John Wood Superflue Power Vent User Manual

PART NO. 186714-000 REV. A (08-05)
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, per­sonal injury or death.
WARNING:
Improper installation, adjustment, alter­ation, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation, consult a qualified installer, serv­ice agency, or the gas utility.
FOR YOUR SAFETY
• Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
• Installation and service must be per­formed by a qualified installer, service agency or the gas utility.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
WHAT TO DO IF YOU SMELL GAS
GSW Water Heating is a division of A. O. Smith Enterprises Ltd.
POWER VENTED GAS
FIRED WATER HEATER
INSTALLATION AND OPERATING INSTRUCTIONS
Read these instructions thoroughly before starting
– 2 –
This page intentionally left blank. May be used for notes or to record other installation information.
– 3 –
TABLE OF CONTENTS
Replacement Parts Listing/
Clearance to Combustibles . . . . . . . . . . . . . . . . . 4
I) INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
User Responsibilities 5
II) SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
For Installations in Canada: 6 For Installations in the United States: 6 Safety Warning (Flammable Vapours) 6 Safety Warning (Scalding) 6 Safety Warning (Carbon Monoxide) 6 Relief Valve Requirements (T&P) 7
III) INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unpacking the Water Heater 7 Location Requirements 7
In Earthquake Zones Clearances and Accessibility 8 Gas Supply 8
Gas Supply Pressure
Gas line purging
Gas Leak Testing
Gas Operating Pressures Air Requirements 9
General Combustion Air “Supply” Ducts 9 Louvers and Grilles 9 Air Requirements 10 Confined Space Air Requirements for Canadian Installations 10 Confined Space Air Requirements for U.S. Installations 11 Exhaust Venting 12
Important Notes and Warnings
Venting terminations and sizing
Venting instructions
Vent pipe connection to blower Water Supply 16
Piping Installation
Filling the Water Heater
Closed System/Thermal Expansion Temperature and Pressure (T&P) Relief Valve 17
The Temperature and Pressure Relief Valve:
The Discharge Line/Driptube: Electrical Supply 18 Installation Checklist 19
IV) OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . 21
Temperature Regulation 21 Mixing Valves 21 Lighting Instructions (Robertshaw) 22
Gas Control/Thermostat
Putting the Heater into Service
Temperature Adjustment
Heater Shutdown
Water Heater Operation
Lighting Instructions (White-Rodgers Intelli-Vent
TM
)24 Gas Control/Thermostat Putting the Heater into Service Temperature Adjustment Heater Shutdown System Error Codes Intelli-VentTMSystem Error Codes
V) OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Performance Checks 28
Burner Manifold Pressure Checking Input Checking burner flame
VI) SERVICE AND MAINTENANCE. . . . . . . . . . . . . . 28
Not Enough or No Hot Water Energy Cut-off Control (ECO) Water is Too Hot Hot Water Odour Discoloured Water Water Heater Makes Noise Extended Non Use Service Condensation Anode Maintenance To inspect or change an anode: Tank Flushing Relief Valve Check Vent Maintenance Burner Maintenance
VII) COMBO HEATING . . . . . . . . . . . . . . . . . . . . . . . . 31
System Requirements 31 Installation 32
Fan Coil Baseboard Radiator Heating
Maintenance 32
VIII) TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . 33
SUPERFLUE
TM
33
White-Rodgers Intelli-Vent
TM
35
INSTALLATION RECORD . . . . . . . . . . . . . . . . . . 36
LIMITED WARRANTY. . . . . . . . . . . . . . . . . . . . . . 37
RETAIN THESE INSTRUCTIONS IN A SAFE LOCATION FOR FUTURE REFERENCE
– 4 –
Replacement Parts Listing/Clearance to Combustibles
1. TERMINATION ELBOW WITH RODENT SCREEN
2. PIPE LENGTH *
3. PIPE COUPLING *
4. PIPE ELBOW *
5. RUBBER COUPLING
6. AIR TUBING
7. AIR SWITCH
8. JUNCTION BOX
9. JUNCTION BOX COVER
10. POWER CORD
11. BLOWER
12. BLOWER SUPPORT BRACKET
13. DRAFT DIVERTER
14. HIGH LIMIT SWITCH
15. ANODE (UNDER CAP)
16. INLET NIPPLE
17. DIPTUBE
18. T&P VALVE
19. DRIPTUBE *
20. BAFFLE ASSEMBLY
21. CONTROL VALVE (WHC)
22. CONTROL VALVE COVER (WHC)
23. INNER GAS DOOR
24. OUTER GAS DOOR
25. DRAIN VALVE
26. FLARE TUBE (GAS SUPPLY)
27. IGNITER ASSEMBLY
28. FLAME SENSOR
29. IGNITER BRACKET
30. ORIFICE
31. AIR SHUTTER
32. CAST IRON BURNER
33.
