Johnson Controls Series 20 J**ZJ models are either single
package air conditioners equipped with optional factory
installed electric heaters, or single package gas-fired central
heating furnaces with cooling unit. Both are designed for
outdoor installation on a rooftop or slab.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electrical
wiring is factory installed and tested. The units require electric
power, gas connection, duct connections, installation of
combustion air inlet hood, flue gas outlet hoods and fixed
outdoor air intake damper (units without economizer or
motorized damper option only) at the point of installation.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury. Improper installation,
adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to this manual.
For assistance or additional information consult a
qualified installer, service agency or the gas supplier.
The supplemental electric heaters have nickel-chrome
elements and utilize single point power connection.
These gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition with
proven pilot. All gas heaters are shipped from the factory equipped
for natural gas use, but can be field converted to L.P./Propane with
Kit Model # 1NP0418. See Gas Heat Application Data Table.
Safety Considerations
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION.
DANGER indicates an imminently hazardous situation, which,
if not avoided,
WARNING indicates a potentially hazardous situation, which,
if not avoided,
CAUTION indicates a potentially hazardous situation, which, if
not avoided
used to alert against unsafe practices and hazards involving
only property damage.
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage. Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to this manual for assistance or
for additional information, consult a qualified contractor,
installer or service agency.
will result in death or serious injury.
could result in death or serious injury.
may result in minor or moderate injury. It is also
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system. Gage sets, hoses, refrigerant
containers and recovery systems must be designed to
handle R-410A. If you are unsure, consult the equipment
manufacturer. Failure to use R-410A compatible servicing
equipment may result in property damage or injury.
If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage,
personal injury or loss of life.
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
a. Do not try to light any appliance.
b. Do not touch any electrical switch; do not use any
phone in your building.
c. Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
d. If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Due to system pressure, moving parts, and electrical
components, installation and servicing of air conditioning
equipment can be hazardous. Only qualified, trained service
personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions
of cleaning coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags
accompanying the equipment whenever working on air
conditioning equipment. Be sure to follow all other applicable
This product must be installed in strict compliance with
the installation instructions and any applicable local,
state and national codes including, but not limited to
building, electrical, and mechanical codes.
2Johnson Controls Unitary Products
safety precautions and codes including ANSI Z223.1 or CSAB149.1- latest edition.
349218-JIM-F-0512
Wear safety glasses and work gloves. Use quenching cloth and
have a fire extinguisher available during brazing operations.
Inspection
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier’s freight bill. A separate
request for inspection by the carrier’s agent should be made in
writing.
This product must be installed in strict compliance with
the enclosed installation instructions and any applicable
local, state and national codes including, but not limited
to, building, electrical, and mechanical codes.
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing at pressures in excess of 1/2 PSIG.
Pressures greater than 1/2 PSIG will cause gas valve
damage resulting in a hazardous condition. If it is
subjected to a pressure greater than 1/2 PSIG, the gas
valve must be replaced.
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG.
Renewal Parts
For authorized replacement parts call Johnson Controls, Inc.
National Source 1 Parts outlet at 1-866-523-9670.
Approvals
Design certified by CSA as follows:
1.For use as a cooling only unit, cooling unit with
supplemental electric heat or a forced air furnace.
2.For outdoor installation only.
3.For installation on combustible material.
4.For use with natural gas (convertible to LP with kit).
This product must be installed in strict compliance with
the enclosed installation instructions and any applicable
local, state, and national codes including, but not limited
to, building, electrical, and mechanical codes.
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage.
Reference
Additional information is available in the following reference
forms:
• Technical Guide - J15 thru 25 ZJ/ZR/ZF, 349690
• General Installation - J15 thru 25 ZJ, 349218
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system.
