of one or more phases (indicating an alarm condition).
For Standard JSP units (120, 160, 200, 240, 300, and 400) or
-M (60, 80 and 100kA) and JSPR Units
Verify that all “Protection Available” indicating lights are illuminated. The “Protection Available” lights extinguish only upon failure of one or more phases (indicating an alarm condition).
R
Figure 10 JSP with Counter Option Diagnostics
Audible alarm should not operate under normal conditions. The audible alarm can be “muted” by pressing the “ALARM SILENCE” button, which subsequently will illuminate the “ALARM SILENCED” light. Pressing the “ALARM SILENCE” button again will enable the audible alarm.
CAUTION: Pressing the “ALARM SILENCE” button when the alarm
has not triggered will prevent the audible alarm from sounding during a failure.
For JSP units with surge counter option (Not available on 60, 80 and 100kA or JSPR units)
The number of surges detected by the SPD is displayed on an eight digit LCD display on the front of the JSP door. The LCD counter is battery backed to maintain the number of surges even during a power loss. Press the reset button on the counter to reset the surge count.
R
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Your JSP Series unit does not require scheduled maintenance. The unit’s
Troubleshooting
heavy duty construction is designed to provide years of uninterrupted service. The unit contains no serviceable parts.
INDICATION PROCEDURE
One or more phase protection status indicating lights are off, service required indicating light is on, or Form “C” alarm contacts have changed state.
Our staff is ready to support you and answer any questions.
Installation Assistance
Monday through Friday, 8:00 a.m. to 5:00 p.m. (EST) at 800.238.5000 or 804.236.3300 joslyn@tnbpowersolutions.com
JSP Series units are warranted for a period of 10 years from date of purchase. In the event that any module or subassembly within the SPD fails to perform as specified during the warranty period, call our Technical Support at
800.238.5000.
13
Verify that the input power feeding the JSP Series unit is energized using a voltage tester. If power is present, contact factory for assistance: 800.238.5000
Standards and Listings
Return and Warranty Procedures
The following standards and listings apply to the JSP Series product line:
• UL Listed 1449 4th Edition for Type 1 and Type 2 SPD application, cUL, and UL 1283
• Meets Requirements for UL 96A
• Compliant to IEEE C62.41.1-2002, C62.41.2-2002 and C62.45-2002
• NFPA 70 [NEC], Article 285
• RoHS Compliant
A Return Material Authorization (RMA) number must be obtained from T&B Customer Service department before replacement products can be shipped.
INFORMATION EXAMPLE
Model Number JSP(R)120277/4803GY Serial Number 15478-0113-001 Date of Purchase January 2, 2013 Description of Failure “Service Required” indicating light illuminated Desired Action from Joslyn Replace
tnbpowersolutions.com/joslynsurge
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
14
Warranty Statement
Thomas & Betts Power Solutions, LLC, A Member of the ABB Group (“Seller”) warrants that your Joslyn surge protective device (the “Product”), shall meet applicable industry standards and specifications and be free from defects in materials and/or workmanship. Should any failure of the Product to conform to this warranty appear within the standard warranty period, Seller shall either repair or replace the defective Product, or part thereof, upon return to Seller’s manufacturing facility in Richmond, Virginia with transportation charges prepaid. The applicable warranty period as outlined herein.
Seller shall have no liability under this warranty for any problems or defects directly or indirectly caused by misuse of the Product, alteration of the Product (including removal of any warning labels), accidents, or improper installation, application, operation, or repair of the Product.
THIS WARRANTY REPRESENTS THE ENTIRE WARRANTY OF SELLER. ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, ORAL OR WRITTEN, INCLUDING, BUT NOT LIMITED TO, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
The liability of Seller under this warranty is expressly limited to the replacement or repair of the defective part thereof, at Seller’s sole option.
IN NO EVENT SHALL SELLER BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND OR CHARACTER, NOR SHALL SELLER’S LIABILITY EVER EXCEED THE PURCHASE PRICE PAID FOR SUCH DEFECTIVE PRODUCT.
Warranty Period
This warranty is not transferable and may only be enforced by the sole purchaser. Claims under this warranty must be submitted to Seller within thirty (30) days of discovery of any of Seller’s product defect.
JSP Series (AC) – (All)
10 Year 15 Year Optional
tnbpowersolutions.com/joslynsurge
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Notes
15
JOSLYN® JSPTM, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL
16
Model #
Date of Purchase
Date Installed
Installer
Thomas & Betts Power Solutions
5900 Eastport Blvd. • Richmond, VA 23231-4453 USA
Tel: (804) 236-3300 • Toll free: (800) 238-5000 • Fax: (804) 236-4841