ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS
PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE
PRINTED 0609 316312-000
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
1
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and
others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important
that the meaning of each safety message is understood by you and others who install, use or service this water heater.
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and
how to avoid the risk of injury.
IMPORTANT DEFINITIONS
• Qualied Installer: A qualied installer must have ability equivalent to a licensed tradesman in the elds of plumbing,
air supply, venting and gas supply, including a thorough understanding of the requirements of the Natural Gas and
Propane Installation Code as it relates to the installation of gas red water heaters. The qualied installer must also
be familiar with the design features of water heaters, and have a thorough understanding of this instruction manual.
• Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the elds of plumbing,
air supply, venting and gas supply, including a thorough understanding of the requirements of the Natural Gas and
Propane Installation Code as it relates to the installation of gas red water heaters. The service agency must also
have a thorough understanding of this instruction manual, and be able to perform repairs strictly in accordance with
the service guidelines provided by the manufacturer.
• Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of
gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also
offer service and inspection of appliances within the building.
2
GENERAL SAFETY
3
GENERAL SAFETY
4
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE............................2
GENERAL SAFETY..................................................................3
TABLE OF CONTENTS ............................................................5
Thank You for purchasing this water heater. Properly installed and
maintained, it should give you years of trouble free service.
Abbreviations Found In This Instruction Manual:
• CSA - Canadian Standards Association
• ANSI - American National Standards Institute
• NFPA - National Fire Protection Association
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturer’s Association
• UL - Underwriters Laboratories Inc.
This gas-red water heater is design certied by Underwriters
Laboratories Inc. under American National Standard/CSA
Standard for Gas Water Heaters ANSI Z21.10.3 • CSA 4.3 (current
edition).
PREPARING FOR THE INSTALLATION
1. Read the “General Safety” section, page 3 and 4 of this manual
rst and then the entire manual carefully. If you don’t follow the
safety rules, the water heater will not operate properly. It could
cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY
DAMAGE.
This manual contains instructions for the installation, operation,
and maintenance of the gas-red water heater. It also contains
warnings throughout the manual that you must read and be
aware of. All warnings and all instructions are essential to the
proper operation of the water heater and your safety. Since we
cannot put everything on the rst few pages, READ THE ENTIRE
MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE
THE WATER HEATER.
2. The installation must conform with these instructions and the
local code authority having jurisdiction. In the absence of local
codes, installations shall comply with the Natural Gas and Propane
Installation Code CAN/CSA B149.1 and the Canadian Electrical
Code CAN/CSA C22.1. These publications are available from the
Canadian Standards Association, 5060 Spectrum Way, Suite 100,
Mississauga, Ontario, Canada L4W 5N6.
3. The water heater when installed must be grounded in accordance
with the local codes, or in the absence of local codes: the Canadian
Electrical Code (C22.1).
4. If after reading this manual you have any questions or do not
understand any portion of the instructions, call the local gas utility
or the manufacturer whose name appears on the rating plate.
5. Carefully plan the place where you are going to put the water
heater. Correct combustion, vent action, and vent pipe installation
are very important in preventing death from possible carbon
monoxide poisoning and res, see Figures 1 and 2.
Examine the location to ensure the water heater complies with
the “Facts to Consider About Location” section in this manual.
5
GET TO KNOW YOUR WATER HEATER - GAS MODELS
A Control Assembly
B Blocked Inlet Switch
C Blocked Outlet Switch
D Fan Prover Switch
E Blower Assembly
F Burner Assembly
G Flame Sensor
H Hot Surface Igniter
I Junction Box
J Gas Valve Assembly
K Display Board
L Top Plastic Enclosure
M Display Enclosure
** N Exhaust Elbow Assembly
** O Condensate Tubing
P Off/On Switch
Q Display Label
R Hot Water Outlet
*S Electrical Outlet (120VAC)
T Gas Supply
U Main Manual Gas Shutoff Valve
V Union
W Inlet Water Shutoff Valve
X Cold Water Inlet
REPLACEMENT PARTS AND DELIMING PRODUCTS
Replacement parts and recommended delimer may be ordered through
authorized servicers or distributors. When ordering parts, provide complete
model and serial numbers (see rating plate), quantity and name of part
desired. Standard hardware items may be purchased locally.
Y Inlet Dip Tube
Z T/P Relief Valve
AA Rating Plate
BB Labels
CC Drain Valve
** DD Vent Terminal
EE Metal Drain Pan
FF Anode
GG Insulation
HH Upper Temperature Probe
II Access Door
VACUUM RELIEF
VALVE
*INSTALL PER
LOCAL CODES
ACCESS PANEL
Caution:
This access panel covers
a 2” NPT plug that was required
during the manufacturing of this
water heater. This 2” NPT ange is
not a cleanout tting, removing the
2” NPT plug and using this tting as a
cleanout could void your warranty.
* CAUTION HARNESS HAS 120 VAC. IN OPERATION.
** See “Planning the Vent System,” “Installation of Vent System” and “Condensate” for more information.
FIGURE 1.
6
INSTALLATION CONSIDERATIONS
ROUGH IN DIMENSIONS
FIGURE 1A.
Rough-In-Dimensions
ModelUnitsABCDEF
Inches 68.5049.2522.0015.753.008.00
100
Top/Side Inlet and Outlet: 3/4” NPT
Gas Inlet: 1/2” NPT
Capacity, Gas and Electrical Characteristics
Model
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa)
Minimum Supply Pressure for Natural Gas: 3.50” (.87kPa)
Minimum Supply Pressure for Propane Gas: 8.00” (1.99kPa)
Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
Recovery Capacities - U.S. Gallons/Hr. and Liters/Hr. at Temperature Rise Indicated
* The side recirculation loop connections may not be used as the primary water inlet and outlet connections. For your convenience, plugs are installed
in these ttings at the factory. Remove these plugs if needed for your specic installation. Otherwise (as with all connections) check for leaks while
lling the tank with water and after completing the installation.
FIGURE 2.
This appliance has been design certified as complying with
American National Standard/CSA Standard for water heaters and
is considered suitable for:
Water (Potable) Heating and Space Heating: All models are
considered suitable for water (potable) heating and space heating.
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated
to a temperature which will satisfy space heating, clothes
washing, dish washing, and other sanitizing needs can scald
and permanently injure you upon contact. Some people are more
likely to be permanently injured by hot water than others. These
include the elderly, children, and the physically or developmentally
disabled. If anyone using hot water from this heater fits into one
of these groups or if there is a local code or state law requiring
a certain temperature water at the hot water tap, then you must
take special precautions. In addition to using the lowest possible
temperature setting that satisfies your hot water needs, a means
such as a Mixing Valve should be used at the hot water taps
used by these people or at the water heater, see Figure 2. Mixing
valves are available at plumbing supply or hardware stores.
Consult a Qualified Installer or Service Agency. Follow mixing
valve manufacturer’s instructions for installation of the valves.
Before changing the factory setting on the thermostat, read the
“Temperature Regulation” section in this manual.
8
FACTS TO CONSIDER ABOUT THE LOCATION
Carefully choose an indoor location for the new water heater, because
the placement is a very important consideration for the safety of the
occupants in the building and for the most economical use of the
appliance. This water heater is not for use in manufactured
(mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater in
a new location, the following critical points must be observed:
1. Select a location indoors as close as practical to the vent terminal or
location to which the water heater vent piping is going to be connected,
and as centralized with the water piping system as possible.
2. Selected location must provide adequate clearances for servicing
and proper operation of the water heater.
Installation of the water heater must be accomplished in such a manner
that if the tank or any connections should leak, the ow will not cause
damage to the structure. For this reason, it is not advisable to install
the water heater in an attic or upper oor. When such locations cannot
be avoided, a suitable drain pan should be installed under the water
heater. Drain pans are available at your local hardware store. Such
a metal drain pan must have a clearance of at least 1.0” (2.5cm)
greater than any point on the water heater’s outer jacket and must
be piped to an adequate drain. The pan must not restrict combustion
air ow. For example, if a circular pan is used, it must be a minimum
of 27” (69cm) in diameter. See Figure 1.
Water heater life depends upon water quality, water pressure and
the environment in which the water heater is installed. Water heaters
are sometimes installed in locations where leakage may result in
property damage, even with the use of a metal drain pan piped to a
drain. However, unanticipated damage can be reduced or prevented
by a leak detector or water shut-off device used in conjunction with
a piped drain pan. These devices are available from some plumbing
supply wholesalers and retailers, and detect and react to leakage
in various ways:
• Sensors mounted in the metal drain pan that trigger an alarm or turn off
the incoming water to the water heater when leakage is detected.
• Sensors mounted in the metal drain pan that turn off the water supply
to the entire building when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water
pressure differential between the cold water and hot water pipes
connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while
at the same time shutting off its water supply.
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS
(VA PORS) ARE LIK ELY TO BE PRESENT OR STORE D
(GARAGES, STORAGE AND UTILITY AREAS, ETC.): Flammable
liquids (such as gasoline, solvents, propane (LP or butane, etc.) and
other substances (such as adhesives, etc.) emit ammable vapors
which can be ignited by a gas water heater’s hot surface igniter or
main burner. The resulting ashback and re can cause death or
serious burns to anyone in the area.
Also, the water heater must be located and/or protected so it is not
subject to physical damage by a moving vehicle.
This water heater must not be installed directly on carpeting.
Carpeting must be protected by metal or wood panel beneath the
appliance extending beyond the full width and depth of the appliance
by at least 3” (7.6 cm) in any direction, or if the appliance is installed
9
in an alcove or closet, the entire oor must be covered by the panel.
Failure to heed this warning may result in a re hazard.
Minimum clearances between the water heater and combustible
construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the front
and 12” (30.5 cm) from the top. (Standard clearance.) If clearances
stated on the heater differ from standard clearances, install water
heater according to clearances stated on the heater.
Adequate clearance 24” (61.0 cm) for servicing this appliance should be
considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to
replaceable parts such as the thermostats, drain valve and relief valve.
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the wall as practicable
and as centralized with the water piping system as possible.
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it
does not sag, thereby obstructing combustion air ow.
COMBUSTION AIR AND VENTILATION
A gas water heater cannot operate properly without the correct amount
of air for combustion. Do not install in a conned area such as a closet,
unless you provide air as shown in the “Facts to Consider About
Location” section. Never obstruct the ow of ventilation air. If you have
any doubts or questions at all, call your gas supplier. Failure to provide
the proper amount of combustion air can result in a re or explosion
and cause death, serious bodily injury, or property damage.
FIGURE 3. FIGURE 4.
INSULATION BLANKETS
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with these products. The
purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your water heater meets or
exceeds the Energy Policy Act standards with respect to insulation and
standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you
should follow these instructions (For identication of components
mentioned below, see Figure 1). Failure to follow these instructions
can restrict the air ow required for proper combustion, potentially
resulting in re, asphyxiation, serious personal injury or death.
• Do not apply insulation to the top of the water heater, as this will
interfere with safe operation of the blower assembly.