34. HEATING SYSTEM SUPPLY
35. HEATING SYSTEM RETURN
36. PVC ADAPTER
* OWNER SUPPLIED
Note: Manifold Tube Connections at Control Valve;
Right-Hand Threads for Natural Gas, Left-Hand Threads for Propane
10
11
12
20
34
21 22
23 24
MINIMUM CLEARANCE 50mm (2 in.)
DRAIN PAN IF REQUIRED MIN. DIA. 660mm (26 in.)
MAX. PAN DEPTH 45mm (1 3/4 in.)
25
FLOOR DRAIN
MINIMUM CLEARANCE 25mm (1 in.)
19
MINIMUM CLEARANCE 25mm (1 in.)
18
17
16
14
15
MINIMUM CLEARANCE 300mm (12 in.)
13
5
4
3
2
6
7
9
8
35
36
CAST IRON BURNER ASSEMBLY USED WITH THE INTELLI-VENT
TM
GAS VALVE.
Figure 1 Water Heater and Burner Assemblies
1
30
28
32
27
29
31
26
26
27
28
29
32
30
31
CAST IRON BURNER ASSEMBLY USED WITH THE 2000N WDER GAS VALVE.
– 5 –
Your safety and the safety of others is very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING”.
DANGER
WARNING
You can be killed or seriously injured if you don’t immediately follow instructions.
You can be killed or seriously injured if you don’t follow instructions.
I) INTRODUCTION
We thank you for choosing a GSW/John Wood Water Heater. Your satisfaction with this product is very important
to us. This gas-fired water heater has been developed to produce potable hot water and may also be used in combi­nation with space heating applications. The “Superflue”™ series is designed to vent the products of combustion (flue gases) horizontally through an exterior wall or vertically through the roof using an integrated blower assembly and plastic piping, without the need for a conventional chimney.
User Responsibilities
This manual has been prepared to acquaint you with the installation, operation and maintenance of your gas fired water heater and provide important safety information in these areas. It is your responsibility to ensure that your water heater is properly installed and cared for.
FAILURE TO FOLLOW THE INSTRUCTIONS IN THIS MANUAL MAY RESULT IN SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. THOROUGHLY READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE YOU ATTEMPT TO INSTALL, OPERATE OR MAINTAIN THIS HEATER.
Installation and service requires trade knowledge in the areas of plumbing, electricity, venting, air supply and gas supply. If you lack these skills or have difficulty understand­ing these instructions, you should not proceed. Enlist the help of a qualified service technician to install this water heater. Examples of qualified service technicians include those trained in the plumbing and heating industry, local gas utili­ty personnel or an authorized service person.
Service to the Power Vent System should only be per­formed by a qualified service technician.
The manufacturer and seller of this water heater will not assume any liability for any property damage, personal injury or death resulting from improper sizing, installation or failure to comply with these instructions.
The warranty on this water heater is in effect only when the water heater is installed and operated in accordance with these instructions. A data plate identifying your water heater can be found above the gas control/thermostat. When refer­ring to your water heater, always have the information listed on the data plate readily available.
Protect your warranty: Regularly service your water heater as directed in the "Maintenance" section of this man­ual. Retain your original receipt as proof of purchase.
Do not discard this manual. You or future users of this water heater will need it for reference.
II) SAFETY
This water heater is design-certified by CSA International as a Category III, non-direct vented water heater that takes its combustion air either from the installation area or from air ducted to the unit from the outside.
In addition to the installation instructions found in this man­ual, the water heater must be installed in accordance with all local and provincial or state codes or, in the absence of such, with the latest editions of the following specifications.
