Sv-120 SOLNOID VALVE INSTALLATION
Special care should be taken to ensure all foreign objects are removed
from air supply piping before installation of solenoid valve.
Ensure adequate space is left for servicing or removal of solenoid valve.
Pipe sealant should be put on pipe thread, never on threads of solenoid
valve. If PTFE tape is used, special care must be taken so that tape does
not enter solenoid valve air paths.
The exhaust ports should be protected with breather mufflers or speed
control valves so as to prevent foreign material from entering solenoid
valve.
Wiring
WARNING: Wiring should be performed only by qualified electricians.
The SV-120 is a 120vac, 2- wire solenoid valve standard.
Therefore only standard 2-wire, 120/60/1 wiring should be connected to
the solenoid valve.
(Optional voltages, 24vac, 24vdc, and 240vac can be ordered.)
Ensure valves are properly grounded.
Manual Override
The SV-120 is equipped with a manual override for use when power
supply is interrupted, simply push the RED manual override button.
WARNING: Always remove power supply before servicing.