John Wood RESIDENTIAL GAS WATER HEATERS Installation And Operating Manual

Installation and Operating Manual
RESIDENTIAL GAS WATER HEATERS
POWER DIRECT VENT GAS MODELS
WITH HOT SURFACE IGNITION
NOT FOR USE IN MANUFACTURED (MOBILE) HOMES
ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE CONTACT THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
1410 328126-000
AN ODOURANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE . . . . . . . . . . .3
GENERAL SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Qualifi ed Installer Or Service Agency . . . . . . . . . . . . 6
Preparing For The Installation. . . . . . . . . . . . . . . . . . 6
TYPICAL INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . .7
Get To Know Your Water Heater -
Gas Models (List Referencing Figures 1-5) . . . . . . . 7
Replacement Parts And Deliming Products . . . . . . . 8
Combo Heating Inlet And Outlet Side Taps . . . . . . . . 8
Water Piping - Mixing Valve Usage . . . . . . . . . . . . . . 9
Mixing Valves
Water Heater Operation . . . . . . . . . . . . . . . . . . . . . 10
Electrical Requirements & Wiring Diagram . . . . . . . .11
SAFETY LOCKOUTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
High Limit Controls (Energy Cut Off). . . . . . . . . . . . 12
Thermostat/Water Temperature Blower High Limit Switch
Blower Air Pressure SwitchEs. . . . . . . . . . . . . . . . . 12
LOCATING THE NEW WATER HEATER. . . . . . . . . . . . .13
Facts To Consider About The Location . . . . . . . . . . 13
Clearances To Combustibles Floors With Carpeting Clearances For Servicing
High Ambient Temperature Installations . . . . . . . . . 14
Important Notes and Warnings
Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 15
INSTALLING THE NEW WATER HEATER . . . . . . . . . . . 16
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Space Heating And Potable Water Systems . . . . . . 16
Combo Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
System Requirements Installation
Closed Water Systems . . . . . . . . . . . . . . . . . . . . . . 18
Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . 18
Temperature-Pressure Relief Valve. . . . . . . . . . . . . 19
T&P Valve Discharge Pipe Requirements: Temperature-Pressure Relief Valve And
Pipe Insulation
High Altitude Installation . . . . . . . . . . . . . . . . . . . . . 20
Gas Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Sediment Traps. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Filling The Water Heater . . . . . . . . . . . . . . . . . . . . . 22
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Termination Clearances (Sidewall) . . . . . . . . . . . . . 24
Side Wall Vent Terminal Installation Roof Vent Terminal Installation Concentric Vent Termination Kit Installation Multiple Concentric Vent Installations Vent Pipe Length Vent Pipe Termination Venting Terminations And Sizing Vent Screen Installation Vent Pipe Material Vent Pipe Installation Vent Pipe Runs Vent Terminal Installations
Blower Assembly Installation. . . . . . . . . . . . . . . . . . 30
Vent/Intake Pipe Connections To Blower/Air Duct Coupling Installations According To Vent Sizes
Sound Suppressor . . . . . . . . . . . . . . . . . . . . . . . . . 33
Side Wall Vent Installation Vertical Vent Installation
Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . 34
LIGHTING INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . . . .35
OPERATING THE TEMPERATURE
CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Gas Control Valve/Thermostat . . . . . . . . . . . . . . . . 37
FOR YOUR INFORMATION. . . . . . . . . . . . . . . . . . . . . . . 38
Start Up Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 38
Condensate Smoke/Odour Strange Sounds
Operational Conditions . . . . . . . . . . . . . . . . . . . . . . 38
Smelly Water
“Air” In Hot-Water Faucets . . . . . . . . . . . . . . . . . . . 38
PERIODIC MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . 39
General Upkeep . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Venting System Inspection . . . . . . . . . . . . . . . . . . . 39
Burner Operation And Inspection . . . . . . . . . . . . . . 39
Combustion Chamber And Burner Cleaning. . . . . . 40
Housekeeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Temperature-Pressure Relief Valve Test . . . . . . . . . 40
Draining And Flushing. . . . . . . . . . . . . . . . . . . . . . . 41
To Drain The Water Heater Storage Tank: To Flush The Water Heater Storage Tank:
Anode Rod Maintenance. . . . . . . . . . . . . . . . . . . . . 42
LEAKAGE CHECKPOINTS . . . . . . . . . . . . . . . . . . . . . . .43
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
REFERENCE PARTS LISTING . . . . . . . . . . . . . . . . . . . .44
TROUBLESHOOTING GUIDELINES. . . . . . . . . . . . . . . .46
Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Soft Lockout Hard Lockout
Resetting The Heater Control . . . . . . . . . . . . . . . . . 46
Ignition State And Timing . . . . . . . . . . . . . . . . . . . . 46
System Status And Error Codes . . . . . . . . . . . . . . . 47
Reading The LED Flash Sequence. . . . . . . . . . . . . 47
Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Other Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
2 www. johnwoodwaterheaters .com 328126-000
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very
important that the meaning of each safety message is understood by you and others who install, use or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
CAUTION
hazardous situation which, if not avoided, will result in death or injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.