For Installations in Canada:
"Natural Gas and Propane Installation Code" CAN/CSA­B149.1 and "Canadian Electrical Code” (CAN/CSA C22.1), Part I available from:
Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, Canada L4W 5N6
For Installations in the United States:
"National Fuel Gas Code" ANSI Z223.1 (NFPA 54) and "National Electrical Code" (NFPA 70) available from:
American National Standards Institute, 25 West 43rd Street, New York, NY 10036 Massachusetts code requires this water heater to be installed in accordance with Massachusetts Plumbing and Fuel Gas Code 248 CMR Section 2.00 and 5.00.
Check your phone listings for the local authorities having jurisdiction over your installation.
Safety Warning (Flammable Vapours)
There is a risk of property damage, personal injury or death from the by-products of combustion (e.g., flue gases), in using fuel-burning appliances such as water heaters. Areas that may not be suitable for water heater installation include those where flammable liquids, gasoline, solvents, adhe­sives etc. are stored, or where engine-driven equipment or vehicles are stored, operated or repaired. These, and simi-
lar products, should not be stored or used near the water heater or air intake. Due to the nature of air movement, flammable vapours can be carried some distance from the point of storage. The gas-fired water heater igniter or burn­er flame can ignite these vapours causing a flashback, fire or explosion, which may result in severe property damage, serious personal injury or death. If flammable liquids or vapours have spilled or leaked in the area of the water heater, leave the area immediately and call the fire depart­ment from a neighbor's home. Do not attempt to clean the spill until all ignition sources have been extinguished.
Safety Warning (Scalding)
Hot water produced by this appliance can cause severe burns due to scalding. The hazard is increased for young children, the aged or the disabled when water temperatures exceed 52°C (125°F). Use tempering valves, also known as mixing valves, in the hot-water system to reduce the risk of scalding at point-of-use such as lavatories, sinks and bathing facilities (see Figure 16). Such precautions must be followed when this heater is operated in combination with dishwashing or space heating applications.
Safety Warning (Carbon Monoxide)
As with all fuel burning equipment, this heater requires an adequate supply of air for combustion and ventilation. An insufficient air supply can result in poor combustion or the re-circulation of the flue gases. Such a condition can cause soot build-up and present a fire hazard. Flow reversal of flue gases can cause an increase of carbon monoxide inside of the dwelling that could result in serious bodily harm or death from asphyxiation.
MAKE SURE THE FLOW OF COMBUSTION AND VENTILATION AIR IS NOT RESTRICTED.
WARNING
Flammable Vapours
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapours or liquids in the vicinity of this or any other appliance can result in serious injury or death.
DANGER
DANGER
Carbon Monoxide Warning
• Follow all vent system requirements by the local authorities having jurisdiction over your installation.
• Failure to do so can result in death, explo­sion or carbon monoxide poisoning.
– 6 –
Relief Valve Requirements (T&P)
All water heaters must be fitted with a proper temperature and pressure relief valve. These valves must be certified as meeting the requirements of the "Standard For Relief
Valves For Hot Water Supply Systems”, ANSI Z21.22/CSA 4.4.
If this water heater has been exposed to flooding, freezing, fire or any unusual condition, do not put it into operation until it has been inspected and approved by a qualified service technician. THESE CONDITIONS CAN RESULT IN UNSEEN INTERNAL DAMAGE and are not subject to war­ranty coverage.
III) INSTALLATION
Unpacking the Water Heater
Important: Do not remove any permanent instructions, labels, or the data label from outside of the water heater or on the inside of panels.
Remove exterior packaging and place installation com­ponents aside.
Inspect all parts for damage prior to installation and start-up.
Completely read all instructions before attempting to
assemble and install this product. If you observe damage to the water heater or any of its com­ponents, DO NOT ASSEMBLE OR INSTALL IT OR MAKE ANY ATTEMPT TO FIX THE DAMAGED PART(S). Contact the place of purchase for further instructions.
After installation, dispose of packaging material in the
proper manner.
Location Requirements
The water heater must be installed indoors in an area not subject to freezing temperatures and in a vertical position on a level surface. Water heaters located in unconditioned spaces (e.g., attics, basements etc.) may require insulation of the water piping, drain piping and venting to protect against condensation. The power vented series of water heaters are designed to vent the products of combustion horizontally through the wall or vertically through the roof. The blower expels the products of combustion by means of plastic piping to the outdoors without the need for a con­ventional chimney. Select a location as centralized within the piping system as possible. The heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower floors of the structure (see "IMPORTANT" notice above). Before installing this water heater, consideration and planning must be given to the following details:
Proximity to walls and other objects (see "Clearance and Accessibility").
