John Wood Water Heater Installation And Operating Instructions Manual

ATMOSPHERIC VENTED WATER HEATER
WARNING:
Improper installation, adjustment, altera­tion, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation, consult a qualified installer, ser­vice agency, or the gas utility.
• Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
• Installation and service must be per­formed by a qualified installer, service agency or the gas utility.
INSTALLATION AND
OPERATING INSTRUCTIONS
Read these instructions thoroughly before starting
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, per­sonal injury or death.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
PART NO. 324331-000 Rev. 01 (13-04)
TABLE OF CONTENTS
I) INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . .3
User Responsibilities 3
II) SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
For Installations in Canada 3 For Installations in the United States 3 Safety Warning (Flammable Vapours) 4 Safety Warning (Scalding) 4 Safety Warning (Carbon Monoxide) 4 Relief Valves (T&P) 4 Backflow Prevention 4
III) INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Unpacking the Water Heater 5 Location Requirements 5 In Earthquake Zones Clearances and Accessibility 5 Gas Supply 6 Gas Pressure Gas line purging Gas Leak Testing Air Requirements 8 Confined Space Air Requirements for Canadian
Installations 8
Confined Space Air Requirements for U.S.
Installations 9 Exhaust Venting 10 Vent Pipe System Check for proper vent size Drafthood Installation Water Supply 10 Piping Installation Union Connections Mixing Valves 11 Closed System/Thermal Expansion Temperature and Pressure (T&P) Relief Valve 12 The Temperature And Pressure Relief Valve: The Discharge Line: Electrical Supply 13 24 Volt Control precautions Installations Check 14
IV) OPERATING INSTRUCTIONS. . . . . . . . . . . . . . . .14
Water Temperature Regulation 14 Temperature Adjustment Lighting Instructions (White-Rodgers 37C) 16 Lighting Instructions (Honeywell 24 Volt) 17
V) OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Burner Flames 18 Emergency Shut Down 18 Checking the Draft 18 Operating Conditions 18 Condensation Water Heater Sounds Safety Shut-off Anode/Water Odour Water Heater Operation (24 Volt only) 19 System Error Codes for 24 Volt Controls
VI) MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Periodic Cleaning of the Wrap-around Filter 21 Draining and Flushing 21 Periodic Inspection 21 External Cleaning of the Flame-arrestor 21 Temperature and Pressure Relief Valve 22 Resetting and Replacing the Safety (TCO)
Switch (NG models) 22
Replacing the Thermocouple (TCO)
Assembly (LP models) 22 24 Volt Honeywell Control Service 23 Electronic Control Module Replacement Valve Module Replacement Temperature Sensor and Cable Replacement
VII) COMBO HEATING . . . . . . . . . . . . . . . . . . . . . . . . . 25
System Requirements 25
VIII) TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . .26
IX) REPAIR PARTS ILLUSTRATION . . . . . . . . . . . . .28
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . .31
RETAIN THESE INSTRUCTIONS IN A SAFE LOCATION FOR FUTURE REFERENCE
– 2 –
Your safety and the safety of others is very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING”.
DANGER
You can be killed or seriously injured if you don’t immediately follow instructions.
WARNING
You can be killed or seriously injured if you don’t follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
I) INTRODUCTION
We thank you for choosing a Flammable Vapour Resistant Water Heater. Your satisfaction with this product
is very important to us. This gas-fired water heater has been developed to produce domestic hot water and may also be used in combination with space heating applications but not space heating only. The Flame GuardTM safety system is designed to reduce the risk of flammable vapour related fires by trapping the burning vapours within the water heater combustion chamber using the special flame arrestor. The burning vapours literally “burn themselves out” without escaping back into the room.
User Responsibilities
These instructions have been written for the proper instal­lation, safe operation and maintenance of this water heater. It is your responsibility to ensure that your water heater is properly installed and cared for.