This product is certifi ed to comply with a maximum weighted average of 0.25% lead content as required in some areas.
IMPORTANT DEFINITIONS
Quali ed Installer: A qualifi ed installer must have ability equivalent to a licensed tradesman in the fi elds of plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fi red water heaters. The qualifi ed installer must also be familiar with the design features and use of fl ammable vapor ignition resistant water heaters and have a thorough understanding of this Installation and Operating manual.
Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fi elds of plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fi red water heaters. The service agency must also have a thorough understanding of this Installation and Operating manual, and be able to perform repairs strictly in accordance with the service guidelines provided by the manufacturer.
Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances within the building.
328126-000 www. johnwoodwaterheaters .com 3
GENERAL SAFETY
4 www. johnwoodwaterheaters .com 328126-000
GENERAL SAFETY
WARNING
Breathing Hazard - Carbon Monoxide Gas
• Install vent system in accordance with codes.
• Do not operate water heater if flood damaged.
• For operation above 3,079 m (10,100’), a high altitude orifice must be installed.
• Do not operate if soot buildup is present.
• Do not obstruct water heater air intake with insulating jacket.
• Do not obstruct blower air intake.
• Do not place chemical vapour emitting products near water heater.
• Gas and carbon monoxide detectors are available.
• No vent damper installation is compatible with this power vented water heater.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
DANGER
FLAMMBLE
Vapours from flammable liquids may explode and catch fire causing death or severe burns.
Do not use or store flammable products such as gasoline, solvents or adhe­sives in the same room or area near the water heater.
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. out of children's reach.
Installation: Do not install the water heater where flammable products will be stored or used.
Flammable Vapours
Water heater has a main burner and hot surface igniter. The hot surface igniter:
1. can be triggered at any time and
2. the hot surface will ignite flammable vapours.
Vapours:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the floor and
4. can be carried from other rooms to the electrodes by air currents.
328126-000 www. johnwoodwaterheaters .com 5
INTRODUCTION
Thank You for purchasing this water heater. Properly
installed and maintained, it should give you years of trouble free service.
Abbreviations found in this Installation and Operating manual:
CSA - Canadian Standards Association
ANSI - American National Standards Institute
ASME - American Society of Mechanical Engineers
This gas-fi red water heater is design certifi ed by CSA International, under Water Heater Standard ANSI Z21.10.1 • CSA 4.1 or ANSI Z21.10.3 • CSA 4.3 (current edition), as applicable.
QUALIFIED INSTALLER OR SERVICE AGENCY
Installation and service of this water heater requires ability equivalent to that of a Qualifi ed Agency (as defi ned by ANSI below) in the fi eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service.
ANSI Z223.1 2006 Sec. 3.3.83: “Qualifi ed Agency” - “Any individual, fi rm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required and that has complied with all the requirements of the authority having jurisdiction.”
If you are not qualifi ed (as defi ned by ANSI above) and licensed or certified as required by authority having jurisdiction to perform a given task, do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.
The installation must conform with these instructions and local code authority having jurisdiction. In absence of local codes, installation must comply with current editions of the “Natural Gas and Propane
Installation Code” B149.1 and “Canadian Electrical Code (CAN/CSA C22.1), Part I” . All documents are
available from:
Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, Canada L4W 5N6
2. The water heater, when installed, must be electrically grounded in accordance with the local codes or in the absence of local codes: current edition of the
“Canadian Electrical Code (CAN/CSA C22.1), Part I” .
3. If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate.
4. Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and res (see Figure 12). Examine the location to ensure the water heater complies with the “Locating The New Water Heater” section in this manual.
5. For installation in areas subject to earthquakes, this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. Contact local utilities for code requirements in your area.
PREPARING FOR THE INSTALLATION
1. Read the “General Safety” section of this manual rst and then entire manual carefully. If you don’t follow safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. This manual contains instructions for installation, operation, and maintenance of the gas-fi red water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and instructions are essential to proper operation of the water heater and your safety. Since we cannot put everything on the fi rst few pages, READ ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER.