Air supply (see “Air Requirements”).
Access to gas supply (see "Gas Supply").
Routing and support of the vent piping and termination (see "Exhaust Venting").
Position of water supply and placement of water piping and floor drain (see "Water Supply").
In Earthquake Zones
Note: The water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area.
IMPORTANT:
This water heater must be installed strictly in accordance with the instructions enclosed, and local electrical, fuel and building codes. It is possible that connections to the water heater, or the water heater itself, may develop leaks. IT IS THEREFORE IMPERATIVE that the water heater be installed so that any leakage of the tank or relat­ed water piping is directed to an adequate drain in such a manner that it cannot damage the building, furniture, floor covering, adjacent areas, lower floors of the structure or other property subject to water damage. This is particular­ly important if the water heater is installed in a multi-story building, on finished flooring or carpeted surfaces. GSW WILL NOT ASSUME ANY LIABILITY for damage caused by water leaking from the water heater, pressure relief valve, or related fittings. Select a location as centralized within the piping system as possible. In any location selected, it is recommended that a suitable drain pan be installed under the water heater. This pan must limit the water level to a MAXIMUM depth of 45mm (1 3/4 in.) and have a diameter that is a minimum of 50mm (2 in.) greater than the diameter of the water heater. Suitable piping shall connect the drain pan to a properly operating floor drain. When used with a fuel-fired heater, this drain pan must not restrict combustion air flow.
WARNING
Excessive Weight Hazard
Use two or more people to move and install water heater. Failure to do so can result in back or other injury.
CAUTION
Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long period of time (generally two (2) weeks or more).
Hydrogen gas is extremely flammable and can ignite when exposed to a spark or flame. To reduce the risk of
injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance con­nected to the hot water system. Use caution in opening faucets. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.
– 7 –
Note: The water heater may be installed in a closet with a door off a bedroom or bathroom providing the units are installed and vented per the manufacturer's instructions. Important: If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least 76mm (3 in.) in each direction or if in an alcove or closet installation, the entire floor must be covered by the panel.
Clearances and Accessibility
The minimum clearances between the heater and com-
bustible materials are:
Top 300mm (12 in.) Front 100mm (4 in.)
Rear and Sides 25mm (1 in.) Note: These requirements are also listed on the data plate located on the front of the water heater.
The water heater is certified for installation on a com-
bustible floor. Figure 2 may be used as a reference guide to locate the specific clearance locations. A minimum of 600mm (24 in.) of front clearance and 100mm (4 in.) on each side should be provided for inspection and service.
Gas Supply
Read the data plate to be sure the water heater is made for the type of gas you will be using in your home. This
information will be found on the data plate located above the gas control valve. If the information does not agree with the type of gas available, do not install or attempt to start. Call your dealer.
Note: An odourant is added by the gas supplier to the gas used by this water heater. This odourant may fade over an extended period of time. Do not depend upon this odourant as an indication of leaking gas.
This gas piping must be installed in accordance with all local and provincial or state codes or, in the absence of such, the latest edition of "Natural Gas and Propane Installation
Code" CAN/CSA-B149.1 (Canada), or "National Fuel Gas Code" ANSI Z223.1 (NFPA 54) (U.S.A.).
Use properly sized gas piping and to ensure full gas input and a properly sized gas supply regulator to ensure ade-
DANGER
Explosion Hazard
• Use a new CSA approved gas supply line.
• Install a gas supply shut-off valve.
• Do not connect a natural gas water heater to a L.P. gas supply.
• Do not connect a L.P. gas water heater to a natural gas supply
• Failure to follow these instructions can result in death, an explosion or carbon monoxide poisoning.
GROUND-JOINT UNION
MANUAL
GAS
SHUT-OFF
SEDIMENT TRAP
GAS VALV E
GAS MANIFOLD
76mm (3 in.)