FAILURE TO FOLLOW THE INSTRUCTIONS IN THIS MANUAL MAY RESULT IN SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. THOROUGHLY READ ALL INSTRUCTIONS BEFORE YOU ATTEMPT TO INSTALL, OPERATE OR MAINTAIN THIS HEATER.
Installation and service requires trade knowledge in the area of plumbing, electricity, venting, air supply and gas supply. If you lack these skills or do not understand these instructions, enlist the help of a qualified professional. The manufacturer of this water heater cannot be held liable for those damages caused by improper installation, sizing or failure to comply with these instructions. Protect your warranty: Regularly maintain your water heater and venting system as detailed in the “Maintenance” section of this manual.
WARNING
Service to the Flame Guard
TM
safety system should only be performed by a qualified ser­vice technician.
II) SAFETY
This water heater is design-certified by CSA International as a Category I, non-direct vented water heater which takes its combustion air either from the installation area or from air ducted to the unit from the outside.
In addition to the installation instructions found in this man­ual, the heater shall be installed according to all local and provincial or state codes and with the latest edition of the following specifications.
For Installations in Canada
"Natural Gas and Propane Installation Code" CSA­B149.1 and "Canadian Electrical Code (CAN/CSA C22.1), Part I" available from:
Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, Canada L4W 5N6
For Installations in the United States
"National Fuel Gas Code" ANSI Z223.1 (NFPA 54) and "National Electrical Code" (NFPA 70)" available from:
American National Standards Institute, 25 West 43rd Street, New York, NY 10036
Massachusetts code requires this water heater to be installed in accordance with Massachusetts Plumbing and Fuel Gas Code 248 CMR Section 2.00 and 5.00.
Check your phone listings for the local authorities having jurisdiction over your installation.
Important: All supply equipment, installation, approvals, permits, inspections, etc. are the responsibility of the owner of this water heater. Consult your local authorities for regula­tions specific to your area.
– 3 –
Safety Warning (Flammable Vapours)
WARNING
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapours or liquids in the vicinity of this or any other appliance can result in serious injury or death.
There is a risk in using fuel-burning appliances such as water heaters. Areas that may not be suitable for water heater installation include those where flammable liquids, gasoline, solvents, adhesives, etc., or engine-driven equip­ment or vehicles are stored, operated or repaired. Due to the nature of air movement, flammable vapours can be car­ried some distance from the point of storage. The gas-fired water heater igniter or main burner flame can ignite these vapours causing a flashback, fire or explosion which may result in serious personal injury or death, as well as severe property damage.
Safety Warning (Scalding)
Flammable Vapours
DANGER
result in serious bodily harm or death from asphyxiation.
MAKE SURE THE FLOW OF COMBUSTION AND VENTILATION AIR IS NOT RESTRICTED.
DANGER
Carbon Monoxide Warning
• Follow all vent system requirements by the local authorities having jurisdiction over your installation.
• Failure to do so can result in death, explo­sion or carbon monoxide poisoning.
Relief Valves (T&P)
All water heaters must be installed with a proper tem­perature and pressure relief valve. These valves must be certified as meeting the requirements of the “Standard
for Temperature, Pressure, Temperature and Pressure Relief and Vacuum Relief” CSA 4.4 in Canada. In the United States “Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems”, ANSI Z21.22 is
applicable. If this water heater has been exposed to flooding, freezing, fire or any unusual condition, do not put it into operation until it has been inspected and approved by a qualified profes­sional. THESE CONDITIONS CAN RESULT IN UNSEEN INTERNAL DAMAGE which is not subject to warranty coverage.
Backflow Prevention
Certain jurisdictions may require the installation of a back­flow device (e.g., check valve) in the water supply line. Such a device will require the use of a system expansion tank of adequate size to control the thermal expansion generated during the heating cycle. Consult your water supplier or local plumbing authority. Important: The supply water meter may have a built-in check valve device. Contact your local water authority.