6 www. johnwoodwaterheaters .com 328126-000
GET TO KNOW YOUR WATER HEATER - GAS MODELS (LIST REFERENCING FIGURES 1-5)
1 Termination Elbow with Rodent
Screen 2 *Vent Pipe 3 *Vent Pipe Elbow (long radius) 4 Sound Suppressor (Tee fi tting) 5 *Union (Di-electric water
connection) 6 Cold-Water Inlet Nipple/Diptube 7 **Combo Heating System Supply
Outlet (Optional) 8 T&P Valve 9 * Discharge Pipe 10 **Combo Heating System Return
Inlet (Optional) 11 Gas Control Valve/Thermostat
(Honeywell) 12 Gas Valve Electronic Control
Module And Cover (Honeywell) 13 Drain Valve 14 Outer Gas Door 15 Manifold Door Assembly (behind
outer door) (see Figure 3 &
Figure 4) 16 *Metal Drain Pan 17 *Floor Drain
1
2
TYPICAL INSTALLATION
18 Flexible Manifold Tube (see
Figure 3 & Figure 4) 19 ***Control Harness 20 *Sediment Trap 21 *Ground Joint Union (gas
connection) 22 *Main Manual Gas Shut-off Valve 23 *Gas Supply* 24 Anode (under cap) 25 Baffl e Assembly 26 Hot-Water Outlet Nipple/Anode 27 *Inlet Water Shut-off Valve 28 ****Rubber Coupling (see Figure 5) 29 Gear Clamp (see Figure 5) 30 ***Blower with Power Cord (see
Figure 5) 31 Air Duct Adapter 32 Air Inlet Snorkel 33 Air Duct 34 *Thermal Expansion Tank (see
“Closed Water Systems” and
“Thermal Expansion” sections) 35 Flame Sensor Rod (see Figure 3 &
Figure 4) 36 Sheet Metal Burner (see Figure 3 &
3
Figure 4)
37 Gas Orifi ce (see Figure 3 &
Figure 4)
38 Gas Manifold (see Figure 3 &
Figure 4)
39 Hot-Surface Igniter (see Figure 3 &
Figure 4) Manifold Door Gasket (see Figure 3
40
& Figure 4)
41 Manifold Door (see Figure 3 &
Figure 4)
42 Two Piece Grommet With Clip (see
Figure 3 & Figure 4) 43 Viewport (see Figure 3 & Figure 4) 44 Air Tubing (Intake) (see Figure 5) 45 Blower High Limit Switch (see
Figure 5) 46 Intake Air Pressure Switch (NC)
(inside box) (see Figure 5) 47 Capacitor (see Figure 5) 48 Air Tubing (Exhaust) (see Figure 5) 49 Exhaust Air Pressure Switch (NO)
(inside box) (see Figure 5) *, **, ***, **** see notes on following
page
1
5
26
25 24
23
22
21
4
2
5
AIR INLET
27
PIPING
6 7
34
EXHAUST OUTLET
PIPING
28
29
30
5
8
9
33
31
6
10
32
11 12
13
20
19
Front View
Figure 1 Figure 2
328126-000 www. johnwoodwaterheaters .com 7
14 15
16
1718
Rear View
Natural gas and Propane main burner with igniter assembly for 40k and 45k Btu/hr models
18
36
35
Vacuum relief valve install per local codes (not supplied with heater).
37
43
Figure 3
Natural gas and Propane (LP) main burner with igniter assembly for 58k, 62k, 72k and 76k Btu/hr models
Flare Nut ††
36 35
39
42
40
41
37
38
38
Figure 6
Notes:
* Items not supplied with the water heater. ** The side recirculation loop connections may not be
used as the primary water inlet and outlet connections. See “Combo Heating Inlet And Outlet Side Taps”
below. *** Caution harness has 120 VAC In operation. **** See “Vent Pipe Installation” for more information.
REPLACEMENT PARTS AND DELIMING PRODUCTS
Replacement parts and recommended delimer may be ordered through authorized servicers or distributors. When ordering parts, provide complete model and serial numbers (see rating plate), quantity and name of part desired. Standard hardware items may be purchased locally.
COMBO HEATING INLET AND OUTLET SIDE TAPS
Models equipped with Combo Heating capabilities have the two side plumbing taps plugged (item 7 and item 10 in Figure 1 and see also Figure 7 & Figure 8). If the heater is to be installed in a Combo Heating application, these plugs must be removed.
