These instructions are to be left with the User or adjacent to the Gas Meter
HI-SPEC J50 WARM AIR HEATERS
with MODAIRFLOW and non-MODAIRFLOW Control
INST ALLA TION, COMMISSIONING & SERVICING INSTRUCTIONS
G.C. No 42 451 13
This appliance has been tested and certified for use with natural gas
1.BRIEF DESCRIPTION
16
1
Publication No. ZZ 851/6
October 2006
2
3
4
5
6
8
7
Fig. 1
15
14
13
12
11
10
9
FEA TURES
1Air circulation fan
2Fuse/s
3Electronics module (MODAIRFLOW)
4Spillage monitoring device (TTB) (at rear)
5Multifunctional control
6Limit Switch
7Airflow sensor (Modairflow models)
8Fan delay control (non modairflow models)
9Pilot burner
10Burner and control assembly
1 1Data plate
1 2Piezo unit
13Gas connection
1 4Electrical assembly
1 5Time control
1 6Air filter
1. 1HI-SPEC J50 is an open-flued, fan assisted downflow, ducted warm air heater , which may be supplied with MODAIRFLOW
control and in combination with an ELJAN 6 water circulator. A non-MODAIRFLOW version is available as an option.
A Spillage Monitoring Device (TTB) is fitted which senses the temperature in the draught diverter, and shuts down the
appliance when this temperature rises due to the presence of flue gases.
1. 2The air heater output can be adjusted between 11.72kW (42.2MJ/h, 40,000Btu/h) and 14.65kW (57.75MJ/h, 50,000Btu/h).
“Summer air circulation” of unheated air is available by manual selection (see User’s Instructions). ELJAN 6 output is 3.32kW
(11.5MJ/h, 11.340Btu/h).
THIS APPLIANCE CONFORMS TO BS EN 45014
Installation shall be in accordance with the current editions of:
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt. 1 (Flues for Gas Appliances)
BS 5440 Pt. 2 (Air Supply for Gas Appliances)
BS 5864 Installation of Gas Fired Ducted Air Heaters
Model and Local Authority Bye-laws
132
Page 2
IMPORT ANT : STATUTE LAW DEFINES THA T ALL GAS APPLIANCES MUST BE INSTALLED BY COMPETENT
PERSONS, (i.e. CORGI REGISTERED INSTALLERS) IN ACCORDANCE WITH THE GAS SAFETY
(INST ALLA TION AND USE) REGULA TIONS (CURRENT EDITION). F AILURE T O COMPL Y WITH THESE
REGULA TIONS MA Y LEAD TO PROSECUTION.
2.HEA TER COMP ARTMENT AND CLEARANCES (SEE BS 5864)
2.1IMPORTANT: If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that installation is carried
out such that the rear left hand corner of the heater is aligned with the rear left hand corner of the base duct, so that any
overhang or blanking off will be at the front and/or right hand side. In any event, blanking plates must be mechanically
secured and all joints sealed.
2. 2When the heater is fitted into a compartment, a minimum clearance from the compartment walls of 25mm (1in) at the sides, rear
and front must be left. Consideration should also be given to the space required for the removal and replacement of the filter
tray and the entry of the gas and electrical supplies.
2. 3For service access, a minimum of 450mm (18ins) is required at the front of the heater. Space must also be allowed, in a
compartment installation, to permit the removal of the heater. The clearance between the appliance and the compartment
should not be less than 75mm (3in). However, where clearances are less than 75mm, the internal surface of the compartment
must be lined with non-combustible material. The compartment must be of a fixed rigid structure.
2.4In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of BS 5864
and must be completely separated by either a non-combustible partition or a perforated metal partition with the perforations
not exceeding 13mm (1/2in). The secondary flue must be a tight fit where it passes through the partition and must be suitably
protected (see BS 5440:Part 1).
2.5In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided that in addition, all
internal surfaces, including the base, are non-combustible or lined with non-combustible material. This requirement is
applicable only to dwellings of more than two storeys.
2.6In slot fit installations (see instructions packed with Slotfit Kit TS50), the slot fit compartment must comply with the relevant
section of BS 5864. Side and rear clearances should be not less than 25mm (1in).
Important: Ensure that the rear of the heater is at no time subjected to air pressure subject to leaks from underfloor, joists or
roof spaces.
2.7In freestanding installations (see instructions packed with T op Closure Kit TCS50), only one or two walls will be in close
proximity to the air heater; these must be non-combustible in compliance with the relevant section of BS 5864.
2.8If the appliance is to be installed onto a combustible surface, a suitable base tray (BT50 ) is required. However, when a base
duct is used, this provides sufficient protection for combustible material and no further insulation is required.
2.9For Slot Fix applications (see instructions packed with the Slot Fix Kit), it is important to ensure that the draught diverter relief
is maintained on both sides of the application.
3.VENTILA TION AND COMBUSTION AIR
3. 1The room or internal space in which the heater is installed requires a permanent air vent of minimum effective area 81cm
(12in2). The air vent should be either direct to outside air or to an adjacent room or internal space (other than a toilet or
bathroom) that itself has an equivalent air vent direct to outside.
3. 2Combustion air may be introduced, via a 120mm (5in) nominal bore pipe, connected to a return air duct or plenum from a
ventilated area and fitted with a lockable damper. The damper should be adjusted to control combustion airflow to 0.0137m3/s
(29cfm), (i.e. 1.11m/s [220ft/min] velocity in a 120mm [5in] bore pipe). If this arrangement is used, a non-closeable warm air
register MUST be provided in the same area as the front of the air heater or heater compartment if a return air grille is not
located in that area.