Figure 3 Gas Piping
– 8 –
Figure 2 Rough-in Dimensions
“G”
COLD INLET 3/4” NPT
HOT OUTLET
3/4” NPT
HEATING
OUTLET
HEATING
INLET
POWER CORD
(120) VAC/60Hz
GAS INLET
1/2” NPT
DRAIN VALV E
T&P
VALV E
“A”
“I”
“B”
“E”
“D”
“F”
“C”
“H”
ABCD E FGH I
mm
610 302 432 1388 1575 1826 76 305 537
in. 24 11- 7/8 17 54-5/8 62 71-7/8 3 12 21-1/8
G/JW75
M ODEL NO.
quate gas supply pressure. The supply piping and regulator must be large enough to satisfy the requirements of all appliances connected to the gas service and when all appli­ances are operating simultaneously. Undersize piping and insufficient pressure can restrict the gas flow causing the water heater to perform poorly. Improperly sized piping may pose a safety hazard.
Note: When installing gas piping, apply sealing compounds approved for use with natural and propane gas.
1. Install a readily accessible manual shut-off valve in the gas supply line as recommended by the local utility. The owner/operator must be shown the location of this valve and be given instructions on how to use it to shut off the gas to the heater.
2. Install a drip leg (if not already incorporated as part of the water heater) as shown. The drip leg must be no less than 76mm (3 in.) long for the accumulation of dirt, foreign material, and water droplets.
3. Install a ground joint union between the gas control /thermostat and the manual shut-off valve. This is to allow easy removal of the gas control/thermostat.
4. Turn the gas supply on and check for leaks. Use a chlo­ride-free soap and water solution (bubbles forming indi­cate a leak) or other approved method.
Gas Supply Pressure
Important: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater's data plate.
Gas line purging
Air may be present in the gas lines and could prevent the burner from lighting on initial start-up. The gas lines should be purged of air by a qualified service technician after instal­lation of the gas piping system.
Gas Leak Testing
Important: This water heater and its gas connection must be leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a pres­sure exceeding 14 in. w.c. (3.5 kPa), the water heater and its manual shut-off valve must be disconnected from the gas supply piping system and the line capped.
If the gas lines are to be tested at a pressure less than 14 in. w.c. (3.5 kPa), the water heater must be isolated from the gas supply piping system by closing its manu­al shut-off valve.
Gas Operating Pressures
The gas supply pressure and burner manifold pressure is listed on the data plate located on the front of the heater above the gas control/thermostat. Ensure the gas supply pressure to the water heater and the burner manifold pres­sure are properly adjusted while all appliances are in oper­ation. Refer to Figure 20 for Gas Control/Thermostat Details.
U.L. and CSA recognized fuel gas and Carbon Monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer's instructions and local codes, rules or regulations.
Air Requirements
General
An adequate air supply shall be provided for combus­tion and ventilation of this water heater. An insufficient supply can result in poor combustion and possible soot­ing of the burner, combustion chamber or flue passage­way. This may present a potential fire hazard or could create a serious health hazard by producing carbon
monoxide. Where an exhaust fan or any other air consuming appliance (e.g., clothes dryer, furnace, etc.) is installed in the same space as the water heater, sufficient air openings must be available to provide fresh air when all appliances are oper­ating simultaneously.
For buildings that are not well-sealed (do not have tight fit­ting doors and windows) natural air infiltration may provide sufficient air required for combustion and ventilation. For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the out­doors, regardless of whether the space is confined or unconfined.
Combustion Air “Supply” Ducts
Air supply ducts shall be of galvanized steel or equivalent corrosion resistant material. A single air duct may not be substituted when required for upper and lower air openings. Horizontal combustion air ducts shall not slope downward toward the air inlet.
Louvers and Grilles
Openings for air supply ducts must provide free unobstruct­ed air movement. Louver and grille openings must be sized to ensure that the FREE OPEN AREA is never less than the area of the air duct.
– 9 –
WARNING
Exposure to a higher gas supply pressure may cause damage to the control, resulting in explosion or fire. Consult your local gas supplier and gas authorities. DO NOT PUT INTO SERVICE IF OVER-PRESSURIZATION HAS OCCURRED.
WARNING
Failure to properly install this heater may result in a fire hazard.
Air Requirements
Important: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to cor­rosive elements in the atmosphere is excluded from war­ranty coverage. Installations in or for certain places including, but not limited to, those listed below will require outdoor air for combustion to reduce the risk of chemical exposure:
Beauty shops Photo processing labs Buildings with indoor pools Water heaters installed in laundry, hobby or craft rooms Water heaters installed near chemical storage areas
In such circumstances, outdoor combustion air may reduce, but will not eliminate the presence of corrosive chemicals in the air. Combustion air must be free of acid-forming chemi­cals such as sulfur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrig­erants and many other commercial and household prod­ucts. When burned, vapours from these products form high­ly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet.