43
Shown with Junction Box Cover removed for clarity.
29
30
49
48 47
42
Figure 4
Figure 5
39
40
41
28
44
45
46
8 www. johnwoodwaterheaters .com 328126-000
WATER PIPING - MIXING VALVE USAGE Mixing Valves
Water temperature over
DANGER
125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the disabled and are at highest risk of scald injury.
This appliance has been design certifi ed as complying with CSA Standard for water heaters and are considered suitable for combination Water (Potable) Heating and Space Heating but not space heating only applications.
The water supply pressure should not exceed 80 psi. If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.
Feel water before bathing or showering.
HOT
HOT
Temperature limiting devices such as mixing must be installed when required by
BURN
codes and to ensure safe temperatures at fixtures.
Water heated to a temperature which satisfi es space heating, clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot-water uses can cause a temperature increase of the hot water by 11C° (20F°) higher than the heater’s temperature settings.
TEMPERED POTABLE WATER
MIXING
VALV E
TEMPERATURE­PRESSURE RELIEF VALVE
DISCHARGE PIPE (DO NOT CAP OR PLUG)
* NOTE: THE
T&P VALVE
DISCHARGE
PIPE MUST
BE PIPED
DIRECTLY TO
THE DRAIN
OR EXTERNAL
TO THE
BUILDING
SUGGESTED PIPING ARRANGEMENT
FOR TOP CONNECTIONS
SHUT-OFF
VALV E
COLD-WATER
INLET
CERTAIN MODELS
ARE EQUIPPED WITH
SIDE PLUMBING
CONNECTIONS FOR
SPACE HEATING.
THE HOT AND COLD FITTING
ASSEMBLIES (PART
#9001262005) CAN
BE ORDERED
THROUGH THE
MANUFACTURER
METAL DRAIN
PAN 45mm (1.75”)
MAX. DEPTH. AT
LEAST 50mm (2”)
GREATER THAN THE
DIAMETER OF THE
WATER HEATER.
TEMPERED
POTABLE WATER
NON-TEMPERED
WATER SUPPLY
SUGGESTED PIPING ARRANGEMENT FOR
TOP CONNECTIONS
TEMPERATURE­PRESSURE RELIEF VALVE
DISCHARGE PIPE (DO NOT CAP OR PLUG)
* NOTE: THE
T&P VALVE
DISCHARGE PIPE
MUST BE PIPED
DIRECTLY TO
THE DRAIN OR
EXTERNAL TO
THE BUILDING
DRAIN VALV E
SHUT-OFF
VALV E
COLD-WATER
INLET
NON-TEMPERED
WATER RETURN
MIXING VALVE
METAL DRAIN
PAN 45mm
(1.75”) MAX.
DEPTH. AT
LEAST 50mm
(2”) GREATER
THAN THE
DIAMETER OF
THE WATER
HEATER.
305mm (12”) MAX. AIR GAP*
Figure 8
DRAIN VALV E
Figure 7
328126-000 www. johnwoodwaterheaters .com 9
305mm (12”) MAX. AIR GAP*
Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infi rm and the physically/mentally disabled. Table 1 (published by U.S. Government Memorandum,
1978) shows the approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fi ts into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken.
Water
Temperature
°C (°F)
Time for 1st
Degree Burns
(Less Severe Burns)
44 (110) (normal shower temp.) 47 (116) (pain threshold) 47 (116) 35 minutes 45 minutes 50 (122) 1 minute 5 minutes 55 (131) 5 seconds 25 seconds 60 (140) 2 seconds 5 seconds 65 (149) 1 second 2 seconds 68 (154) instantaneous 1 seconds
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)
Time for Permanent
Burns 2nd & 3rd
Degree (Most
Severe Burns)
Table 1
In addition to using lowest possible temperature setting that satisfi es demand of application, a mixing valve should be installed at water heater (see Figure 7 & Figure 8) or at hot-water taps to further reduce system water temperature. Mixing valves are available at plumbing supply stores. Consult a Qualifi ed Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “Operating The Temperature Control System” section in this manual.
WATER HEATER OPERATION
Figure 9 shows the water heater’s sequence of operation when a call for heat is initiated. The ignition control module will attempt to light the burner three times. If the ignition control does not detect ignition it will enter lockout mode and fl ash the corresponding error code.
