Johnson & Starley WARMCAIR C36U, WARMCAIR C36D, WARMCAIR C26U, WARMCAIR C26D, WARMCAIR C16D Installation, Commissioning & Servicing Instructions

...
INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS
WARMCAIR C36U
Condensing Air Heater
High Efciency Upow Condensing Air Heater
WarmCair C36U - G.C. No. 42-451-27
Publication No. ZZ 1414-4
December 2016
www.johnsonandstarley.co.uk
2
www.johnsonandstarley.co.uk
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE
STARTING INSTALLATION. LEAVE THESE INSTRUCTION WITH
THE USER OR AT THE GAS METER AFTER INSTALLATION
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are
provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with
the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building
Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of
Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
In the interest of continuous development Johnson and Starley reserve the right to change specification without prior notice.
Johnson and Starley prides itself on it’s ability to supply spare parts quickly and efficiently.
CONTENTS
The Benchmark Scheme 2
1 Features 3
2 General Description 3
3 Building Standards & Regulations 4
4 Safety &Gas Information 5
General Safety Information Gas Categories Gas Supply
5 Technical Data 5
6 Heater Positioning 6
7 Heater Compartment Clearances 6
8 Duct System 7
Return Air Warm Air Delivered
9 Flue Instructions 8
Flue Configuration Diagram of Terminal Position Types of Flue Systems Flue Terminal Positions Plume Terminal Outlets Flue Requirements & General Information Conventional 80/125mm Flue Accessories Part No.s Extended Horizontal Flue System Optional Roof Outlets Flat Roof & Pitched Roof
11 Condensate Pump & Drain Tube 13
Condensate Pump Technical Data Condensate Tube Routing Options
11 Gas 14
12 Electrical 14
Mains Supply Thermista-stat & It’s Location
13 Fitting Instructions 15
14 Commissioning 15
System Balancing Lighting the Main Burner Gas Rate Check
15 Handing Over 17
16 Servicing & Maintenance 18
Servicing Schedule Servicing Sequence Component Servicing Checklist Gaining Access for Servicing Main Burner Assembly Ignition & Flame Detection Electrode Heat Exchanger/Combustion Chamber Combustion Air Fan Flue Collection Box & Heat Exchanger Air Circulations Fan Condensate Drain Pipes Condensate Pump
17 Parts Replacements 22
Control Panel Air Circulation Fan Return Air Temperature Sensor Flue Temperature Sensor High Limit Temperature Sensor Air Pressure Switch Condensate Drain Pump Main Ignition/Control PCB Gas Valve & Venturi Assembly Burner Assembly Ignition Electrode Flame Detection Electrode Combustion Air Fan
18 Control Panel Modes 25
19 Fault Code & Blocking Code Table 26
20 Fault Finding Flowcharts 28
21 Defect Diagnosis for the Circulation Air Fan 29
22 Functional Wiring Diagrams 30
23 Dimensions 32
24 List of Spares 33
25 Important Information & Ancillaries 36
26 Code of Practice 37
27 Benchmark Checklist and Service Record 38
3
Sales/Spares & Replacement Help Line 01604 762881
1. FEATURES
Appliance Classification:
The WarmCair C36U has been tested
and CE certified by B.S.I Ltd for use with NATURAL gas G20.
FEATURES
1. 60/100mm to 80/125mm Adapter
2. 60/100mm Flue Turret
3. Combustion Measuring Point
4. Time Control
5. Condensing Pump Drain Tube
6. Inspection Glass
7. Sliding Flue Connector
8. Flue Sensor
9. Condense Outlet
10. Condense Pipe
11. Condensate Trap
12. Air Pressure Switch
13. Condensate Pump
14. Return Air Filter
15. Air Circulation Fan 16 PCB Control Wiring Panel
17. Return Air Sensor
18. Flue Collector Box
19. Combustion Air fan Assembly
20. High Limit Temperature Sensor
21. Gas Cock
22. ESYS
23. Burner Assembly
24. Gas Valve
25. Ignition & Detection Electrodes
26. MMI Control Panel
27. Duct Temperature Sensor
(behind control panel)
2. GENERAL DESCRIPTION
2.1 The WarmCair C36U is a highly efficient condensing gas fired upflow forced convection air heater. Significant reductions in Low Carbon and NOx emissions are achieved.
It has been designed to provide the user with on demand Warm Air Central Heating. Using sophisticated
controls enabling it to provide the precise amount of heat output to match demand. It is room sealed, with a stainless steel heat exchanger, using a vertical or horizontal Concentric Flue System.
The WarmCair C36U air heater is ideally suited for new built dwellings and the replacement of existing non-
condensing air heaters.
2.2 The air heater output modulates 31.68kW (114.05MJ/h, 108,092 Btu/h) down to 9.68kW (34.85MJ/h, 33,028Btu/h) “Summer Air Circulation” of unheated air is available by manual selection (see the user’s instructions).
FIGURE 1. C36U FEATURES
7
9
15
16
17
20
21
22
18
19
23
25
26
27
14
24
4
6
1
2
3
8
10
5
12
11
13
4
www.johnsonandstarley.co.uk
GAS LEAKS
DO NOT OPERATE ANY ELECTRICAL SWITCHES, OR USE A
NAKED FLAME TURN OFF THE GAS SUPPLY. VENTILATE THE
AREA BY OPENING DOORS AND WINDOWS.
CALL THE NATIONAL GAS EMERGENCY SERVICE ON
0800 111999
3. BUILDING STANDARDS & REGULATIONS
STATUTE LAW DEFINES THAT ALL GAS APPLIANCES MUST BE INSTALLED BY
COMPETENT PERSONS, i.e. GAS SAFE REGISTERED INSTALLERS.
GAS SAFE MEMBERSHIP ENQUIRIES TEL: 0800 408 5500 IN ACCORDANCE WITH THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS (CURRENT EDITION).
FAILURE TO COMPLY WITH THESE REGULATIONS MAY LEAD TO PROSECUTION.
3.1 INSTALLATION REGULATIONS
Gas Safety (Installation and Use) Regulations (as amended)
Model and Local Authority Byelaws
Health & Safety Document No. 635.
The Electricity at Work Regulations
Institute of Electrical Engineers (I.E.E) Wiring Regulations
British System Design Manual “Gas Fired Warm Air Heating”
EN Regulations No. 1196 Supplementary Instructions - Condensing Air Heaters
3.2 BUILDING STANDARDS AND REGULATIONS
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
Building Standards (Scotland) (Consolidation) Regulations
Building Regulation (Northern Ireland)
Building Regulations Part L
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440:1 Flues (for gas appliances of rated input not exceeding 70 kW).
BS 5440:2 Ventilation (for gas appliances of rated input not exceeding 70 kW).
BS 5864 Installation of Gas Fired Ducted Air Heaters
IMPORTANT: This appliance is CE certificated for safety and performance. It is important that no modifications are
made to this appliance, unless fully approved in writing by Johnson & Starley Ltd. If in doubt please ring Johnson & Starley Ltd on Telephone 01604 762881.
5
Sales/Spares & Replacement Help Line 01604 762881
4. SAFETY & GAS INFORMATION
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE COMMENCING WITH THE INSTALLATION
4.1 GENERAL SAFETY INFORMATION
4.1.1 Ensure the mains supply voltage, frequency, number of phases and power rating comply with details on the rating label.
4.1.2 All wiring must be in accordance with the appropriate standards. The equipment must be supplied with a double pole isolator switch.
4.1.3 Ensure safety regulations and practices are adhered to when installing and using this equipment.
4.1.4 The weight of this appliance exceeds that recommended for a one-man lift. It will therefore be necessary to gain assistance at times during the installation procedure.
4.1.5 It should be noted that this appliance may contain sharp edges. Care MUST be taken when handling the appliance to prevent injury.
4.1.6 Once the appliance has been fired beware that certain parts will be hot to the touch.
4.1.7 Do not install flues during rain, high winds or in severe weather conditions.
4.2 GAS INFORMATION
4.2.1 Gas Categories
a. The appliance is certified as a CAT I 2H (20) appliance.
4.2.2 Gas Supply
a. The gas installation must be completed in accordance with the relevant standards (BS 6891). b. The supply must be capable of providing a steady inlet working pressure to the appliance of
20 mbar at a rate of 1.94m³/h or 52.64ft²/h (Calculated with a Gas C of 38.7MJ/m³)
c. The installation must be tested for gas tightness using suitable methods. The Pipework should
also be purged of air in accordance with the IG Publication Standard.
5. TECHNICAL DATA
TABLE 1. C36U TECHNICAL DATA
C36U
WEIGHT
96kg
GAS
G20
GAS SUPPLY PRESSURE
20mbar
GAS CATEGORY
I 2 H
COUNTRIES OF INSTALLATION
GB & IE
ELECTRICAL SUPPLY
250v ~ 50Hz fused 5A 530 watts
MAXIMUM MINIMUM
KW MJ/h Btu/h KW MJ/h Btu/h
INPUT (GROSS)
36 129.6 122,832 11 39.6 37,532
OUTPUT
31.86 114.05 108,092 9.68 34.85 33,028
GAS RATE CV 1037Btu/FT³
3.35m³/h (118.45ft³/h) 1.025m³/h (36.2ft³/h)
BURNER % CO²
9 ± 1 9 ± 1
6
www.johnsonandstarley.co.uk
6. HEATER POSITIONING
6.1 This heater is not suitable for external installation unless it is protected from the elements by a suitable enclosure. The enclosure must provide the clearance for installation, servicing and maintenance as well as the correct level of ventilation. The selected position should allow for a suitable flue system to be installed.
