This appliance is for use with liquid petroleum gas G31, and is approved for use in GB, IE, FR, NL BE & NO,
IMPORT AN T : STA TUTE LAW DEFINES THAT ALL GAS APPLIANCES MUST BE INSTALLED, COMMISSIONED
AND MAINTAINED BY COMPETENT PERSONS, (ie CORGI REGISTERED INSTALLERS) IN ACCORDANCE
WITH THE GAS SAFETY (INSTALLATION AND USE) REGULATIONS (CURRENT EDITION). FAILURE TO
COMPL Y WITH THESE REGULA TIONS MA Y LEAD TO PROSECUTION.
1.BRIEF DESCRIPTION
16
1
4
3
12
6
15
2
14
11
1 Air Filter
2 Air circulating fan
3 Fuse
4 Time control
5 Data plate
6 Fan Delay Control
7 Multifunctional control
8 Pilot burner
9 Main burner assembly
1 0 Gas connection
11 Limit Switch
1 2 Control panel
1 3 Piezo unit
1 4 Summer air circulation switch
1 5 Spillage monitor device (TTB) (at rear)
16 Draught Diverter
7
13
5
9
10
Fig. 1
1. 1JB25P is an open-flued, fan assisted downflow, ducted warm air heater. A Spillage Monitoring Device is fitted which
senses the temperature around the draught diverter, and shuts down the appliance when this temperature rises due to the
presence of flue gases.
1. 2The Air heater output is 7.6kW (27.5MJ/h, 26,000Btu/h). “Summer air circulation” of unheated air is available by manual
selection (see User’s Instructions).
1. 3For Caravan installations, Slot Fit Kit ATL30 is available for this appliance. For Permanent Dwellings, Free-Standing Kit
TC30 and Slot Fit Kits TS30 and TSA30 are available for this appliance.
THIS APPLIANCE CONFORMS TO BS EN 55014
8
1
Installation shall be in accordance with the current editions of:
ZZ1031/4
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt.1 (Flues for Gas Appliances)
BS 5440 Pt.2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
BS 5482 Pt.1 Installation of LPG appliances in permanent dwellings
BS 5482 Pt.2 Installation of LPG appliances in caravans and non-permanent dwellings
British System Design Manual “Gas Fired Warm Air Heating”
Model and Local Authority Bye-laws
2.HEATER COMP ARTMENT AND CLEARANCES (See BS 5864)
2. 1When the heater is fitted into a compartment, a minimum clearance from the compartment walls of 6mm (1/4 in ) at the sides
and rear, and 25mm (1 in) at the front must be left. Consideration should be given to the space required for the removal and
replacement of the filter tray and the entry of the gas and electrical supplies.
2. 2For service access, a minimum of 450mm (18ins) is required at the front of the heater. Space must also be allowed, in a
compartment installation, to permit the removal of the heater. The clearance between the appliance and the compartment
should be not less than 75mm (3 in). However, if clearances are less than 75mm, the internal surface of the compartment
must be lined with noncombustible material. The compartment must be of a fixed rigid structure.
2. 3In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of BS
5864 and must be completely separated by either a noncombustible partition or a perforated metal partition with the
perforations not exceeding 13mm (1/2in). The secondary flue must be a tight fit where it passes through the partition and
must be suitably protected (see BS 5440: Part 1).
2. 4In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided that in addition, all internal surfaces, including the base, are noncombustible or lined with noncombustible material. This requirement is applicable only to dwellings of more than two storeys. Combustible floors must be insulated from the heater.
2. 5In slot fit installations (for caravan installations see instructions packed with Slot Fit Kit TS30 or TSA30), the slot fit
compartment must comply with the appropriate section of BS 5864. Side and rear clearances should be no less than 6mm
(1/4in).
2.6In freestanding installations (see instructions packed with the T op Closure kit TCB30), only one or two walls will be in
contact with the air heater; and therefore must comply with the appropriate sections of BS 5864.
2.7The base duct on which the air heater stands must be placed on a noncombustible floor.
2. 8IMPORT ANT : When the heater is installed in a compartment, the Safety Label supplied with the heater MUST BE AFFIXED
in a PROMINENT POSITION on the INSIDE of the COMP AR TMENT DOOR.
3.VENTILATION AND COMBUSTION AIR
3. 1The room or internal space in which the heater is installed requires a permanent air vent of minimum effective area 13cm
2
(2 in2 ). The air vent should be either direct to outside air or to an adjacent room or internal space (other than a toilet or
bathroom) that itself has an equivalent air vent direct to outside.
3. 2Combustion air may be introduced, via a 100mm (4in) nominal bore pipe, connected to a return air duct or plenum from a
ventilated area and fitted with a lockable damper. The damper should be adjusted to control combustion airflow to
0.0064m3/s (13.6cfm), (i.e. 0.86m/s [160ft/min] velocity in a 100mm [4in] bore pipe). If this arrangement is used, a noncloseable warm air register MUST be provided in the same area as the front of the air heater or heater compartment if a
return air grille is not located in that area.