Johnson Controls Unitary Products3
349218-JIM-F-0512
Nomenclature
Nominal Cooling Capacity
J15 = 15 Ton
J18 = 17.5 Ton
J20 = 20 Ton
J25 = 25 Ton
A = Std. Motor
B = Std. Motor/Economizer
C = Std. Motor/Economizer/Power Exhaust
(Downflow Only)
D = Std. Motor/Motorized Damper
E = Std. Motor/Motorized Damper/Barometric Relief
J = Std. Motor/Economizer/Barometric Relief
N = Hi Static
P = Hi Static/Economizer
Q = Hi Static/Economizer/Power Exhaust
(Downflow Only)
R = Hi Static/Motorized Damper
K = Hi Static/Motorized Damper/Barometric Relief
S = Hi Static/Economizer/Barometric Relief
2 = Low Static
3 = Low Static/Economizer
4 = Low Static/Economizer/Power Exhaust
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Access Panels
tor, Coil Guard & Dirty Filter Switch,
4Johnson Controls Unitary Products
349218-JIM-F-0512
Installation
Installation Safety Information
Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and cooling
unit. The installer must assure that these instructions are made
available to the consumer and with instructions to retain them
for future reference.
1.Refer to the unit rating plate for the approved type of gas
for this product.
2.Install this unit only in a location and position as specified
on Page 7 of these instructions.
3.Never test for gas leaks with an open flame. Use
commercially available soap solution made specifically for
the detection of leaks when checking all connections, as
specified on Pages 5, 28 and 52 of these instructions.
4.Always install furnace to operate within the furnace's
intended temperature-rise range with the duct system
and within the allowable external static pressure range,
as specified on the unit name/rating plate, specified on
Page 27 of these instructions.
5.This equipment is not to be used for temporary heating of
buildings or structures under construction.
Limitations
These units must be installed in accordance with the following:
In U.S.A.:
2.National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3.Gas-Fired Central Furnace Standard, ANSI Z21.47a. Latest Edition
4.Local building codes, and
5.Local gas utility requirements
In Canada:
1.Canadian Electrical Code, CSA C22.1
2.Installation Codes, CSA - B149.1.
3.Local plumbing and waste water codes, and
4.Other applicable local codes.
Refer to unit application data found in this document.
After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating
plate.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result
in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage,
personal injury or loss of life.
6.If a factory option convenience outlet is installed, the
weatherproof outlet cover must be field installed. The cover
shall be located in the unit control box. To install the cover,
remove the shipping label covering the convenience outlet,
follow the instructions on the back of the weatherproof
cover box, and attach the cover to the unit using the (4)
screws provided.
208/230-3-60 and 380/415-3-50 units with factory
installed Powered Convenience Outlet Option are wired
for 230v and 415v power supply respectively. Change
tap on transformer for 208-3-60 or 380-3-50 operation.
See unit wiring diagram.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or customer’s
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of Air
Conditioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings
or structures under construction.
.
The control board used in this product will effectively
operate the cooling system down to 0°F when this
product is applied in a comfort cooling application for
people. An economizer is typically included in this type
of application. When applying this product for process
cooling applications (computer rooms, switchgear, etc.),
please reference applications bulletin AE-011-07 or call
the applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional accessories
may be needed for stable operation at temperatures
below 30°F.
Johnson Controls Unitary Products5
349218-JIM-F-0512
Slide In/ Plug In
Internal Economizer
(Optional)
2” Disposable Filters
(4” Filters Optional)
Copper Tube/
Aluminum Fin
Evaporator
Coils
Thermal
Expansion
Valve
1” NPT
Condensate Drain
Filter Drier
(Solid Core)
Unit Control Board
110 Volt Convenience
Outlet (“Powered” or
“Non-Powered” Optional)
Disconnect Location
(Optional Disconnect Switch)
Bottom Power and
Control Wiring Entry
Power Ventor Motor
Electric Heater Location
(Optional Electric/Electric Units)
Location of VFD (Optional)
Location of VFD Bypass (Optional)
Belt Drive
Blower Motor
14 Gauge
Base Rails
with Lifting Holes
Outdoor Fan #2
Outdoor Fan #1
Outdoor Fan #4
Outdoor Fan #3
Copper Tube/Aluminum Fin
Condenser Coils
Compressor #4
Compressor #3
High Efficiency Scroll Compressors
Compressor #2
Compressor #1
Figure 1: J15 thru 25 ZJ Component Location
6Johnson Controls Unitary Products
Table 1: J15 thru 25 ZJ Unit Limitations
349218-JIM-F-0512
Size
(Tons)
J15
(15)
J18
(17.5)
J20
(20)
J25
(25)
Unit Voltage
208/230-3-60187252125
460-3-60432504125
575-3-60540630125
208/230-3-60187252125
460-3-60432504125
575-3-60540630125
208/230-3-60187252125
460-3-60432504125
575-3-60540630125
208/230-3-60187252125
460-3-60432504125
575-3-60540630125
Applied VoltageOutdoor DB Temp
MinMaxMax (°F)
Location
Use the following guidelines to select a suitable location for
these units:
1.Unit is designed for outdoor installation only.