HEATER
THERMOSTAT
CALLS FOR
HEAT
HEATER CONTROL
CHECKS TO ENSURE
BLOWER EXHAUST
PRESSURE SWITCH IS
OPEN
BLOWER IS
ENERGIZED
CONTROL CHECKS
TO ENSURE: EXHAUST PRESSURE SWITCH CLOSES AND
INTAKE PRESSURE
SWITCH REMAINS
CLOSED INDICATING
BLOWER IS
OPERATING AND
THERE ARE NO
BLOCKAGES (INTAKE
OR EXHAUST)
TEMPERATURE
SWITCH REMAINS
CLOSED INDICATING
VENT TEMPARATURE IS
NOT ABOVE THE
ALLOWEBLE LIMIT
IGNITER IS ENERGIZED
AND GAS VALVE IS
OPENED
BURNER COMES ON
AND THE FLAME IS
SENSED BY CONTROL
BURNER CONTINUES
TILL THE WATER IN THE
TANK REACHES THER-
MOSTAT SETTING
GAS VALVE IS CLOSED
AND BURNER SHUTS
OFF
BLOWER CONTINUES
FOR A POST PURGE
TIME
HEATER
REMAINS ON
STANDBY UNTIL
NEXT CALL FOR
HEAT
10 www. johnwoodwaterheaters .com 328126-000
Figure 9
ELECTRICAL REQUIREMENTS & WIRING DIAGRAM
WARNING
Electric Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
Before plugging in the water heater, always make sure:
The voltage and frequency correspond to that
specifi ed on the water heater wiring diagram.
The electrical outlet has the proper overload fuse or
breaker protection.
1. The unit must be connected to a dedicated power supply.
2. The unit must be connected to a 120VAC power supply.
3. The water heater must be properly grounded.
4. This water heater is a polarity sensitive appliance and will not operate if the power supply polarity is reversed.
Note: Always reference the wiring diagram for the correct electrical connections.
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING. POWER VENT WIRING SCHEMATIC.
NOTE: REFER TO THE “INSTALLATION CHECKLIST” BEFORE OPERATING THIS HEATER.
N
1
L1
1
EARTH GND
CAPACITOR
3
6
BLOWER
2
5
P1
4
1
4
3
P2
2
1
2
4
P3
1
3
3
FLAME SENSOR
6
5
HOT SURFACE IGNITER
4
PRESSURE SWITCH (CLOSED)
PRESSURE SWITCH (OPEN)
2
PRESSURE SWITCH (CLOSED)
4
HIGH LIMIT SWITCH (CLOSED)
4
After making all electrical connections, completely fi ll the tank with water and check all connections for leaks. Open the nearest hot-water faucet and let it run for 3 minutes to purge the water lines of air and sediment and to ensure complete fi lling of the tank. The electrical power may then be turned on. Verify proper operation after servicing. See also “Installation Checklist”.
IF WIRING HAS TO BE REPLACED IN THE FIELD, USE ONLY TYPE TEW 105°C WIRE.
3
1
4
2
1
2
3
4
1
4
2
5
3
6
YELLOW
YELLOW
WHITE
WHITE
WHITE
BLUE
BLUE
BLACK
GREEN
IGNITER - FLAME ROD ASSEMBLY
P4
ELECTRICAL RATING 120V, 5A, 60 HZ.
PRESSURE
SWITCH
YELLOW
BLUE
JP 1
1
2
2
3
3
4
4
5
5
6
6
(NO)
BLACK SMOOTH - LINE
BLACK RIBBED - NEUTRAL
BLACK MIDDLE - GND
Circled numbers indicate sequence of operation.
Figure 11
PRESSURE
SWITCH
(NC)
CAPACITOR
BLACK
BLACK
BLACK
WHITE
GREEN
120Vac/60Hz Wall Plug
HIGH LIMIT
BLOWER
SWITCH
HONEYWELL GAS VALVE
Figure 10
328126-000 www. johnwoodwaterheaters .com 11
JUNCTION BOX
SAFETY LOCKOUTS
This water heater has several lockout features designed to prevent the heater from operating in unsafe conditions.
HIGH LIMIT CONTROLS (ENERGY CUT OFF) Thermostat/Water Temperature
This feature is a part of the gas control valve/thermostat (see Figure 1, item 10) and limits the maximum water temperature. In the event of the water overheating, this safety feature shuts off the fuel supply to the burner.
Blower High Limit Switch
This device is located on the blower (see Figure 5, item
45) and limits the maximum temperature of the blower. If the blower temperature rises above the temperature setting, the switch opens causing the heater to shut down. The switch will auto reset once the temperature drops suffi ciently.