6.2 When installed in a timber frame building guidance should be taken from the Gas Industry Publication IGE/ UP-7 (Guide for Gas Installations in Timber Frame Housing).
6.3 BS 6798 gives details of the essential features for a compartment or cupboard where a gas appliance is to be installed. An existing cupboard may require modification.
6.4 If the heater is installed in a room containing a bath or shower it is important to locate the electrical switch in a position where it cannot be touched by anyone using the bath or shower. The current IEE Wiring Regulations (BS 7671) for England and electrical provision of the Building Regulations for Scotland gives details.
6.5 Room ventilation for the heater is not necessary as the heater draws its combustion air from the outside of the building, cupboard or compartment ventilation is not necessary providing that the minimum clearances are maintained. However, reference should be made to BS 5440 Pt. 2.
IMPORTANT: This appliance must be completely level. It MUST NOT lean in any direction. Otherwise this
will cause problems with the condense draining.
7. HEATER COMPARTMENT CLEARANCES (see BS 5864)
7.1 IMPORTANT - If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that installation is carried out such that the rear of the heater is aligned with the rear of the base duct, so that any overhang or blanking off will be at the front. In any event, blanking plates must be mechanically secured and all joints sealed.
7.2 When the heater is fitted into a compartment, a minimum clearance from the compartment walls of 3mm (
1
/8”) at the sides, rear and front must be left. Where clearances are less than 75mm, internal surface must be lined with non-combustible material and the compartment must be of a fixed rigid structure. However, there is no requirement for the use of non-combustible material at the front of the unit. Consideration should also be given to the space required for the removal and replacement of the filter tray and the entry of the gas and electrical supplies. If gas connections are made from a side entry, a minimum clearance of 75mm (3”) is required at that side.
7.3 For service access, a minimum of 450mm (18”) is required at the front of the heater. Space must also be allowed, in a compartment installation, to permit the removal of the heater.
7.4 In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of BS 5864 and must be completely separated by either a non-combustible partition or a perforated metal partition with the perforations not exceeding 13mm (½”). The secondary flue must be a tight fit where it passes through the partition and must be suitably protected (see BS 5440: Part 1).
7.5 In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided that in addition all internal surfaces (including the base) are non-combustible or lined with non-combustible material. This requirement is applicable only to dwellings of more than two storeys.
7.6 In free-standing installations, (Refer to instructions packed with top closure kit), only one or two walls will be in close proximity to the air heater; these must be non-combustible.
7.7 Where the air heater is to be installed onto a combustible surface and under-floor ducting used, a suitable base tray MUST be used in order to provide insulation.
NB where a base plenum is used no base tray is required!
7.8 Although two permanent ventilation openings are not required, consideration should be given to the amount of heat emitted by any ductwork present in the compartment, otherwise the compartment temperature could increase and will affect the safe operation of the appliance and its controls.
7
Sales/Spares & Replacement Help Line 01604 762881
8. DUCT SYSTEM
(See British Design Manual - Gas fired Warm Air Heating)
8.2 RETURN AIR
8.1.1 Room-sealed appliances may be installed without return air ducting, provided that the path between the return air grille and the appliance return air inlet is protected in such a manner that the required air-flow will be maintained at all times. The return air grille MUST have a free area of not less than 3200cm
2
(469in2). It is recommended that the return air duct not be routed directly
from the main living area, but from a convenient central area serving the remainder of the dwelling.
8.1.2 The return air system should be constructed of fire-resistant material. The flue shall not be run through an area serving as a return air plenum. It is extremely important that the correct size of return air grilles and ducting is used. The return air duct area should not be less than 1600cm² (248in²). If flexible duct is used the duct diameter should not be less than 450mm (18”) diameter.
8.1.3 An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m
2
/kW (1in2/250Btu/h) of heat supplied to the room. The only
exceptions are kitchens, bathrooms and WC.’s.
8.1.4 The return air duct should allow for ease of removal, for access to the flue.
8.1.5 All duct work in the room or internal space in which the heater is installed shall be mechanically secured and sealed with ducting tape.
8.1.6 This unit is also designed to use a side return air kit. For further details telephone Johnson & Starley Ltd.
8.2 WARM DELIVERED AIR
8.2.1 All duct work, including riser ducts, should be fully insulated with 50mm (2”) fibre-glass or similar. If short extended duct runs are taken below floor level these should be similarly insulated and in addition wrapped with a sound vapour proof barrier. They must also be protected from crushing.
8.2.2 The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to suit the needs of specific heating requirements and building layout. The type of duct system (e.g. radial/extended plenum stepped) should be installed using the least number of fittings to minimise airflow resistance. The base duct, which equalises the air pressure to supply ducts, must be constructed to support the weight of the heater, which must be sealed using self­adhesive foam strip, ducting tape or sealing compound. All ducting and blanking plates must be mechanically secured and sealed.
8
www.johnsonandstarley.co.uk
VERTICAL FLUE
FIGURE 2.
EXTENDED HORIZONTAL REAR FLUE
FIGURE 3. VERTICAL FLUE
FIGURE 4. HORIZONTAL TERMINAL DIMENSIONS & POSITION
CORRECT POSITION OF HORIZONTAL TERMINAL END
100mm
19mm
EXTENDED HORIZONTAL REAR FLUE
Can be fitted to the left or the right.
Vertical Appliance Adaptor Horizontal Terminal 90˚ Elbow Required Extension Length
Vertical Appliance Adaptor Required Extension Lengths Vertical Terminal
EXTENDED HORIZONTAL REAR FLUE
9. FLUE INSTRUCTIONS
9.1 The WarmCair C36U Condensing Air Heater is certified as a warm air heater with corresponding flue systems according to EU Directive 2009/142/EC on gas-fired devices. These installation instructions are covered by this certification and are referred to in the design approval test certificate.
9.2 The installation of the warm air heater and flue system must be in accordance with the Gas Safety (Installation and Use) Regulations 1998 and the Building Regulations. If no specific instructions are given, reference should be made to the relevant codes of practice.
THESE RELEVANT STANDARDS SHOULD BE FOLLOWED
BS 5440:1 Flues and ventilation for gas appliances of rated heating input not exceeding 70kW (net) : Flues
BS 5440:2 Flues and ventilation for gas appliances of rated heating input not exceeding 70kW (net) : Air Supply Ensure all legislation, regulations and directives mentioned are observed.
9.3 The air/flue duct operates at very low temperatures therefore no clearance is necessary between the air duct and the adjacent services.
9.4 Ensure while installation work is being carried out that no debris such as swarf, filings or fragments of mortar are allowed to remain in the air/flue duct.
10.5 FLUE CONFIGURATIONS
NOTE: Vertical Appliance adaptor is fitted as part of the air heater.
9
Sales/Spares & Replacement Help Line 01604 762881
FIGURE 5. TERMINAL POSITIONS
TABLE 2. TERMINAL DIMENSIONS
TERMINAL POSITION MINIMUM DISTANCE
A Directly below an opening, air brick, opening window etc 300mm
B Above an opening, air brick, opening window, etc. 300mm
C Horizontally to an opening, air brick, opening window etc. 300mm
D Below gutters, soil pipes or drain pipes. 75mm
E Below eaves. 200mm
F Below balconies. 200mm
G From a vertical drain pipe or soil pipe. 150mm
H From an internal or external corner. Greater than 450mm protrusion. 300mm
I Above ground, roof or balcony level. 300mm
J From a surface facing the terminal. 600mm
K From a terminal facing the terminal. 1,200mm
M Vertically from a terminal on the same wall. 1,500mm
N Horizontally from a terminal on the same wall. 300mm
Q Above intersection with roof. 530mm
P From a vertical structure on the roof 300mm
R From the terminal to the boundary 300mm
10
www.johnsonandstarley.co.uk
9.5 TYPE OF FLUE SYSTEMS
Two types of flue systems are available for the C36U. i) The standard concentric flue system 80/125mm (125mm diameter) ii) A Flexible flue kit (FFK) 80/125mm (125mm diameter) For further information contact the sales
office at Johnson & Starley Ltd. Telephone 01604 762881
9.6 FLUE TERMINAL POSITIONS
9.6.1 The following information provides the general requirements for siting flue terminals. As part of
the recommendation given in BS 1550 Part 1. For IE recommendations, see the current issue of I.S. 813 “Domestic Gas Installations.” Also publication a “Guide for Gas Installations in Timber Framed Housing DM2” or consult your local gas region, They MUST be consulted when installing the appliance into a timber-framed building.
NOTE: Due to the nature of the warm air heater, water vapour will discharge from the flue. This should be
taken into account when siting the flue
9.6.2 Both the extended horizontal and vertical terminals must be positioned on the outside of the
building and the free passage of air must be available at all times. It is not recommended to position the terminal close to projections especially under a balcony or near to a drainpipe. See Figure 5.
9.6.3 Ensure that combustion products cannot enter the building where the heater is installed or near to
any other building where doors or windows may be open.
9.6.4 Recommended terminal positions for both extended horizontal and vertical flues are shown and
flue components and installation options are also detailed.