3. 3When installed in a compartment, two permanent ventilation openings into the compartment are required, one at high
level and one at low level, both communicating either directly with outside air or with a ventilated room or space. The
minimum effective areas specified in Table 1 are related to the rated heat input of the Air Heater.
3.4If any room or area from which air is drawn for ventilation or combustion contains an extract fan, the permanent vents must
be sized to ensure that the operation of the appliance at full rate is not adversely affected. A spillage test as specified in subpara 6.7 (Safety Checks) is carried out and any remedial work undertaken.
(See British Design Manual - Gas fired Warm Air Heating)
4.1RETURN AIR
4.1.1 All return air shall be POSITIVELY ducted from outside the compartment to the top of the unit via a return air duct,
and mechanically secured. It is recommended that the return air duct be not routed directly from the main living
area, but from a convenient central area serving the remainder of the dwelling.
4.1.2 The return air system should be constructed of fire-resistant material. The flue shall not be run through an area
serving as a return air path. It is extremely important that the correct size of return air grilles and ducting is used.
The return air duct size should not be less than the equivalent of 200mm x 200mm (8" x 8"). If flexible duct is used
the duct diameter should not be less than 254mm (10") dia. The return air grille should have a free area of not less
than 650cm2 (100in2).
4.1.3 An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to
which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m2/
kW (1in2/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC.’s.
4.1.4 The return air duct should allow for ease of removal for access to the flue.
4.1.5 All duct work in the room or internal space in which the heater is installed shall be mechanically secured, and
sealed with ducting tape.
4.2 W ARM DELIVERED AIR
4.2.1 All duct work, including riser ducts, should be fully insulated with 50mm (2in) fibreglass or similar. If short
extended duct runs are taken below floor level these should be similarly insulated, and in addition wrapped with a
sound vapour proof barrier, and protected from crushing.
4.2.2 The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to
suit the needs of its specific heating requirements and building layout. The type of duct system, (i.e. radial/
extended plenum/stepped) should be installed using the least number of fittings to minimize airflow resistance.
The base duct, which equalizes the air pressure to supply ducts, shall be constructed to support the weight of the
heater, which shall be secured to the plenum with screws on at least two sides, and sealed using self-adhesive
foam strip, ducting tape or sealing compound. All ducting and blanking plates shall be mechanically secured and
sealed.
5.INSTALLATION REQUIREMENTS
5.1 FLUES (see British Standards BS 5440 Pt.1 Flues)
5.1.1 All joints shall be soundly sealed.
5.1.2 The flue should be kept as short and warm as possible, but must have a minimum equivalent height of 1m..
5.1.3 Sufficient support brackets shall be installed to bear the weight of the total flue system.
5.1.4 The spigot connection of the heater draught diverter will internally accept the spigot end of a non-asbestos flue
to BS 567 or twin wall metal flue to BS 715 of nominal 100mm (4in) diameter.
5.1.5 A split collar should be fitted to provide for flue maintenance or inspection.
5.1.6 The flue shall be in accordance with the Building Regulations and British Gas Materials and Installations
specification (3rd edition) with regard to clearance and shielding from combustible materials.
5.1.7 All materials shall be in accordance with Building Regulations requirements.
5.1.8 The flue should run as vertically as possible. Horizontal runs should be avoided if at all possible and any
directional change should be as gentle as possible. If there is any doubt about the flue configuration, the
equivalent flue height should be determined (see 5.1.10).
5.1.9 If the appliance to be fitted is a replacement, the old appliance should be checked for signs of spillage prior to
commencement of the installation and appropriate action taken, (i.e. check flue system and renew as necessary).
ZZ1031/4ZZ1031/4
3
ZZ1031/4
5.1.10 It is recommended that at least 600mm of vertical flue should be provided from the top of the draught diverter
(for new installations this shall be incorporated into the flue design). However, when carrying out replacement
installations, an existing flue system may be encountered, where the vertical flue above the appliance to the first
bend is less than 600mm. In the first instance, the installer must judge whether this distance can be achieved
practicably by some means. Where this is not practicable, the existing flue system may be used, providing there is
no evidence of spillage from the old appliance (see 5.1.9 above). Every effort must be made, however, to ensure
that the existing flue complies in every other way with BS 5440 Part 1, including the visual inspection, flue flow
and spillage test described in clause 4.3.2 of the above standard. Flue configurations may be assessed in terms of
equivalent vertical height - details. For air heaters, the minimum equivalent vertical height is 1 metre. The
installer must make a judgement based on his knowledge and experience and the examination and testing
described above as to whether an existing flue system can be used.
Note: Ventilation of the compartment, room or internal space in which the appliance is to be installed must be checked
for compliance with the requirements of BS 5440 Part 2 ( Ref. Section 3 of these instructions) and upgraded as
necessary.