2
3.3When installed in a compartment, two permanent ventilation openings into the compartment are required, one at high level
and one at low level, both communicating either directly with outside air or with a ventilated room or space. The minimum
effective areas specified in Table 1 are related to the rated heat input of the Air Heater, and assuming that an ELJAN 6
circulator is fitted.
3.4If any room or area from which air is drawn for ventilation or combustion contains an extract fan, the permanent vents must be
sized to ensure that the operation of the appliance(s) at full rate is/are not adversely affected. A spillage test as specified in
sub-para 6.8 (Safety Checks) is carried out and any remedial work undertaken.
231
Page 3
T able 1
Minimum Effective Ar eas
4.DUCT SYSTEM
(See British Design Manual - Gas fired W arm Air Heating)
4.1RETURN AIR
4.1.1All return air shall be POSITIVEL Y ducted from outside the compartment to the top of the unit via a return air duct or , if
appropriate, using a Side Return Air Kit SR50, and mechanically secured. It is recommended that the return air duct not
be routed directly from the main living area, but from a convenient central area serving the remainder of the dwelling.
4.1.2The return air system should be constructed of fire-resistant material. The flue shall not be run through an area serving
as a return air path. It is extremely important that the correct size of return air grilles and ducting is used. For heaters on
maximum output the return air duct size should not be less than the equivalent of 300mm x 250mm (12" x 10"). If flexible
duct is used the duct diameter should not be less than 350mm (14") dia. The return air grille should have a free area of
not less than 1266cm2 (196in2).
4.1.3An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to
which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m2/kW
(1in2/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC.’ s.
4.1.4The return air duct should allow for ease of removal for access to the flue.
4.1.5All duct work in the room or internal space in which the heater is installed shall be mechanically secured, and sealed
with ducting tape.
4.2W ARM DELIVERED AIR
4.2.1All duct work, including riser ducts, should be fully insulated with 50mm (2in) fibreglass or similar. If short extended
duct runs are taken below floor level these should be similarly insulated, and in addition wrapped with a sound vapour
proof barrier, and protected from crushing.
4.2.2The duct system should be carefully designed to suit the needs of its specific heating requirements and building
layout. The type of duct system, (i.e. radial/extended plenum/stepped) should be installed using the least number of
fittings to minimise airflow resistance. The base duct, which equalises the air pressure to supply ducts, shall be
constructed to support the weight of the heater, which shall be secured to the plenum with screws on at least two
sides, and sealed using self-adhesive foam strip, ducting tape or sealing compound. All ducting and blanking plates
shall be mechanically secured and sealed.
5.INST ALLA TION REQUIREMENTS
Note: For ELJAN 6 circulator Installation Instructions, see separate instructions ZZ778.
5.1 FLUES (see British Standards BS 5440 Pt. 1 Flues)
5.1.1All joints shall be soundly sealed.
5.1.2The flue should be kept as short and warm as possible.
5.1.3Sufficient support brackets shall be installed to bear the weight of the total flue system.
5.1.4The spigot connection of the heater draught diverter will accept internally the spigot end of a non-asbestos flueto BS
567 or twin wall metal flue to BS 715 of nominal 100mm (4in) diameter.
5.1.5A split collar should be fitted to provide for flue maintenance or inspection.
5.1.6The flue shall be in accordance with the Building Regulations and British Gas Materials and Installations specification
3rd edition) with regard to clearance and shielding from combustible materials.
330
Page 4
5.1.7All materials shall be in accordance with Building Regulations requirements.
5.1.8The flue should run as vertically as possible. Horizontal runs should be avoided if at all possible and any directional
change should be as gentle as possible. If there is any doubt about the flue configuration, the equivalent flue height
should be determined (see 5.1.11).
5.1.9If the appliance to be fitted is a replacement, the old appliance should be checked for signs of spillage prior to
commencement of the installation and appropriate action taken, (i.e. check flue system and renew as necessary).
5.1.10 It is recommended that at least 600mm of vertical flue should be provided from the top of the draught diverter (for new
installations this shall be incorporated into the flue design). However, when carrying out replacement installations, an
existing flue system may be encountered, where the vertical flue above the appliance to the first bend is less than
600mm. In the first instance, the installer must judge whether this distance can be achieved practicably by some means.
Where this is not practicable, the existing flue system may be used, providing there is no evidence of spillage from the
old appliance (see 5.1.9 above). Every effort must be made, however, to ensure that the existing flue complies in every
other way to BS 5440 Part 1, including the visual inspection, flue flow and spillage test described in 4.3.2 of the above
standard. Flue configurations may be assessed in terms of equivalent vertical height - details are given in 5.1.11. For air
heaters, the minimum equivalent vertical height is 1 metre. The installer must make a judgement based on his
knowledge and experience and the examination and testing described above as to whether an existing flue system can
be used.
Note: Ventilation of the compartment, room or internal space in which the appliance is to be installed must be checked for
compliance with the requirements of BS 5440 Part 2 ( Ref. Section 3 of these instructions) and upgraded as necessary.