• Do not cover the outer door, thermostat or temperature & pressure
relief valve.
• Do not allow insulation to come within 2” (5.1 cm) of the oor to
prevent blockage of combustion air ow to the burner.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from the manufacturer
FIGURE 5.
If this water heater will be used in beauty shops, barber shops, cleaning
establishments, or self-service laundries with dry cleaning equipment,
it is imperative that the water heater (s) be installed direct vent so that
all air for combustion and ventilation is taken from outdoors.
Propellants of aerosol sprays and volatile compounds, (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being highly
ammable in many cases, will also react to form corrosive hydrochloric
acid when exposed to the combustion products of the water heater.
The results can be hazardous, and also cause product failure.
APPLIANCES IN UNCONFINED SPACES
UNCONFINED SPACE is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the
aggregate input rating of all appliances installed in that space. Rooms
communicating directly with the space in which the appliances are
installed, through openings not furnished with doors, are considered
a part of the unconned space.
In unconned spaces in buildings, inltration may be adequate to
provide air for combustion, ventilation and dilution of ue gases.
However, in buildings of tight construction (for example, weather
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in “Appliances
in Conned Space” that follows.”
APPLIANCES IN CONFINED SPACES
CONFINED SPACE is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input
rating of all appliances installed in that space.
When drawing combustion air from inside a conventionally constructed
building to a confined space, such a space shall be provided with
two permanent openings. ONE WITHIN 12 INCHES (30 cm) OF
THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES (30
cm) OF THE ENCLOSURE BOTTOM. Each opening shall have
10
a free area of one square inch per 1000 Btu/hr (22 cm2/kW) of the
total input of all appliances in the enclosure, but not less than 100
square inches (645 cm
2
).
If the conned space is within a building of tight construction, air for
combustion and ventilation must be obtained from outdoors. When
directly communicating with the outdoors or communicating through
vertical ducts, two permanent openings, located in the above manner,
shall be provided. Each opening shall have a free area of not less
than one square inch per 4000 Btu/hr (5.5 cm
2
/kW) of total input of all
appliances in the enclosure. If horizontal ducts are used, each opening
shall have a free area of not less than one square inch per 2000 Btu/
hr (11cm
2
/kW) of the total input of all appliances in the enclosure.
A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 5 and 6)
The conned space shall be provided with two permanent openings
communicating directly with an additional room(s) of sufcient volume
so that the combined volume of all spaces meets the criteria for an
unconned space. The total input of all gas utilization equipment installed
in the combined space shall be considered in making this determination.
Each opening shall have a minimum free area of one square inch
per 1,000 Btu per hour (22 cm
utilization
inches (645 cm
equipment in the conned space, but not less than 100 square
2
). One opening shall commence within 12 inches
2
/kW) of the total input rating of all gas
(30 cm) of the top and one commencing within 12 inches (30 cm) of the
bottom of the enclosures.
Btu per hour (11 cm2/kW)) of total input rating of all equipment in the
enclosure, see Figure 9.
FIGURE 8.
4. When ducts are used, they shall be of the same cross-sectional area
as the free area of the openings to which they connect. The minimum
short side dimension of rectangular air ducts shall not be less than 3
inches (7.6 cm), see Figure 9.
FIGURE 6.
B. ALL AIR FROM OUTDOORS: (See Figures 7, 8 and 9)
The conned space shall be provided with two permanent openings,
one commencing within 12 inches (30 cm) of the top and one
commencing within 12 inches (30 cm) from the bottom of the enclosure.
The openings shall communicate directly, or by ducts, with the outdoors
or spaces (crawl or attic) that freely communicate with the outdoors.
1. Wh en di re ct ly co mm un ic ati ng wi th th e o utdo or s, eac h o pe ni ng s ha ll ha ve
a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW)
of total input rating of all equipment in the enclosure, see Figure 7.
FIGURE 7.
2. When communicating with the outdoors through vertical ducts, each
opening shall have a minimum free area of 1 square inch per 4,000
Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the
enclosure, see Figure 8.
3. When communicating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch per 2,000
FIGURE 9.
5. Alternatively a single permanent opening may be used when
communicating directly with the outdoors, or with spaces that freely
communicate with the outdoors. The opening shall have a minimum
free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of
total input rating of all equipment in enclosure. See Figure 9A.
FIGURE 9A.
6. Louvers and Grilles: In calculating free area, consideration shall be
given to
the blocking effect of louvers, grilles or s protecting openings. Screens
used shall not be smaller than 1/4 inch (6.4 mm) mesh. If the free area through
a design of louver or grille is known, it should be used in calculating the size
opening required to provide the free area specied. If the design and free area
is not known, it may be assumed that wood louvers will be 20-25 percent free
area and metal louvers and grilles will have 60-75 percent free area. Louvers
and grilles shall be xed in the open position or interlocked with the equipment
so that they are opened automatically during equipment operation.
7. Special Conditions Created by Mechanical Exhausting or Fireplaces:
operation of exhaust fans, ventilation systems, clothes dryers or
replaces may create conditions requiring special attention to avoid
unsatisfactory operation of installed gas utilization equipment.
11
INSTALLING THE NEW WATER HEATER
CHEMICAL VAPOR CORROSION
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF
AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH
CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium and
sodium chloride (water softener salt), waxes, and process chemicals
are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which is
brought in contact with the heater should not contain any of these
chemicals. If necessary, uncontaminated air should be obtained from
remote or outside sources. The limited warranty is voided when failure
of water heater is due to a corrosive atmosphere. (See limited warranty
for complete terms and conditions).
WATER PIPING
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such
conditions as high line pressure, among others, have installed devices
such as pressure reducing valves, check valves, and back ow preventers.
Devices such as these cause the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed system
the volume of water will grow when it is heated. As the volume of water
grows there will be a corresponding increase in water pressure due
to thermal expansion. Thermal expansion can cause premature tank
failure (leakage). This type of failure is not covered under the limited
warranty. Thermal expansion can also cause intermittent temperaturepressure relief valve operation: water discharged from the valve due to
excessive pressure build up. This condition is not covered under the
limited warranty. The temperature-pressure relief valve is not intended
for the constant relief of thermal expansion.
A properly sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion..
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes washing, dish
washing, cleaning and other sanitizing needs can scald and permanently
injure you upon contact. Some people are more likely to be permanently
injured by hot water than others. These include the elderly, children, the
physically or developmentally disabled. If anyone using hot water ts into
one of these groups or if there is a local code or state law requiring a
certain temperature water at the hot water tap, then you must take special
precautions. In addition to using the lowest possible temperature setting
that satises your hot water needs, a means such as a *mixing valve
should be used at the hot water taps used by these people or at the water
heater, see Figure 2. Valves for reducing point of use temperature by
mixing cold and hot water are also available:
Consult a Qualied Installer or Service Agency. Follow manufacturer’s
instructions for installation of the valves. Before changing the factory
setting on the thermostat, read the “Temperature Regulation” section in
this manual.
This water heater shall not be connected to any heating systems or
component(s) used with a non-potable water heating appliance.
All piping components connected to this unit for space heating
applications shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment shall not be
introduced into this system.
When the system requires water for space heating at temperatures higher
than required for domestic water purposes, a tempering valve must be
installed. Please refer to Figure 2 for suggested piping arrangement.
FIGURE 10.
NOTE: To protect against untimely corrosion of hot and cold
water ttings, it is strongly recommended that di-electric unions
or couplings be installed on this water heater when connected
to copper pipe, see Figure 2 also.
12
Figures 2 and 10 show the typical attachment of the water piping to
the water heater. The water heater is equipped with 3/4 inch NPT
water connections.
If replaced, the valve must meet the requirements of local codes, but
not less than a combination temperature and pressure relief valve
certied as indicated in the above paragraph.
NOTE: If using copper tubing, solder tubing to an adapter
before attaching the adapter to the water heater connections.
Do not solder the water lines directly to the water heater
connections. It will harm the dip tube and damage the
tank.
T & P Valve and Pipe Insulation (if supplied)
Remove insulation for T & P valve and pipe connections from
carton.
FIGURE 11.
Fit pipe insulation over the incoming cold water line and the
hot water line. Make sure that the insulation is against the top
cover of the heater.Fit T & P valve insulation over valve. Make
sure that the insulation does not interfere with the lever of the
T & P valve.
The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water heater
(150 psi = 1,035 kPa) and a discharge capacity not less than the
water heater
model rating plate.
For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly into
the fitting of the water heater designed for the relief valve. Position
the valve downward and provide tubing so that any discharge will
exit only within 6 inches (15.2 cm) above, or at any distance below
the structural floor. Be certain that no contact is made with any
live electrical part. The discharge opening must not be blocked
or reduced in size under any circumstances. Excessive length,
over 30 feet (9.14 m), or use of more than four elbows can cause
restriction and reduce the discharge capacity of the valve, see
Figures 10.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. If the discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.
Btu/hr input rate as shown on the water heater’s
Secure all insulation using tape.
TEMPERATURE-PRESSURE RELIEF VALVE
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The Discharge Pipe:
• Should not be smaller in size than the outlet pipe size of the valve,
or have any reducing couplings or other restrictions.
• Should not be plugged or blocked.
• Should be of material listed for hot water distribution.
• Should be installed so as to allow complete drainage of both the
temperature-pressure relief valve, and the discharge pipe.
• Must terminate a maximum of six inches above a oor drain or
external to the building. In cold climates, it is recommended that
the discharge pipe be terminated at an adequate drain inside the
building.
• Should not have any valve between the relief valve and tank.
The valve is certied by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment of
materials as meeting the requirements for Relief Valves for Hot Water
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements
of ASME.
13
The temperature-pressure relief valve must be manually
operated periodically, see Figure 28. Caution should be taken
to ensure that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) the
water manually discharged will not cause any bodily injury or
property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions, and
replace the temperature-pressure relief valve with a new one.
GAS PIPING
Make sure gas supplied is same type listed on model rating plate.
The inlet gas pressure must not exceed 14 inch water column (3.5
kPa) for natural and propane gas (L.P.). The minimum inlet gas
pressure shown on rating plate is that which will permit ring at
rated input.
All gas piping must comply with local codes and ordinances or with the
Natural Gas and Propane Installation Code (CAN/CSA B149.1).
Copper or brass tubing and ttings (except tin lined copper tubing)
shall not be used.
HIGH ALTITUDE INSTALLATIONS
Rated inputs are suitable up to 10,100 feet (3,079m) elevation. Consult
the factory for installation at altitudes over 10,100 feet (3,079m).
WARNING:
FOR USE WITHOUT MODIFICATION FOR AN ALTITUDE OF 10,100
FEET (3,079 METERS). INSTALLATIONS ABOVE THESE ALTITUDES
MAY REQUIRE REPLACEMENT OF BURNER ORIFICE. CALL THE
TECHNICAL CENTER AT (800) 527-1953 FOR
Some gas utility companies derate their gas for altitude, making
it unnecessary to install high altitude orices. Call the local gas or
utility company to verify BTU content.