9.6.5 The flue MUST NOT be installed under a car port.
9.7 PLUME TERMINAL OUTLETS
9.7.1 A flue duct outlet of an appliance should be at least 600mm from the boundary line when facing it
and at least 300mm from the boundary line when running parallel to it. See Figure 6.
NOTE: When the flow of products is at an angle to the boundary, the 600mm dimension may be measured
in the direction of the flow, as long as the terminal is not less than 300mm from the boundary.
9.7.2 It is recommended the terminals are not sited within 2m of an opening in an adjacent building
or within 2m of the boundary facing the terminal if the plume is likely to cause a nuisance to a neighbour, e.g discharging over a walkway or patio.
9.8 FLUE REQUIREMENTS & GENERAL INFORMATION
9.8.1 Extended horizontal and vertical concentric flues (80/125mm diameter) with balanced terminals may be
installed on the
WarmCair C36U warm air heater.
9.8.2 If an extended horizontal flue is being used it must have a continuous fall back towards the appliance of
3° (52mm) per meter. This ensures that condensate runs back into the appliance from the flue system for safe discharge via the condensate waste pipe. Reference should be made to Table 3 for relevant part numbers.
9.8.3 The maximum length of flue permissible is 10
meters including terminal
9.8.
4 The minimum vertical flue length is 1.25m from
the top of the appliance case to the top of the terminal.
9.8.5 Longer flues may be fitted, however the input
of the appliance will be reduced accordingly.
9.8.6 Elbows may be fitted within the flue system
with a corresponding reduction in overall flue.
9.8..7 Guidelines for the maximum flue length are as
follows.
FIGURE 6. PLUME TERMINAL OUTLET DIMENSIONS
HORIZONTAL FLUE VERTICAL FLUE
UNIT
TURRET
90° ELBOW
STRAIGHT
1m FLUE
90° ELBOW
STRAIGHT
1m FLUE
1 - 12 - 12
1 1 8 1 8
1 2 6 2 6
1 3 4 3 4
When using 45° elbows: 2 x 45° elbow = 1 x 90° elbow
TABLE 3
11
Sales/Spares & Replacement Help Line 01604 762881
TABLE 4. 80/125mm FLUE COMPONENTS
9.9 CONVENTIONAL 80/125mm FLUE ACCESSORY PARTS No’s
DESCRIPTION COLOUR QTY APPLICATION PART No.
1
800mm Horizontal Terminal White 1 Horizontal 1000-0023830
2
Vertical Adaptor 60mm to 80mm White 1 Vertical 1000-0023810
3
45° Elbow White 1 Horizontal & Vertical 1000-0020110
4
90° Elbow White 1 Horizontal & Vertical 1000-0020100
5
500mm Straight Extension White 1 Horizontal & Vertical 1000-0025590
6
1000mm Straight Extension White 1 Horizontal & Vertical 1000-0023840
7
2000mm Straight Extension White 1 Horizontal & Vertical 1000-0025600
8
Flat Roof Weather Collar 1 Vertical 1000-0014890
9
Pitched Roof Collar Black 1 Vertical 1000-0014900
10
Wall Fixing Bracket 125mm 1 Horizontal & Vertical 1000-0016620
11
1140mm Vertical Terminal
White/Black
1 Vertical 1000-0023820
12
Plume Management Kit
Black 1 Horizontal & Vertical 1000-0020730
13
1000mm Extension Flue 80mm Black 1 Horizontal & Vertical 1000-0020740
14
90° Elbow 80mm Ø Black 1 Horizontal & Vertical 1000-0020680
15
45° Elbow 80mm Ø Black 2 Horizontal & Vertical 1000-0020670
16
Wall Fixing Bracket 80mm Black 1 Horizontal & Vertical 1000-0020090
17
Flexible Flue Kit 80/125mm
5m
Black 1 Flexible
FFK5
10m FFK10
18
Flexible Black Outer Pipe
5m
Black 1 Flexible
1000-0026030
10m 1000-0025930
19
Flexible Grey Inner Pipe
5m
Grey 1 Flexible
1000-0026040
10m 1000-0025940
20
Outer/Inner Rigid to Flex Adapter Grey 1 Flexible 1000-0025950
21
Outer Flex to Rigid Connector Grey 1 Flexible 1000-0025970
22
Flex to Rigid Transition Connector White 1 Flexible 1000-00225960
23
Transition Sealing Ring 1 Flexible 1000-0026010
24
Inner Flex to Rigid Connector Grey 2 Flexible 1000-0025980
25
Outer Flue Pipe Sealing Rings 2 Flexible 1000-0025990
26
Inner Flue Pipe Sealing Rings 1 Flexible 1000-0026000
27
Flue Support Kit 1 Flexible 1000-0026020
28
Draw Cone & Rope 1 Flexible 1000-0026050
29
Chimney Terminal Kit 80/125mm
Black 1 Vertical CTK-80/125
30
Slimline Terminal Black 1 Vertical 1000-0026650
31
Flue Terminal Connector Grey 1 Vertical 1000-0026670
32
Chimney Cover Plate Grey 1 Vertical 1000-0026640
33
Circlip 1 Vertical 1000-0026680
12
www.johnsonandstarley.co.uk
FIGURE 7. EXTENDED HORIZONTAL FLUE
FIGURE 8. OPTIONAL ROOF OUTLETS
FIGURE 9. OPTIONAL ROOF OUTLETS
9.12 EXTENDED HORIZONTAL FLUE SYSTEM
Extended horizontal flue set up comprises of:
The required flue lengths up to a length of 10m 80/125mm Horizontal Terminal Kit 90° Elbow 60/100mm to 80/125mm Adapter Inside Wall Cover Plate Outside Wall Cover Plate 125mm Diameter Clamp (1 per flue length)
OPTIONAL ROOF OUTLETS AVAILABLE
9.10 FLAT ROOF OPTION
The Flat Roof Collar.
9.11 PITCHED ROOF OPTION
A Pitched Roof Collar can be fitted on a pitched roof
with an angle of between 20° to 50° pitch.
HORIZONTAL
TERMINAL
VERTICAL
TURRET
ADAPTER
EXTENSION LENGTH
CLAMP
CLAMP
90° ELBOW
500mm
PITCHED ROOF
WEATHER
COLLAR
500mm
FLAT ROOF
WEATHER
COLLAR
20˚
to 50˚
1140mm
1140mm
13
Sales/Spares & Replacement Help Line 01604 762881
FIGURE 10. CONDENSE PUMP
10. CONDENSATE PUMP & DRAIN TUBE
10.1 CONDENSATE PUMP
10.1.1 Supplied with 6mm x 10m condense tube. Condense adapter and 2 x clips
SAFETY NOTE: If the pump fails, the safety float switch will shut off the heater operation.
10.1.2 DO NOT HANDLE PUMP IN WET CONDITIONS OR WITH WET HANDS.
10.1.3 To reduce the risk of electric shock, ensure the electrical supply is permanently wired to earth
10.1.4 TECHNICAL DATA
a) Tank capacity : 0.7L
b) High level safety cut out.
c) Outlet size 6mm I.D.
d) Maximum water temperature: 60°
10.1.5 Where the tubing from the pump is connected directly to the soil
stack or waste pipe, there must always be either a waste trap after the tubing connections, or a 75mm U trap formed within the tubing.
10.1.6 Where the tubing from the pump is connected to an external soil and
vent stack extra care is necessary to ensure that the condense pipe could not be blocked through the condense freezing.
10.1.7 The tank pump uses small bore (6mm) flexible hose which can be
routed above or below doors, windows and under kitchen cabinets.
NOTE:
7m MAXIMUM
HEAD LENGTH OF
CONDENSE TUBE
10.2 CONDENSE TUBE ROUTING OPTIONS
Option A. Routing to outside drain via sink Option B. Routing to drain pipe via roof Option C. Routing to bath waste Option D. Routing under floor to sink waste
FIGURE 11. CONDENSATE ROUTING OPTIONS
B
C
D
A
14
www.johnsonandstarley.co.uk
11. GAS (See BS 5864 and BS 6891)
11.1 The local gas supply conditions MUST be adequate for the specified burner pressures as stated in the technical specification (section 5).
11.2 An independent gas supply pipe from the meter is to be preferred wherever possible. Where this is not possible, the pipe must be capable of taking the complete input of the heater and all other gas appliances being served by the same pipe. This supply should be suitably sized to conform to British Standards requirements of no more than 1.0 mbar (0.4” wg) pressure drop (See table of discharge in BS 6891).
11.3 The ¾” union gas cock (supplied) MUST be fitted to the gas inlet of the heater for easy isolation during servicing. The gas pipe should be fitted and installed so as to be durable, substantial and gas tight. To assist in determining where a gas connection may not be tight, a leak detection fluid should be applied around the connection. Under no circumstances should a flame be used to locate a gas leak. Gas entry to the air heater is through either side or the base, to a 22mm compression fitting.
12. ELECTRICAL
WARNING: THIS APPLIANCE MUST BE EARTHED!
12.1 MAINS SUPPLY
The heater is supplied with mains cable (PVC sheathed, heat resisting to
85˚C), 3 core: Brown; Blue; Green/Yellow, 6A, 0.75mm²), connected to
a PCB control panel and exiting through the heater at the left hand top. The cable is suitable for a 230V 50Hz supply and requires connection to the fixed wiring using a double pole switched, fused spur with a contact separation of at least 3mm in ALL poles. The fuse fitted must be rated 5A to BS 1362. Connections must also be in accordance with the current edition of I.E.E Regulation BS 7671.