BLOWER AIR PRESSURE SWITCHES
The blower/heater is equiped with two air pressure switches located in the junction box (see Figure 5, item 46 and item 49). These devices are connected in series and monitor the air pressure produced by the blower. In the event that the exhaust venting becomes blocked or suffi ciently restricted, the normally open (NO) air pressure switch will shut down the heater. In the event that the intake pipe becomes suffi ciently blocked or restricted, the normally closed (NC) air pressure switch will shut down the heater.
12 www. johnwoodwaterheaters .com 328126-000
LOCATING THE NEW WATER HEATER
FACTS TO CONSIDER ABOUT THE LOCATION
Carefully choose an indoor location for the new water heater because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. This water heater is not for use in manufactured (mobile) homes or outdoor installation. Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed:
1. Select a location indoors as close as practical to the vent termination or location to which the water heater vent piping is going to be connected, and as centralized with the water piping system as possible.
2. Selected location must provide adequate clearances for servicing and proper operation of the water heater.
3. Avoid locations that could cause the water heater to freeze from outside air.
4. Selected location must provide access to a properly grounded electrical branch circuit. A dedicated circuit is preferred. Do not use a GFI outlet.
5. Avoid locations that expose the water heater to direct sunlight.
6. Keep combustibles such as boxes, magazines, clothes, etc., away from the water heater area.
Important: Do not use an extension cord to connect the water heater to an electrical outlet.
CAUTION
Sensors mounted in the metal drain pan that trigger an
alarm or turn off the incoming water to the water heater when leakage is detected.
Sensors mounted in the metal drain pan that turn off
the water supply to the entire building when water is detected in the metal drain pan.
Water supply shut-off devices that activate based on
the water pressure differential between the cold-water and hot-water pipes connected to the water heater.
Devices that will turn off the gas supply to a gas water
heater while at the same time shutting off its water supply.
WARNING
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapours
and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater control to excessive gas
pressure.
Use only gas shown on rating plate.
Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended
period of non-use.
Read instruction manual before
installing, using or servicing
water heater.
Property Damage Hazard
All water heaters eventually leak.
Do not install without adequate drainage.
Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the fl ow of water will not cause damage to the structure. For this reason it is not advisable to install the water heater in an attic or upper fl oor. In all cases, a metal drain pan should be installed under the water heater. Metal drain pans are available at your local hardware store. Such a metal drain pan must have a clearance of at least 25mm (1”) greater than any point on the water heater’s outer jacket and must be piped to an adequate drain. The pan must have a maximum depth of 45mm (1.75”). Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a metal drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped metal drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
WARNING
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Storage or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or death.
Flammable Vapors
WARNING
Fire Hazard
For continued protection against risk of fire:
Do not install water heater on
carpeted floor.
Do not operate water heater if
flood damaged.
328126-000 www. johnwoodwaterheaters .com 13
Clearances To Combustibles
Minimum clearances between water heater and combustibles are 0mm (0”) at the sides and rear, 140mm (5.5”) from the front and 305mm (12”) from top (standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater (see Figure 12).
Floors With Carpeting
This water heater must not be installed directly on carpeting. Carpeting must be protected by a metal or wood panel beneath the appliance extending beyond the full width and depth of the appliance by at least 76mm (3”) in every direction, or if the appliance is installed in an alcove or closet, the entire fl oor must be covered by the panel. Failure to heed this warning may result in a fi re hazard.
Clearances For Servicing
When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.
Servicing this appliance, such as changing the anodes, etc. requires clearances for accesability and replacement of parts. The anode could be as long as 0.89m (35”).
Refer to the current edition of the “Natural Gas and Propane Installation Code” B149.1 for detailed requirements.
HIGH AMBIENT TEMPERATURE INSTALLATIONS
As the room temperature rises, the water heater venting is exposed to high temperatures from the inside and the outside. In these situations, attention to the choice of venting material is necessary. Establishing the ambient temperatures where the heater and the venting are installed is very important. Areas that can experience high ambient environments include closets, alcoves, areas under staircases, attics (especially in metal roofed buildings), areas with restricted air movement, rooms with large solar gains, metal sheds, industrial or commercial enterprises and venting systems exposed to direct sunlight. Water heater installations in ambient conditions hotter than 43°C (110°F) require the installation of a high ambient limit switch (kit number 9009024015) and use of CPVC or polypropylene venting material. Failure to install
the proper vent material will result in a non-compliant installation and can result in deformation/breakage of the pipe.
WARNING
Breathing Hazard - Carbon Monoxide Gas
• Flue gases may escape if vent pipe is deformed, broken, or not properly connected.