2.Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3.Suitable for mounting on roof curb.
4.For ground level installation, use a level concrete slab with
a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the unit base rails.
Do not tie slab to the building foundation.
5.Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on a
solid, level roof curb or appropriate angle iron frame.
6.Maintain level tolerance to 1/2” across the entire width and
length of unit.
Unit Limitations
Clearances
All units require particular clearances for proper operation and
service. Installer must make provisions for adequate
combustion and ventilation air in accordance with section 5.3 of
Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2,
7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) Latest Edition, and/or applicable provisions of the local building
codes. Refer to Table 6 for clearances required for combustible
construction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion air
inlet or vent outlets.
Rigging And Handling
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include:
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be used
across the top of the unit.
permanent wave solution, chlorinated waxes and
cleaners, chlorine based swimming pool chemicals,
water softening chemicals, carbon tetrachloride,
Halogen type refrigerants, cleaning solvents (e.g.
perchloroethylene), printing inks, paint removers,
varnishes, hydrochloric acid, cements and glues,
antistatic fabric softeners for clothes dryers, masonry
If a unit is to be installed on a roof curb other than a
Unitary Products roof curb, gasketing must be applied to
all surfaces that come in contact with the unit underside.
acid washing materials.
Johnson Controls Unitary Products7
349218-JIM-F-0512
Before lifting, make sure the unit weight is distributed
equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift, from the side only,
providing an accessory skid is used.
LENGTH OF FORKS MUST BE A MINIMUM OF 90 INCHES.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
C
B
A
F
Figure 3: Unit 6 Point Load Weight
D
E
B
A
D
Figure 2: Unit 4 Point Load Weight
Table 2: Weights and Dimensions
Size
(Tons)
J15ZJ
(15)
J18ZJ
(17.5)
J20ZJ
(20)
J25ZJ
(25)
Weight (lbs.)Center of Gravity4 Point Load Location (lbs.)6 Point Load Location (lbs.)
Shipping OperatingXYABCDABCDEF
2614260985.2544467781852510287392568620428313
2670266585.2544477797870520293401580633437320
2702269785.0544485805878529298406585638443326
2788278385.2544498833908544306419606661457334
X
LEFT
Y
FRONT
Figure 4: Center of Gravity
C
8Johnson Controls Unitary Products
Table 3: J15 thru 25 ZJ Unit Accessory Weights
(C) GAS
SUPPLY
ENTRY
136-1/4
Weight (lbs.)
21.00
7-1/8
6-3/8
46-5/8
5-7/8
35
35-1/4
33
2-3/4
11-1/8
12-1/2
46-5/8
9-3/4
RETURN
AIR
21-1/2
ECONOMIZER / MOTORIZED DAMPER
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail Y)
5
11-1/2
SUPPLY
AIR
9-1/4
Unit Accessory
ShippingOperating
Economizer165160
Power Exhaust9085
Electric Heat
Gas Heat
1
2
4040
240240
Double Wall260260
Motorized Damper150150
Barometric Damper5045
Econ./Motorized Damper Rain Hood6055
Econ./Power Exhaust Rain Hood9590
Wood Skid220220
Roof Curb190185
Hot Gas Bypass1010
Supply Fan VFDSee Table 5
1. Weight given is for the maximum heater size available (54KW).
2. Weight given is for the maximum number of tube heat exchangers available (8 tube).
UNIT BASE RAILS
Shown separately to illustrate
Bottom Duct openings. Power
and Gas Piping Connection
location.
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for proper size of the
supply and return air duct connections.
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET HOOD
52-5/8
BLOWER ACCESS
(Location of
Optional VFD)
CONTROL BOX
ACCESS
(D)
GAS SUPPLY
ENTRY
Figure 5: J15 thru 25 ZJ Unit Dimensions Front View
Table 4: Utilities Entry
Hole
A
B
C2-3/8” KOGas Piping (Front)
D1-11/16” HoleGas Piping (Bottom)
1. One-inch Gas Piping NPT Required.
2. Opening in the bottom to the unit can be located by the slice in the
Note:All entry holes should be sealed to prevent rain water entry
Opening Size
Diameter
1-1/8” KO
3/4” NPS (Fem.)Bottom
3-5/8” KO
3” NPS (Fem.)Bottom
Control Wiring
Power Wiring
Used For
insulation.
into building.