Due to the input ration reduction at high altitudes, the output rating
of the appliance is also reduced and should be compensated for in
the sizing of the equipment for applications.
THIS HIGH EFFICIENCY WATER HEATER IS CERTIFIED
REQUIREMENTS.
If the gas control valve is subjected to pressures exceeding 1/2 psi
(3.5 kPa), the damage to the gas control valve could result in a re
or explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also
turn “off” the gas at each appliance. Leave all gas appliances shut
“off” until the water heater installation is complete.
A gas line of sufcient size must be run to the water heater. Consult
the current edition of the Natural Gas and Propane Installation Code
(CAN/CSA B149.1) and your gas supplier concerning pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
• A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve.
• A exible gas connector or a ground joint union between the shut
off valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water
heater. Use a soapy water solution, not a match or open ame. Rinse
off soapy solution and wipe dry.
Use pipe joint compound or teon tape marked as being resistant
to the action of petroleum [Propane (L.P.)] gases.
The appliance and its gas connection must be leak tested before
placing the appliance in operation.
The appliance and its individual Shut-off valve shall be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 pound per square inch
(3.5 kPa). It shall be isolated from the gas supply piping system
by closing its individual manual Shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 pound per square inch (3.5 kPa).
IMPORTANT: MAKE SURE THE GAS LINE IS PIPED IN WITH
HARD PIPE. AVOID FLEX LINE CONSTRUCTION FOR GAS DUE
TO POSSIBLE GAS FLOW PROBLEMS.
14
SEDIMENT TRAPS
A sediment trap shall be installed as close to the gas inlet of the water
heater as practical at the time of water heater installation. The sediment
trap shall be either a tee tting with a capped nipple in the bottom outlet
or other device recognized as an effective sediment trap.
Contaminants in the gas lines may cause improper operation of the
gas control valve that may result in re or explosion. Before attaching
the gas line be sure that all gas pipe is clean on the inside. To trap any
dirt or foreign material in the gas supply line, a drip leg (sometimes
called a sediment trap) must be incorporated in the piping. The drip
leg must be readily accessible. Install in accordance with the “Gas
Piping” section. Refer to the current edition of the Natural Gas and
Propane Installation Code (CAN/CSA B149.1).
FILLING THE WATER HEATER
VENTING
VENT PIPE TERMINATION
Never use this water heater unless it is completely full of water. To prevent
damage to the tank, the tank must be lled with water. Water must ow
from the hot water faucet before turning “ON” gas to the water heater.
To ll the water heater with water:
1. Close the water heater drain valve by turning the handle to the right
(clockwise). The drain valve is on the lower front of the water heater.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when
the water heater is in use.
3. To insure complete lling of the tank, allow air to exit by opening the
nearest hot water faucet. Allow water to run until a constant ow is
obtained. This will let air out of the water heater and the piping.
4. Check all water piping and connections for leaks. Repair as needed.
The first step is to determine where the vent pipe will terminate.
See Figures 19, 20, and 21. The vent may terminate through a
sidewall as shown in Figure 19 or through the roof as shown in
Figures 20 and 21.
The vent system must terminate so that proper clearances
are m aintaine d as ci t e d in l ocal co d es or the cu r r e nt
edition of the Natural Gas and Propane Installation Code (CAN/
CSA-B149.1).
Instructions on proper installation through a sidewall are provided
in Figures 15A and 15B.
Plan the vent system layout so that proper clearances are
maintained from plumbing and wiring.
Vent pipes serving power vented appliances are classified by
building codes as “vent connectors”. Required clearances from
combustible materials must be provided in accordance with
information in this manual under FACTS TO CONSIDER ABOUT LOCATION and INSTALLING THE WATER HEATER, and with
the National Fuel Gas Code and local codes.
15
CAUTION
TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN
WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO
TERMINALS IS RECOMMENDED.
CANADIAN POWER VENT
VENT HOOD(S) MAY BE
WARNING
EXTREMELY HOT
DURING OPERATION.
FIGURE 12.
16
CAUTION
TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN
WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO
TERMINALS IS RECOMMENDED.
CANADIAN DIRECT VENT
VENT HOOD(S) MAY BE
WARNING
EXTREMELY HOT
DURING OPERATION.
FIGURE 13.
17
PLANNING THE VENT SYSTEM
Plan the route of the vent system from the exhaust elbow to the
planned location of the vent terminal.
1. Layout total vent system to use a minimum of vent pipe and elbows.
2. This water heater is capable of venting ue gases equivalent to
25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m) of
4” pipe as listed in Table 1.
TABLE 1
Number of 2” Maximum 3” Maximum 4” Maximum
90° Elbows Pipe - ft. (m) Pipe - ft. (m) Pipe - ft. (m)
The minimum vent lengths for each of the pipe sizes is one 90° plus
2’ (61 cm) of straight pipe and the appropriate termination.
NOTE: The equivalent feet (m) of pipe listed above are exclusive
of the termination. That is, the termination, with an installed
screen, is assumed to be in the system and the remainder of the
system must not exceed the lengths discussed above.
3. The exhaust elbow assembly is designed to accept only straight
sections of 2” pipe. To start, a minimum of 2” (5.1cm) of 2” pipe
must be inserted and glued to the exhaust elbow assembly if
utilizing 3” or 4” vent pipe. Use the same method with the blower
inlet if a direct vent conguration is utilized.
joints between elbows and other ttings and straight runs of vent
pipe. Check system for signs of sagging or other stresses in joints
as a result of misalignment of any components in the system. If any
of these conditions are found, they must be corrected in accordance
with the venting instructions in this manual before completing
installation and putting the water heater into service.
NOTE:A. For water heaters in locations with high ambient
temperatures (above 100°F) it is recommended that CPVC pipe
and ttings be used. B. A 22.5 degree elbow (2” vent pipe) or a
45 degree elbow (3” and 4” vent pipe) with an installed screen
VENT TERMINAL must be used in all cases.
4. There will be some installations where condensate will be formed
in the horizontal runs of the vent system. This condensate will
run into the condensate elbow. The water heater is shipped with
a condensate hose that attaches to the condensate elbow. No
other tee or tting is required.
CONDENSATE
This water heater is a condensing unit and requires a drain to be located in
close proximity to allow the condensate to drain safely. The condensate
drains from the unit at the exhaust tee located at the bottom of the unit
(see gure 16). Condensate from this water heater is mildly acidic.
Please note that some local codes require that condensate is treated
by using a pH neutralizing lter prior to disposal.
Caution must be used to ensure that the drain is free and clear of debris
and will not allow backow through the condensate hose. Consideration
must be given to avoid freezing of the condensate lines which could
result in excessive build up of condensate inside the water heater.
Waterproof heat tape may be required to prevent freezing of the condensate
lines. Please ensure that the outlet of the condensate drain does
not create a slippery condition which could lead to personal injury.
If using 2” inch vent pipe:
A minimum of 2” (5.1cm) diameter vent pipe must be attached
to the exhaust elbow assembly. The total system cannot exceed
the lengths discussed above, where each elbow is equal to 5
equivalent feet (1.5m) of straight pipe.
If using 3” or 4” inch vent pipe:
Two inches (5.1cm) of 2” pipe must be attached to the exhaust
elbow assembly before adding a reducer to acquire the desired
pipe diameter. An appropriately sized 45 degree elbow (supplied
locally-a schedule 40 DWV) vent terminal must be obtained with
an equivalent screen (supplied in vent kit). The total system cannot
exceed the equivalent pipe lengths discussed above where each
elbow is equal to 5 feet (1.5m) of straight pipe (3” vent pipe) or 8
feet (2.4m) of straight pipe (4” vent pipe).
Installation of this water heater must comply with CAN/CSA
B149.1 - Natural Gas and Propane Installation Code which
requires the vent system components be certied to ULC
S636.
This water heater has been design certied to be vented with PVC
pipe certied and marked as complying with ULC S636. This water
heater is supplied with a 2 inch 22.5 degree termination elbow
that is a special tting that must be used with the appliance. Any
outlet piping, ttings and glue used to vent this appliance that
is not supplied by the manufacturer must comply with the ULC
S636 requirements.
CONDENSATION WARNING: THIS WATER HEATER IS A CONDENSING
UNIT AND REQUIRES A DRAIN TO BE LOCATED IN CLOSE
PROXIMITY TO ALLOW CONDENSATE TO DRAIN SAFELY. THE
CONDENSATE DRAINS FROM UNIT AT THE EXHAUST ELBOW
LOCATED AT BOTTOM OF UNIT. NOTE: IT IS IMPORTANT THAT THE
CONDENSATE HOSE NOT BE ELEVATED ABOVE THE EXHAUST
ELBOW, SEE FIGURE 16. CONDENSATE BUILD-UP WILL BLOCK THE
EXHAUST OUTLET, WHICH WILL CAUSE IMPROPER OPERATION.
If the water heater is being installed as a replacement for an existing
power vented heater in pre-existing venting, a thorough inspection of
existing venting system must be performed prior to any installation
work. Verify that correct material as detailed above has been used,
and that the minimum or maximum vent lengths and terminal location
as detailed in this manual have been met. Carefully inspect the entire
venting system for any signs of cracks or fractures, particularly at
FIGURE 14.
18
INSTALLATION OF VENT SYSTEM
DIRECT VENTING
Before beginning installation of piping system thoroughly read
the section of this manual VENT PIPE PREPARATION.
If you are installing your system so that it vents through roof,
please refer to section titled INSTALLATION OF VERTICAL
VENT SYSTEM.
VENT TERMINAL INSTALLATION, SIDEWALL
1. Install the vent terminal by using the cover plate as a template
to mark the hole for the vent pipe to pass through the wall.
BEWARE OF CONCEALED WIRING AND PIPING INSIDE
THE WALL.
2. If the Vent Terminal is being installed on the outside of a
finished wall, it may be easier to mark both the inside and
outside wall. Align the holes by drilling a hole through the
center of the template from the inside through to the outside.
The template can now be positioned on the outside wall using
the drilled hole as a centering point for the template.
3. A) MASONRY SIDE WALLS
Chisel an opening approximately one half inch (1.3 cm) larger
than the marked circle.
B) WOODEN SIDE WALLS
Drill a pilot hole approximately one quarter inch (0.64 cm) outside
of the marked circle. This pilot hole is used as a starting point
for a saws-all or sabre saw blade. Cut around the marked
circle staying approximately one quarter inch (0.64 cm) outside
of the line. (This will allow the vent to easily slide through
the opening. The resulting gap will be covered up by the
Vent Terminal cover plate.) Repeat this step on inside wall if
necessary.
SEQUENCE OF INSTALLATIONS, FIGURE 18A
The air intake provided on the unit contains a mesh screen to prevent
large particles from entering the unit.
FIGURE 16.
WHEN THE UNIT IS TO BE SETUP AS A DIRECT VENT, THE
MESH SCREEN MUST BE REMOVED. THE INLET VENT PIPE
MAY THEN BE GLUED TO THE AIR INTAKE (See Figure 18B)
PROVIDED ON THE UNIT. THE SCREEN REMOVED FROM THE
INTAKE NEEDS TO BE INSERTED INTO THE 2” - 22.5 DEGREE
VENT TERMINAL SUPPLIED IN THE VENT TERMINAL KIT.