0mm
(0”) MIN.
TOP VIEW
OF CLOSET
WITHOUT DOOR
0mm
(0”) MIN.
(5.5”) MIN.
140mm
TOP VIEW OF
CLOSET WITH
Figure 12
WARNING
Breathing Hazard - Carbon Monoxide Gas
• Install water heater in accordance with the instruction manual and B149.1.
• To avoid injury, combustion and ventilation air must be taken from outdoors.
• Do not place chemical vapour emitting products near water heater.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
14 www. johnwoodwaterheaters .com 328126-000
DOOR
0mm (0”) MIN.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
Important Notes and Warnings
This heater is certifi ed to be installed using Schedule 40
PVC or CPVC or polypropylene plastic vent material. All jurisdictions in Canada require that the material used to exhaust combustion products is approved to ULC S636. Only use approved material. All venting material and components must be joined with the approved primer/ cleaner and solvent cement.
Do not common vent this heater with any other
appliance.
During operation the plastic piping will expand as it
heats up and contract as it cools down. This is normal for this type of venting. Rigidly fastening the vent piping can cause undue stress that may result in the cracking or fracturing the vent piping material. A fracture of the venting pipe may pose a serious safety hazard. To prevent stressing of the vent system, all hangers and supports must allow the vent piping freedom to move.
Use long sweep elbows wherever possible. Closely
coupled elbows and short radius elbows can reduce the venting capacity.
All power vented water heaters generate a certain
amount of operational noise. In order to minimize noise transmission to the support structure, it is recommended to use isolation pads between the pipe hangers and the vent pipe.
Most power vent installations develop some
condensation in the vent piping. When using long runs of venting or when the venting passes through cold or unheated areas, considerable amounts of condensate from the fl ue gases can develop. Provision must be made for the condensate to drain freely from the system or to be collected in a condensate trap(s) that can be drained. Damage or fracture of the vent piping may occur if the condensate is allowed to collect and freeze. Pooling of condensate can restrict airfl ow and can cause nuisance failures of the system.
AIR REQUIREMENTS
For safe operation an adequate supply of fresh, uncontaminated air for combustion, dilution and ventilation must be provided. Note: Contaminated or dusty air may cause build-up on the blower wheel resulting in nuisance shut downs.
328126-000 www. johnwoodwaterheaters .com 15
INSTALLING THE NEW WATER HEATER
WATER PIPING
Water temperature over
DANGER
HOT
HOT
BURN
The water supply pressure should not exceed 80 psi. If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.
HOT WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, cleaning and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infi rm, or physically/ mentally handicapped. If anyone using hot water fi ts into one of these groups you must take special precautions. The National Plumbing Code requires certain fi xtures to not exceed 49°C (120°F). In addition to using lowest possible temperature setting that satisfi es your hot water needs, a means such as a mixing valve, should be used at hot-water taps used by these people or at the water heater (see Figure 7 & Figure 8). Valves for reducing point of use temperature by mixing cold and hot water are also available.
SPACE HEATING AND POTABLE WATER SYSTEMS
This appliance has been design certifi ed as complying with CSA Standard for water heaters and is suitable for combination water (potable) heating and space heating but not space heating only applications.
125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the disabled and are at highest risk of scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing must be installed when required by codes and to ensure safe temperatures at fixtures.
WARNING
Toxic Chemical Hazard
Do not connect to non-potable water system.
Consult a Qualifi ed Installer or Service Agency. Follow manufacturer’s instructions for installation of valves. Before changing the factory setting on thermostat, read “Operating The Temperature Control System” section in this manual.
This water heater should not be connected to any
heating systems or components previously used with a non-potable water heating appliance.
All piping components connected to this unit for space
heating applications should be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment
shall not be introduced into the potable water used for space heating.
When the system requires water for space heating at
temperatures higher than required for domestic water purposes, a mixing valve must be installed. Please refer to Figure 7 & Figure 8 for suggested piping arrangement.
Note: Water piping and vent piping occupy the space above the water heater. Plan the water piping to ensure it does not cause interference with the vent piping (see “Planning the Vent System”). If this water heater is to be used to supply both space heating and potable water, the instructions listed below must be followed:
Be sure to follow the manual(s) shipped with the air
handler or other type heating system.
This water heater is not to be used as a replacement
for an existing boiler installation.
Do not use with piping that has been treated with
chromates, boiler seal or other chemicals and do not add any chemicals to the water heater piping.