5.1.11 Calculation method for flue sizing: ( from BS 5440: Part 1, Appendix A)
a.This appendix provides a procedure for estimating whether a given flue design is likely to ensure full clearance of
combustion products.
b.The procedure is based on calculating the ‘equivalent height’ of the flue under consideration, (i.e. that height of the
straight vertical circular flue pipe of specific size which will produce the same flow rate as the flue under
consideration). The equivalent height is calculated from the formula:
(Ki + Ko )
e
He = Ha x ____________________
(Ki + Ko)a - KeHa + Sum K
where:
He is the height of the equivalent flue;
Ha is the vertical height of the actual or proposed flue;
Ki is the inlet resistance of the flue;
Ko is the outlet resistance from the flue;
subscript e refers to the equivalent flue diameter;
subscript a refers to the actual or proposed flue diameter;
Ke is the resistance per unit length of the equivalent flue;
Sum K is the resistance (other than the inlet and outlet resistance) of the actual or proposed flue.
Note: K and Sum K are obtained from T able 2. Ko and Ki are obtained from T able 3.
c.T able 2 gives resistance factors for common flue components for use in the formula. Table 3 contains the appropriate
inlet and outlet flue resistances, (the flue is likely to be satisfactory if its equivalent height exceeds 1m).
d.W orked Calculation Example:
A warm air unit with a 100 mm diameter flue spigot, fitted with a pre-fabricated flue system leading to a ridge tile in the loft (refer Fig.
2):
From table 3:
Kia Inlet resistance of actual flue= 2.5
Koa Outlet resistance of actual flue= 2. 5
Kie Inlet resistance of equivalent flue= 2. 5
Koe Outlet resistance of the actual flue= 2.5
4
Page 5
Resistance factors for use in calculating equivelent lengths
From table 2:
Other resistances of actual flue:
Terminal= 2.5
Pipe bend ( 2 x 0.61)= 1.22
Pipe (4 x 1m @ 0.78)= 3.12
(5 x 0.3m @ 0.78)= 1.17
Sum K= 8.01
Equivalent height:
T able 2
T able 3
Inlet and outlet resistance
From the formula
(2.5 + 2.5)
He = 6.2 x ______________________
(2.5 + 2.5) - (0.78 x 6.2) + 8.01
He = 3.793 This flue exceeds 1.0m equivalent height and is therefore satisfactory .
528
Page 6
Ha = 6.2m
Ridge T erminal
2 x 300 mm lengths
100 mm dia flue pipe
4.6m
4 x 1000 mm lengths
45O bend
300 mm length
1.6m
Fig. 2
Worked example of equivalent flue height
5.1.12 Where flue blocks are used, builders should ensure that no obstruction is created during erection. The installer should
ensure that the connection flue does not project beyond the internal wall of the flue blocks and that there is provision
for examination and servicing.
5.1.13 Important: Before installing the appliance, carry out a visual check of the flue system as directed in the relevant
section of BS 5440 Pt. 1, then check the flue performance as follows:
a.Close all doors and windows in the room in which the appliance is to be installed.
b.Introduce some heat into the flue, using a blow torch or other means.
45O bend
2 x 300 mm lengths
Flue spigot
c.Carry out a flow visualisation check with a smoke pellet at the intended position for the appliance. Ensure that
there is discharge of smoke from the correct terminal only , and no spillage into the room. Smoke coming out of
other than the correct terminal only, or a down draught or ‘no flow’ condition, indicates that the flue has failed
the test, and the appliance shall not be connected until the defect has been found and rectified, and the test
satisfactorily completed.
627
Page 7
5.2ELECTRICAL
5.2.1Mains.
a.The heater is supplied with mains cable (PVC sheathed, heat resisting to 85oC), 3-core Brown-Blue-Green/Y ellow ,
6A, 0.75mm2), connected to a terminal block and exiting through the heater at the right hand top front. The cable
is suitable for a 230V 50Hz supply and shall be connected to the fixed wiring using a double pole switched,
fused spur, incorporating a protective earth link. The fuse fitted shall be rated 5A to BS 1362. Connections shall
be in accordance with the current edition of I.E.E Regulations BS 7671.
b.MODAIRFLOW Models: An electronic control (Thermista-stat) is supplied which acts as a room thermostat.
c.Non-MODAIRFLOW models: A 24V room thermostat (not supplied), that complies with BS 800, BS 3955 and BS
4201 is essential to ensure close control of comfort conditions. An anticipator is located within the thermostat
and is graded in amps. The anticipator should be checked and adjusted to 0.2A.
5.2.2Thermista-stat/Room Thermostat and its location.
a.The Thermista-stat/Room Thermostat should be located where there is free air circulation approx. 1.5m (5ft) from
the floor.
b.A void the following locations:-
i )In a room where temperature is greatly affected by the sun or any other heat source, e.g. radiant fire, wall
light fittings or TV set.
i i)Near an outside door or windows, or on an outside wall.
iii)Where affected by warm air ducts, diffusers, waste pipes or the heater itself.
iv)Where subject to vibration.
c.For MODAIRFLOW models, connect Thermista-stat wires to control panel terminals ‘4’ and ‘5’ (see Fig. 5a and
6a), connection polarity being important, connect +ve side on control panel to +ve side on Thermista- stat.
d.For non-MODAIRFLOW models, connect room thermostat wires control panel terminals ‘16’ and ‘17’
5.3GAS(SEE BS 5864 AND BS 6891)
5.3.1An independent gas supply pipe from the meter is to be preferred wherever possible. When this is not possible, the
pipe must be capable of taking the complete input of the heater and all other gas appliances being served by this same
pipe. This supply should be suitably sized to conform to British Standards requirements of no more than 1.0 mbar (0.4in
wg) pressure drop (See table of discharge in BS 6891).