5.1.11 Calculation method for flue sizing: (BS 5440: Part 1, Appendix A)
a.This appendix provides a procedure for estimating whether a given flue design is likely to ensure full
clearance of combustion products.
b.The procedure is based on calculating the ‘equivalent height’ of the flue under consideration, i.e. that
height of the straight vertical circular flue pipe of specific size which will produce the same flow rate as
the flue under consideration. The equivalent height is calculated from the formula:
(Ki + Ko )
e
He = Ha x
(Ki + Ko)a - KeHa + SumK
where:
He is the height of the equivalent flue;
Ha is the vertical height of the actual or proposed flue;
Ki is the inlet resistance of the flue;
Ko is the outlet resistance from the flue;
subscript e refers to the equivalent flue diameter;
subscript a refers to the actual or proposed flue diameter;
Ke is the resistance per unit length of the equivalent flue;
SumK is the resistance (other than the inlet and outlet resistance) of the actual or proposed flue.
Note: K and SumK are obtained from Table 2. Ko and Ki are obtained from Table 3.
c.Table 2 gives resistance factors for common flue components for use in the formula. Table 3 contains the
appropriate inlet and outlet flue resistances. The flue is likely to be satisfactory if its equivalent height
exceeds 1 metre.
Flue Blocks197 x 670.85 per metre45O Bend100 mm pipe0.61 per
231 x 650.65 run125 mm pipe0.25 fitting
317 x 630.35150 mm pipe0.12
140 x 1020.60197 x 670.30
200 x 750.60231 x 650.22
183 x 900.45317 x 630.13
Pipe1 000.78Raking blockAny0.30 per block
1250.25
1500.12Adaptor blockAny0.50
Chimney213 x 2130.02Terminal100 mm ridge2 .5
125 mm ridge1.0
90O Bend100 mm pipe1.22 per150 mm ridge0.48
125 mm pipe0.50 fitting100 mm GCI0.6
150 mm pipe0.24125 mm GCI0.25
150 mm GCI0.12
T able 2
Resistance factors for use in calculating equivalent heights
4
ApplianceInletFlueOutlet
Resistance (Ki)Resistance (Ko)
100 mm dia spigot2.5100 mm flue2. 5
125 mm dia spigot1.0125 mm flue1. 0
150 mm dia spigot0.48150 mm flue0.48
Table 3
Inlet and outlet resistance
d.Worked Calculation Example:
A warm air unit with a 100 mm diameter flue spigot, fitted with a prefabricated flue system leading to a
ridge tile (refer Fig. 2):
From table 3:
Kia Inlet resistance of actual flue= 2. 5
Koa Outlet resistance of actual flue= 2.5
Kie Inlet resistance of equivalent flue= 2.5
Koe Outlet resistance of the actual flue= 2.5
From table 2:
Other resistances of actual flue:
Terminal= 2.5
Pipe bend ( 2 x 0.61)= 1.22
Pipe (4 x 1m @ 0.78)= 3.12
(5 x 0.3m @ 0.78)= 1.17
SumK= 8.01
Equivalent height :
From the formula
ZZ1031/4
(2.5 + 2.5)
He = 6.2 x
(2.5 + 2.5) - (0.78 x 6.2) + 8.01
He = 3.793 This flue exceeds 1.0m equivalent height and is therefore satisfactory.
5.1.12 Where flue blocks are used, builders should ensure that no obstruction is created during erection. The installer
should ensure that the connection flue does not project beyond the internal wall of the flue blocks and that there
is provision for examination and servicing.
5.1.13 Important: Before installing the appliance, carry out a visual check of the flue system as directed in the relevant
section of BS 5440 Pt.1, then check the flue performance as follows:-
a.Close all doors and windows in the room in which the appliance is to be installed.
b.Introduce some heat into the flue, using a blow torch or other means.
c.Carry out a flow visualization check with a smoke pellet at the intended position for the appliance. Ensure
that there is discharge of smoke from the correct terminal only , and no spillage into the room. Smoke coming
out of other than the correct terminal only, or a down draught or ‘no flow’ condition, indicates that the flue
has failed the test, and the appliance shall not be connected until the defect has been found and rectified,
and the test satisfactorily completed.
5
Ha = 6.2m
ZZ1031/4
Ridge Terminal
2 x 300 mm lengths
100 mm dia flue pipe
4.6m
4 x 1000 mm lengths
5.2ELECTRICAL:
5.2.1Mains.
a.The heater is supplied with mains cable (PVC sheathed, heat resisting to 85oC), 3-core Brown-Blue-Green/
O
45
bend
300 mm length
1.6m
45O bend
2 x 300 mm lengths
Flue spigot
Fig. 2
Worked example of equivalent flue height
Y ellow , 5A, 0.75mm2), connected to a terminal block and exiting through the heater at the right hand top. The
cable is suitable for a 230V 50Hz supply and shall be connected to the fixed wiring using a double pole
switched, fused spur, incorporating a protective earth link. The fuse fitted shall be rated 5A to BS 1362.