NOTE: If, for any reason, the heater is re-wired, then 3 core cable that meets the
above specification MUST be used. Under NO circumstances, should 5 core cable be used for the combined purpose of supplying power to the heater and connecting the thermista-stat!
a. Fan delay and overheat (limit controls) are not adjustable and are
factory set.
b. An Open Therm Controller is supplied which acts like a room
thermostat.
12.2 THERMISTA-STAT & ITS LOCATION
This appliance can be interfaced with the following:-
1) Open therm room units (supplied).
2) 33k NTC room temperature sensor.
3) 230 VAC room thermostats.
12.2.1 The room-stat should be located where there is free air circulation and positioned approx. 1.5m
(5ft) from the floor.
12.2.2 Avoid the following locations:
a. In a room where temperature is greatly affected by the sun or any other heat source, e.g.
radiant fire, wall light fittings or TV set.
b. Near an outside door or windows, or on an outside wall.
c. Where it will be affected by warm air ducts, diffusers, waste pipes or the heater itself.
d. Where it will be subjected to vibration.
12.2.3 Refer to wiring diagram 1 for the installation of the thermista-stat. See Figure 31.
FIGURE 12. CABLE POSITIONING
CONDENSATE DRAIN
TUBE
MAINS SUPPLY
OPEN THERM CABLE
15
Sales/Spares & Replacement Help Line 01604 762881
10
FIGURE 13. CONTROL PANEL
FIGURE 14. LED READ OUT
CONTROL PANEL
1
Time control
2
A +
3
B -
4
LED Display
5
E +
6
D -
7
Summer Air Circulation
8
C
9
Reset
LED READ OUT
1
Open therm symbol
2
Installer mode indicator
3
Service indicator
4
Stand by
5
Degrees
6
Error - ‘e’ or celsius - ‘c’
7
Reset button indicator
8
Flame indicator
9
Button ‘c’ indication
10
Summer circulation
11
Central heating
11
1
2
3 4
7
6
89
5
1 2 3 4 5 6
7
9
8
13. FITTING INSTRUCTIONS
CAUTION: This appliance exceeds the recommended weight for a one man lift as detailed in the Manual Handling Operations, 1992 Regulations.
It should be noted that this appliance could contain sharp edges and care MUST be taken when handling.
13.1 FITTING THE APPLIANCE
13.1.1 Making sure the plenum is clear from all debris, lift the appliance into place.
13.1.2 Using a spirit level it is important the appliance is completely level, this appliance MUST NOT lean
or tilt in any direction. This will cause problems with the condense draining.
13.1.3 Seal the unit to the plenum, using ducting tape (not supplied). Ensure a good seal is made.
13.1.4 Installation of the condense tube is a maximum of 10 meters. There should be no trapped kinks in
this length of tube.
13.1.5 Fix all connections to the appliance ready for commissioning.
14. COMMISSIONING
14.1 After installation of the appliance, you MUST do the following:
14.1.1 Test for gas leakage using proprietary detection fluid and seal any leaks found.
14.1.2 Carry out preliminary electrical system checks.
14.1.3 Ensure that:
a. the filter, fan and fan compartments are free from obstructions. b. all registers or grilles are open and conform to design specifications. c. the return, relief and ventilation air installations are adequate.
14.2 Switch the air heater electrical Supply ON.
14.3. To fill the flue condensate trap, disconnect the sliding flue connector and slowly pour tap water into the el­bow until you hear the condensate pump operating. Failure to do this will result in a whistling sound. Check for leaks.
NOTE: The appliance must be connected to the mains for the pump to operate.
14.4 SYSTEM BALANCING
14.4.1 Press button ‘7’ to put the appliance into Summer Air Circulation mode.
14.4.2 Balance the system to provide the required volume proportions at the warm air outlets.
16
www.johnsonandstarley.co.uk
NOTE: If the system includes ceiling diffusers, the air through these should be NOT LESS THAN 1.5m/s (300ft/
min), except for very small rooms, (i.e. bathrooms etc.). Outlet faces may require partial blanking in order to achieve this.
14.5 LIGHTING MAIN BURNER
14.5.1 Turn on the gas supply to the heater.
14.5.2 Set both switches on the time control unit to the “OFF” position.
14.5.3 Set the thermista-stat to “MAX”.
14.5.4 Turn on the mains power supply to the heater.
14.5.5 Set the “AIR HEATER” switch on the time control to “ON” and observe the ESYS status indicator.
14.5.6 The ESYS on the control panel will run through the ID setting, when finished it shows a flashing “--”
sign. This shows its ready.
14.5.7 The ignitor will spark for 5 seconds during which time the main burners SHOULD ignite and the
igniter will stop.
14.5.8 If, after the 5 second period, the main burner has ignited the ESYS will show “ON” and the blue LED
“ON” light on the indicator panel will remain steady.
14.5.9 If the main burner fails to ignite, 4 more attempts at ignition will occur.
14.5.10 In the event of a lockout “1” (ignition and main burners failing to ignite), reference should be made
to Table 4 in the fault finding section of these instructions in order to establish the fault condition.
14.5.11 Allow the air heater to operate for a minimum of 15 minutes to ensure stability.
14.5.12 Reset the thermista-stat to the desired comfort level.
14.5.13 Set the time control to the desired “on and “off” periods.
14.4 GAS RATE CHECK
14.4.1 There is no burner pressure test with this air heater. It has a 1-1 ratio
Valve.
14.4.2 Natural Gas (G20) consumption is calculated using gross CV 38.7
MJ/m³ or 34.9 MJ/m³ net. Maximum rate 118.45ft³/h (3.35m³/h) and minimum rate 36.2ft³/h (1.025m³/h).
14.5 Complete all relevant sections of the Benchmark Commissioning Checklist located on the inside back pages.
FIGURE 15. C36U FAN PERFORMANCE GRAPH
Resistance External to Heater
Fan Performance
PASCALS
175
150
125
100
75
50
25
0
1000 1200 1400 1600 1800 2000 2100 2400 2600 2800m³/h
FAN MODULATION RANGE
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
IN Wg
NOTE
The gas valve is factory preset and must not be
adjusted. A replacement
valve must only be supplied
by Johnson & Starley Ltd.
17
Sales/Spares & Replacement Help Line 01604 762881
15. HANDING OVER
15.1 After commissioning, the installer should hand the appliance over to the occupier of the house by the following procedure:
15.2 Hand the User Instructions ZZ1340 to the occupier and explain their responsibilities in respect of current legislation and regulations, both national and local.
15.3 Explain and demonstrate how to light and shut down the appliance.
15.4 In order to gain the best possible fuel economy in relation to the heating requirements of the household, carefully explain the operation of the appliance and the use/adjustment of all the system controls.
15.5 Advise on the precautions required to prevent damage to the appliance; the system and the building in the event of the appliance being shut down in very cold weather.
15.6 Explain how, in the event of a fault, the appliance will display a fault code, emphasising that if a fault is indicated they should note the fault code, turn off the appliance and contact a “competent person” which in normal circumstances would be a GAS SAFE registered engineer.
15.7 Explain and demonstrate the function/operation of time/temperature controls, emphasising the economic use of the appliance.
15.8 A comprehensive service should be carried out ANNUALLY. Stress the importance of regular servicing by a Gas Safe Registered Engineer. In IE servicing work must be carried out by a Registered Gas Installer (RGI).
NOTE
This appliance is not intended for use by persons (including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
REMINDER: At the time of commissioning, complete all
relevant sections of the Benchmark Checklist located on the
inside back pages of this document prior to handing over the
appliance to the occupier.
18
www.johnsonandstarley.co.uk
COMPONENT SERVICING CHECKLIST
16.2.6 Clean and check the main burner and electrodes. See paragraph 16.4.
16.2.7 Visually check combustion chamber, removing any debris. See section 16.8.
16.2.8 Remove the Combustion Air Fan (CAF) and clean. See section 16.8.
16.2.9 Check the condensate pipes and tubes for blockages.
16.2.10 Checkthat theue terminalisunobstructed and thattheuesystemisfullyassembledcorrectly.
16.2.11 Removethe Air Circulation Fan (ACF) and lter,
inspect and clean. See paragraph 16.7.
16.2.12 After completing the servicing or exchange of components, always test for gas tightness and carry out functional checks as described above.
16.2.13 When work is complete, check the condition of the sealing foam in the inside of the front door panel. When the door is refitting you must make ensure a good seal is made.
16.2.14 After servicing, complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back pages of this document.
FIGURE 16.
GAS FLUE TEST POINT
FIGURE 17. SERVICING SEQUENCE
1
2
3
16. SERVICING & MAINTENANCE
16.1 SERVICING SCHEDULE
To ensure that the appliance gives continued operation that is both safe and efficient, it is necessary to carry
out regular service checks and whilst the period between servicing will depend on the installation condition and the demands placed upon the appliance, it is recommended that the appliance be serviced annually.
IMPORTANT: It is a statutory requirement that ALL work be carried out by a “competent person” which in normal circumstances would be a GAS SAFE registered engineer.