5.3.2The 1/2in union gas cock (supplied) must be fitted to the gas inlet of the heater for easy isolation during servicing. The
gas pipe should be fitted and installed so that it is durable, substantial and gas tight. To assist in determining whether
a gas connection may not be tight, a leak detection fluid should be applied around the connection. Under no
circumstances should a flame be used to locate a gas leak. Gas entry to the air heater is through either side to a Rc1/
(1/2in BSP . external [taper] thread).
5.4DRAUGHT DIVERTER & DEFELCT OR PLATE:
5.4.1The HI-SPEC J50 heater is supplied with a draught diverter which houses the TTB, and which requires fitting to the
rear of the heater prior to installation, using 6 x 4mm screws and lock washers (provided). Connect the TTB to the
terminal block situated on the rear upper left hand corner of the appliance.
5.4.2The deflector plate prevents spillage from the draught diverter in the event of a leak between the air heater and the
base plemum and MUST be fitted as shown in fig 3 using the screws provided.
5.5DEFLECTOR PLA TE SAFETY CHECK:
2
In order to ensure that the deflector plate is preventing warm air from entering the draught diverter and therefore causing spillage, the
following test MUST be carried out BEFORE commissioning:
5.5.1Turn on the power supply to the heater.
5.5.2Set the summer airflow switch to “on”.
5.5.3Using a smoke match, introduce smoke into the heat exchanger at the burner opening.
5.5.4Ensure that the smoke is drawn into the heat exchanger and not blown back from the burner opening.
5.5.5If smoke is blown back from the burner opening, check for air leaks between the heater and the base plenum,
paying particular attention to the rear of the heater directly beneath the draught diverter.
Page 8
6.COMMISSIONING
6.1PREPARATION:
6.1.1Ensure that:
HEA TER
DEFLCTOR PLA TE
a.Gas and Electrical supplies are OFF.
b.Filter, fan and fan compartments are free from
obstructions.
c.All registers or grilles are open and conform to
design specifications.
d.Return, relief and ventilation air installations are
adequate.
6.1.2 SE TT IN G F A N SPEED (NON MODAIRFLOW MODELS ONL Y):
6.1.2.1 Remove air filter and chamber door.
6.1.2.2 Ensure fan control is set to “100o” OFF and “40o” DIFF
6.1.2.3 Ensure overheat (limit) control is set to “200o F” This control is not to be set to any other setting!
6.1.2.4 Refit fan chamber door and air filter.
6.2SYSTEM BALANCING:
6.2.1Set the Air Heater electrical supply ON.
6.2.2Set the ‘SUMMER AIR CIRCULATION’ switch to ‘ON’.
6.2.3Balance the ducting system to provide the required volume proportions at the
warm air outlets.
NOTE: If the system includes ceiling diffusers, air velocities through these should be NOT
LESS THAN 1.5m/s (300 ft/min), except for very small rooms (i.e., bathrooms
etc.). Outlet faces may require partial blanking in order to achieve this.
6.2.4Set the ‘SUMMER AIR CIRCULATION’ switch to ‘OFF.
130mm
Fig. 3
Deflector Plate Fitted
Thermocouple
Pilot Burner
Electrode
6.3IGNITION OF PILOT AND MAIN BURNERS:
W ARNING: If the Pilot Burner is extinguished either intentionally or unintentionally , no
attempt should be made to relight the gas for a minimum of 3 minutes. Ensure
that the Electrical supply , Time Control and Selector switches are set to
‘OFF’.
6.3.1Set the Thermista-stat/room thermostat to its lowest or OFF setting.
6.3.2On the Multifunctional Control, remove the Outlet Pressure test point cover,
and a fit pressure test gauge (refer Fig. 5).
6.3.3Turn the heater Gas supply ON, test for gas soundness and purge the whole
gas pipe as described in BS 6891.
Pilot Burner Assembly
6.3.4Referring to Fig .5, press and hold the OPERA TING CONTROL, and whilst
observing the Pilot Burner, repeatedly press the Piezo igniter button until the
Pilot Burner ignites.
6.3.5After 20 seconds release the OPERA TING CONTROL and let it spring out; ensure that the Pilot Burner remains alight.
If the Pilot Burner extinguishes, rotate the OPERA TING CONTROL clockwise to the ‘l’ position and ensure that the
OPERA TING CONTROL is fully reset. W ait three minutes and repeat steps 6.3.4 and 6.3.5 until Pilot Burner remains
alight.
Fig.4
Page 9
6.3.6Ensure that the pilot flame envelops the thermocouple tip, adjusting the Pilot Adjuster as required (Refer Figs. 4 and
5).
6.3.7Set the Heater Electricity supply ON.
6.3.8Set the Time Control to the required Heating On periods.
6.3.9Set the Selector switch to ‘TIMED’.
6.3.10 Set the Thermista-stat or room thermostat to MAXIMUM.
6.3.11 Ensure that the Main Burner has now ignited.
6.3.12 Test for gas leakage at the supply, Multifunctional Control, and Pilot and Main Burners using proprietary detection
fluid, sealing any leaks found.
6.3.13 Allow the heater to operate for a minimum of 15 minutes to ensure stability .
6.4MAIN BURNER PRESSURE TEST:
NOTE: AIR HEATER BURNERS ARE FACTOR Y SET TO PROVIDE A NOMINAL HIGH RA TE OUTPUT AS DETAILED IN SUB
P ARA 1.2
6.4.1Referring to Table 4 and Fig. 5 below, ensure that the pressure test gauge indicates correct burner pressure, resetting
if required as follows:
a.At the Multifunctional Control:
i .Remove the Burner Pressure Adjuster cover .
ii.Set the Burner Pressure Adjuster to provide a pressure test gauge indication for the correct burner
pressure as detailed in Table 4.
iii.Refit the Burner Pressure Adjuster cover.