Connections shall be in accordance with the current edition of I.E.E. Regulations BS 7671.
b.A 24V room thermostat (not supplied), that complies with BS 800, BS 3955 and BS 4201 is essential to ensure
close control of comfort conditions. An anticipator is located within the thermostat and is graded in amps.
The anticipator should be checked and adjusted to 0.2A.
6
5.2.2Room Thermostat and its location.
a.The Room Thermostat should be located where there is free air circulation approx. 1.5m (5ft) from the floor.
b.A void the following locations:-
i)In a room where temperature is greatly affected by the sun or any other heat source, e.g. radiant
fire, wall light fittings or TV set.
ii )Near an outside door or windows, or on an outside wall.
iii)Where affected by warm air ducts, diffusers, waste pipes or the heater itself.
c.Connect room thermostat wires control panel terminals ‘5’ and ‘6’
5.3GAS (See BS 5864 and BS 6891)
5.3.1An independent gas supply pipe is to be preferred wherever possible. When this is not possible, the pipe must be
capable of taking the complete input of the heater and all other gas appliances being served by this same pipe. This
supply should be suitably sized to conform to British Standards requirements of no more than 2.5 mbar (1.0 in wg)
pressure drop (see table of discharge in BS 5482).
5.3.2The 1/2in union gas cock (supplied) must be fitted to the gas inlet of the heater for easy isolation during servicing.
The gas pipe should be so fitted and installed as to be durable, substantial and gas tight. To assist in determining
where a gas connection may not be tight, a leak detection fluid should be applied around the connection. Under no
circumstances should a flame be used to locate a gas leak. Gas entry to the air heater is through either side to a
Rc1/2 (1/2in BSP . external [taper] thread).
6.COMMISSIONING
6.1PREP ARATION:
ZZ1031/4
6.1.1Ensure that:
a.Gas and Electrical supplies are OFF.
b.Filter, fan and fan compartments are free from obstructions.
c.All registers or grilles are open and conform to design specifications.
d.Return, relief and ventilation air installations are adequate.
6.2SYSTEM BALANCING:
6.2.1Set the heater electrical supply ON.
6.2.2Set the SUMMER AIR CIRCULA TION switch to ‘ON’.
6.2.3Balance the system to provide required volume proportions at warm air outlets.
NOTE: If the system includes ceiling diffusers, air velocities through these should be NOT LESS THAN 1.5m/s (300ft/
min), except for very small rooms (ie. bathrooms etc.). Outlet faces may require partial blanking in order to achieve this.
6.2.4 Set the SUMMER AIR CIRCULATION switch to ‘OFF’.
6.3IGNITION OF PILOT AND MAIN BURNERS:WARNING: If the pilot light is extinguished either intentionally or unintentionally, no attempt should be made to
relight the gas for a minimum of 3 minutes. Ensure that the Electrical supply, Time Control and Selector switches are set
to ‘OFF’.
6.3.1 Set the Room Thermostat to its lowest or OFF setting.
6.3.2 On the Multifunctional Control, slacken the pressure test point screw, and fit a pressure test gauge (refer fig. 4).
6.3.3 Turn the heater Gas supply ON, test for gas soundness and purge the whole gas pipe as described in BS 6891.
6.3.4 Referring to Fig. 4, press and hold the OPERATING CONTROL, and whilst observing the Pilot Burner, repeatedly
press the Piezo igniter button until the Pilot Burner ignites.
6.3.5 After 20 seconds release the OPERATING CONTROL and let it spring out; ensure that the Pilot Burner remains
alight. If the Pilot Burner extinguishes, wait three minutes and repeat steps 6.3.4 and 6.3.5 until the Pilot Burner
remains alight.
6.3.6 Ensure that the pilot flame envelops the Thermocouple tip, adjusting the Multifunctional Control Pilot Adjuster as
required (refer Fig. 4).
6.3.7Set the Heater Electricity supply ON.
6.3.8Set the Time Control to required Heating On periods.
6.3.9Set the Selector switch to ‘TIMED’.
7
6.3.10 Set the thermostat to MAXIMUM.
6.3.11 Ensure that the Main Burner has now ignited.
6.3.12 Test for gas leakage at the supply, Multifunctional Control, Pilot and Main burners using a proprietary detection
fluid, and sealing any leaks found.
6.3.13 Allow the heater to operate for a minimum of 15 minutes to ensure stability.
ZZ1031/4
Thermocouple
Electrode
Fig. 3
Pilot Burner Assembly
6.4MAIN BURNER PRESSURE TEST AND TEMPERA TURE RISE CHECK:
6.4.1Referring to Table 4 and Fig. 4 below, ensure that the pressure test gauge indicates correct pressure, adjusting the
supply pressure if required.
a.At the Multifunctional control:
i.Remove the Burner Pressure Adjuster cover.
ii.Set the Burner Pressure Adjuster to provide a pressure test gauge indication for the correct burner
pressure as detailed in Table 4.
iii.Refit the Burner Pressure Adjuster cover.