NOTE: In order to carry out either servicing or replacement of components the heater
front door must be removed.
16.2 SERVICING SEQUENCE
16.2.1 Light the heater and carry out a pre-service check, noting any operational faults.
16.2.2 Check the gas consumption.
16.2.3 Put the appliance in test mode. Refer to paragraph 18.1. Connect a
suitableuegasanalysertothesamplingpointonthetopoftheair heaterorinto the ueterminal if accessispossible (optionaltest).
See Figure 16.
16.2.4 For correct air heater operation, the CO to CO² ratio should be checked at the maximum and minimum in test mode.
16.2.5 Check that the gas input is at least 90% of the nominal.
WARNING. Always turn OFF the gas supply at the gas service cock and switch
OFF. Disconnect the electricity supply to the appliance before servicing.
2
1
3
FLUE GAS
TEST
POINT
19
Sales/Spares & Replacement Help Line 01604 762881
16.3 GAINING ACCESS FOR SERVICING
16.3.1 Ensure the electrical & gas supply is isolated as needed.
16.3.2 Remove the return air filter.
16.3.3 Remove the front panel by unscrewing the 4 retaining screws at top and bottom of the panel.
16.3.4 Remove the front cover.
16.4 MAIN BURNER ASSEMBLY
16.4.1 Refer to section 16.3. See Figure 18.
16.4.2 Disconnect the gas pipe at the top of the isolation valve.
16.4.3 Disconnect the electrode, igniter and earth leads from the ESYS, then remove the screw and panel on the ESYS and remove. Disconnect the electrical connections.
16.4.4 Remove the two screws from the valve/venturi assembly and withdraw.
16.4.5 Remove the 4 nuts and washers securing the burner assembly to the heat exchanger and withdraw the assembly, take care not to damage the internal ceramic pad.
16.4.6 Inspect the inside of the burner assembly for debris. Clean with a soft brush if necessary.
16.4.7 Inspect the gaskets and replace if necessary.
16.4.8 Inspect and clean the spark ignition and flame sensing electrode, removing any debris and oxidization. Check the spark gap and position of the spark electrode and the positioning of the flame sensing electrode.
16.4.9 Once reassembled re-check electrode and igniter nuts are tight.
16.4.10 Refit in reverse order ensuring a good seal is made.
16.5 IGNITION & FLAME DETECTION ELECTRODE
16.5.1 Refer to section 16.3 and Figure 19.
16.5.2 Follow 16.4.4 to remove the valve and venturi.
16.5.3 Unscrew the two nuts that retain the electrode to the cover plate and remove the assembly.
16.5.4 Inspect and clean the electrode, removing any debris and oxidization. If necessary use an abrasive paper or cloth.
16.5.5 Inspect the gasket and replace if necessary during re-assembly.
16.5.6 Repeat sequence for the flame detection electrodes with the exception of the earth lead.
16.5.7 Refit in reverse order and tighten nuts.
FIGURE 19. ELECTRODE GAPS
FIGURE 18. MAIN BURNER ASSEMBLY REMOVAL
ESYS
PANEL
SCREW
FLAME DETECTION ELECTRODE
IGNITION ELECTRODE
GAS
VALVE
VENTURI
ESYS
BURNER
ASSEMBLY NUTS
BURNER ARM
COMBUSTION
CHAMBER
ELECTRODE
NUTS
GAS PIPE
ELECTRICAL
CONNECTION
20
www.johnsonandstarley.co.uk
FIGURE 22.
FILTER & AIR CIRCULATION FAN
FIGURE 21.
COMBUSTION AIR PASSAGE REMOVAL
16.6 HEAT EXCHANGER/COMBUSTION CHAMBER
16.6.1 Refer to section 16.3, 16.4 and Figure 18.
16.6.2 Once the burner assembly has been removed inspect the inside of the combustion chamber for debris. If the inner insulation is damaged, do NOT try to clean. Replace the heat exchanger.
16.6.3 Refit in reverse order.
16.7 COMBUSTION AIR FAN (CAF)
16.7.1 Refer to section 16.3 & Figure 20.
16.7.2 To release the sliding flue connection, slide upwards.
16.7.3 Unplug the multi pin plug connections from the fan and remove the connector from the flue sensor.
16.7.4 Carefully remove the condensate pipe from the bottom of the flue elbow. This will contain water.
16.7.5 Rotate the CAF and elbow assembly 45˚ clockwise and withdraw complete assembly.
16.7.6 Carefully inspect both the impellor.
16.7.8 Refit in reverse order.
16.8 FLUE COLLECTION BOX & HEAT EXCHANGER
16.8.1 Refer to section 16.3, 16.7 & Figure 21.
16.8.2 Unscrew the collection box from the heat exchanger.
16.8.3 Check for blockages. Carefully clean with a soft brush. Do not damage the heat exchanger fins.
NOTE:
Pre 2016 models inspect the mesh in the collection box for debris. If the mesh is full replace with new.
16.9 AIR CIRCULATING FAN (ACF)
16.9.1 Refer to section 16.3.
16.9.2 Unplug sensor wires and tubes from the air pressure switch, main power connector and low voltage flying leads.
16.9.3 Release the fan assembly securing screws, slide the fan assembly forwards on the runners and drop down, remove from the heater cabinet. Avoid damaging the fan blades. See Figure 22.
16.9.4
Remove all dust from both the impellor and motor, taking care not to disturb the balance of the fan.
16.9.5 Refit in reverse order.
RETURN
AIR
SENSOR
SLIDING FLUE
PIPE
COMBUSTION
AIR FAN
FLUE SEAL
FLUE SENSOR
45°
CONDENSE PIPE
OUTLET
CONDENSATE PIPE
MULTI PIN
ELECTRICAL
CONNECTIONS
FIGURE 20. COMBUSTION AIR FAN REMOVAL
21
Sales/Spares & Replacement Help Line 01604 762881
FIGURE 23. CONDENSE PIPEWORK LAYOUT
FIGURE 24. CONDENSE PUMP REMOVAL
16.10 CONDENSATE DRAIN PIPES
16.10.1 Refer to section 16.3. See Figure 23.
16.10.2 Be careful when disconnecting the drain pipes, they will contain water. Drain as necessary.
16.10.3 The flexible condensate pipes are push fit. Disconnect the pipes from the condense pump and combustion tray.
16.10.4 Reconnect the condense drain pipe to the condense pump.
16.10.5 Disconnect the flue elbow outlet and pour water into the condense drain pipe and check for leaks. Re-connected the pipe to the flue outlet.
16.10.6 Refit in reverse order.
16.11 CONDENSE PUMP
16.11.1 Refer to section 16.3.
16.11.2 Remove the filter which is located behind the condensate inlet pipe.
16.11.3 Clean the filter rinsing it with clear water and remove any debris.
16.11.4 Re-fit in reverse order.
CONDENSATE
PIPE TO
OUTSIDE DRAIN
CONDENSE DRAIN
TUBE MUST HAVE A
6mm FALL
FLUE CONDENSE
PIPE OUTLET
FROM
COMBUSTION
AIR FAN
CONDENSE PIPE
OUTLET FROM
COMBUSTION TRAY
TO PUMP
CONDENSATE
PIPE FROM
COMBUSTION TRAY
TO CONDENSATE
PUMP
CONDENSATE
PUMP
CONDENSATE
TRAP
CONDENSING
DRAIN PIPE FROM
COMBUSTION
AIR FAN TO
CONDENSATE TRAP
FLUE
COLLECTION
TRAY
FILTER
22
www.johnsonandstarley.co.uk
FIGURE 26.
SENSORS & AIR PRESSURE SWITCH
17. REPLACEMENT PARTS
17.1 IMPORTANT: Before commencing with any part replacement the appliance should be isolated from the electrical supply and the gas service cock on the appliance closed.
17.1.1 All parts removed should be replaced and refitted in reverse
order, ensuring correct seals are made and wires are connected correctly.
17.1.2 Remove any debris from within the appliance.
17.1.3 When gas-carrying components are replaced the appliance must
be tested for gas tightness.
17.2 CONTROL PANEL
17.2.1 Refer to section 16.3.
17.2.2 Because of the complexity and delicate nature of the control panel
assembly, it is supplied as a complete kit in a plastic housing.
17.2.3 Remove the control panel by unscrewing the 2 screws that hold
the module in place, withdraw and unplug the flying leads at the rear and remove the assembly.
17.2.4 Fit new and re-fit in reverse order.
17.3 AIR CIRCULATION FAN ASSEMBLY (ACF)
17.3.1 Refer to section 16.3.
17.3.2 Unplug sensor wires and tubes from the air pressure
switch, main power connector and low voltage flying leads.
17.3.3 Release the fan assembly securing screws, slide the
fan assembly forwards on the runners and drop down, remove from
the heater cabinet. Avoid damaging the fan
blades. See Figure 19.
17.3.4 Fit the new fan assembly and re-fit in reverser order.
17.4 RETURN AIR TEMPERATURE SENSOR
17.4.1 Refer to section 16.3.
17.4.2 Remove the air circulation fan assembly as described in
section 17.3. See Figure 19.
17.4.3 Unscrew securing nut and remove sensor.
17.4.4 Fit new and re-fit in reverse order.
17.5 FLUE TEMPERATURE SENSOR
17.5.1 Refer to section 16.3.
17.5.2 Carefully remove the 2 spade connectors from the sensor
and unscrew the sensor from the plastic flue elbow.