Front
Front
1
1,2
Table 5: Supply Fan VFD Weights, In Lbs.
W/O Manual Bypass
W/Manual Bypass
349218-JIM-F-0512
92
DISCONNECT
SWITCH
LOCATION
3-3/4
(B) POWER WIRING
ENTRY
5.0 hp
7.5 hp
5.0 hp
7.5 hp
COMPRESSOR ACCESS
CONDENSER
COILS
(A) CONTROL WIRING
ENTRY
COIL
GUARD
KIT
252530
303030
303035
303040
303035
353535
353540
403545
180-19/32
(B) POWER
WIRING
ENTRY
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
8-1/8
(A) CONTROL WIRING
ENTRY
9-3/4
Supply Fan Motor230V460V575V
10.0 hp
15.0 hp
10.0 hp
15.0 hp
Johnson Controls Unitary Products9
349218-JIM-F-0512
Dot Plug
(for Pressure
Drop Reading)
Evaporator
Section
40-3/8”
Supply Air
Access
Dimensions listed are for side duct
flange opening; see Field Accessories
Supply
Air
Return
Air
18-5/8”
27-3/4”
5-1/8”
Return Air
Access
for Side Duct Flange Kit.
Figure 6: J15 thru 25 ZJ Unit Dimensions Rear View
NOTE: Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for
connecting side ducts.
For
bottom duct applications:
1.Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
2.Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except when
the unit includes a power exhaust option. The covering
consists of a heavy black paper composition.
3.Replace the side supply and return air compartment
panels.
Outdoor
Air
40-1/2”
Filter
39-5/8”
Outdoor Air
Compartment
Access
Access
1” NPT Female
Cond. Drain
Connector
For side duct applications:
1.Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2.Connect ductwork to the flanges on those panels.
10Johnson Controls Unitary Products
349218-JIM-F-0512
Economizer Motorized
Damper Rain Hood
(on Outdoor
Air Compartment)
36-5/8”
Economizer/Motorized Damper
and Power Exhaust Rain Hood
Fixed
Outdoor Air
Intake Hood
(Located on
Return Air
Compartment)
16-1/8”
5”
Supply Air
Compartment
Power Exhaust
Rain Hood
(on Return
Air Compartment)
Rear View
Detail “Y”
Unit with Rain Hoods
Figure 7: J15 thru 25 ZJ Unit Dimensions Rain Hood
Table 6: J15 thru 25 ZJ Unit Clearances
DirectionDistance (in.)DirectionDistance (in.)
1
Top
Front36Bottom
Rear
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge
outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
3. If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of
the evaporator coil, or in the outdoor air compartment, prior to final installation.
Note:ELEC/ELEC Models: Units and ductwork are approved for zero clearance to combustible material when
equipped with electric heaters.
GAS/ELEC Models: A 1" clearance must be provided between any combustible material and the supply air
ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).
• Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.
• Four (4) feet from electric and gas meters, regulators and relief equipment.
72 With 36 Maximum
Horizontal Overhang (For
Condenser Air Discharge)
24 (W/O Economizer)
49 (W/Economizer)36 (W/Economizer)
Right36
2
Left
24 (W/O Economizer)
0
1” Condensate
Drain (Must be
Trapped)
92”28-3/16”
LH View
3
Johnson Controls Unitary Products11
349218-JIM-F-0512
Figure 8: J15 thru 25 ZJ Roof Curb
25-1/4"
Ductwork
Ductwork should be designed and sized according to the
methods in Manual D of the Air Conditioning Contractors of
America (ACCA) or as recommended by any other recognized
authority such as ASHRAE or SMACNA.
A closed return duct system should be used. This will not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
The supply and return air duct systems should be designed for
the CFM and static pressure requirements of the job. They
should NOT be sized to match the dimensions of the duct
connections on the unit.
Refer to Figure 5 for bottom air duct openings. Refer to Figure 6
for side air duct openings.