Hot water produced by this appliance can cause severe burns due to scalding. The hazard is increased for young children, the aged or the disabled where water temperatures exceed 52°C (125°F). Use tempering valves (see Figure
11), in the hot water system to reduce the risk of scalding at point-of-use such as lavatories, sinks and bathing facili­ties. Such precautions must be followed when this heater is operated in combination with dishwashing or space heating applications.
Safety Warning (Carbon Monoxide)
As with all fuel burning equipment, this heater requires an adequate supply of air for combustion and ventilation. An insufficient air supply can result in poor combustion or the re-circulation of the exhaust flue gases. Such a condition can cause soot build-up or present a fire hazard, and may
– 4 –
CAUTION
Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long period of time (generally two (2) weeks or more).
Hydrogen gas is extremely flammable and can ignite when exposed to a spark or flame. To reduce the risk
of injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance con­nected to the hot water system. Use caution in opening faucets. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.
III) INSTALLATION Unpacking the Water Heater
WARNING
Excessive Weight Hazard
How and where to obtain combustion and ventilation air
Routing and support of the vent piping.
Position of water supply and placement of water piping
Floor drain and service.
Use two or more people to move and install water heater. Failure to do so can result in back or other injury.
Important: Do not remove any permanent instructions,
labels or the rating plate from the outside of the water heater or on the inside of panels.
1. Move the water heater to the location of installation before removing the exterior packaging.
2. Remove exterior packaging and place installation com­ponents aside.
3. Inspect all parts for damage prior to installation and start-up.
4. Completely read and understand all instructions before attempting to assemble and install this product.
If you observe damage to the water heater or any of its com­ponents, DO NOT ASSEMBLE OR INSTALL IT OR MAKE ANY ATTEMPT TO FIX THE DAMAGED PART(S). Contact the place of purchase for further instructions.
5. After installation, dispose of packaging material in the proper manner.
Location Requirements
IMPORTANT:
This water heater must be installed strictly in accordance with the instructions enclosed, and local electrical, fuel and building codes. It is possible that connections to the water heater, or the water heater itself, may develop leaks. IT IS THEREFORE IMPERATIVE that the water heater be installed so that any leakage of the tank or related water piping is directed to an adequate drain in such a manner that it cannot damage the building, furniture, floor cover­ing, adjacent areas, lower floors of the structure or other property subject to water damage. This is particularly important if the water heater is installed in a multi-story building, on finished flooring or carpeted surfaces. THE MANUFACTURER WILL NOT ASSUME ANY LIABILITY for damage caused by water leaking from the water heater, pressure relief valve, or related fittings. Select a location as centralized within the piping system as possible. In any location selected, it is recommended that a suitable drain pan be installed under the water heater. This pan must limit the water level to a MAXIMUM depth of 45mm (1 3/4 in.) and have a diameter that is a minimum of 50mm (2 in.) greater than the diameter of the water heater. Suitable piping shall connect the drain pan to a properly operating floor drain. When used with a fuel-fired heater, this drain pan must not restrict combustion air flow.
Note: Before installing this water heater, consideration and planning must be given to the following details:
In Earthquake Zones
Note: The water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area.
Note: REVIEW SAFETY WARNINGS FOUND IN THE FRONT OF THIS MANUAL BEFORE PROCEEDING
Clearances and Accessibility
Specific clearance locations are shown in Figure 3. A mini­mum of 600mm (24 in.) of front clearance shall be provided for inspection and service. We recommend that 0.9m (36 in.) above be maintained for serviceability.
Locate the water heater such that all controls are easily accessible, and the rating plate is visible.
Clearance to combustibles varies by model. Refer to rating plate to confirm clearances. Heaters with a volume of 19 gallons through 50 gallons and 60 gallon (standard input) must have the following minimum clearances to combustibles: Front 102mm (4 in.) Sides and Rear 25mm (1 in.) Top 203mm (8 in.) Flue 152mm (6 in.)