3
4
Fig. 5
Multifunctional Control
1
1. Operating control
2. Burner Pressure Adjuster
2
3. Outlet Pressure test point
4. Pilot Adjuster
6.4.2Apply the pressure set arrow to indicate the appropriate burner pressure on the data badge.
6.5EXTINGUISHING OF PILOT AND MAIN BURNERS:
6.5.1On the Multifunctional Control, rotate the OPERA TING CONTROL clockwise to the ‘O’ position and ensure that the
OPERA TING CONTROL fully resets, and both Pilot and Main Burners are extinguished.
6.5.2On the Multifunctional Control, remove the pressure test gauge and refit the Outlet Pressure test point cover, and test
for gas soundness.
6.6TEMPERA TURE RISE CHECK:
6.6.1Ignite the Pilot and Main Burners and allow to operate for 15 minutes to ensure stability.
6.6.2With the Main Burner operating continually, check that the temperature rise across heater is between 45oC - 55oC,
setting the fan speed accordingly, (decrease fan speed to increase temperature rise). For MODAIRFLOW heaters,
adjusting the balancing screw sets fan speed; for non-MODAIRFLOW heaters, fan speed is adjusted by selecting the
fan speed at the control panel (decrease voltage selection to decrease fan speed).
924
Page 10
Note: T apping 1 = 150V, T APPING 2 = 170V, T APPING 3 = 190V , T APPING 4 = 210V, T APPING 5 = 230V.
6.7AUTOMATIC CONTROLS CHECK:
6.7.1Set the TIME CONTROL to ‘ON’.
6.7.2Turn the Thermista-stat or room thermostat slowly clockwise until the Main Burner ignites.
6.7.3Ensure that the fan starts to operate after a short period (approx. 1-2 minutes).
MODAIRFLOW models:
6.7.4Ensure that the fan speed increases to full speed.
6.7.5When the temperature reaches the control setting, check that the Main burner cycles ON and OFF, at approximately
75 to 120 seconds.
Non-MODAIRFLOW models:
6.7.6When the temperature reaches the control setting, ensure that the Main Burner extinguishes followed by the fan
switching off after a short period.
6.7.7When the temperature falls below the control setting, ensure that the Main Burner re-ignites followed by fan
operation.
6.8SAFETY CHECKS:
6.8.1Check for gas soundness within the appliance.
6.8.2Spillage test: Carry out a full spillage test as follows, and ensure that the flue operates effectively with all doors
closed and any extractor fans in operation.
NOTE: If an extractor fan is situated in an adjoining or adjacent room, carry out the spillage test with the interconnecting doors
open.
If the draught diverter is accessible:
a.Introduce smoke into the draught diverter adjacent to an exit from the heat exchanger, by means a smoke match or
puffer.
b.Ensure that there is no spillage present (indicated by displacement of smoke downwards and out of the draught
diverter).
If the Draught Diverter is not accessible:
a.Introduce smoke, by means of part of a smoke pellet on a non-combustible support, into the heat exchanger.
b.Extinguish the Main and Pilot burners.
c.Ensure that there is no spillage evident by visually observing the draught diverter location on the air heater.
d.If spillage is evident, further investigation and rectification is required before re-testing the appliance.
e.Repeat spillage tests but with the fan running, or Summer Airflow switch set to ON.
W ARNING: The appliance shall not be left connected to the gas supply unless it has successfully passed the spillage test.
6.8.3Turn OFF the gas supply at the service cock and ensure that the Multifunctional Control fail-safe operates within 60
secs (indicated by loud click from Multifunctional Control).
T able 4
Main Burner Pressure Settings
1023
Page 11
mbar in.wg.
0.500.20
0.375 0.15
0.250.10
Response
Area
RESIST ANCE EXTERNAL T O HEA TER
35 040 04 5 050 055 0600 ft
0.1650.1890.2120.2360.2560.283 m3/sec
AIR VOLUME
T able 5
Fan Performance Curve
6.8.4Turn the gas supply ON at service cock.
6.8.5Switch the appliance electrical supply OFF .
6.8.6Disconnect the fan at the flying socket
6.8.7Switch the appliance electrical supply ON.
6.8.8Ignite the Main and Pilot Burners as detailed in sub para 6.3.1 to 6.3.5
6.8.9Ensure that the Limit Switch operates, indicated by the Main Burner extinguishing, within 120 and 180 seconds.
6.8.10 Switch the appliance electrical supply OFF .
6.8.11 Reconnect the Air Heater Fan.
6.8.12 Switch the appliance electrical supply ON.
6.8.13 Ensure that the Main Burner re-ignites when the appliance temperature reduces, (note: with the fan disconnected, there
may be some delay before the Main Burner re-ignites).
3
/min
7.INSTRUCTIONS FOR USERS
7.1If the building is unoccupied, ensure that the Instructions for the User are left taped to the air heater, and that the Installation,
Commissioning and Maintenance Instructions are left at or near the air heater for use on future service calls.
7.2If the building is occupied, hand the User Instructions over and ensure the User understands:
7.2.1How to ignite the Pilot and Main Burners.
7.2.2How to operate the Thermista-stat/room thermostat, time and heater ON/OFF switch and summer air circulation switch,
and that the time control must be reset following a power failure.