NOTE: It is recommended that, in Canada, the outlet duct be
provided with a removable access panel. It is
recommended that this opening be accessible when
the unit is installed in service, and of a size such that
smoke or reflected light may be observed inside the
casing to indicate the presence of leaks in the heat
exchanger. The cover should be attached in a
manner adequate to prevent leakage.
Gasketing and mounting screws are provided in a parts bag
attached to the hood assembly. Apply gasketing to the three
flange surfaces on the hood prior to installing the hood. Extend
gasketing 1/4 inch beyond the top and bottom of the two side
flanges to insure adequate sealing.
Adjusting the damper to the desired air flow may be done
before mounting the hood into position or after installation by
removing the front hood panel or the screen on the bottom of
the hood. Damper baffle in position 1 will allow approximately
10% outdoor air flow, position 2 approximately 15% and, to
allow approximately 25%, remove the damper baffle.
On units with bottom return air application install the damper
assembly over the opening in the side return air access panel.
Remove and discard the opening cover and the covering over
the hood mounting holes (used for shipping) before installing.
Secure with the screws provided.
On units with side return air applications, install the damper
assembly on the return air ductwork as close to the unit as
possible. Cut an opening 16 inches high by 18 inches wide in the
ductwork to accommodate the damper. Using the holes in the
hood flanges as a template, drill 9/64 inch diameter (#26 drill)
holes into the ductwork and secure with the screws provided.
Fixed Outdoor Air Intake Damper
This damper is shipped inside the return air compartment. It is
completely assembled and ready for installation. A damper
baffle inside of the hood is adjustable to provide variable
amounts of outdoor air intake on units that are not provided with
an economizer or a motorized damper option. Refer to the
Fixed Outdoor Damper Figure 9.
12Johnson Controls Unitary Products
If outdoor air intake will not be required on units with
bottom return air applications, the damper assembly
should still be mounted on the side return air access
panel, per the instructions above, to insure moisture is
not drawn into the unit during operation. The covering
over the mounting holes only need be removed. Do not
remove the opening cover.
Side Supply
Air Access
Panel
349218-JIM-F-0512
The compressor also uses a polyolester (POE oil), Mobil 3MA
POE. This oil is extremely hygroscopic, meaning it absorbs water
readily. POE oil can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.
Screen
Flange
*
Side Return Air
Access Panel
2
1
Rear View
Outdoor Air
Opening Cover
Damper
Baffle
Hood
* Gasketed
Figure 9: Fixed Outdoor Air Damper
Condensate Drain
Plumbing must conform to local codes. Use a sealing compound
on male pipe threads. Install a condensate drain line from the
one-inch NPT female connection on the unit to an open drain.
NOTE: The condensate drain operates in a negative pressure
in the cabinet. The condensate drain line MUST be
trapped to provide proper drainage. See Figure 10.
Base
Pan
Unit Condensate
Connection
3” Min.
Do not leave the system open to the atmosphere. Unit
damage could occur due to moisture being absorbed by
the POE oil in the system. This type of oil is highly
susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause
long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause
embrittlement (leading to cracking) to occur in one year
or more. When performing any service that may risk
exposure of compressor oil to the roof, take precautions
to protect roofing.
Procedures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, replacing
refrigerant components such as filter drier, pressure switch,
metering device or coil.
Units are shipped with compressor mountings which are
factory-adjusted and ready for operation.
2”
Drain
Plug
Base
Rails
Figure 10: Condensate Drain
Compressors
The scroll compressor used in this product is specifically
designed to operate with R-410A Refrigerant and cannot be
interchanged.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system.
Do not loosen compressor mounting bolts.
Filters
Two-inch filters are supplied with each unit, but units can be
converted easily to four-inch filters. Filters must always be
installed ahead of the evaporator coil and must be kept clean or
replaced with same size and type. Dirty filters will reduce the
capacity of the unit and will result in frosted coils or safety
shutdown. Minimum filter area and required sizes are shown in
Physical Data Table 9.
Make sure that panel latches are properly positioned on
the unit to maintain an airtight seal.
Johnson Controls Unitary Products13
349218-JIM-F-0512
Power And Control Wiring
Field wiring to the unit, fuses, and disconnects must conform to
provisions of National Electrical Code (NEC), ANSI/NFPA No.