The area in which the heater is located is classified as either "an unconfined sp
ace
" or "a confined sp
ace
."
An unconfined sp
ace is defined as a space having a vol­ume not less than 50 cubic feet per 1000 BTU/hour (4.8 cubic metres per kilowatt) of combined input rating of all appliances using the space. Adjacent open rooms may be included as part of the unconfined space, provided there are no closeable doors between these rooms. An exam­ple of this is an open basement.
A confined sp
ace is one smaller than described above. For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the out­doors, regardless of whether the space is confined or unconfined.
Confined Space Air Requirements for Canadian Installations
Refer to Figure 4 (a), or (b), and Table 1 for proper sizing and location of combustion air ducts and openings. CHECK LOCAL CODES. a). Two permanent openings shall be provided connecting
the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space. The top opening shall be located as close to the ceiling as prac­tical but never lower than the top of the heater. (see Figure 4 (a)). The bottom opening shall be located nei­ther more than 450mm (18 in.), nor less than 150mm (6
in.), above floor level. Note: Ensure sufficient ventilation air to prevent elevated temperatures in closets and confined spaces.
b). When using a single air supply, the duct shall terminate
within 300mm (12 in.) above and within 600mm (24 in.) horizontally of the burner level
of the appliance having the largest input. For example: GSW's water heaters' burners are 150mm (6 in.) from the floor, plus 300mm (12 in.) equals 450mm (18 in.) as shown in Figure 4 (b). All exterior vent openings are to be at least 300mm (12 in.) above the ground and clear of snow levels.
– 10 –
CONFINED
SPACE
PERMANENT OPENINGS
EQUIPMENT LOCATED IN CONFINED SPACES;
ALL AIR FROM INSIDE THE BUILDING.
(a)
UNCONFINED SPACE
BASEMENT INSTALLATION, EQUIPMENT LOCATED
IN CONFINED SPACES; ALL AIR FROM OUTDOORS
(b)
CONFINED
SPACE
GRADE
COMBINATION COMBUSTION/
VENTILATION
AIR DUCT
300mm (12 in.) (MIN)
450mm (18 in.)
600mm (24 in.)
Figure 4 Combustion Air Supply Openings And Ducts
(Canada)
BTU / h (kW / hr)
cm2in.2mm in. mm in.
75,000 23 70 11 100 4 125 5 100,000 30 90 14 100 4 125 5 125,000 37 120 18 125 5 150 6 150,000 45 140 22 125 5 150 6
Acceptable Round
Duct Size Diameter
Combined Input of
All Appliances in
Confined Space*
Required
Free Area
A**
B***
Table 1 Air Supply Sizing (Canada)
* All appliances refers to, and includes, those appliances
using the same air source (e.g. water heater, furnace, boiler, clothes dryer etc.).
** Maximum allowable length of ductwork listed in column
A is 6.1 equivalent metres (20 ft.).
*** Maximum allowable length of ductwork listed in column
B is 15.2 equivalent metres (50 ft.).
Confined Space Air Requirements for U.S. Installations
Refer to Figure 5 (a), (b), (c) or (d) for proper sizing and location of combustion air ducts and openings. CHECK
LOCAL CODES.
(a) Equipment located in confined spaces; all air from
inside the building.
Two permanent openings shall be provided connecting the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space, but not less than 100 square inches (645 cm²). The top open­ing shall commence within 300mm (12 in.) of the top of space and the bottom opening shall commence within 300mm (12 in.) of the bottom of the enclosure.
(b) Basement installation, equipment located in con-
fined spaces; all air from outdoors.
When supplying air directly from the outdoors, each opening shall have a minimum free area of one square inch per 4,000 BTU/hour input (5.5 cm²/kW) of total input rating of all appliances in the confined space. The inlets shall be a minimum of 300mm (12 in.) above the grade (snow) line. The top opening shall commence within 300mm (12 in.) of the top of the confined space.
(c) Equipment located in confined spaces; all air from
outdoors.
When supplying air directly from the outdoors using hor­izontal ducting, each opening shall have a free mini­mum area of one square inch per 2,000 BTU/hour (11 cm²/kW) of total input rating of all appliances in the con­fined space.
(d) Equipment located in confined spaces; all air from
outdoors through ventilated attic.