7.2.3How to extinguish the Pilot and Main Burner at the Multifunctional Control, and switch off the electrical supply to the
heater.
7.2.4How to remove, clean and refit the air filter and at what intervals (i.e. fortnightly, or weekly for new houses.)
7.2.5How to control the heating system by opening and closing warm air outlets.
7.2.6How to obtain summer air circulation.
7.2.7That the air grilles on the heater or heater compartment; grilles and ventilators in the walls, windows or doors of the
building must not be obstructed.
7.2.8That the heater must be serviced at least once a year by a competent person to ensure efficient and safe operation.
7.2.9That the red instructions for safe use have been pointed out and understood.
7.2.10 That expert help must be obtained if persistent failure of the pilot burner occurs.
1122
Page 12
8.MAINTENANCE
IMPORTANT: Ensure that the gas and electricity supplies are isolated before commencing any maintenance or replacement of
components. After completion of any maintenance, always test for gas soundness and carry out a complete functional test of the
appliance in accordance with the Commissioning Instructions at Sect 6.1 to 6.8 inclusive.
8.1ROUTINE MAINTENANCE:
8.1.1Operate the appliance and check for the correct function of the burner and controls.
8.1.2Turn OFF the gas and electrical supplies to the appliance.
8.1.3Remove the air heater front panel.
8.1.4Remove and check the return air filter/cleaner for debris, remove and clean the Air Circulation fan as detailed at S 8.8.
8.1.5Remove the Burner and Controls Assembly as detailed in para 8.2. Inspect and clean the main burner and injector as
necessary . Examine the main burner for cracks, including hairline cracks, exchanging the burner as necessary .
8.1.6Inspect and clear the pilot burner orifice.
8.1.7Clean the heat exchanger flueways by thoroughly brushing from above and below.
8.1.8By viewing through the Fan Aperture, and using a torch or similar , examine the heat exchanger externally for signs of
cracks or holes, particularly around welded joints.
8.1.9Using a torch or similar, introduce a light source into the heat exchanger burner aperture and upper access port, and
again examine the heat exchanger for signs of cracks or holes, particularly around welded joints, whilst again viewing
through the Fan Aperture.
8.1.10 Refit the Air Circulation fan, Burner and Controls Assembly , and air filter/air cleaner .
8.1.11 Light the appliance and note the main burner flame profile. If the flame profile is affected when the Air Circulation fan
switches on, check for any air leaks between the air heater and the base plenum, paying particular attention to heaters
with rear draught diverters. Rectify any air leaks before continuing with this procedure.
8.1.12 Allow the air heater to operate for approximately 15 minutes to ensure stability and, with the main burner lit, ensure
that the operation of Air Circulation fan does not af fect the main burner flame profile.
8.2BURNER AND CONTROL ASSEMBL Y REMOVAL:
8.2.1Ensure that the Gas and Electrical supplies are switched OFF
8.2.2Remove the appliance lower front door.
8.2.3Disconnect the igniter at the Piezo unit.
8.2.4Disconnect the Multifunctional Control electrical connection.
8.2.5Disconnect the water heater (if necessary).
8.2.6Disconnect the gas supply by breaking the union at the input side of the Multifunctional Control.
8.2.7Remove 6 x Burner Assembly fixing screws and withdraw the Burner Assembly .
8.2.8Refit the Burner and Control Assembly in reverse order , ensuring that the spillage baf fle above the Burner Assembly
contacts the top of each burner arm.
8.3MAIN BURNER ASSEMBL Y CLEANING:
8.3.1Remove the Burner and Control Assembly as detailed in 8.2.
8.3.2Clean the burner thoroughly both inside and out with a soft brush. DO NOT ENLARGE, DISTORT OR DAMAGE
BURNER HOLES.
8.3.3Reassemble in reverse order.
8.4MAIN INJECTORS REMOVAL, CLEANING AND REPLACEMENT :
8.4.1Remove the Burner and Control Assembly as details in 8.2
8.4.2Remove 2 x screws securing the Pilot Burner assembly to the Burner and Control Assembly and withdraw the Pilot
Burner assembly , taking care to avoid damage to the thermocouple capillary .
8.4.3Remove 2 x screws securing the Burner arm to the Burner and Controls Assembly , and withdraw the Burner Arm.
8.4.4Unscrew 2 x Main injectors, and 1 x cross lighter injector from their housings.
8.4.5Clean as necessary. DO NOT ENLARGE, DISTORT OR DAMAGE MAIN INJECT OR HOLES.
8.4.6If the injectors are to be replaced, ensure that they are correctly marked, referring to the Data Badge for details.
8.4.7Refit or replace the injectors in reverse order.
1221
Page 13
8.5PILOT BURNER, THERMOCOUPLE AND ELECTRODE, REMOV AL AND REPLACEMENT:
8.5.1Remove the Burner and Control Assembly as detailed in 8.2
8.5.2Disconnect the Igniter lead from the Piezo unit.
8.5.3Disconnect the Thermocouple from the Thermocouple adapter on the Multifunctional Control, taking care to avoid
damage to the thermocouple capillary.
8.5.4Release the Pilot Feed Pipe from the Multifunctional Control.
8.5.5Remove 2 x 4mm screws securing the Pilot Burner assembly to the Burner and Control assembly, and withdraw the Pilot
Burner Assembly.
8.5.6Release the Thermocouple securing nut from the Pilot Burner assembly and withdraw the Thermocouple, taking care to
avoid damaging the Thermocouple capillary .