70 – Latest Edition (in U.S.A.), current Canadian Electrical
Code C221, and/or local ordinances. The unit must be
electrically grounded in accordance with NEC and CEC as
specified above and/or local codes.
208/230-3-60 and 380/415-3-50 units control
transformers are factory wired for 230v and 415v power
supply respectively. Change tap on transformer for 2083-60 or 380-3-50 operation. See unit wiring diagram.
Voltage tolerances which must be maintained at the
compressor terminals during starting and running conditions are
indicated on the unit Rating Plate and Table 1.
The internal wiring harnesses furnished with this unit are an
integral part of the design certified unit. Field alteration to
comply with electrical codes should not be required. If any of
the wire supplied with the unit must be replaced, replacement
wire must be of the type shown on the wiring diagram and the
same minimum gauge as the replaced wire.
A disconnect must be utilized for these units. Factory installed
disconnects are available. If installing a disconnect (field supplied
or Unitary Products supplied accessory), refer to Figure 1 for the
recommended mounting location.
Avoid damage to internal components if drilling holes for
disconnect mounting.
NOTE: Since not all local codes allow the mounting of a
disconnect on the unit, please confirm compliance with
local code before mounting a disconnect on the unit.
Electrical line must be sized properly to carry the load. USE
COPPER CONDUCTORS ONLY. Each unit must be wired with
a separate branch circuit fed directly from the meter panel and
properly fused.
Refer to Figures 11 and 12 for typical field wiring and to the
appropriate unit wiring diagram mounted inside control doors
for control circuit and power wiring information.
When connecting electrical power and control wiring to
the unit, water-proof connectors must be used so that
water or moisture cannot be drawn into the unit during
normal operation. The above water-proofing conditions
will also apply when installing a field supplied disconnect
switch.
Power Wiring Detail
Units are factory wired for the voltage shown on the unit
nameplate. Refer to Electrical Data Table 8 to size power
wiring, fuses, and disconnect switch.
Power wiring is brought into the unit through the side of the unit
or the basepan inside the curb.
TERMINAL BLOCK TB1
GROUND
LUG
FACTORY OR FIELD
SUPPLIED DISCONNECT
Figure 11: Field Wiring Disconnect - Cooling Unit With/Without Electric Heat
THREE
PHASE
POWER
SUPPLY
14Johnson Controls Unitary Products
349218-JIM-F-0512
Thermostat Wiring
The thermostat should be located on an inside wall approximately
56 inch above the floor where it will not be subject to drafts, sun
exposure or heat from electrical fixtures or appliances. Follow the
manufacturer's instructions enclosed with thermostat for general
installation procedure. Seven (7) color-coded, insulated wires
should be used to connect the thermostat to the unit. Refer to
Table 7 for control wire sizing and maximum length.
CONTROL
THERMOSTAT
TERMINALS
TERMINAL
BLOCK
W1
W1
W2
Y1
1
W2
Y1
G
OCC
Y2
P
Y3
P1
Space Sensor
The space sensor, if used, should be located on an inside wall
approximately 56 inches above the floor where it will not be
subject to drafts, sun exposure or heat from electrical fixtures or
appliances. Follow manufacturer's instructions enclosed with
sensor for general installation procedure.
Table 7: Control Wire Sizes
Wire SizeMaximum Length
18 AWG150 Feet
1. From the unit to the thermostat and back to the unit.
1
208/230-3-60 and 380/415-3-50 units control
transformers are factory wired for 230v and 415v power
supply respectively. Change tap on transformer for 2083-60 or 380-3-50 operation. See unit wiring diagram.
Y4
G
Y2
X
R
3
RC
OCC
R
C
4
5
X
SD
C
EXPANSION
BOARD
TERMINAL
BLOCK
Y3
Y4
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
Figure 12: Typical Field Wiring 24 Volt Thermostat
1
Second stage heating not required on single stage heating units.
2
Jumper is required if there is no S moke Detect or circuit.
3
Jumper is required for any combination of R, RC, or RH.
4
OCC is an output from the thermostat to in dicate the Occup ied condition.
5
X is an input to the thermostat to display Error Status conditions.
R
SD
SD
C
Smoke
Detector
Jumper
2
24 VAC
Class 2
Johnson Controls Unitary Products15
349218-JIM-F-0512
Table 8: Electrical Data
J15 thru 25 ZJ - Standard Drive Without Powered Convenience Outlet