17.5.3 Fit new and re-fit in reverse order.
17.6 HIGH LIMIT TEMPERATURE SENSOR
17.6.1 Refer to section 16.3.
17.6.2 Unplug the 2 wires from the temperature sensor and
remove the 2 retaining screws.
17.6.3 Fit the new high limit temperature sensor and re-fit in
reverse order.
17.7 AIR PRESSURE SWITCH
17.7.1 Refer to section 16.3.
17.7.2 Disconnect the electrical wire
connections and disconnect the two air pressure tubes.
17.7.3 Remove the 2 screws holding
it to the electrical panel assembly. Unclip the air pressure switch.
17.7.4 Replace and fit new. Re-fit in reverse order.
NOTE: Make sure the air pressure tubes from the Air Circulation Fan and wires from the electrical
connections are in the correct position. The top air
pressure tube from the fan goes to P1 and the bottom air
pressure tube to P2.
FIGURE 25.
AIR CIRCULATION FAN ASSEMBLY
RETURN AIR
TEMPERATURE
SENSOR
P2 AIR
PRESSURE TUBE
P1 AIR
PRESSURE TUBE
(under ange)
FLYING LEAD
RETURN
AIR
SENSOR
HIGH LIMIT
TEMPERATURE
SENSOR
FLUE
TEMPERATURE
SENSOR
CONDENSE
TUBE
OUTLET
23
Sales/Spares & Replacement Help Line 01604 762881
17.8 CONDENSATE DRAIN PUMP
17.8.1 Refer to section 16.3.
17.8.2 Remove the wires from the terminal strip marked fan compartment for the float switch condensate pump.
17.8.3 Disconnect the condensate pipes from the pump. Taking care as these will contain water.
17.8.4 Remove the 2 screws holding the condense pump in position and remove the pump. Taking care as this will also contain water.
17.8.5 Replace with new.
17.8.6 Reconnect the condense drain pipe to the condense pump, leaving the flue outlet disconnected, pour water into the flue pipe outlet to fill the condensate drain pipe and check for leaks. Re­connected the pipe to the flue outlet.
17.8.7 Re-fit in reverse order.
17.9 MAIN IGNITION/CONTROL PCB (ESYS Red Housing on Gas Valve)
17.9.1 Refer to section 16.3.
17.9.2 Unplug the connections from the top of the control and remove the ignition spark detection wires. See Figure 28.
17.9.3 Unscrew the ESYS single retaining screw. Remove cover & unplug the multi pin connections from the control. Slide the housing off the gas valve electrical connections.
17.9.4 Replace with the new ignition control PCB and re-fit in reverser order.
17.10 GAS VALVE & VENTURI ASSEMBLY
NOTE: The gas valve is factory preset and must not be adjusted. A replacement valve can only be
supplied by Johnson & Starley Ltd.
17.10.1 Remove the 2 fixing screws securing the venturi (and gas valve to the burner and remove the assembly from the burner carefully removing the gasket.
17.10.2 Replace with the new component and re-fit in reverse order, ensuring all the seals are in good condition and correctly positioned.
17.10.3 Check the gas rate and combustion as described in paragraph 14.4.
FIGURE 27.
CONDENSE PUMP REMOVAL
FIGURE 28. MAIN BURNER ASSEMBLY
ESYS
PANEL
SCREW
ELECTRICAL
CONNECTIONS
VALVE/ VENTURI SCREWS
BURNER ASSEMBLY
NUTS
BURNER ARM
COMBUSTION
CHAMBER
ELECTRODE
NUTS
BURNER
ASSEMBLY NUT
FLAME DETECTION ELECTRODE/ IGNITION ELECTRODE
GASKET
GAS VALVE
VENTURI
GAS INLET
ESYS
SCREWS
CONDENSE PIPE
CONNECTIONS FROM
THE COMBUSTION
TRAY
FILTER
CONDENSE
DRAIN
TUBE FROM
CONDENSATE
TRAP
24
www.johnsonandstarley.co.uk
FIGURE 29. COMBUSTION AIR FAN ASSEMBLY
17.11 BURNER ASSEMBLY
17.11.1 Refer to section 16.3.
17.11.2 Unscrew the gas joint at the top of the gas cock.
17.11.3 Remove the ESYS (red ignition box) & gas valve venturi assembly. Refer to 17.10 & 17.9 and Figure 25.
17.11.4 Remove the 4 nuts which secure the burner assembly.
17.11.5 Carefully withdraw the assembly from the heat exchanger.
17.11.6 Remove the spark detection electrodes, allowing the burner sealing plates to be separated.
17.11.7 Replace with new component. Ensure the gaskets are replaced with new ones and re-fit in reverse order.
17.11.8 Ensure the rotation position of the burner is correct (indicated by a notch).
17.11.9 Refit in reverse order ensuring the viewing window is correctly positioned.
17.12 IGNITION ELECTRODES
17.12.1 Refer to section 16.3.
17.12.2 Unplug the lead from the ESYS (red ignition box) and earth wire from the back of the electrode. See Figure 25.
17.12.3 Remove the 2 remaining nuts and withdraw the electrode.
17.12.4 Replace with a new unit, ensuring the gasket is replaced with a new one.
17.13 FLAME DETECTION ELECTRODES
17.13.1 Refer to section 16.3.
17.13.2 Unplug the lead from the ignition control. See Figure 28.
17.13.3 Remove the two retaining nuts and withdraw the electrode.
17.13.4 Replace with new unit, ensuring the gasket is replaced with a new one.
IMPORTANT:Wheneithertheignitionoramedetectionelectrodeshavebeenservicedorreplacedyou
MUST set the clearances as shown. See Figure 15.
17.14 COMBUSTION AIR FAN (CAF)
17.14.1 Refer to section 16.3.
17.14.2 To remove the CAF refer to 16.7 and Figure 20 and 29.
17.14.3 Remove the 4 retaining screws that attach the CAF to the flue elbow.
17.14.4 Replace with new components, gaskets, ‘O’ ring and re-fit in reverse order.
COMBUSTION
AIR FAN
ELECTRICAL
CONNECTIONS
SCREWS
FLUE
ELBOW
FLUE
SENSOR
TELESCOPIC
FLUE
FLANGE
CONNECTION ON
CONDENSATE TRAY
GASKET SEALING
RING
‘O’ RING
25
Sales/Spares & Replacement Help Line 01604 762881
18. CONTROL PANEL MODES
18.1 TEST MODE
18.1.1 To put the appliance in test mode, press Summer Air Circulation (SAC) and C buttons together for more than 3 seconds, until the display changes. (Possible 5 second time delay.)
t100 is displayed
along with the flame symbol.
18.1.2 Whilst in test mode, the appliance overrides all temperature setting and defaults to maximum rate. Pressing the D and E buttons allows you to scroll between maximum and minimum rates, whilst maintaining all protection and error conditions.
18.1.3 Press RESET to take the appliance out of test mode. If no changes are made, the appliance will stay in test mode for 30 minutes.
18.2 AIR CIRCULATION FAN MODE
18.2.1 This mode can be used to adjust the maximum and minimum fan speed output value allowed to drive the ACF fan. (minimum value of 50 to 100 being maximum)
18.2.2 Put into ACF mode by pressing ‘C’ and ‘RESET’ for 3 seconds. The ACF fan will run with the fan speed value showing on the LCD display, the Value from the ESYS is bypassed.
18.2.3 On the display, letter F and the fan speed value will display, this value can be changed by pressing the A and B buttons accordingly. Once the required value is reached the values can be saved as:
- minimum by pressing button D
- maximum by pressing button E
18.2.4 The display will flash for 2 seconds to confirm it has been saved to the ESYS.
18.2.5 Timeout mode is set for 30 minutes, this can be terminated by pressing RESET.
18.2.6 The backlight stays on when the test mode is active.
18.3 ERROR HISTORY MODE
18.3.1 The control panel can store the last 8 error codes. To access these codes press the RESET button for more than 1 second, this will then flash ‘H1’ on the LCD display.
13.3.2 Error 1 being the most recent, along with the error code after the dot. To scroll though the error history press the ‘C’ button.
18.3.3 The unit will stay in error history mode for 30 seconds.
18.3.4 To take the unit out of the error history mode press RESET.
18.3.5 In order to limit the warm air temperature the heater will shut off the burner and Lt will be displayed in the centre of the display. This will be stored as Error 57.
18.3.6 Check the filter is clean and the warm air outlets are open.
CONTROL PANEL
1
Time control
2
A +
3
B -
4
LED Display
5
E +
6
D -
7
Summer Air Circulation
8
C
9
Reset
1 2 3 4 5 6
7 98
FIGURE 30. CONTROL PANEL
26
www.johnsonandstarley.co.uk
19. FAULT CODE TABLE
19.1 CAUTION
Before commencing any mechanical servicing the appliance should be isolated from the electrical supply
and the gas service cock on the appliance closed. All parts that are removed during a service operation should be replaced in reverse order, ensuring correct seals are made and wires are connected correctly. During the service remove any debris from within the appliance. When gas-carrying components are serviced the appliance must be tested for gas tightness after re-assembly. On completion of a service carry out a full functional test of all appliance components and ensure system controls are operating correctly.