If the space heating system requires water temperatures
in excess of 49°C (120°F), steps must be taken to limit temperatures at fi xtures in the potable hot-water supply for safety and regulatory requirements.
Pumps, valves, piping and fi ttings must be compatible
with potable water.
A properly installed fl ow control valve is required to
prevent thermosiphoning. Thermosiphoning is the result of a continuous fl ow of water through the air handler circuit during the off cycle. Weeping (blow off) of the temperature-pressure relief valve (T&P) or higher than normal water temperatures are the fi rst signs of thermosiphoning.
The hot-water line from the water heater should be
vertical past any mixing valve or supply line to the heating system to remove air bubbles from the system.
Do not connect the water heater to any system or
components previously used with non-potable water heating appliances when used to supply potable water.
16 www. johnwoodwaterheaters .com 328126-000
COMBO HEATING
This section serves as a guide for the installation and use of “Combo” heating systems utilizing a domestic water heater that has been specifi cally approved for such use. It is written for those knowledgeable in the required trades and professionals involved in the design and installation of Combo Heating Systems. It is the responsibility of the installer/designer to follow all applicable codes to ensure the effectiveness and safety of the installation.
System Requirements
The following requirements must be met for the installation of Combo Heating Systems:
1. All components used for the distribution of water in the heating loop must be suitable for potable water. These include all piping, fi ttings, solder and fl uxes, pumps for circulation of water, valves, etc.
2. The water heater must not be connected to a hydronic heating system that has been used previously.
3. No boiler treatment chemicals of any kind shall be introduced into the system.
4. The Combo System components must be selected and sized to meet and maintain the total calculated demands for both domestic service hot water and space heating requirement. The sizing and installation must be performed in accordance with good engineering practice such as “ASHRAE
Handbooks”, HRAI’s Unifi ed Combo Guidelines, “Hydronics Institute Manuals”, ANSI Z223.1, CSA F280, National/Provincial Building Codes, ANSI
and/or codes having jurisdiction.
5. The air handler (fan coil) and/or the circulating pump in a baseboard hydronic loop will require a dedicated 120V circuit. This must be provided and identifi ed for this purpose.
6. All piping between the water heater and the air handler or hydronic baseboard loop must be adequately insulated to reduce heat loss.
7. If the local jurisdiction requires a back-fl ow preventer in the cold water line, an expansion tank of adequate size must be installed.
8. “Combo” Heating Systems require higher water temperatures than other applications. When the system is used to supply water for Combo Heating applications, a means, such as mixing valve, must be installed to temper the water in order to reduce scald hazard potential (see Figure 13 & Figure 14).
Installation
The heating mode may be one of the following options: A. A fan coil/air handler (Figure 13). B. A hydronic baseboard (fi nned tube) loop/In fl oor heating
(Figure 14). The following is a list of requirements for the installation of option A or B.
1. Install shut-off valves and unions so that the water
heater can be isolated from the heating module should servicing of the water heater become necessary.
2. Install a drain valve at the lowest point of the heating loop so that water can be drained from the heating module without affecting the water heater.
3. If the air handler does not have a venting means at the highest point of the piping arrangement, install an air bleed at the highest point of the plumbing arrangement.
HOT WATER
TO HOUSE
FIXTURE
MIXING
VALV E
HOT
OUTLET
EXPANSION TANK (OPTIONAL)
C
M
H
WATER
HEATER
COLD SUPPLY
code requirements
CHECK VALVE (IF USED REQUIRES EXPANSION TANK)
CHECK
COLD INLET
AIR
HANDLER
VALV E
FLOW CONTROL
HOSE BIB
(OPTIONAL)
SUPPLY
(see also
Massachusetts
on pg 8)
EXTERNAL CIRCULATOR
RETURN
DRAIN/ PURGE VALV E
INTERNAL
CIRCULATOR
Figure 13
HOT WATER
TO HOUSE
FIXTURE
MIXING
VALV E
HOT
OUTLET
EXPANSION TANK (OPTIONAL)
C
M
H
WATER
HEATER
COLD SUPPLY
code requirements
CHECK VALVE (IF USED REQUIRES EXPANSION TANK)
CHECK
COLD INLET
VALV E
FLOW CONTROL
HOSE BIB
(OPTIONAL)
SUPPLY
(see also
Massachusetts
on pg 8)
EXTERNAL CIRCULATOR
RETURN
HYDRONIC
BASEBOARDS
(SERIES
CONNECTED
SHOWN)
Figure 14
328126-000 www. johnwoodwaterheaters .com 17
Loading...
+ 38 hidden pages