6.4.2 Check that the temperature rise across heater is between 45oC - 55oC, setting the fan speed accordingly by
alteration of the voltage selection at the tap changer on the control panel, (decrease voltage to decrease fan speed
thus increase temperature).
6.5.1On the Multifunctional Control, rotate the OPERA TING CONTROL clockwise to the ‘ l’ position and ensure that
the OPERA TING CONTROL fully resets, and both Pilot and Main Burners are extinguished.
6.5.2On the Multifunctional Control, remove the pressure test gauge and secure the Pressure test point screw.
6.6AUTOMA TIC CONTROLS CHECK
6.6.1Ignite the Pilot burner.
6.6.2Set the TIME CONTROL to ‘ON’.
6.6.3Set the Room Thermostat slowly clockwise until the Main Burner ignites.
6.6.4Ensure that the fan starts to operate after a short period.
6.6.5When the temperature reaches the control setting, check that the Main Burner extinguishes followed by the fan
switching off after a short period.
6.6.6 When the temperature falls below the control setting, ensure that the Main Burner re-ignites followed by fan
operation.
6.7SAFETY CHECKS:
6.7.1Check for gas soundness within the appliance.
6.7.2Spillage test: Carry out a full spillage test as follows, and ensure that the flue operates effectively with all doors
closed and any extractor fans in operation.
NOTE: If an extractor fan is situated in an adjoining or adjacent room, carry out the spillage test with the interconnecting
doors open.
If the draught diverter is accessible:
a.Introduce smoke into the draught diverter adjacent to an exit from the heat exchanger, by means a smoke
match or puffer.
b.Ensure that there is no spillage present (indicated by displacement of smoke downwards and out of the
draught diverter).
If the Draught Diverter is not accessible:
a.Introduce smoke, by means of part of a smoke pellet on a non-combustible support, into the heat
exchanger.
b.Extinguish the Main and Pilot burners.
c.Ensure that there is no spillage evident by visually observing the draught diverter location on the air
heater.
d.If spillage is evident, further investigation and rectification is required before re-testing the appliance.
WARNING: The appliance shall not be left connected to the gas supply unless it has successfully passed
the above spillage test.
6.7.3Turn OFF the gas supply at the service cock and ensure that the Multifunctional Control fail-safe operates within
60 secs (indicated by loud click from Multifunctional Control).
ZZ1031/4
6.7.4Turn gas supply ON at service cock.
6.7.5Switch the appliance electrical supply OFF.
6.7.6Disconnect the fan at the fan flying lead connection.
6.7.7Switch the appliance electrical supply ON.
6.7.8Ignite the Pilot and Main Burners as detailed in sub paras 6.3.4 and 6.3.5
6.7.9Ensure that the Limit Switch operates, indicated by the Main Burner extinguishing, within 120 and 180 seconds.
6.7.10 Switch the appliance electrical supply OFF .
6.7.11 Reconnect the Air Heater Fan at the flying lead.
6.7.12 Switch the appliance electrical supply ON.
6.7.13 Ensure that the Main Burner re-ignites when the appliance temperature reduces.
9
kWMJ/hBtu/h
INPUT9.734.933,100
OUTPUT7.627.526,000
PROPANE G31
Gas rate cv0.705kg/h
GasG31 cv(gross) 95.65MJ/m
Gas Pressure26mbar (10.2 in wg)
Main InjectorBRAY Cat 23/380
T able 4
Main Burner Pressure Settings
mbar in wg
0.50 0.20
0.375 0.15
210V
190V
170V
150V
3
230V
ZZ1031/4
0.25 0.10
0.125 005
200 250 300 350 ft3/min
0.09 0.12 0.14 0.17 m
3
/s
Table 5
Fan Performance Curve
7.INSTRUCTIONS FOR USERS
7. 1If the dwelling is unoccupied, ensure that the Instructions for User are left with the air heater for the User, and the
Installation Instructions are left at or near the air heater for use on future service calls.
7. 2If the dwelling is occupied, hand the User Instructions over and ensure that the User understands:
7.2.1 How to ignite the pilot and burner.
7.2.2 How to operate the Room Thermostat, time control, heater ON/OFF switch and summer air circulation switch,
and that the time control must be reset following a power failure.
7.2.3 How to extinguish the pilot and main burner at the Multifunctional control, the sequence of actions when switch-
ing off the gas supply and the subsequent delay in relighting the pilot burner if these actions are not followed, and
switch off electrical supply to the heater.
7.2.4 How to remove, clean and refit the air filter and at what intervals (i.e. fortnightly, or weekly for new houses).
7.2.5 How to control the heating system by opening and closing warm air outlets.
7.2.6 How to obtain summer air circulation.
7.2.7That the air grilles on the heater or heater compartment; grilles and ventilators in the walls, windows or doors of the
building must not be obstructed.
7.2.8The heater must be serviced at least once a year by a competent person to ensure efficient and safe operation.