DIRECT VENT TERMINAL INSTALLATION IMPORTANT
THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE
VENT TERMINAL AND AN EXHAUST VENT TERMINAL. THE INTAKE
VENT TERMINAL IS A 2” 22.5° PVC ELBOW(-) WITH A MESH
SCREEN AND THE EXHAUST VENT TERMINAL IS A 2” 22.5° PVC
ELBOW WITH A MESH SCREEN.
NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM
CIRCULATING TO THE AIR INTAKE IN WINDY/COLD AREAS,
THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO
TERMINALS IS RECOMMENDED.
Cut a length of PVC pipe about 3.5 inches (8.9 cm) longer than the
wall thickness at the opening. Glue the vent terminal to this
section of pipe. Slide the wall plate over the pipe to stop against
the vent terminal. Place a bead of caulking (not supplied) around
the gap between the pipe and cover plate. Apply enough to
fill some of the gap between the pipe and wall. Place some of
the caulking on the back of the plate to hold it against the wall
after installation. If the vent pipe is installed up to the wall, with
a coupling on the end against the wall opening, the pipe with
the vent terminal can be prepared for gluing before inserting
through the wall. Slide the pipe through the wall and insert
into the coupling on the other side of the wall, making sure that
the vent terminal ends up pointed in the correct position, see
Figure 15.
VENT TERMINATION - FIGURE 15.
FIGURE 17.
WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE
FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL
LOCATION MUST BE FOLLOWED.
1. The intake air terminal and the exhaust vent terminal must terminate
on the same exterior wall and must be separated by a minimum of
24” (61cm) on vertical centerline (see Figure 18C). In colder climates
increasing the 24” (61cm) minimum will reduce possibility of frost
over from side winds blowing exhaust vapors to the air intake of the
direct vent.
2. The horizontal centerline of the intake air terminal may not be located
lower than the horizontal centerline of the exhaust vent terminal (see
Figure 17).
19
INSTALLATION SEQUENCE
VERTICAL VENT TERMINAL INSTALLATION
VENT TERMINALS SUPPLIED WITH HEATER MUST BE USED.
NOTE: BEFORE BEGINNING INSTALLATION OF ANY
VENT PIPE READ THE VE NT PIPE MANUFACTURER’S
INSTALLATION INSTRUCTIONS.
1. After the points of termination have been determined,
use the cover plates as templates to mark the holes for
the vent pipes to be inserted through the wall. BEWARE OF
CONCEALED WIRING AND PIPING INSIDE OF WALL. If the
vent terminals are being installed on the outside of a nished
wall, it may be easier to mark both the inside and outside
wall. Align the holesby drilling a hole through the center of the
template from the inside through to the outside. The template
can now be positioned on the outside wall using the drilled holes
as a centering point for the template.
A.) MASONRY SIDE WALLS Chisel an opening approximately
1/2” (1.3 cm) larger than the marked circle.
B.) WOODEN SIDE WALLS Drill a pilot hole approximately
one quarter inch outside of the marked circle. This
pilot hole is used as a starting point for a saws-all or
sabre saw blade. Cut around the marked circle staying
approximately one quarter inch outside of the line.
(This will allow the vent pipe to easily slide through
the opening. The resulting gap will be covered by the
vent terminal cover plates.) Repeat this step on the
inside wall if necessary.
2. Cut a length of 3” PVC pipe about 3.5” (8.9 cm) longer than the
wall thickness at the opening.
3. Glue the intake vent terminal to the section of the pipe.
4. Slide the wall plate over pipe to stop against intake vent terminal.
5. Place a bead of caulking (not supplied) around the gap between
the pipe and the wall. Place some of the caulking on the
back of the plate to hold it against the wall after installation.
6. If the vent pipe is installed up to the wall, with a coupling on the
end against the wall opening, the pipe with the vent terminal can
be prepared for gluing before inserting through the wall. Slide the
pipe through the wall and insert into coupling on the other side of
the wall, making sure that the vent terminal ends up pointed in the
correct position (Figure 18 and 19).
CAUTION
IMPORTANT
WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING
SPECIFICATIONS PERTAINING TO TERMINAL LOCATION
MUST BE FOLLOWED.
1. Proper support must be provided for all pipe protruding through
the roof.
2. The vertical roof terminals should be sealed with a plumbing
roof boot or equivalent ashing.
3. The intake vent terminals and the exhaust vent terminals must
penetrate the same side of roof.
4. The center line of the intake vent terminal and the center
line of the exhaust vent terminal must be no closer
than 24” (61cm).
5. The intake vent terminal and the exhaust vent terminal must be
oriented facing downward and the same direction.
The specications are displayed in Figures 20 & 21.
NOTE: Exhaust vent terminal is installed using the same
procedure.
FIGURE 18.
FIGURE 19.
FIGURE 20.
FIGURE 21.
20
INSTALLATION OF VENT SYSTEM, SIDEWALL
Item Description Qty.
Rain Cap 3 in. 1
SDR-26 pipe 4 in. dia. 1
SDR-26 pipe 2½ in. dia. 1
Y Concentric Fitting 3 in. 1
Installation Instructions 194504 1
With the route of the venting system and selection of materials completed,
as discussed in the section of this manual titled PLANNING THE VENT
SYSTEM, the through the wall vent terminal in place and the rst section
of piping, up to rst elbow, installed at the blower it is time to complete the
installation of the venting system for the sidewall installation.
FIGURE 22.
Before completing the installation of the venting system be sure to read
the sections of this manual discussing the proper method of cutting and
cementing PVC pipe and ttings: VENT PIPE PREPARATION.
It is recommended that the completion of the venting system start at
the blower assembly and run to the coupling on the inside wall of the
vent terminal, Figure 18A.
The vent system piping should be supported every 5 feet (1.5 m)
of vertical run and every 3 feet (91 cm) of horizontal run. All piping
and ttings must be joined by the proper procedures as described
under: VENT PIPE PREPARATION.
INSTALLATION OF VERTICAL VENT SYSTEM
A proper ashing or “BOOT” should be used to seal the pipe where it
exits the roof. The total vent system should not exceed the equivalent
feet of pipe as listed in Table 1.
Provide support for all pipe protruding through the roof. All piping
should be properly secured. The vent system piping should be
supported every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm)
of horizontal run. All piping and ttings must be joined by the proper
procedures as described under: VENT PIPE PREPARATION.
FIGURE 23.
IMPORTANT
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
Natural Gas and Propane Installation Code (CAN/CSA-B149.1) and
as listed below:
1. Vent Termination must extend a minimum of 12 inches (30.5 cm)
above roof or above the anticipated snow level to prevent blockage
of the vent termination, as shown in Figures 20 and 21.
CONCENTRIC VENT INSTALLATION
This appliance is certied for concentric venting with concentric vent
kit #9006328005. Follow instructions below for proper installations.
KIT COMPONENTS
Each kit is comprised of the following:
Field supplied pipe and fittings are required to complete the
installation.
21
This concentric vent termination kit may be used with 3 or 4 inch diameter
pipe systems. When connecting to a 4 in. diameter pipe system a 3 x 4
inch eld supplied reducer is to be installed at the intake and exhaust
connection of the concentric vent termination kit.
1. Determine best location for termination kit.
NOTE: Roof termination is preferred since it is less
susceptible to damage, has reduced chances to intake
contaminants, and less visible vent vapors.
SAFETY CONSIDERATIONS
Installing and servicing water heating equipment can be hazardous due to
gas and electrical components. Installation and service of the concentric
vent termination requires ability equivalent to that of a qualied installer or
service agent, see page 2. All precautions in the literature, on tags, and
labels attached to the unit must be observed.
Follow all safety codes. Wear safety glasses and work gloves.
FIGURE 24.
2. Cut 1 hole (5 in. diameter)
3. Partially assemble concentric vent termination kit.
a) Cement Y co ncentri c fitti ng to larger diameter kit
pipe, see Figure A.
b) Cement rain cap to smaller diameter kit pipe, see Figure A.
FIGURE 27.
NOTE: Instead of cementing the smaller pipe to the rain cap, a
eld-supplied stainless steel screw may be used to secure the
2 components together when eld disassembly is desired for
cleaning, see Figure 27.
WARNING
When using alternate screw method, drill clearance hole in rain
cap and pilot hole in vent pipe for screw size being used. Failure
to drill adequate holes may cause cracking of PVC components,
allowing combustion products to be recirculated. Failure to
follow this warning could result in personal injury or death.
FIGURE 25.
* Dimension 21 1/8 in. may be lengthened to 60 in. maximum.
Dimension 21 1/8 in. may also be shortened by cutting the
pipes, provided in the kit, to 12 in. minimum.
** Dimension 39 will change accordingly as dimension
21 1/8 in. is lengthened or shortened.
WARNING
Do not operate the heater with rain cap removed or recirculation
of combustion products may occur. Water may also collect inside
larger combustion-air pipe and ow to the burner enclosure.
Failure to follow this warning could result in product damage or
improper operation, personal injury or death.
4. Install Y concentric fitting and pipe assembly through
structure’s hole and eld supplied roof boot/ashing.
FIGURE 26.
INSTALLATION PROCEDURE 1 ROOF TERMINATION,
see Figure 26.
FIGURE 28.
NOTE: Do not allow insulation or other materials to accumulate
inside pipe assembly when installing through hole.
22
5. Secure assembly to roof structure as shown in Figure E using
field supplied metal strapping or equivalent support material.
NOTE: See the venting information (pages 16-20) in this
manual for additional vent location requirements.
NOTE: Ensure termination height is above the roof surface or
anticipated snow level as shown in Figure C.
6. Install rain cap and small diameter pipe assembly in
roof penetr a t ion as s e mbly, En s u re sm a l l dia m e ter pi p e
is cemented and bottomed in Y concentric fitting.
7. Cement water heater combustion air intake and vent pipes to
con centr ic ve nt te rmina tion asse m bly. See Fi gure E for
proper pipe attachment.
8. Operate heater through 1 heat cycle to ensure combustion air
and vent pipes are properly connected to concentric vent termination
connections.
NOTE: All vent terminations must be the same height when
installing multiple unit venting. If assembly is too short to meet
height requirement, the 2 pipes supplied in the kit may be replaced
by using same diameter, eld supplied ULC S636 approved pipe.
Do not extend the 21-1/8” dimension outer pipe to be more than
60 inches, see Figure 25.
CAUTION
Do not use eld-supplied couplings to extend pipes. Airow
restriction will occur and the heater pressure switch may cause
intermittent operation.
PROCEDURE 2 SIDE WALL TERMINATION, see Figure 29.
2. Cut 1 hole (5 in. diameter)
3. Pa r t i a l l y assemble c o n c e n t r i c v e n t termination k i t .
a) Ceme nt the Y con centric fi tting to larg er diam eter
kit pipe, see Figure 24.
b) C e ment th e r ain cap t o t he small e r diamet e r kit
pipe, see Figure 24.