JW6058 and G6058 (high input) series heaters must have the following minimum clearances to combustibles: Front 127mm (5 in.) Sides and Rear 25mm (1 in.) Top 203mm (8 in.) Flue 152mm (6 in.)
Location and Clearances.
Access for gas supply; See “Gas Supply”.
– 5 –
supply; See “Air Requirements”.
for hot and cold water; See “Water Supply”.
45mm
(1 3/4 in.)
MAX
AT LEAST 50mm (2 in.)
GREATER THAN THE
DIAMETER OF THE
WATER HEATER.
Figure 1 Typical Drain Pan Installation
PIPE TO
ADEQUATE
DRAIN
The 60 gallon heater is equipped with a Heat Reflector Shield (see Figure 2). This Shield reflects heat from the High-input heaters to prevent damage to combustible floors. The Shield is held in place by three (3) tabs that rest on the inside of the legs of the water heater. Ensure the Shield is positioned horizontally (parallel to the bottom of the heater) and in the designated position of 38mm (1.5 in.) below the flame-arrestor.
DRAIN VALV E
BOTTOM
PAN
LEG
FLAME
HEAT SHIELD
ARRESTOR
Figure 2 Heat Shield Installation (60 gallon only)
WARNING
Do not install directly on carpet. Instead, place the water heater on a metal or wood panel extending a minimum of 75mm (3 in.) from all sides. In alcoves or closets, cover the carpet completely. Ensure this panel is capable of supporting the weight of this heater when filled with water. FAILURE TO PROPERLY INSTALL THIS HEATER MAY RESULT IN A FIRE HAZARD.
The water heater shall be located in an area not subject to freezing temperatures. Water heaters located in uncon­ditioned spaces (e.g., attics, basements, etc.) may require insulation of the water and drain piping to protect against freezing. Proper ventilation needs to be provided for water heaters installed in unconditioned spaces (e.g., attics, base­ments, etc.) in order to avoid an event where air tempera­ture exceeds 42°C (108°F). The drain and controls must be easily accessible for operation and service. Maintain proper clearances as specified on the data plate. Ensure that the water heater is level. This heater may be installed in a closet or alcove and is certified for operation on a combustible floor.
VENT
BACK 25mm (1 in.)
TOP TO CEILING
200mm (8 in.)
affect the proper operation of the water heater. Special attention must be given to conditions these devices may create. Flow reversal of flue gases may cause an increase of carbon monoxide inside of the dwelling, as shown in Figure 7. If the water heater is located in an area that is subject to an excessive amount of lint, dirt or oil, it may be necessary to clean the flame arrestor periodically (see “Maintenance” section).
Important: It is always recommended that a suitable drain pan be installed under the water heater to protect the area from water damage resulting from normal condensation, a leaking tank or piping connections. Refer to Figure 1. Under no circumstances is the manufacturer to be held responsible for any water damage in connection with this water heater.
Gas Supply
Install the gas piping as shown in Figure 4. Use only new pipe and fittings with clean-cut threads. Sealing compounds used on the pipe threads shall be approved for use with natural and propane gas. Use gas piping of adequate sizing to ensure gas input. Gas piping material must be approved for use with natu­ral gas and propane fuels. All piping must comply with all local codes and with the latest edition of “Natural Gas
and Propane Installation Code” CSA-B149.1 in Canada, “National Fuel Gas Code” ANSI Z223.1 (NFPA 54) in the
U.S.A. The final connection to the water heater is made using 1/2” NPT. Before connecting to the gas service, check that a properly sized gas meter and regulator are available to service the water heater. If other appliances are using the same meter and regulator, ensure that the capacity of the meter and regulator matches that of the combined input of all appli­ances connected to it. DO NOT tamper with the gas control/thermostat, igniter, thermocouple, or temperature and pressure relief valve. Tampering voids all warranties. Only a qualified service technician should service these components.