When supplying air directly through vertical ducting, each opening shall have a free minimum area of one square inch per 4,000 BTU/hour (5.5 cm²/kW) of total input rating of all appliances in the confined space.
Note: Ensure sufficient ventilation air to prevent elevated temperatures in closets and confined spaces.
CONFINED
SPACE
PERMANENT OPENINGS
EQUIPMENT LOCATED IN CONFINED SPACES;
ALL AIR FROM INSIDE THE BUILDING.
(a)
UNCONFINED SPACE
CONFINED
SPACE
ATTIC LOUVERS TO OUTDOORS
EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR
FROM OUTDOORS THROUGH VENTILATED ATTIC.
(d)
INLET AIR DUCT
OUTLET
AIR
BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS
(b)
CONFINED
SPACE
GRADE
300mm
(12 in.)
300mm
(12 in.)
Figure 5 Combustion Air Supply Openings And Ducts
(U.S.A.)
COMBUSTION
AIR DUCT
PERMANENT
VENTILATION
AIR.
300mm
(12 in.)
ABOVE
GRADE
OR
SNOW
LINE
EQUIPMENT LOCATED IN CONFINED
SPACES; ALL AIR FROM OUTDOORS.
(c)
CONFINED
SPACE
COMBUSTION
300mm (12 in.)
300mm (12 in.)
300mm (12 in.)
OUTDOORS
AIR DUCT
VENTILATION
Burn Hazard Do not touch vent. Doing so can result in
burns.
– 11 –
Exhaust Venting
This heater is designed to exhaust the products of combus­tion (flue gases) to the outdoors using a sealed piping sys­tem. Table 2 lists the allowable vent materials and sizing information. Figure 8 shows the general venting layout while Figures 9-12 show various end termination details and clearances. Connection of the venting piping to the blower is shown in Figure 14. Correct installation of the venting system is essential to the safe and efficient operation of this water heater. Vent piping must be installed in accordance with all applicable local and provincial or state codes. In the absence of such codes, all installation shall meet the requirements as stated in the lat­est edition of the "Natural Gas and Propane Installation
Codes" CAN/CSA-B149.1 (Canada) or "National Fuel Gas Code" ANSI Z223.1 (NFPA 54) (U.S.A.).
Important Notes and Warnings
This heater is certified to be installed using Schedule 40 PVC or CPVC plastic vent material. In Canada some jurisdictions require that this material be approved to ULC S636. ULC S636 mandates that components from different systems must not be mixed in the same vent runs. Check local codes to determine which materials are allowed in your area and only use approved materi­al. All venting material and components must be joined with the approved primer/cleaner and solvent cement.
Do not common vent this heater with any other appli­ance.
During operation the plastic piping will expand as it heats up and contract as it cools down. This is normal for this type of venting. Rigidly fastening the vent piping can cause undue stress that may result in the cracking or fracturing the vent piping material. A fracture of the venting pipe poses a serious safety hazard. To prevent stressing of the vent system, all hangers and supports must allow the vent piping freedom to move.
All power vented water heaters generate a certain amount of operational noise. In order to minimize noise transmission to the support structure, use isolation pads between the pipe hangers and the vent pipe.
Most power vent installations develop some condensa­tion in the vent piping. When using long runs of venting or when the venting passes through cold or unheated areas, considerable amounts of condensate from the flue gases can develop. Provision must be made for the condensate to drain freely from the system or to be col­lected in a condensate trap(s) that can be drained. Damage or fracture of the vent piping may occur if the condensate is allowed to collect and freeze. Pooling of condensate can restrict airflow and can cause nuisance failures of the system.
Be aware of any concealed wiring or piping inside the walls.
– 12 –
PREFERRED PRACTICE
150mm
(6 in.) min.
STREET ELBOW NORMAL ELBOW
BACK TO BACK ELBOWS
Figure 6 Correct Pipe Fittings
90° LONG SWEEP ELBOW
90° SHORT SWEEP ELBOW
VENT LENGTH LESS THAN OR
EQUAL TO 6.1 EQUIVALENT METRES
(20 FT.) USE PLASTIC SCREEN.
VENT LENGTH GREATER THAN 6.1 EQUIVALENT METRES (20 FT.) USE
STEEL MESH SCREEN.
Figure 7 Rodent Screens
Loading...
+ 26 hidden pages