NOTE: Instead of cementing the smaller pipe to the rain cap, a
eld-supplied stainless steel screw may be used to secure the
2 components together when eld disassembly is desired for
cleaning, see Figure 27.
WARNING
When using alternate screw assembly method, drill clearance
hole in rain cap and pilot hole in vent pipe for screw being
used. Failure to drill adequate holes may cause cracking
of PVC components, allowing combustion products to be
recirculated. Failure to follow this warning could result in
personal injury or death.
WARNING
Do not operat e the hea t er wi th ra in ca p re moved or
recirculation of combustion products may occur. Water may
also collect inside larger combustion-air pipe and flow to the
burner enclosure. Failure to follow this warning could result
in product damage or improper operation, personal injury
or death.
FIGURE 29.
1. Determine best location for termination kit.
NOTE: Consideration for the following should be used when
determining an appropriate location for the termination kit:
• Termination kit positioned where the vent vapors will
n ot d am age pl a n ts/ s hr u bs o r ai r c on d it ion i ng
equipment.
• Termination kit positioned so it will not be affected by
wind eddy that may allow recirculation of combustion
products, or airborne leaves, or light snow.
• Termination kit positioned where it will not get damaged
or be subjecte d to foreign obj ects, such as st ones ,
balls, etc.
• Termination kit positioned where the vent vapors will
not be objectionable.
4. Inst all Y concent ric fitting and pipe assem bly thr ough
structure’s hole.
NOTE: Do not allow insulation or other materials to accumulate
inside pipe assembly when installing through hole.
5. Insta ll rain cap and smal l di amet er pipe asse mbly in
Y concentric fitting and large pipe assembly. Ensure
small diameter pipe is bottomed and cemented in Y
concentric tting.
6. Secure assembly to structure as shown in Figure G using eldsupplied metal strapping or equivalent support material.
NOTE: Ensure termination location clearance dimensions are as
shown in the diagrams found in Figure 12 and Figure 13. When
extending the length of the 4” pipe, the added length beyond
21-1/8” must be deducted from the maximum equivalent feet of
vent pipe.
NOTE: If assembly needs to be extended to allow side wall
thickness requirement, the 2 pipes supplied in the kit may be
replaced by using same diameter, field-supplied ULC S636
approved pipe. Do not extend 21 1/8” dimension more than 60
in. (See Figure 25.)
CAUTION
Do not use eld-supplied couplings to extend pipes. Airow
restriction will occur and the heater pressure switch may cause
intermittent operation.
7. Cement heater combustion-air and vent pipes to concentric
vent termination assembly. See Figure 30 for proper pipe
attachment.
23
8. Operate heater through 1 heat cycle to ensure combustion-air and
vent pipes are properly connected to concentric vent termination
connections.
FIGURE 30.
MULTI-CONCENTRIC VENT TERMINATIONS
When two or more appliances are directed vented with concentric
vent terminations near each other, each appliance must be
individually vented. NEVER common vent this appliance. When
two or more appliances are direct vented using concentric vent
terminations, the appliances may be vented as shown in Figure H
and Figure 32.
Concentric Vent Terminations
FIGURE 31.
for Horizontal Direct Venting.
FIGURE 32.
Concentric Vent Terminations for Vertical
Direct Venting through a roof.
24
VENT PIPE PREPARATION
PRIMER
1. INITIAL PREPARATION.
A.) Make sure the solvent cement you are planning to use
is designed for the specic application you are attempting.
B.) Know the physical and chemical characteristics and limitations of the
PVC and CPVC piping materials that you are about to use.
C.) Know the reputation of your manufacturer and their products.
D.) Know your own qualications or those of your contractor. The solvent
welding technique of joining PVC and CPVC pipe is a specialized skill
just as any other pipe tting technique.
E.) Closely supervise the installation and inspect the nished job before
start-up.
F.) Contact the manufacturer, supplier, or competent consulting
agency if you have any questions about the application or
installation of PVC and CPVC pipe.
G.) Take the time and effort to do a professional job. Shortcuts will only
cause you problems and delays in start-up. By far, the majority of
failures in PVC and CPVC systems are the result of shortcuts and/or
improper joining techniques.
2. SELECTION OF MATERIALS.
Cutting Device - Saw or Pipe Cutter.
•
Deburring Tool, Knife, File, or Beveling Machine (2” and above).
•
Brush - Pure Bristle.
•
Rag - Cotton (Not Synthetic).
•
Primer and Cleaner.
•
Solvent Cement - PVC for PVC Components and CPVC for CPVC
•
Components.
Containers - Metal or Glass to hold Primer and Cement. Select the
•
type of PVC or CPVC materials to be used on the basis of their
application with respect to chemical resistance, pressure rating,
temperature characteristics, etc.
Insertion Tool - Helpful for larger diameter pipe and ttings 6 inches
•
(15.2cm) and above.
It is recommended that Tetrahydrofuran (THF) be used to prepare the
surfaces of pipe and ttings for solvent welding. Do not use water,
rags, gasoline or any other substitutes for cleaning PVC or CPVC
surfaces. A chemical cleaner such as MEK may be used.
CEMENT
The cement should be a bodied cement of approximately 500 to
1600 centipoise viscosity containing 10-20% (by weight) virgin PVC
material solvated with tetrahydrofuran (THF). Small quantities of
dimethyl formamide (DMF) may be included to act as a retarding
agent to extend curing time. Select the proper cement; Schedule 40
cement should be used for Schedule 40 pipe. Never use all-purpose
cements, commercial glues and adhesives or ABS cement to join PVC
or CPVC pipe and ttings.
APPLICATORS
Select a suitable pure bristle type paint brush. Use a proper width
brush or roller to apply the primer and cement (see Table 2). Speedy
application of cement is important due to its fast drying characteristics.
IMPORTANT NOTE: A dauber type applicator should only be used
on pipe sizes 2” and below. For larger diameter pipe, a brush or roller
must be used.
TABLE 2.
RECOMMENDED BRUSH* SIZE FOR PRIMER
AND CEMENT APPLICATIONS
Nominal Pipe (IPS)Size Brush Width
21.5” (3.8cm)
31.5”-2.5” (3.8cm - 6.4cm)
*USE ONLY NATURAL BRISTLE
3. MAKING THE JOINT.
A.) Cutting Pipe must be squarely cut to allow for the proper
interfacing of the pipe end and the tting socket bottom. This
can be accomplished with a miter box saw or wheel type cutter
Wheel type cutters are not generally recommended for larger
diameters since they tend to are the corner of the pipe end. If
this type of cutter is used, the are on the end must be
completely removed.
NOTE: Power saws should be specically designed to cut plastic pipe.
STEP A
25
B. Deburring
Use a knife, plastic pipe deburring tool, or file to remove burrs from
the end of small diameter pipe. Be sure to remove all burrs from
around the inside as well as the outside of the pipe. A slight chamfer
(bevel) of about 10°-15° should be added to the end to permit easier
insertion of the pipe into the end of the fitting. Failure to chamfer the
edge of the pipe may remove cement from the fitting socket, causing
the joint to leak.
STEP B
C. Test dry t of the joint
Tapered tting sockets are designed so that an interfaced t should
occur when the pipe is inserted about 1/3 to 2/3 of the way into the
socket. Occasionally, when pipe tting dimensions are at the tolerance
extremes, it will be possible to fully insert dry pipe to the bottom of
the tting socket. When this happens, a sufcient quantity of cement
must be applied to the joint to ll the gap between the pipe and tting.
The gap must be lled to obtain a strong, leak-free joint.
D. Inspection, cleaning, priming
Visually inspect the inside of the pipe and tting sockets and
remove all dirt, grease or moisture with a clean dry rag. If wiping
fails to clean the surfaces, a chemical cleaner must be used.
Check for possible damage such as splits or cracks and replace
if necessary.
Depth-of-entry
Marking the depth of entry is a way to check if the pipe has
reached the bottom of the fitting socket in Step F. Measure
the fitting depth and mark this distance on the pipe O.D. You
may want to add several inches to the distance and make a
second mark as the primer and cement will most likely destroy
your first one.
Apply primer to the surface of the pipe and tting socket with
a natural bristle brush. This process softens and prepares the
PVC or CPVC for the solvent cementing step. Move quickly and
without hesitation to the cementing procedure while the surfaces
are still wet with primer.
STEP E
F. Joint assembly
Working quickly, insert the pipe into the tting socket bottom and
give the pipe or tting a 1/4 turn to evenly distribute the cement.
Do not continue to rotate the pipe after it has hit the bottom of the
tting socket. A good joint will have sufcient cement to make a
bead all the way around the outside of the tting hub. The tting
will have a tendency to slide back while the cement is still wet
so hold the joint together for about 15 seconds.
STEP F
G. Cleanup and joint movement
Remove all excess cement from around the pipe and tting with a
dry cotton rag. This must be done while the cement is still soft.
The joint should not be disturbed immediately after the cementing
procedure, and sufcient time should be allowed for proper curing
of the joint. Exact drying time is difcult to predict because it
depends on variables such as temperature, humidity and cement
integrity. For more specic information, you should contact your
solvent cement manufacturer.
E. Application of solvent cement
• Apply the solvent cement evenly and quickly around the
outside of the pipe at a width a little greater than the depth
of the tting socket.
• Apply a light coat of cement evenly around the inside of the
tting socket. Avoid puddling.
• Apply a second coat of cement to the pipe end.
STEP G
26
CONTROLS AND SWITCHES
This model is provided with three pressure switches. These switches
are essential to the safe and proper operation of the unit. All switches
are wired in series. The controller is set up to shut the unit down
whenever there is a failure of any of the switches. It is important to
understand the purpose of each switch.
FIGURE 33.
BLOWER PROVER SWITCH
(SEE FIGURE 12)
The Blower Prover Switch is provided on the heater to verify that
the fan is operating. It is a positive pressure switch whose electrical
contacts are normally open. When the fan increases the pressure
in the burner, the pressure switch will allow the electrical contacts
to close. The pressure switch is connected to the burner tap by a
piece of tygon tubing. This tubing must be connected in order for
the switch to change the electrical contacts. The controller requires
that the electrical contacts on this air ow switch be open before it
will allow the blower to come on.
BLOCKED EXHAUST SWITCH
(SEE FIGURE 12)
The Blocked Exhaust Switch is set up to shut the unit off when a
build-up of positive pressure in the exhaust vent pipe occurs. This
switch is a positive pressure switch that requires an increase in
pressure to change the electrical contacts from normally closed to
open. When this switch prevents the unit from igniting, most likely the
exhaust is blocked by some means. Check to see if the condensate
is allowed to ow freely from the exhaust elbow and for obstructions
in the exhaust venting and exhaust vent terminal. Also verify that
the vent length does not exceed the maximum allowed as shown in
the Vent Section of this manual.