MANUAL
GAS
SHUT-OFF
GAS CONTROL/THERMOSTAT
SIDES
25mm
(1 in.)
SIDES
AND BACK
25mm (1 in.)
FRONT 600mm
(24 in.) MIN.
FOR SERVICE
Figure 3 Minimum Clearance Locations
Do not locate the water heater near an air-moving device. The operation of air-moving devices such as exhaust fans, ventilation systems, clothes dryers, fireplaces, etc., can
– 6 –
AIR INTAKE
75mm (3 in.)
GROUND-
JOINT UNION
Figure 4 Recommended Gas Piping
Gas Pressure
WARNING
Exposure to a higher gas supply pressure may cause damage to the control, resulting in explosion or fire. Consult your local gas supplier and gas authorities. DO NOT PUT INTO SERVICE IF OVER-PRESSURIZATION HAS OCCURRED.
The Manufacturer recommends that the gas supply pres­sure, as measured on the inlet side of the water heater control, be set at 7.0 in. w.c. (1.7 kPa) for natural gas and
11.0 in. w.c. (2.7 kPa) for propane gas. The above pressures
must be measured during water heater operation.
The gas control supplied with this water heater is designed for a maximum inlet pressure of 0.5 psi (14 in. w.c.). Do not exceed this limit. The Flame GuardTM safety system is designed to operate within the pressure ranges shown in Table 1. Rated manifold pressures are indicated on the rat­ing plate of the water heater.
Rated Manifold
Pressure.
in. w.c. (kPa)
10 (2.48) 9.2 (2.28) 10.2 (2.53)
5 (1.24) 4.5 (1.11) 5.1 (1.26)
4 (0.99) 3.6 (0.89) 4.4 (1.09)
Min. Manifold
Pressure.
in. w.c. (kPa)
Max. Manifold
Pressure.
in. w.c. (kPa)
Gas line purging
Gas line purging is required to eliminate air from the piping system. Purging should be performed by persons experi­enced in this type of gas service in compliance with the code having jurisdiction. Do not purge in confined areas or space where ignition may occur. To avoid risk of fire or explosion ensure the area is well ventilated and all sources of ignition are de-activated. Contact your local gas authority for local requirements.
Gas Leak Testing
Important: This water heater and its gas connection must be tested for leaks before placing the appliance in operation. Perform a leak test at normal gas pressure. If the applicable code(s) require the gas lines to be tested at a pressure of 14 in. w.c. (3.5 kPa) or greater, the water heater and its manual shut-off valve must be disconnected from the gas supply piping system and the line capped. Test all connections of the gas system with a chloride-free soap and water solution or equivalent leak test liquid. Bubbles will indicate leaks. Never use a match or open flame to test for gas leaks. A fire or explosion could result. If leaks exist repair as required and retest. DO NOT light the burner before the tank is filled with water and you have confirmed that there are no leaks in the piping and connections.
Table 1 Manifold Pressure
– 7 –
Air Requirements
Important: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corro­sive elements in the atmosphere is excluded from warranty coverage. Installations in or for certain places including, but not limited to, those listed below will require outdoor air for combustion due to chemical exposure:
Beauty shops
Photo processing labs
Buildings with indoor pools
Water heaters installed in laundry, hobby or craft rooms
Water heaters installed near chemical storage areas
(12 in.) equals 450mm (18 in.) as shown in Figure 5 (b). All exterior vent openings are to be at least 300mm (12 in.) above the ground and clear of snow levels.
(a)
PERMANENT
OPENINGS
CONFINED
SPACE
UNCONFINED
SPACE
In such circumstances, outdoor combustion air may reduce, but will not eliminate, the presence of corrosive chemicals in the air. Combustion air must be free of acid-forming chemi­cals such as sulfur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrig­erants and many other commercial and household products. When burned, vapours from these products form highly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet. The area in which the heater is located is classified as either “an unconfined space” or “a confined space”. An unconfined space is defined as a space having a vol- ume not less than 50 cubic feet per 1000 BTU/hour (4.8 cubic metres per kilowatt) of combined input rating of all appliances using the space. Adjacent open rooms may be included as part of the unconfined space, provided there are no closeable doors between these rooms. An example of this is an open basement. A confined space is one smaller than described above. For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the outdoors, regardless of whether the space is confined or unconfined.