8.5.7Release the Electrode securing nut from the Pilot Burner assembly and withdraw the Electrode.
8.5.8Release the Pilot Feed Pipe securing nut from the Pilot burner assembly and withdraw the Pilot Feed Pipe and Pilot
Injector from the Pilot Burner assembly, and disconnect the Pilot Injector from the Pilot Feed Pipe hook.
8.5.9Refitting or replacement is in reverse order.
NOTE: When refitting or r eplacing Thermocouple, tighten only to FINGER TIGHT + 1 FLA T.
8.6MUL TIFUNCTIONAL CONTROL REMOV AL:
8.6.1Remove the Burner and Control Assembly as detailed in 8.2
8.6.2Disconnect the Thermocouple at the Multifunctional Control (including the adapter), avoiding damage to the capillary .
8.6.3Disconnect the Pilot Feed Pipe from the Multifunctional Control.
8.6.4Disconnect the Multifunctional Control input and output supply feeds.
8.6.5Refitting or replacement is in reverse order.
8.7PIEZO UNIT REMOV AL:
8.7.1Disconnect 2 x conductors from Piezo unit.
8.7.2Unscrew the Piezo retaining nut and remove the unit from its mounting bracket.
8.7.3Refitting or replacement is in reverse order.
8.8AIR CIRCULATING F AN, REMOV AL AND CLEANING:
8.8.1Ensure that the electrical supply is isolated.
8.8.2Remove the appliance lower and upper doors.
8.8.3Disconnect the 230V connections (L/N/E) from the Fan Assembly .
8.8.4Release 4 x screws securing the control panel, and withdraw the panel, avoiding damage to wiring.
8.8.5Release 2 x Fan Assembly securing screws and withdraw the Fan Assembly from the Heater cabinet, avoiding damage
to fan blades.
8.8.6Remove all dust from the impeller and motor, avoiding damage to the fan blades.
8.8.7Refitting or replacement is in reverse order.
8.9ELECTRICAL ASSEMBL Y REMOV AL:
8.9.1Ensure that the electrical supply is isolated.
8.9.2Remove the appliance lower and upper doors.
8.9.3Release 2 x 4mm screws securing the Limit switch cover and the withdraw cover.
8.9.4Release the Electrical Assembly cable clamp,
MODAIRFLOW models:
8.9.5Disconnect the following:
a.Disconnect 230V connections (L/N/E) from Fan Assembly ,
b.230V mains ‘L’, ‘N’ and ‘ E’ from connection block terminals ‘1’, ‘3’ and ‘2’ respectively ,
c.Thermista-stat connections from connection block terminals ‘4’ (+ve) and ‘5’ (-ve),
d.Limit Switch ‘LOAD’ and ‘COMMON’ connections,
e.2 x Airflow sensor connections,
1320
Page 14
NON-MODAIRFLOW models:
8.9.6 Disconnect the following:
a.Disconnect 230V connections (L/N/E) from the Fan Assembly ,
b.230V mains ‘L’, ‘N’ and ‘E’ from connection block terminals ‘1’ and ‘ 3’, and earth stud respectively ,
c.Room thermostat from connection block terminals ‘5’ and ‘6’,
d.Limit switch ‘LOAD’ and ‘COMMON’ connections,
e.Fan Control ‘LOAD’, ‘COMMON’ and ‘EARTH’ connections,
Both model types:
8.9.7Disconnect 2 x TTB connections.
8.9.8Disconnect the Multifunctional Control connections.
8.9.9Disconnect the W ater Circulator electrical connections (if fitted).
8.9.10 Release 4 x 4mm screws securing the Electrical assembly to the heater cabinet and remove the Electrical assembly ,
releasing wiring from cable clamps and grommets as required..
8.9.11 Refitting or replacement is in reverse order.
8.10ELECTRONIC MODULE REMOV AL (MODAIRFLOW MODELS ONLY)
8.10.1 Remove the Electrical Assembly as detailed in sect 8.9.
8.10.2 Disconnect the Electronic Module from the Electrical Assembly .
8.10.3 Release 3 x screws securing the Electronic Module to the Electrical Mssembly and remove the module.
8.10.4 Refitting or replacement is in reverse order.
8.11TRANSFORMER REMOV AL (MODAIRFLOW MODELS ONLY):
8.11.1 Remove the Electrical Assembly as detailed in sect 8.9.
8.11.2 Disconnect the Transformer from the Electrical Assembly terminal block, and the fuse from the Earth stud,
8.11.3 Release 2 x screws and nuts securing the Transformer to the Electrical Assembly, and remove the T ransformer .
8.11.4 Refitting or replacement is in reverse order.
8.12TIME CONTROL REMOV AL:
8.12.1 Ensure that the electrical supply is isolated.
8.12.2 Release the securing screw situated on the lower face of the Time Control and remove it by partially withdrawing
bottom of the Time Control and then lifting upwards.
8.12.3 Disconnect the Time Control electrical connections from its integral terminal strip.
8.12.4 Refitting or replacement is in reverse order.
8.12.5 Set the Time Control to the required ON and OFF times.
8.12.6 Set the Time Control to the correct time.
8.13FAN DELA Y CONTROL, LIMIT SWITCH AND AIRFLOW SENSOR REMOV AL:
NOTE: Airflow sensor applies to MODAIRFLOW models only , whilst Fan Delay Control applies solely to non-MODAIRFLOW
models.