7.2.9That the red instructions for safe use have been pointed out and understood.
7.2.10 That expert help must be obtained if persistent failure of the pilot burner occurs.
10
8.MAINTENANCE
IMPORTANT: Ensure that the gas and electricity supplies are isolated before commencing any maintenance or
replacement of components. After completion of any maintenance, always test for gas soundness and carry out a
complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6.1 to 6.7 inclusive.
8.1ROUTINE MAINTENANCE:
8.1.1 Operate the appliance and check for the correct function of the burner and controls.
8.1.2 Turn OFF the gas and electrical supplies to the appliance.
8.1.3 Remove the air heater front panel.
8.1.4 Remove and check the return air filter/cleaner for cleanliness, remove and clean the Air Circulation fan as
detailed in para 8.8.
8.1.5 Remove the Burner and Controls Assembly as detailed in para 8.2. Inspect and clean the main burner and injector
as necessary. Examine the main burner for cracks, including hairline cracks, exchanging the burner as necessary.
8.1.6 Inspect and clear the pilot burner orifice.
8.1.7 Clean the heat exchanger flueways by thoroughly brushing from above and below.
8.1.8 By viewing through the Fan Aperture, and using a torch or similar, examine the heat exchanger externally for signs
of cracks or holes, particularly around welded joints.
8.1.9 Using a torch or similar, introduce a light source into the heat exchanger burner aperture and upper access port,
and again examine the heat exchanger for signs of cracks or holes, particularly around welded joints, whilst again
viewing through the Fan Aperture.
8.1.10 Refit the Air Circulation fan, Burner and Controls Assembly, and air filter/air cleaner.
8.1.11 Light the appliance and note the main burner flame profile. If the flame profile is affected when the Air
Circulation fan switches on, check for any air leaks between the air heater and the base plenum, paying particular
attention to heaters with rear draught diverters. Rectify any air leaks before continuing with this procedure.
8.1.12 Allow the air heater to operate for approximately 15 minutes to ensure stability, and with the main burner lit,
ensure that the operation of Air Circulation fan does not affect the main burner flame profile.
8.1.13 If no defects are found, fully commission the air heater in accordance with the Installation, Commissioning and
Maintenance instructions applicable to the appliance.
ZZ1031/4
8.2BURNER AND CONTROL ASSEMBLY REMOVAL:
8.2.1 Ensure that the Gas and Electrical supplies are switched OFF
8.2.2 Remove the appliance lower front door.
8.2.3 Disconnect the Multifunctional Control electrical connection.
8.2.4 Disconnect the gas supply by breaking the union at the input side of the Multifunctional Control.
8.2.5 Remove the Burner Assembly fixing 3 x screws and withdraw the Burner Assembly.
8.2.6 Refit the Burner and Control Assembly in reverse order.
8.3BURNER ARM REMOVAL AND CLEANING:
8.3.1 Remove the Burner and Control Assembly as detailed in 8.2.
8.3.2 Remove the Pilot Burner Assembly as detailed in para 8.5
8.3.3 Remove the 2 x screws and lock washers securing burner arm to Main Burner Assembly, and remove the burner.
8.3.4 Clean the burner thoroughly both inside and out with a soft brush. DO NOT ENLARGE, DISTORT ORDAMAGE THE BURNER HOLES.
8.3.5 Reassembly or replacement is in reverse order.
8.4MAIN INJECTOR REMOVAL, CLEANING AND REPLACEMENT:
8.4.1Remove the Burner and Control Assembly as details in 8.2
8.4.2Unscrew the main injector from the extension fitted to the housing.
8.4.3Clean as necessary. DO NOT ENLARGE, DISTOR T OR DAMAGE THE MAIN INJECT OR HOLE.
8.4.4If the injector is to be replaced, ensure that it is correctly marked, referring to the Data Badge for details.
8.4.5Refit or replace injector in reverse order.
11
8.5PILOT BURNER ASSEMBL Y , REMOVAL AND REPLACEMENTS:
8.5.1Remove the Burner and Control Assembly as detailed in 8.2
8.5.2Disconnect the Igniter lead from the Piezo unit.
8.5.3Release the Thermocouple locking nuts from the Pilot Assembly and Multifunctional Control, and withdraw the
Thermocouple, taking care to avoid damaging the capillary.
8.5.4 Release the Pilot Feed Pipe from the Pilot Burner.
8.5.5 Remove the 2 x 4mm screws, locking washers and nuts securing the Pilot Burner Assembly to the Main Burner,
and withdraw the Pilot Burner Assembly.
8.5.6 Release and remove the 2 x 4mm screws securing the Igniter electrode to the Pilot Burner and withdraw the
electrode.
8.5.7 Refitting or replacement is in reverse order.
NOTE: When refitting or replacing Thermocouple, tighten only to FINGER TIGHT + 1 FLAT.