Confined Space Air Requirements for Canadian Installations
Refer to Figure 5 (a), or (b), and Table 2 for proper sizing and location of combustion air ducts and openings. CHECK
LOCAL CODES.
(a). Two permanent openings shall be provided connect-
ing the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space. The top opening shall be located as close to the ceiling as practical but never lower than the top of the heater (see Figure 5 (a)). The bottom opening shall be located nei­ther more than 450mm (18 in.), nor less than 150mm (6 in.), above floor level.
(b). When using a single air supply, the duct shall terminate
within 300mm (12 in.) above and within 600mm (24 in.) horizontally of the burner level of the appliance having the largest input. For example: if the water heaters’ burners are 150mm (6 in.) from the floor, plus 300mm
– 8 –
EQUIPMENT LOCATED IN CONFINED SPACES;
ALL AIR FROM INSIDE THE BUILDING.
300mm
(b)
(12 in.)
(MIN)
GRADE
COMBINATION
COMBUSTION/
VENTILATION
AIR DUCT
BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS
450mm (18 in.)
CONFINED
SPACE
600mm (24 in.)
Figure 5 Combustion Air Supply Openings And Ducts
(Can.)
Combined Input of
All Appliances in
Confined Space*
Required
Free Area
Acceptable Round
Duct Size Diameter
A** B***
BTU/h (kW/hr) cm2in.2mm in. mm in.
25,000 8 45 7 76 3 100 4
50,000 15 45 7 76 3 100 4
75,000 23 70 11 100 4 125 5
100,000 30 90 14 100 4 125 5
125,000 37 120 18 125 5 150 6
150,000 45 140 22 125 5 150 6
* All appliances refers to, and includes, those appliances
using the same air source (e.g. water heater, furnace, boiler, clothes dryer etc.).
** Maximum allowable length of ductwork listed in column
A is 6.1 equivalent metres (20 ft.).
*** Maximum allowable length of ductwork listed in column
B is 15.2 equivalent metres (50 ft.)
Table 2 Air Supply Sizing (Can.)
(a)
Confined Space Air Requirements for U.S. Installations
Refer to Figure 6 (a), (b), (c) or (d) for proper sizing and location of combustion air ducts and openings. CHECK
LOCAL CODES.
CONFINED
SPACE
(b)
CONFINED
SPACE
(c)
CONFINED
SPACE
UNCONFINED
EQUIPMENT LOCATED IN CONFINED SPACES;
ALL AIR FROM INSIDE THE BUILDING.
COMBUSTION
AIR DUCT
BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS
EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS.
300mm
(12 in.)
OUTDOORS
AIR DUCT
300mm (12 in.)
VENTILATION
COMBUSTION
300mm (12 in.)
PERMANENT
OPENINGS
SPACE
PERMANENT
VENTILATION
AIR.
300mm
(12 in.) ABOVE GRADE
OR
SNOW
LINE
GRADE
300mm
(12 in.)
(a) Equipment located in confined spaces; all air from
inside the building.
Two permanent openings shall be provided connect-
ing the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space, but not less than 100 square inches (645 cm²). The top open­ing shall commence within 300mm (12 in.) of the top of space and the bottom opening shall commence within 300mm (12 in.) of the bottom of the enclosure.
(b) Basement installation, equipment located in con-
fined spaces; all air from outdoors.
When supplying air directly from the outdoors, each
opening shall have a minimum free area of one square inch per 4,000 BTU/hour input (5.5 cm²/kW) of total input rating of all appliances in the confined space. The inlets shall be a minimum of 300mm (12 in.) above the grade (snow) line. The top opening shall commence within 300mm (12 in.) of the top of the confined space.