8.13.1 Ensure that the electrical supply is isolated.
8.13.2 Remove the appliance lower and upper doors.
8.13.3 Release 2 x 4mm screws securing the Limit Switch cover and withdraw the cover.
8.13.4 Disconnect the required control/switch.
8.13.5 Release 2 x securing screws and remove the required control/switch.
8.13.6 Refitting or replacement is in reverse order.
1419
Page 15
8.14SPILLAGE MONITOR DEVICE (TTB) REMOV AL:
8.14.1 Ensure that the electrical supply is isolated.
8.14.2 Remove the appliance lower and upper doors.
8.14.3 Remove the Air Circulation fan as detailed in para 8.8.
8.14.4 Cover the aperture to the heat exchanger in the top shelf to prevent objects falling into the heat exchanger .
8.14.5 Release and remove 6 x screws securing the fan compartment rear access panel, and withdraw the panel.
8.14.6 Disconnect the TTB terminal block plug from the terminal block socket, situated on the compartment rear bulkhead,
remove the grommet rearwards and pass the terminal block through the aperture in the rear bulkhead.
8.14.7 Release and remove the 5mm nut and lock washer securing the TTB Assembly to the Draught Diverter , and withdraw
the TTB Assembly .
8.14.8 Refitting or replacement is in reverse order.
8.15H EA T E XC H AN G ER ACCESS:
8.15.1 Release 2 x securing screws and remove heat exchanger access caps and gaskets.
8.15.2 Remove the heat exchanger baffles.
8.15.3 Reassembly is in reverse order .
NOTE: When reassembling, ensure that the baffles are pushed fully home and the access caps are fully sealed. In the event of
heat exchanger replacement being necessary , contact Johnson and S tarley Service Department.
9.DEFECT DIAGNOSIS
9.1IMPORT ANT :
If an electrical defect occurs after installation of the appliance; preliminary earth continuity, polarity, and resistance to earth
checks should be carried out with a multimeter. On completion of any maintenance/fault-finding task that has required the
breaking and remaking of electrical connections, then checks of continuity , polarity, and resistance to earth must be
repeated.
9.2W ARNINGS:
9.2.1When purging or checking gas supplies, ensure that ventilation to the room or cupboard is adequate, and that all
naked lights are extinguished.
9.2.2MODAIRFLOW models: Before commencing defect diagnosis, ensure that the Thermista-stat is set to maximum,
mains supply is ‘ON’ and the time control is at an ‘ON’ position.
9.2.3Care is to be taken during the replacement and handling of electronic assemblies, (i.e., electronic panel, airflow sensor
or Thermista-stat). It is not practical to rectify defects on these assemblies, except at the manufacturer , and any
attempt to do so may render the guarantee or factory replacement arrangement invalid.
1518
Page 16
Symptom
A) Pilot will not light
B ) Pilot lights but goes out on releasing
ST AR T button during initial light-up,
or after normal operation.
C ) Main burner lights but the fan fails to
run after approx. 3 mins.
Possible Cause
1) No gas to the heater
2) Gas supply not purged
3) Pilot orifice restricted
4) Piezo system faulty.
5) Excessive gas supply pressure
1) Connection between thermocouple and
mutifunctional control not secure
2 ) Faulty power unit multifunctional
control
3 ) Faulty thermocouple
1) No voltage to fan
2) Loose electrical connection on fan
delay control
3) Fan delay control set incorrectly
4) Faulty fan assembly
5) Faulty fan delay control
Remedy
Check for gas at inlet pressure test point
on the multifunctional control
Purge gas suply pip in accordance with BS
6891
Clear pilot orifice or replace pilot injector
Check igniter, lead and electrode.
Check that the mains gas pressure is 20
mbar and reduce if necessary .
Check that connection is secure.
Replace multifunctional control
Replace thermocouple
Check connections from electrical panel to
fan.
Check connections
Check for correct settings
Replace, taking care not to damage impeller
Replace
D )Main burner operating intermittently
E) Main burner operating with
intermittent fan operation
F) Fan runs for excessive periods or
intermittently after main burner shuts
down
G) Noisy operation
MODAIRFLOW MODELS
H ) Incorrect operation of fan and main
burner
1) Gas rate or burner pressure setting
high
2 ) T emp rise excessive
3 ) Air filter or return air path restricted.
4 ) Excessive number of oulets closed
5 ) Spillage of flue gases.
6 ) Spillage monitoring device (TTB) faulty.
1) Gas rate or burner pressure setting too
low
2) Fan delay control set incorretly
1) Fan delay control set incorrectly
1) Gas pressure too high
2 ) Noisy fan motor
3) Fan speed setting too high
1 ) Fault related to Modairflow Control
system.(See relevant pages)
Check gas rate and burner pressure
setting.
Adjust fan speed or gas rate accordingly
Check that filter and air path is clear
Open additional outlets
Carry out spillage test and retify
Replace TTB
Check gas rate and burner pressure
settings
Check for correct settings
Check for correct settings
Check burner pressure settings
Replace fan assembly
Adjust fan speed
Consult diagnostics chart and follow
recommended procedure.
NON-MODAIRFLOW MODELS
I) Pilot alight but main burner not igniting
1) Mains electrical suply not connected
to heater.
2 ) No demand for heat
3 ) 3A fuse failed
4) Loose connection to rom thermostat,
limit switch, Multifunctional Control
lead, Time Control or transformer
When all of the above services have been completed, please contact your service engineer for an additional
service record sheet.
Page 30
NOTES:
Page 31
NOTES:
Page 32
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you
have a problem in obtaining a spare part, please contact Johnson and Starley Spares Department at