BLOCKED INTAKE SWITCH
(SEE FIGURE 12)
The Blocked Intake Switch is set up to shut the unit off when a
build-up of negative pressure in the intake air pipe occurs. This
switch is a negative pressure switch that requires an increase in
negative pressure to change the electrical contacts from normally
closed to open. The switch is connected to the pressure tap on the
PVC pipe connected to the inlet of the blower. When this switch
prevents the unit from igniting, most likely the intake is blocked.
Verify that the screen on the intake air connection (conventional
vent), the intake air pipe and termination (direct vent installations)
are free of obstructions that may prevent air from entering the unit.
Insure the screen on intake air connection has been removed on
direct vent installations, see Figure 18B. Also verify the intake
air pipe length does not exceed the maximum allowed as shown
in the Vent Section of this manual.
ON/OFF SWITCH
The ON/OFF Switch is a single-pole, single-throw rocker switch. This
switch provides 120V from the line source to the heater.
CAUTION
THE WATER HEATER IS POLARITY SENSITIVE. BEFORE
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT
SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES
ZERO VOLTAGE.
HOT SURFACE IGNITER
The Hot Surface Igniter is a device that ignites the main burner by
high temperature (>1800°F or >982°C). When 120VAC is applied
to the igniter, sufcient heat is generated to ignite the main burner.
Although improvements have been made to strengthen the igniter,
it is still fragile and care must be taken when handling the igniter to
prevent breakage.
27
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND
DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
POWER VENT WIRING SCHEMATIC - FIGURE 34.
28
THIS WATER HE ATER
IS POLAR ITY SENSIT VE.
BE FOR E A PPLY IN G
ELECTRICITY TO THIS
HEATER B E CE RTAIN
THAT SUPPLY NEUTRAL
WIRE TO GROU ND
CHECK INDICATES ZERO
VOLTAGE.
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire
or explosion may result causing property damage, personal injury or
loss of life.
BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES.
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
Do NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch;
Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
C. Use only your hand to push in the gas control buttons.
Never use tools. If the control buttons will not push in, don’t
try to repair them, call a qualied service technician. Force
or attempted repair may result in a re or explosion.
D. Do not use this appliance if any part has been under
water. Immediately contact a qualied installer or service
agency to replace a ooded water heater. Do not attempt
to repair the unit! It must be replaced!
OPERATING INSTRUCTIONS
5. This appliance is equipped with a device which
automatically lights the burner.
DO NOT TRY TO LIGHT THE BURNER BY HAND.
6.
Wait five (5) minutes to
gas.
If you smell gas,
in the safety information above on this label.
If you don’t smell gas.
7. Turn on all electrical power to the appliance.
clear out any
STOP! Follow “B”
OFF
O
N
120 F
Operating Set Point
Status: Heating
GAS
Menu Help
UP
DN
ON/OFF SWITCH
1. STOP! Read the safety information above,
on this label.
2. Set the ON/OFF switch on the control panel to
the “ON” position.
3. Set the thermostat to the lowest setting.
4. Set the ON/OFF switch on the control box to the
“OFF” position.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
8. Set the ON/OFF switch on the control box to the
“ON” position.
9. Set the thermostat to the desired setting.
10. I f the appliance will no t oper ate, foll ow the
POWER BEFORE SERVICING
2. Set the ON/OFF switch on the control panel to the
3. Turn off all electrical power to the appliance if service
CAUTION: Hotter water increases the risk
of scald injury. Consult the instruction
manual before changing temperature.
instructions “TO TURN OFF GAS TO APPLIANCE”
and call your technician or gas supplier.
WARNING: TURN OFF ALL ELECTRIC
“OFF” position.
is to be performed.
29
TEMPERATURE REGULATION
It is recommended that lower water temperatures be used to avoid
the risk of scalding. It is further recommended, in all cases, that the
water temperatures be set for the lowest temperature which satises
your hot water needs. This will also provide the most energy efcient
operation of the water heater.
HOT WATER CAN SCALD: Water heaters are intended to produce
hot water. Water heated to a temperature which will satisfy space
heating, clothes washing, dish washing, and other sanitizing needs
can scald and permanently injure you upon contact. Some people
are more likely to be permanently injured by hot water than others.
These include the elderly, children, the inrm, or physically/mentally
handicapped. If anyone using hot water from this heater ts into
one of these groups or if there is a local code or state law requiring
a certain temperature water at the hot water tap, then you must
take special precautions. In addition to using the lowest possible
temperature setting that satises your hot water needs, a means such
as a mixing valve should be used at the hot water taps used by these
people or at the water heater. Mixing valves are available at plumbing
supply or hardware stores, see Figure 2. Follow manufacturer’s
instructions for installation of the valves. Before changing the factory
setting on the thermostat, read the “Temperature Regulation” section
in this manual.
Never allow small children to use a hot water tap, or to draw their own
bath water. Never leave a child or handicapped person unattended
in a bathtub or shower.
The water heater should be located in an area where the general
public does not have access. If a suitable area is not available,
a cover should be installed over the thermostat to prevent
tampering. The water temperature setting was factory set at
the lowest temperature; THIS WATER HEATER IS EQUIPPED
WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER
TEMPERATURE. HOT WATER TEMPERATURES REQUIRED
FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN
CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL
INJURY AND/OR DEATH. THE TEMPERATURE AT WHICH
INJURY OCCURS VARIES WITH THE PERSON’S AGE AND THE
TIME OF THE EXPOSURE. THE SLOWER RESPONSE TIME
OF CHILDREN, AGED OR DISABLED PERSONS INCREASES
THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN
TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN BATH
WATER. NEVER LEAVE A CHILD OR DISABLED PERSON
UNATTENDED IN A BATHTUB OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA
WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO
SET TEMPERATURES.
SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C
WILL REDUCE THE RISK OF SCALDS. Some states require
settings at specific lower temperatures.
The water temperature is controlled using the Temperature
Control on the Display at the front of the unit (See Figure 1).
This control utilizes a temperature probe to determine the tank
temperature. The primary temperature probe is located at the
top of the tank.
The temperature may be adjusted from 90°F/32°C to 160°F/71°C.
The thermostat was adjusted to 120°F/49°C before the heater
was shipped from the factory. It is recommended that lower water
temperature be used to avoid the risk of scalding. It is further
recommended, in all cases, that the water temperature be set
for the lowest temperature which satisfies your hot water needs.
This will also provide the most energy efficient operation of the
water heater and minimize scale formation.
Valves for reducing the point-of-use temperature by mixing cold
and hot water are available, see Figure 2. Also available are
inexpensive devices that attach to faucets to limit hot water
temperatures. Contact a licensed plumber or the local plumbing
authority.
Table 3 shows the approximate time-to-burn relationship for normal
adult skin. Short repeated heating cycles caused by small hot water
uses can cause temperatures at the point of use to exceed the
thermostat setting by up to 20°F/11°C. If you experience this type
of use, you should consider using lower temperature settings to
reduce scald hazards.
TABLE 3.
Time to Produce
2nd & 3rd Degree
Temperature SettingBurns on Adult Skin
160°F (71°C) About 1/2 Second
150°F (65°C) About 1 1/2 Seconds
140°F (60°C) Less than 5 Seconds
130°F (54°C) More than 30 Seconds
120°F (49°C) More than 5 minutes
HI LIMIT SWITCH (E.C.O.)
The top immersion well of the dual bulb controller also contains
the high
interrupts main burner
approximately 202°F/94°C.
Should the high limit switch activate, the control system will
automatically reset the unit once the water temperature in the
tank falls below 140°F/60°C. If the unit is manually shut down
and restarted, as long as the temperature in the tank is lower
than 160°F/71°C, the unit will reset and initiate operation.
If you experience higher than usual water temperature along with
frequent automatic resetting of the system, this is evidence of high
limit switch operation. The following are possible reasons for high
limit switch operation.
• A malfunction in the thermostatic controls would allow the gas
valve to remain open causing water temperature to exceed the
thermostat setting. The water temperature would continue to
rise until high limit switch operation.
Contact your dealer or servicer if continued high limit switch
operation occurs.
limit (energy cutoff) sensor. The high limit switch
gas flow should water temperature reach
30
USING THE ELECTRONIC CONTROLLER
1. Overview
Interaction with the water heater controller is done through an up, a down, and three operation buttons. These buttons are illustrated to the
right. Operation of the three lower buttons is dened immediately above them on the screen. The [UP] and [DN] buttons are used to navigate
through the menus and make adjustments to the water heater.
While the water heater is operating, the user interface will display the desktop screen (if there are no active fault or alert conditions).
An example of this screen is shown to the right. The temperature on this screen is the Operating Set Point. The Operating Set Point is
the temperature at which the water heater will maintain the water inside the tank. The second line on the screen is a text description
of the Operational State of the water heater (please see Operating States for more details).
The following status icons describe graphically operational details of the heater. The legend of all the status icons is listed below.
31
2. Operating States
In the main desktop screen, there are some specic Operating States that
are indicated on the status line. These are summarized below:
3. Adjusting the Operating Set Point
The Operating Set Point of this water heater determines the regulated
temperature for the water in the tank. This parameter is adjusted in the
Temperature menu. Items in this menu allow you to monitor different
temperature readings in the tank along with adjusting the Operating Set
Point.
ACTION:
From the desktop screen, press Menu.
DISPLAY:
ACTION:
From the Main Menu, press Select to enter the "Temperatures" screen.
DISPLAY:
ACTION:
Press Change then use the UP and DOWN buttons to change the Set
Point.
32
3. Changing the Display Units
The display interface to the heater has the option of selecting between
degrees Fahrenheit and degrees Celsius for temperature displays.
This can be found in the “Display Settings” menu. Also in this menu,
you may adjust how the backlight operates and the contrast of the
LCD screen.
ACTION:
From the Main Menu, press the Down button to highlight "Display
Settings" then press Select.
DISPLAY:
ACTION:
Use the UP and DOWN buttons to highlight the desired setting. Then
press Change. Again, use the UP and DOWN buttons to scroll through
the options for that setting.
DISPLAY:
There are two types of conditions that can occur during operation. These
are Alerts and Faults:
• Alerts: This is a non-safety related condition that the control has detected
that may cause the water heater to operate in a less than optimal condition,
but does not pose a safety concern.
NOTE: When these conditions occur, continued heating cycles will
continue and the heater will attempt to regulate the water in the tank to
the Operating Set Point.
Example of an Alert:
• Faults: This is a safety related condition that has been detected
by the heater.
NOTE: When these conditions occur, the water heater will not
continue any further heating cycles and the water will no longer be
heated until the condition is corrected and, in most cases, power has
been cycled.
Example of a Fault:
ACTION:
Press Update to accept the change or Cancel to reject it.
DISPLAY:
4. Fault and Alert Conditions
This water heater is equipped with electronic controls that have the
ability to monitor almost all aspects of the water heater operation. In
the case that there is an undesirable or unsafe condition that occurs,
the water heater controls will detect this condition and determine the
appropriate action. Part of this is displaying the information on the LCD
in plain text that accurately describes the condition and diagnostics
information that can be used to correct the issue.