8.6MULTIFUNCTIONAL CONTROL REMOVAL:
8.6.1 Remove the Burner and Control Assembly as detailed in 8.2
8.6.2 Disconnect the Thermocouple at the Multifunctional Control, avoiding damage to the capillary.
8.6.3 Disconnect the Pilot Feed Pipe from the Multifunctional Control.
8.6.4 Disconnect the Multifunctional Control input and output supply feeds.
8.6.5 Refitting or replacement is in reverse order.
8.7PIEZO UNIT REMOVAL:
8.7.1 Disconnect the 2 x conductors from Piezo unit.
8.7.2 Unscrew the Piezo retaining nut and remove the unit from its mounting bracket.
8.7.3 Refitting or replacement is in reverse order.
8.8AIR CIRCULATING FAN, REMOVAL AND CLEANING:
8.8.1 Ensure that the electrical supply is isolated.
8.8.2 Remove the appliance lower and upper doors.
8.8.3 Disconnect the Fan Assembly flying lead.
8.8.4 Remove the Fan Assembly securing screw and withdraw the Fan Assembly from the Heater cabinet, avoiding
damage to the fan blades.
8.8.5 Remove all dust from the impeller and motor, avoiding damage to the fan blades.
8.8.6 Refitting or replacement is in reverse order.
8.9CONTROL PANEL REMOVAL:
8.9.1 Ensure that the electrical supply is isolated.
8.9.2 Remove the appliance lower and upper doors.
8.9.3 Release the 2 x 4mm screws securing the Limit Switch cover and withdraw the cover.
8.9.3 Disconnect the following:
a.Fan Assembly flying lead,
b.230V mains ‘L’, ‘N’ and ‘E’ from connection block terminals ‘1’ and ‘3’, and earth stud respectively,
c.Room thermostat from connection block terminals ‘5 and ‘6’,
d.Limit Switch ‘LOAD’ and ‘COMMON’ connections,
e.Fan Control ‘LOAD’, ‘COMMON’ and ‘EARTH’ connections,
f.2 x Override-stat connectors (if fitted),
8.9.4Disconnect the 2 x TTB connections.
8.9.5Release the Multifunctional Control solenoid cover retaining screw, remove the solenoid cover and disconnect
the solenoid wiring.
8.9.6Release the 4 x 4mm screws securing the Electrical Assembly to the heater cabinet and remove the Electrical
assembly.
8.9.7Refitting or replacement is in reverse order.
ZZ1031/4
12
8.10TIME CONTROL REMOV AL:
8.10.1Remove the Electrical Assembly as detailed in sect 8.9.
8.10.2Disconnect the wiring from the Time Control connection block terminals as follows:
a.BROWN conductor from terminal marked ‘L’,
a.BLUE conductor from terminal marked ‘N’,
a.GREEN/YELLOW conductor from terminal marked ‘E’,
a.YELLOW conductor from terminal marked ‘3’,
a.WHITE conductor from terminal marked ‘4’,
8.10.3Release the 2 x securing screws situated on the lower face of the Time Control and remove by partially
withdrawing the bottom of the Time Control and then lifting upwards
8.10.3 Refitting or replacement is in reverse order.
8.10.4 Set the Time Control to the required ON and OFF times.
8.10.5 Set the Time Control to the correct time.
8.11 SUMMER CIRCULATION SWITCH REMOVAL:
8.11. 1Ensure that the electrical supply is isolated.
8.11 . 2Remove the appliance upper and lower doors.
8.11 .3Disconnect the Summer circulation switch.
8.11. 4Release the switch securing bezel, and the remove switch.
8.11. 5Refitting or replacement is in reverse order.
8.12 FAN DELAY CONTROL AND LIMIT SWITCH REMOVAL:
8.12.1 Ensure that the electrical supply is isolated.
8.12.2 Remove the appliance lower and upper doors.
8.12.3 Release the 2 x 4mm screws securing the Limit Switch cover and withdraw the cover.
8.12.4 Disconnect the required control/switch.
8.12.5 Release the 2 x securing screws and remove the required control/switch.
8.12.6 Refitting or replacement is in reverse order.
8.13 TTB REMOVAL:
8.13.1 Ensure that the electrical supply is isolated.
8.13.2 Remove the appliance lower and upper doors.
8.13.3 Disconnect the Fan plug from the Electrical Assembly flying lead.
8.13.4 Release and remove the Fan securing screw and remove the Fan from the fan compartment.
8.13.5 Cover the aperture to the heat exchanger in the top shelf to prevent objects falling into the heat exchanger.
8.13.6 Release and remove the 6 x self tapping screws securing the fan compartment rear plate, and withdraw the rear
plate.
8.13.7 Hold the TTB mounting bracket and release the securing screw, rotate the bracket counter clockwise and
remove.