TABLE 4 ERROR CODES
CODE SYMPTOM POSSIBLE CAUSE ACTION
N/A Heater will not run
No call for heat to heater control board
Check all external controls (if fitted)
Check setting on time clock
Check setting of heater controls
1
Flame lockout after several attempts
Flame not detected
Check gas supply and gas cock
If burner lights, check flame sensor and wiring to control board
Check operation of gas valve
2 False flame lockout False flame detected Check wiring on ESYS
3 Condense pump failure Power to the pump Check for any blockages, restrictions or frozen pipes
4 Air pressure switch open Circulation air fan not running Check for any dust restrictions or blocked filter
5 No tacho from fan Fan not running or wiring fault
Check that fan runs
Check wiring between ESYS and fan
7 Flue gas protection High flue gas temperature Check airflow and fan operation
8 Flame circuit error Flame sensing lead shorted to earth
Check flame detection lead between sensing probe and ignition control board
9 Valve driver circuit error Gas valve not detected
Check that ESYS is corrected fitted on gas valve
Replace ignition control board or gas valve
13 Remote reset lockout Exceeded 5 remote resets per hour Reset it by power off/on
21 ADC error Change ESYS
25 CRC error Different software versions Change ESYS
26
Flame lost signal lost 5 times in 4 minutes
Flame sensing error. Failing gas pressures. Fan fault. Flue blockage.
Check flame detection lead between sensor and ignition control board
Check the gas supply, does pressure fall when burner fires?
Check that flue system is not blocked
27
Sales/Spares & Replacement Help Line 01604 762881
BLOCKING CODES
CODE SYMPTOM POSSIBLE CAUSE ACTION
30
Duct air temperature sensor short circuit
Temperature sensor shorted to earth or failed
Check wiring and connections for shorting to earth
Check sensor resistance
31
Duct air temperature sensor open circuit
Temperature sensor not connected or failed
Check wiring connections
Check sensor continuity
34 Low mains supply voltage
Electrical supply fault to property Check incoming mains supply
Faulty wiring to appliance Check wiring to appliance
43 Return air temperature short circuit Temperature sensor shorted to
Check wiring connections not shorting to earth
Check sensor resistance
44
Return air temperature sensor open circuit
Temperature sensor not connected or failed
Check wiring connections
Check sensor continuity
45
Flue gas temperature sensor short circuit
Short circuit in wiring between sensor and control board
Check wiring to sensor
Check electrical resistance of the sensor
46
Flue gas temperature sensor open circuit
Temperature sensor not connected or failed
Check wiring connections
Check sensor continuity
57 Restricted airflow
Blocked filter and return air filter/ Duct
Check blockage from filter and return air filter/ducts
99 Communication MMI-ESYS lost
Connection between MMI & ESYS incorrectly made
Check wiring and connections
28
www.johnsonandstarley.co.uk
20. FAULT FINDING FLOW CHART
29
Sales/Spares & Replacement Help Line 01604 762881
21. DEFECT DIAGNOSIS FOR THE CIRCULATION AIR FAN
21.1 CIRCULATION AIR FAN
21.1.1 Ensure Air Circulation Fan is running at maximum.
21.1.2 A voltage should be measured and blue (-) and yellow (+). Voltage approx. 10 VDC.
21.1.3 If voltage is present and fan is not running at maximum. Replace ACF.
30
www.johnsonandstarley.co.uk
()
22. FUNCTIONAL WIRING DIAGRAMS
FIGURE 31. WIRING DIAGRAM No. 1 WIRING ROUTING TABLE
FROM UNIT WIRE COLOUR
TERMINAL
L/N/E TO UNIT TERMINAL FROM UNIT WIRE COLOUR
TERMINA
L L/N/E TO UNIT TERMINAL
TIMER
red 1 L
PCB INTERFACE
18
ESYS
brown X1 - 5
PCB INTERFACE
14
blue 2 N
PCB INTERFACE
19 blue X1 - 10
PCB INTERFACE
15
blue 2 DSP (MMI) X1 - 1 yellow X2 - 1 DSP (MMI) X4 - 4
brown 3
PCB INTERFACE
22
orange
X2 - 2 DSP (MMI) X4 - 2
brown 4 DSP (MMI) X1 - 3
green
X2 - 3 DSP (MMI) X4 - 3
DSP (MMI)
green X2 - 1
PCB INTERFACE
X2 - 1 black X2 - 4 DSP (MMI) X4 - 4
green X2 - 2
PCB INTERFACE
X2 - 2 blue X2 - 5 DSP (MMI) X4 - 5
orange X2 - 3
PCB INTERFACE
X2 - 4 yellow X3 - 2
PCB INTERFACE
X3 - 1
orange X2 - 4
PCB INTERFACE
X2 - 5 red X3 - 3
PCB INTERFACE
X3 - 3
red X3 - 10
PCB INTERFACE
X3 - 4
GAS VALVE
green/yellow 1 E
PCB INTERFACE
13 yellow X3 - 13
PCB INTERFACE
X3 - 2
green/yellow 1 E
ELECTRODE
CONDENSATE
PUMP
orange B1
PCB INTERFACE
30
violet B2
PCB INTERFACE
29
CLEANFLOW
orange
Transformer
E
PCB INTERFACE
10 blue A3 N
PCB INTERFACE
18
grey L
PCB INTERFACE
11 brown A2 L
PCB INTERFACE
17
- N
PCB INTERFACE
9 green/yellow A1 E
PCB INTERFACE
16
24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4
123
14
25
36
13
24
PCB - INTERFACE
25 26 27 28 29 30 31 32
SL
O/P
N L N L N L E N L E N L E N L E N L E
E L N
r
r
ACF CAF CLEANFLOW ESYS X1 COND/PUMP CLOCK ROOM STAT HTR
y/g
or
or
bl
br
24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4
123
14
25
36
13
24
PCB - INTERFACE
25 26 27 28 29 30 31 32
SL
O/P
N L N L N L E N L E N L E N L E N L E
E L N
X1
1
2
4
5
X5
X4
X2
X3
3
6
123
4
5
123
4
1
3
DSP (MMI)
1
3
BU
BN
or
54
3
21
M
n
CONTROL PANEL
TIMER
24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4
123
14
25
36
13
24
PCB - INTERFACE
25 26 27 28 29 30 31 32
SL
O/P
N L N L N L E N L E N L E N L E N L E
E L N
RD
RD
ACF CAF CLEANFLOW ESYS X1 COND/PUMP CLOCK ROOM STAT HTR
GNYE
OG
OG
BU
BN
ESYS
10
5
1
16
8
3
6
1
15 9
9 8 7 6
4 3 2 1
5 4 3
2
10
14 13
7 6
1112
5 4
2
X3
X1
X2
BN
RD
BK
GN
1 2 3
OPENTHERM
UNIT
AMBIENT
ROOM
SENSOR
(OPTIONAL)
SUMMER
SWITCH
(OPTIONAL)
RD
RD
RD BU
BN
X6 X7
PCB INTERFACE
OR
GY
BU
BN
A2
A3
A1
GNYE
BU
GNYE
BN
CONDENSATE PUMP
FLOAT SWITCH
B2
B1
BK
BK
ROOM STAT
(OPTIONAL)
CLEANFLOW
(OPTIONAL)
L
N
24V
0V
Transformer
MAINS 230V - AC
YE
YE
YE
BU
RD
E
BN
GY
OR
GNYE
BN
BU
OG
YE
BU
GN
GN
OG
OG
GR
GN
GR
BU
BK
YE
BU
RD
BU
BN
BN
COLOUR
ABR
BLACK
BK
BLUE
BU
GREEN
GN
BROWN
BN
RED
RD
GREEN/YELLOW
GNYE
GREY
GY
ORANGE
OG
YELLOW
YE
VIOLET
VT
WHITE
WH
*
Remove link between 21 & 23
when fitting a room stat
Remove link between 25 & 26
*
when fitting an open therm
PLEASE NOTE:-
BN
BU
GNYE
BURNER ARM
GAS
VALV E
EARTH
GNYE
GNYE
VT
N/C
31
Sales/Spares & Replacement Help Line 01604 762881
FIGURE 32. WIRING DIAGRAM No. 2 WIRING ROUTING TABLE
FROM UNIT WIRE COLOUR
TERMINAL
L/N/E TO UNIT TERMINAL FROM UNIT WIRE COLOUR
TERMINAL
L/N/E TO UNIT TERMINAL
COMBUSTION
AIR FAN
(CAF)
white A1 - 2 ESYS X3 - 1
AIR
CIRCULATION
FAN
(ACF)
blue X9 - 2 N
PCB INTERFACE
6
black A1 - 3 ESYS X3 - 12
green/yellow
X9 - 3 E
PCB INTERFACE
4
yellow A1 - 4 ESYS X3 - 5 brown X9 - 4 L
PCB INTERFACE
5
brown A2 - 1 L
PCB INTERFACE
8 black X10 - 1 DSP (MMI) X3 - 3
green/yellow A2 - 2 N
PCB INTERFACE
7 yellow X10 - 2 DSP (MMI) X3 - 1
blue A1 - 3 E
PCB INTERFACE
9
ACF RETURN
AIR SENSOR
green F1 ESYS X3 - 6
CAF FLUE
PROTECTION
SENSOR
black B1 ESYS X3 - 9 green F2 ESYS X3 - 14
black B2 ESYS X3 - 6
AIR PRESSURE
SWITCH
green 1 ACF F2
BULK HEAD
LIMIT SWITCH
violet D1
ESYS
X3 - 4 green 2 ESYS X3 - 7
violet D2
ESYS
X3 - 15
BULK HEAD DUCT
AIR SENSOR
orange C1 ESYS X3 - 8
orange C2 ESYS X3 - 16
32
www.johnsonandstarley.co.uk
23. DIMENSIONS
FIGURE 33. C36U DIMENSIONS
600
1254
1400
142
800
316
97
617
93
89
64
500
708
128
55
533
509
34
198
FRONT VIEW
SIDE VIEW
TOP VIEW
FRONT
BASE VIEW
33
Sales/Spares & Replacement Help Line 01604 762881
24. EXPLODED SPARES DIAGRAMS
ITEM DESCRIPTION QTY PART No. G. C. No.