Advanced Diagnostics Information
When a fault or alert has been declared, advanced information can be found
in the control. By pressing the Advanced button, detailed information can
be found regarding diagnosing and resolving the problem.
WARNING: Usage of the Advanced information requires ability
equivalent to that of a licensed tradesmen in the eld involved.
5. Access to the Current Fault or Alert
When a fault or alert has been detected by the control, it will automatically
be displayed on the screen and the back light will blink. If you choose to
leave the current fault or alert by pressing the Back key, you can always
return to the fault screen through the menu.
33
ACTION:
To get to the current fault information screen, press Menu.
DISPLAY:
ACTION:
Press the DOWN button to highlight "current Fault" and press Select.
DISPLAY:
6. Viewing the Fault History
The controller for this water heater will store a history of ten of the
last Fault and Alert conditions that occurred. This is stored in the
Fault History. Along with all the information about the fault, including
a estimate time of when the fault occurred, information regarding
the advanced diagnostics for that fault can be accessed at any time.
ACTION:
Press the DOWN button for more information.
DISPLAY:
ACTION:
Press the DOWN key to scroll through the fault history. If you select
a specic fault or alert, you may press the VIEW button to view
details regarding this fault.
DISPLAY:
ACTION:
Press the DOWN button for more information.
DISPLAY:
7. Viewing Information About the Heater
The electronic control for this water heater monitors many different aspects
of the water to ensure safe and optimal operation. Much of the information
monitored is available to view in two areas of the control. The rst is the
"Heater Status" and; the second is "Heater Information." These items can
be selected through the main menu in the same fashion as described
above. In these menus, detailed information about the water heater and
the current status of specic conditions can be found.
34
FOR YOUR INFORMATION
START UP CONDITIONS
SMOKE/ODOR
It is not uncommon to experience a small amount of smoke and
odor during the initial start-up. This is due to burning off of oil
from metal parts, and will disappear in a short while.
THERMAL EXPANSION
Water supply systems may, because of such events as high
line pressure, frequent cut-offs, the effects of water hammer
among others, have installed devices such as pressure
reducing valves, check valves, back flow preventers, etc.
to control these types of problems. When these devices
are not equipped with an internal by pass, and no other
measures are taken, the devices cause the water system
to be closed. As water is heated, it expands (thermal expansion)
and closed systems do not allow for the expansion of
heated water.
The water within the water tank expands as it is heated
and increases the pressure of the water system. If the
relieving point of the water heater’s temperature-pressure
relief valve is reached, the valve will release excess pressure. The
temperature-pressure relief valve is not intended for the constant
relief of thermal expansion. This is an unacceptable condition and
must be corrected. It is recommended that any devices
installed which could create a closed system have a
by-pass a n d/or t h e s ystem h a v e an e x p a n s i o n t a n k
or device to relieve the pressure built by thermal
expansion in the water system. Expansion tanks are
available for ordering through a local plumbing
contractor. Contact the local water heater supplier
or qualified service agency for assistance in controlling these
situations.
STRANGE SOUNDS
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not necessarily
represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner area
during heating and cooling periods and should be considered
normal. See “Condensate” in this section.
OPERATIONAL CONDITIONS
SMELLY WATER
In each water heater there is installed at least one anode rod (see
parts section) for corrosion protection of the tank. Certain water
conditions will cause a reaction between this rod and the water.
The most common complaint associated with the anode rod is one
of a “rotten egg smell” in the hot water. The smell is a result of four
factors which must all be present for the odor to develop:
a. A concentration of sulfate in the supply water.
b. Little or no dissolved oxygen in the water.
c. A sulfate reducing bacteria which has accumulated within the
water heater (this harmless bacteria is nontoxic to humans).
d. An excess of active hydrogen in the tank. This is caused by the
corrosion protective action of the anode.
Smelly water may be eliminated or reduced in some water heater
models by replacing the anode(s) with one of less active material, and
then chlorinating the water heater tank and all water lines. Contact
the local water heater supplier or a qualied service agency for
further information concerning an Anode Replacement Kit and this
chlorination treatment.
If the smelly water persists after the anode replacement and chlorination
treatment, we can only suggest that chlorination or aeration of the
water supply be considered to eliminate the water problem.
Do not remove the anode leaving the tank unprotected. By doing
so, all warranty on the water heater tank is voided.
“AIR” IN HOT WATER FAUCETS
HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally
two weeks or more). Hydrogen gas is extremely ammable and
explosive. To prevent the possibility of injury under these conditions,
we recommend the hot water faucet, located farthest away, be
opened for several minutes before any electrical appliances
which are connected to the hot water system are used (such as a
dishwasher or washing machine). If hydrogen gas is present, there
will probably be an unusual sound similar to air escaping through the
pipe as the hot water faucet is opened. There must be no smoking
or open ame near the faucet at the time it is open.
35
PERIODIC MAINTENANCE
VENTING SYSTEM INSPECTION
At least once a year a visual inspection should be made of the venting
system. You should look for:
1. Obstructions which could cause improper venting. The combustion
and ventilation air ow must not be obstructed.
Soot build-up indicates a problem that requires correction before
further use. Turn “OFF” gas to water heater and leave off until repairs
are made, because failure to correct the cause of the sooting can
result in a re causing death, serious injury, or property damage.
BURNER CLEANING
In the event your burner or burner air openings require cleaning,
turn the on/off switch to the “OFF” position and allow the unit to cool.
Call a qualied service agency to remove and clean the burner and
correct the problem that required the burner to be cleaned.
HOUSEKEEPING
Vacuum around base of water heater for dust, dirt, and lint on a
regular basis.
2. Damage or deterioration which could cause improper venting or
leakage of combustion products.
Be sure the vent piping is properly connected to prevent escape of
dangerous ue gasses which could cause deadly asphyxiation.
Obstructions and deteriorated vent systems may present serious
health risk or asphyxiation.
Chemical vapor corrosion of the ue and vent system may occur
if air for combustion contains certain chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioner
refrigerants, swimming pool chemicals, calcium and sodium chloride,
waxes, bleach and process chemicals are typical compounds which
are potentially corrosive.
If after inspection of the vent system you found sooting or
deterioration, something is wrong. Call the local gas utility to correct
the problem and clean or replace the ue and venting before
resuming operation of the water heater.
BURNER OPERATION AND INSPECTION
Flood damage to a water heater may not be readily visible or
immediately detectable. However, over a period of time a ooded
water heater will create dangerous conditions which can cause
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
Contact a qualified installer or service agency to replace a
ooded water heater. Do not attempt to repair the unit! It must be
replaced!
At least once a year a visual inspection should be made of the
main burner and the hot surface igniter assembly for proper ame
characteristics and ignition sequences. You should also check for
sooting. Soot is not normal and will impair proper combustion. A visual
inspection of the main burner and HSI igniter assembly should also be
done at least once a year.
INSTALLED IN SUITABLE AREA: To insure sufcient ventilation
and combustion air supply, proper clearances from the water heater
must be maintained. See “Facts to Consider About Location” section.
Combustible materials such as clothing, cleaning materials, or
ammable liquids, etc. must not be placed against or adjacent to
the water heater which can cause a re.
ANODE ROD INSPECTION
Each water heater contains at least one anode rod, which will
slowly deplete (due to electrolysis) prolonging the life of the water
heater by protecting the glass-lined tank from corrosion. Adverse
water quality, hotter water temperatures, high hot water usage,
and water softening methods can increase the rate of anode rod
depletion. Once the anode rod is depleted, the tank will start to
corrode, eventually developing a leak.
36
Certain water conditions will cause a reaction between the anode
rod and the water. The most common complaint associated with
the anode rod is a “rotten egg smell” produced from the presence
of hydrogen sulde gas dissolved in the water. IMPORTANT: Do
not remove this rod permanently as it will void any warranties.
The parts list includes a special anode rod that can be ordered if
water odor or discoloration occurs. NOTE: This rod may reduce
but not eliminate water odor problems. The water supply system
may require special ltration equipment from a water conditioning
company to successfully eliminate all water odor problems.
Articially softened water is exceedingly corrosive because the
process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water
heater tank.
The anode rod should be removed from the water heater tank every
3 years for inspection. NOTE: articially softened water requires
the anode rod to be inspected annually.
The following are typical (but not all) signs of a depleted anode
rod:
* The majority of the rods diameter is less than 3/8”.
* Signicant sections of the support wire (approx. 1/3 or more of
the anode rod’s length) are visible.
If the anode rod show signs of either or both it should be replaced.
NOTE: Whether re-installing or replacing the anode rod, check
for any leaks and immediately correct if found.
In replacing the anode:
FIGURE 35.
When checking the temperature-pressure relief valve operation,
make sure that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) that the
water discharge will not cause any property damage, as the water
may be extremely hot, see Figure 28.
If after manually operating the valve, it fails to completely reset and
continues to release water, immediately close the cold water inlet
to the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.
If the temperature-pressure relief valve on the appliance weeps or
discharges periodically, this may be due to thermal expansion. You
may have a check valve installed in the water line or a water meter
with a check valve. Consult your local water supplier or a qualied
service agency for further information. Do not plug the temperaturepressure relief valve.
DRAINING and FLUSHING
1. Turn off gas supply to the water heater.
2. Shut off the water supply and open a nearby hot water faucet to
depressurize the water tank.
3. Drain approximately 5 gallons of water from tank (Refer to “Draining
and Flushing” for proper procedures). Close drain valve.
4. Remove old anode rod.
5. Use Teon® tape or approved pipe sealant on threads and install
new anode rod.
6. Turn on water supply and open nearby hot water faucet to purge
air from water system. Check for any leaks and immediately
correct any if found.
Restart the water heater as directed under “Operating Your Water
Heater.” See the Repair Parts Illustration for anode rod location.
FIGURE A. ANODE ROD DEPLETION
TEMPERATURE-PRESSURE
RELIEF VALVE OPERATION
It is recommended that the tank be drained and ushed every 6
months to remove sediment which may build up during operation.
The water heater should be drained if being shut down during
freezing temperatures. To drain the tank, perform the following
steps:
1. Set the power switch to the “OFF” position.
2. Open a nearby hot water faucet until the water is no longer
hot.
3. Close the cold water inlet valve.
4. Connect a hose to the drain valve and terminate to an adequate
drain or external to the building.
5. OPEN the water heater drain valve and allow all of the water
to drain from the tank. Flush the tank with water as needed to
remove sediment.
6. CLOSE the drain valve, rell the tank, and restart the heater as
directed in this manual.
If the water heater is going to be shut down for an extended period,
the drain valve should be left open.
IMPORTANT: Condensation may occur when relling the tank and
should not be confused with a tank leak.
37
SERVICE
If a condition persists or you are uncertain about the operation of
the water heater contact a qualied service agency.
If you are not thoroughly familiar with gas codes, your water heater,
and safety practices, contact your gas supplier or qualied installer
to check the water heater.
Use this guide to check a “Leaking” water heater. Many suspected
“Leakers” are not leaking tanks. Often the source of the water can
be found and corrected.