8.13.8 Disconnect the TTB, taking care to avoid pulling the wires through the grommet in the top of the heater cabinet.
8.13.9 Release the 2 x 4mm screws and remove the TTB.
8.13.10 Refitting or replacement is in reverse order.
8.14 HEAT EXCHANGER ACCESS:
8.14.1 Remove the Burner and Control Assembly as detailed in sect 8.2
8.14.2 Remove the Electrical Assembly and Time Control as detailed in sects 8.9 and 8.10.
8.14.3 Release the 2 x securing screws and remove the heat exchanger access cap and gasket.
8.14.4 Remove the heat exchanger baffle.
8.14.5 Reassembly is in reverse order.
NOTE: When reassembling, ensure that the baffle is pushed fully home and the access cap is fully sealed. In the event of
heat exchanger replacement being necessary , contact Johnson and S tarley Service Department.
ZZ1031/4
13
9.DEFECT DIAGNOSIS
9.1IMPORT ANT : If an electrical defect occurs after installation of the appliance; preliminary earth continuity , polarity ,
and resistance to earth checks should be carried out with a multimeter. On completion of any
maintenance/fault-finding task that has required the breaking and remaking of electrical connections, then checks of
continuity, polarity , and resistance to ear th must be repeated.
9.2W ARNINGS:
9.2.1When purging or checking gas supplies, ensure that the ventilation to the room or cupboard is adequate, and that
all naked lights are extinguished.
SYMPTOMPOSSIBLE CAUSEREMEDY
a. Pilot will not light.i.No gas supply to heater.Check for gas at inlet pressure test
point on Multifunctional Control.
ii.Gas supply pipe not purged.Purge gas supply pipe in accordance
with BS 6891.
iiiPilot orifice restricted.Clear pilot orifice or replace pilot injector.
iv.Piezo system faulty.Check igniter, lead, and electrode.
b. Pilot lights but goesi .Connection between thermo-Check connection is secure.
out on releasing ST ARTcouple and gas
button during initialcontrol not secure.
light-up, or after
normal operation.ii .Faulty power unit onReplace Multifunctional Control.
Multifunctional Control.
ZZ1031/4
iii.Faulty thermocouple.Replace Thermocouple.
iv .Pilot flame too small.Adjust Pilot flame
v .Pilot orifice restricted.Replace pilot injector.
c. Main burner lightsi.Loose electrical connectionCheck fan connections.
but fan fails to runfan control.
after approx. 3 min.
ii.Fan control set incorrectly.Check for correct settings.
iii. Faulty fan assembly.Replace, taking care not to damage
impeller.
iv.Faulty fan control.Replace.
d. Main burner opera-i.Gas rate high.Check gas rate.
ting intermittently
with fan running.ii.Temperature rise excessive.Adjust fan speed.
iii. Air filter or return air pathCheck filter is clean and air path is clear.
restricted.
iv.Excessive number of outletsOpen additional outlets.
closed.
v.Spillage of flue gases.Carry out spillage test and rectify.
vi.Spillage monitor device (TTB)Replace Spillage device (TTB)
faulty.
e. Main burner opera-i.Fan control set incorrectly.Check for correct settings.
ting with intermittent
fan operation.
f. Fan runs for excessive i.Fan control set incorrectly.Check for correct settings.
period or operates
intermittently after
main burner shuts down.
g. Noisy operation.i.Noisy fan motor.Replace fan assembly.
ii.Fan speed setting too high.Adjust fan speed.
14
h. Pilot alight but maini .Mains electrical supply notCheck mains supply .
burner not igniting.connected to heater.
ii.Controls not demanding heatCheck that time control (if fitted) and
room thermostat are operating correctly.
iii. T3.15A fuse failed.Replace. If failure occurs again, check
wiring for short circuits.
iv.Loose connection to room thermo- Check connections.
stat, Limit Switch, gas
control lead, time control, or
transformer.
v.Transformer open circuit.Check with test meter electrical assembly.
vi.Multifunctional control faulty.Replace Multifunctional control.
vii. Limit Switch faulty.Short circuit switch and replace if necessary .
viii. Spillage of flue gasses.Carry out spillage test and rectify.
i x .Spillage monitor device (TTB)Replace
defective
x.Room thermostat or externalFit temporary loop in heater thermostat
wiring faulty.socket. If heater ignites, external circuit
or room thermostat is faulty.
ZZ1031/4
15
Fig. 5, JB25P Mk 5 CIRCUIT DIAGRAM
16
ZZ1031/4
Fig. 6, JB25P Mk 5 FUNCTIONAL DIAGRAM
17
ZZ1031/4
Fig. 7, PRINCIP AL DIMENSIONS (mm)
18
10.SHORT LIST OF SPARES
ITEMG.C.MAKER’SDESCRIPTIONQTY
NoNoNo
1381 7321000-0500130Fan a ssembly1
2244 925B300-0182000Filter tray assembly1
3232 962CL2STime control CL21
4244 9261000-0000070Time control cover1
5384 739BOS 00105Limit Switch1
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.
JOHNSON & ST ARLEY LTD.
Telephone: (01604) 762881Rhosili Road,
Brackmills,
Telefax:(01604) 767408 Northampton NN4 7LZ
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.