1
CONTROL PANEL ASSEMBLY
1 C10D-0501005
2
COMBUSTION AIR FAN (CAF) ASSEMBLY
Includes 3 & 4
1 1000-0525215 J24-837
3 CAF GASKET SEALING RING 1 1000-1507860 H36-837
4 CAF ‘O’ RING 1 1000-2501670 J24-909
5
EXHAUST FLUE ELBOW ASSEMBLY
Includes 6 & 7
1 1000-0022195 J24-836
6 FLUE SEAL 1 1000-2501500 J24-833
7 FLUE GAS SENSOR 1 1000-0522640 J24-836
8
GAS VALVE/VENTURI
Includes 9 & 10
1 1000-0710735 J24-775
9 VENTURI GASKET 1 1000-1508380 J24-772
10 CORK GASKET 2 1000-2501170 H38-674
11
BURNER ARM ASSEMBLY
Includes 12 & 13
1
1000-0710745
J24-764
12 BURNER GASKET A 1 1000-1508160 J24-765
13 BURNER GASKET B 1 1000-1508170 J24-767
14
IGNITION ELECTRODE ASSEMBLY
Includes 15
1 1000-0710455 J24-780
15 ELECTRODE GASKET 1 1000-2501270 J24-755
16
DETECTION ELECTRODE ASSEMBLY
Includes 15
1 1000-0710445 J24-769
4
3
6
7
3
FLANGE
CONNECTION
9
9
12
13
15
15
10
10
34
www.johnsonandstarley.co.uk
25
ITEM DESCRIPTION QTY PART No. G. C. No.
17
AIR CIRCULATION FAN ASSEMBLY
1 C46U-0503005
18
RETURN AIR SENSOR DUCT TEMPERATURE SENSOR FLUE GAS SENSOR
1 1000-0522645 J24-833
19
COMBUSTION AIR BOX ASSEMBLY
Includes 19 & 20
1 C46D-0139005 J24-829
20 SEALING RING 1 1000-2501680 J24-825
21 CONNECTOR SEAL 1 1000-2501710
22
CONDENSATE PUMP
1 1000-0025035 J24-844
23
HEAT EXCHANGER
1 C46D-0330005
24
ELECTRICAL P.C.B. BOARD
Includes 25
1 1000-0526615 J24-838
25 LOCKING CIRCUIT BOARD SUPPORTS 4 1000-0526485
26 HIGH LIMIT TEMPERATURE SENSOR 1 1000-0516835 173-119
12
FLANGE
SOCKET
BACK NUT
CONDENSATE
CONNECTOR
22
CONDENSATE AIR BOX SEAL
21
SEALING
FRAME
18
FLYING LEAD
35
Sales/Spares & Replacement Help Line 01604 762881
ITEM DESCRIPTION QTY PART No. G. C. No.
27 ESYS CONTROL BOX 1 1000-0526595 J24-859
28 ESYS SCREW 1 1000-3004035 J24-855
29 ESYS COVER 1 1000-0522610 J24-856
30 AIR PRESSURE SWITCH 1 1000-0530135 J24-839
31 CONDENSATE TRAP 1 1000-0024525 J24-749
32 VERTICAL FLUE ADAPTER 60/100mm 1 1000-0022225 J24-784
33 TELESCOPIC FLUE 1 1000-00222525 J24-811
34 OPEN THERM SWITCH 1 1000-0525305
29
28
36
www.johnsonandstarley.co.uk
25. LIST OF ANCILLARIES
WARMCAIR C36U ANCILLARY’S
Description Product Code
1
CLEANFLOW AIR FILTER
CF36
2
FILTER REPLACEMENT PADS
(PACK OF 6)
A0212X0212
3
Side Return Air Kit
Includes 4
SRAK36
4
BLANKING PLATE
5
PASSIVE SIDE RETURN AIR KIT
SRAK36P
6
BASE DUCT
WB36
37
Sales/Spares & Replacement Help Line 01604 762881
Code Of Practice
For the installation, commissioning and servicing of domestic heating and hot water products
Benchmark places responsibilities on both manufacturers and installers.* The purpose is to ensure that customers** are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. Installers are required to carry out work in accordance with the following:
Standards of Work
• Be competent and qualified to undertake the work required.
• Install, commission, service and use products in accordance with the manufacturer’s instructions provided.
• Ensure that where there is responsibility for design work, the installation is correctly sized and fit for purpose.
• Meet the requirements of the appropriate Building Regulations. Where this involves notifiable work be a member of a Competent Persons Scheme or confirm that the customer has notified Local Authority Building Control (LABC), prior to work commencing.
• Complete all relevant sections of the Benchmark Checklist/Service Record when carrying out commissioning or servicing of a product or system.
• Ensure that the product or system is left in a safe condition and, whenever possible, in good working order.
• Highlight to the customer any remedial or improvement work identified during the course of commissioning or servicing work.
• Refer to the manufacturer’s helpline where assistance is needed.
• Report product faults and concerns to the manufacturer in a timely manner.
Customer Service
• Show the customer any identity card that is relevant to the work being carried out prior to commencement or on request.
• Give a full and clear explanation/demonstration of the product or system and its operation to the customer.
• Hand over the manufacturer’s instructions, including the Benchmark Checklist, to the customer on completion of an installation.
• Obtain the customer’s signature, on the Benchmark Checklist, to confirm satisfactory demonstration and receipt of manufacturer’s instructions.
• Advise the customer that regular product servicing is needed, in line with manufacturers’ recommendations, to ensure that safety and efficiency is maintained.
• Respond promptly to calls from a customer following completion of work, providing advice and assistance by phone and, if necessary, visiting the customer.
• Rectify any installation problems at no cost to the customer during the installer’s guarantee period.
* The use of the word “installer” is not limited to installation itself and covers
those carrying out installation, commissioning and/or servicing of heating and hot water products, or the use of supporting products (such as water treatment or test equipment).
**Customer includes householders, landlords and tenants.
© Heating and Hotwater Industry Council (HHIC)
www.centralheating.co.uk
This Commissioning Checklist is to be completed in full by the competent person who commissioned the wsnn air unit and associated equipment as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference
Failure to Install and commission this equipment to the manufacturer's instructions may Invalidate the warranty but does not affect statutory rights.
CONDENSING WARM AIR HEATING AND WATER HEATING COMMISSIONING CHECKLIST
Customer name: Telephone number:
Address:
Warm Air Unit Make and Model:
Warm Air Unit Serial Number:
Commissioned by (PRINT NAME): Gas safe register number:
Company name: Telephone number:
Company address:
Commissioning date:
CONTROLS (tick the appropriate boxes)
Time and temperature control to heating
Room thermostat and programmer/timer Programmable Roomstat
Load/weather compensation Optimum start control
Heating zone control Fitted Not required
WARM AIR HEATER
Has the system been balanced in accordance with the heater manufacture's instructions? Yes No
Was an anemometer used? Yes No
Yes No
WARM AIR HEATING: measure and record:
Bumer operating pressure (at maximum rate) mbar
Heat input kW
Temperature difference between return air inlet and nearest outlet °C
WATER HEATING: (If fitted)
Water inlet temperature
Water outlet temperature
°C
°C
CONDENSATE
The condensate drain has been installed in accordance with the manufacture's instructions and/or BS 5546/BS6798 Yes
INSTALLATION
The heating and hot water system complies with the appropriate Building Regulations Yes
The system and associated products have been installed and commissioned in accordance with the manufacturers instructions Yes
Yes
The manufacturer's literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Commissioning Engineer’s Signature
Customer’s Signature
*
© Heating and Hotwater Industry Council (HHIC)
www.centralheating.co.uk
www.centralheating.co.uk
www.centralheating.co.uk
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE RECORD
SERVICE 01
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 02
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 03
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 04
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 05
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 06
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 07
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 08
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 09
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
SERVICE 10
Date:
Engineer name:
Company name:
Telephone No:
Gas safe register No:
Record:
At max. rate: CO ppm AND CO² %
At min. rate:
(Where Possible) CO ppm AND CO
²
%
Comments:
Signature
*All installations in England and Wales must be
to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance
will then be issued to the customer.
© Heating and Hotwater Industry Council (HHIC)
Johnson & Starley Ltd
Rhosili Road, Brackmills, Northampton NN4 7LZ
sales@johnsonandstarley.co.uk marketing@johnsonandstarley.co.uk
Reception/Customer Service
01604 762881
Fax
01604 767408
Anniversary 1922 - 2012
Loading...