(c) Equipment located in confined spaces; all air from
outdoors.
When supplying air directly from the outdoors using
horizontal ducting, each opening shall have a free minimum area of one square inch per 2,000 BTU/hour (11 cm²/kW) of total input rating of all appliances in the confined space.
(d) Equipment located in confined spaces; all air from
outdoors through ventilated attic.
When supplying air directly through vertical ducting,
each opening shall have a free minimum area of one square inch per 4,000 BTU/hour (5.5 cm²/kW) of total input rating of all appliances in the confined space.
(d)
CONFINED
SPACE
EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR
FROM OUTDOORS THROUGH VENTILATED ATTIC.
ATTIC LOUVERS TO OUTDOORS
Figure 6 Combustion Air Supply Openings And Ducts
(U.S.A.)
– 9 –
OUTLET
AIR
INLET AIR
300mm (12 in.)
DUCT
EXHAUST
REVERSE
FLOW OF
GASES
Figure 7 Air Moving Devices
FAN
Exhaust Venting
Vent Pipe System
This water heater is a Category 1, non-direct vented appli­ance. The vent pipe must be sized and installed in accor­dance with all local and provincial or state codes and with the latest edition of “Natural Gas and Propane Installation
Code” CSA-B149.1 in Canada, “National Fuel Gas Code” ANSI Z223.1 (NFPA 54) in the U.S.A.
Check for proper vent size
It is possible that the existing venting system was sized, for a previous installation, through a common vent. Such an arrangement is appropriate for venting two appliances such as the original water heater and a standard vent furnace. If this is true and the second appliance has been removed from the existing venting system (such as when the furnace has been upgraded to a power vent type), the venting sys­tem is now supplying only one appliance. This condition is commonly referred to as “orphaning” the water heater and the venting system must be properly resized for a single appliance. Improper sizing can cause a number of undesir­able and potentially unsafe results including spillage of the products of combustion into the room, poor combustion, excessive condensation, pilot outage or delayed ignition. The vent pipe must not be obstructed so as to prevent the removal of exhaust gases to the outside atmosphere. Note: The horizontal section of the vent must slope up 21mm per metre (1/4 in. per foot), (see Figure 8). CSA/U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules or regulations. Important: If you lack the necessary skills required to prop­erly install this venting system, you should not proceed, but enlist the help of a qualified service technician.
Drafthood Installation
Hook the tab leg of the drafthood into the slot in the heater’s top or the flue damper if the heater is equipped with a flue damper. Align the remaining legs with the hole/dimples and secure the drafthood to the top with three screws as shown in Figure 9. Do not alter the drafthood in any way. If you are replacing an existing water heater be sure to use the new drafthood supplied with the water heater.
DRAFTHOOD
SCREW
TAB LEG
SLOT
Figure 9 Drafthood Installation
Water Supply
Piping Installation
IN A CLOSED SYSTEM USE EITHER:
HOT WATER
OUTLET
1.THERMAL EXPANSION TANK
2.PRESSURE RELIEF VALVE COLD WATER
INLET VALVE
SLOPE UP 21mm PER METRE
(1/4 in. PER ft) MIN.
Figure 8 Vent System
– 10 –
PIPE
INSULATION
UNION
PRESSURE REDUCING
VALVE WITH BYPASS
TEMPERATURE AND
PRESSURE RELIEF VALVE
DISCHARGE LINE 300mm
(12 in.) MAX (CANADA)
OR 150mm (6 in.) MAX
(U.S.A.) ABOVE DRAIN
MASSACHUSETTS:
INSTALL A VACUUM
RELIEF IN COLD WATER
LINE PER SECTION
19MGL 142
DRAIN LINE 19mm
(3/4 in.) ID MIN
Figure 10 Example Of Water Piping Installation
COLD WATER
INLET
Loading...
+ 22 hidden pages