LEAKAGE CHECKPOINTS
Read this manual rst. Then before checking the water heater make
sure the gas supply has been turned “OFF”, and never turn the gas
“ON” before the tank is completely full of water.
Never use this water heater unless it is completely lled with water.
To prevent damage to the tank, the tank must be lled with water.
Water must ow from the hot water faucet before turning “ON” gas
to the water heater.
A *Condensation may be seen on pipes in humid weather or pipe
connections may be leaking.
B. *The anode rod tting may be leaking.
C. Small amounts of water from temperature-pressure relief valve
may be due to thermal expansion or high water pressure in your
area.
D. *The temperature-pressure relief valve may be leaking at the
tank tting.
E. Water from a drain valve may be due to the valve being slightly
opened.
F. *The drain valve may be leaking at the tank tting.
G. Combustion products contain water vapor which can condense
on the cooler surfaces of the tank. Droplets form and drip onto
the burner or run on the oor. This is common at the time of
start-up after installation and when incoming water is cold.
H. Water in the water heater bottom or on the oor may be from
condensation, loose connections, or the relief valve. DO NOT
replace the water heater until a full inspection of all possible water
sources is made and necessary corrective steps taken.
Leakage from other appliances, water lines, or ground seepage
should also be checked.
* To check where threaded portion enters tank, insert cotton
swab between jacket opening and tting. If cotton is wet, follow
“Draining” instructions in the “Periodic Maintenance” section and
then remove tting. Put pipe dope or teon tape on the threads
and replace. Then follow “Filling the Water Heater” instructions
in the “Installing the New Water Heater” section.
38
TROUBLESHOOTING GUIDELINES
These guidelines should be utilized by a qualied service agent.
PROBLEMS
1.) Blower will not run.
a. “ON/OFF” control switch turned off.Turn switch to the “ON” position.
b. Blower unplugged.Plug blower back into 115 VAC outlet.
c. No power at outlet.Repair service to outlet.
d. Thermostat defective.Replace thermostat.
e. Control harness defective.Replace control harness.
Reduce the water temperature below 140°F.
Turn the power switch to the off position.
f. High limit control circuit open.
NOT ENOUGH HOT WATER
g. Blower motor defective.Replace blower assembly.
2.) Thermostat problems
a. Thermostat set too low.Adjust temperature control higher.
b. Thermostat or ECO defectiveReplace thermostat.
3.) Others
a. Heater undersized..Reduce hot water use.
b. Low gas pressureContact dealer.
c. Incoming water is usually cold.Allow more time for heater to reheat.
d. Leaking hot water pipes of fixtures. Have plumber check and repair leaks.
e. Heater not lit or thermostat not on.Refer to LIGHTING INSTRUCTIONS.
VENT PIPE TOO HOT (ABOVE 170°F [77°C]) Wrong burner orice.Turn off heater and gas, clean burner head.
Dirt in burner ports.Turn off heater and gas, clean burner head.
YELLOW FLAME
CONDENSATIONWater on the oor under heater.See CONDENSATION section.
WATER LEAKS
LEAKING T & P
HOT WATER ODORS
(refer to cathodic protection)
HOT WATER TOO HOTThermostat set too high.
WATER HEATER SOUNDSCondensation dripping on burner.Refer to CONDENSATION above.
SIZZLING - RUMBLINGSediment at bottom of heater tank.
SOOTINGImproper combustion.Refer to Air Requirements.
BURNER WILL NOT STAY LIT-GOES OUT
4-5 SECONDS
VENT GAS ODORS
Combustion air path restricted.
Impr operly se aled, hot or co ld supply
connections, relief valve, drain valve or
thermostat threads.
Leakage from other appliances or water lines.
Condensation of ue products.Refer to CONDENSATION section.
Thermal expansion in closed water system.
Improperly sealed valve.
High sulfate or mineral content in water
supply.
Bacteria in water supply.Chlorinate water supply.
Outlet polarity is reversed.Test polarity and correct.
Wait 10 seconds. Turn the power switch to
the on position. Reduce the
point to minimize likelihood of reoccurrence.
this does not solve the problem, replace the
thermostat.
Check exhaust venting and air openings
in bottom base pan for obstructions or
blockage.
Check for leaks. See Figure 1.
Inspect other appliances near water heater.
Install thermal expansion tank (Do not plug
T&P valve).
Check relief valve for proper operation (Do
not plug T&P valve).
Drain and ush heater thoroughly then rell.
Refer to TEMPERATURE REGULATION
section.
Cle a n se d imen t fro m tan k . Ref e r to
DRAINING.
Cont act a quali fied servic e age ncy to
determine cause.
Shut off water heater immediately and contact a
qualied service agency to determine cause.
temperature set
If
39
NOTES
40
Limited Warranty
THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY. If
the glass lined tank in this water heater shall prove upon examination by (the
warrantor) to have leaked during the warranty period in normal residential
use, due to natural corrosion from potable water therein, the warrantor will
furnish the ORIGINAL OWNER a replacement water heater of equivalent
size and current model, or a replacement part for any component part
which fails in normal use, in accordance with the warranty terms and
conditions specied below. THE WATER HEATER REPLACEMENT
MODEL OR PART WILL BE WARRANTED FOR ONLY THE UNEXPIRED
PORTION OF THE ORIGINAL WARRANTY. The warranty period will be
determined by the original installation date of the water heater. PROOF-
OF-PURCHASE AND PROOF-OF-INSTALLATION ARE NECESSARY
TO VALIDATE THIS WARRANTY. This warranty is not transferable.
b. Shipping and delivery charges for forwarding the new water heater or
replacement part from the nearest distributor and returning the claimed
defective heater or part to such distributor except in the state of
California where such charges are the manufacturer’s responsibility.
c. All cost necessary or incidental for handling and administrative
charges, and for any materials and/or permits required for installation
of the replacement heater or part.
LIMITATION ON IMPLIED WARRANTIES
Implied warranties, including any warranty of merchantability imposed on
the sale of this heater under state law are limited to one year duration for the
heater or any of its parts. Some states do not allow limitations on how long
an implied warranty lasts, so the above limitations may not apply to you.
Product LineTANK
WARRANTY PERIOD
1
PARTS
2
6G50100NVC026 YEARS6 YEARS
6G50100PVC026 YEARS6 YEARS
When the water heater has been used for other than single family
residential application: 1. The Tank warranty shall be reduced to 3 years on
10 year models and 1 year on 6 and 8 year models. 2. The parts warranty
shall be reduced to 1 year for all models. Returned parts which meet any
of the following conditions are not covered by this warranty: 1) improper
installation or removal; 2) damaged by other than normal wear; 3) replaced
for cosmetic purposes; or 4) returned with defaced date codes.
CONDITIONS AND EXCEPTIONS
This warranty shall apply only when the water heater is installed and
operated in accordance with: 1) all local re codes and plumbing codes,
ordinances and regulations; 2) the printed instructions provided with it;
3) good industry practices; and 4) proper safety practices such as but
not limited to a properly sized drain pan if installed in an area where
leakage from connections of the tank would result in damage to the area
adjacent to the heater. In addition, a new temperature and pressure relief
valve, certied by the Canadian Standards Association must have been
properly installed and piped to the nearest drain.
This warranty shall apply only when the heater is:
• owned by the original purchaser;
• used at temperatures not exceeding the maximum calibrated setting of
its thermostat;
• not subjected to excessive water pressure uctuations and not subject
to an operating pressure greater than 150 P.S.I.;
• lled with potable water, free to circulate at all times and with the tank
free of damaging water sediment or scale deposits;
• used in a non-corrosive and non-contaminated atmosphere;
• used with factory approved anode(s) installed;
• in its original installation location;
• in the United States and its territories or possessions or Canada;
• sized in accordance with proper sizing techniques for residential water
heaters;
• bearing a rating plate which has not been altered, defaced or removed
except as required by the warrantor;
• used in an open system or in a closed system with a properly sized and
installed thermal expansion tank;
• red at the factory rated input using the fuel stated in the face of the
rating plate;
• operated with the inner and outer combustion chamber doors in place;
• maintained in accordance with the instructions printed in the manual
included with the heater.
Any accident to the water heater or any part thereof (including freezing,
re, oods, or lightning), any misuse, abuse or alteration of it, any
operation of it in a modied form, or any attempt to repair tank leaks or
parts, will void this warranty.
SERVICE AND LABOR RESPONSIBILITY
UNDER THIS LIMITED WARRANTY, THE WARRANTOR WILL PROVIDE
ONLY A REPLACEMENT WATER HEATER OR PART THEREOF. THE
OWNER IS RESPONSIBLE FOR ALL OTHER COSTS. Such costs may
include but are not limited to:
a. Labor charges for service, removal, or reinstallation of the water heater
or part thereof.
CLAIM PROCEDURE
Any claim under this warranty should be initiated with the dealer who sold
the heater, or with any other dealer handling the warrantor’s products.
The warrantor will only honor replacement with identical or similar water heater
or parts thereof which are manufactured or distributed by the warrantor.
Dealer replacements are made subject to in-warranty validation by warrantor.
PROOF-OF-PURCHASE AND PROOF-OF-INSTALLATION DATES
ARE REQUIRED TO SUPPORT WARRANTY FOR CLAIM FROM
ORIGINAL OWNER. THIS FORM DOES NOT CONSTITUTE PROOFOF-PURCHASE OR PROOF-OF-INSTALLATION.
DISCLAIMERS
NO EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF
OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR
REPLACEMENT OF THE HEATER OR PARTS. THE WARRANTOR
SHALL NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF
USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO
PERSONAL PROPERTY, OR OTHER CONSEQUENTIAL DAMAGE.
THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS
WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS
OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER
ARISING IN CONTRACT OR IN TORT.
Some states do not allow the limitation or exclusion of incidental or
consequential damages, so the above limitation or exclusion may not
apply to you.
This warranty gives you specic legal rights, and you may also have other
rights which vary from state to state. Should governmental regulations
or industry standards prohibit the Manufacturer from furnishing a
comparable model replacement under this warranty, the Owner will be
furnished with the closest comparable water heater meeting the current
governmental regulations and industry standards. A supplementary
fee may be assessed to cover the additional cost associated with the
changes made to meet applicable regulations and standards.
Fill out and keep with water heater.
IMPORTANT INFORMATION
Model Number ________________________________________
Serial Number ________________________________________
Installation Information:
Date Installed_________________________________________
Company’s Name _____________________________________
Street or P.O. Box _____________________________________
City, State, and Zip Code ________________________________
Phone Number ____________ Plumber’s Name _____________
41
GSW Water Heating
599 Hill Street West
Fergus, ON Canada N1M 2X1
Should you have any questions please
Email us at techsupport@gsw-wh.com or
Visit our websites: www.gsw-wh.com or
www.johnwoodwaterheaters.com or
Call our Technical Support line at
1-888-GSW-TECH (479-8324)
GSW Water Heating is a division of A.O.Smith Enterprises Ltd.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.