Johnson Controls R-410A, 20 J ZJ Series, ZJ SERIES Installation Manual

R-410A SERIES 20 J**ZJ
15 - 25 Ton 60 Hertz
TABLE OF CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ductwork. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 14
Optional Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Optional Gas Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Options/Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Economizer And Power Exhaust Set Point Adjustments . 29 Optional BAS-Ready Economizer Power Exhaust
Damper Set Point Adjustment. . . . . . . . . . . . . . . . . . . . . . 30
Optional Variable Air Volume (VAV) . . . . . . . . . . . . . . . . . 30
Optional Hot Gas Bypass (HGBP) . . . . . . . . . . . . . . . . . . 32
LIST OF TABLES
1 J15 thru 25 ZJ Unit Limitations . . . . . . . . . . . . . . . . . . . . . 7
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 J15 thru 25 ZJ Unit Accessory Weights . . . . . . . . . . . . . . 9
4 Utilities Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 Supply Fan VFD Weights, In Lbs. . . . . . . . . . . . . . . . . . . . 9
6 J15 thru 25 ZJ Unit Clearances . . . . . . . . . . . . . . . . . . . . 11
7 Control Wire Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9 J15 thru 25 ZJ Physical Data . . . . . . . . . . . . . . . . . . . . . 25
10 Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . 26
11 Gas Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
12 Gas Pipe Sizing - CapacIty of Pipe . . . . . . . . . . . . . . . . . 27
13 Gas Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . 27
14 Altitude/Temperature Correction Factors . . . . . . . . . . . . 35
Air Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Cooling Sequence Of Operation . . . . . . . . . . . . . . . . . . . . 45
No Outdoor Air Options . . . . . . . . . . . . . . . . . . . . . . . . . 45
Cooling Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . 46
Electric Heating Sequence Of Operations. . . . . . . . . . . . . 48
Electric Heat Operation Errors . . . . . . . . . . . . . . . . . . . . 48
Gas Heating Sequence Of Operations . . . . . . . . . . . . . . . 49
Gas Heating Operation Errors . . . . . . . . . . . . . . . . . . . . 50
Start-Up (Cooling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Start-Up (Gas Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Charging The Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Unit Control Board Option Setup . . . . . . . . . . . . . . . . . . . . . . 62
Option Byte Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Heat Delay Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Optional VAV Control Board Flash Codes . . . . . . . . . . . . 62
15 Air Flow Performance - Side Duct Application . . . . . . . . 37
16 Air Flow Performance - Bottom Duct Application . . . . . . 40
17 RPM Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
18 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 43
19 Power Exhaust Specifications . . . . . . . . . . . . . . . . . . . . . 43
20 Limit Control Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
21 Electric Heat Anticipator Setpoint . . . . . . . . . . . . . . . . . . 49
22 Gas Heat Limit Control Setting . . . . . . . . . . . . . . . . . . . . 50
23 Gas Heat Anticipator Setpoints . . . . . . . . . . . . . . . . . . . . 51
24 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . 52
25 Unit Control Board Flash Codes . . . . . . . . . . . . . . . . . . . 61
26 Heat Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
27 VAV Control Board Flash Codes . . . . . . . . . . . . . . . . . . 62
LIST OF FIGURES
1 J15 thru 25 ZJ Component Location . . . . . . . . . . . . . . . . 6
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Unit 6 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Center of Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 J15 thru 25 ZJ Unit Dimensions Front View . . . . . . . . . . . 9
6 J15 thru 25 ZJ Unit Dimensions Rear View . . . . . . . . . . 10
7 J15 thru 25 ZJ Unit Dimensions Rain Hood . . . . . . . . . . 11
8 J15 thru 25 ZJ Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . 12
9 Fixed Outdoor Air Damper . . . . . . . . . . . . . . . . . . . . . . . 13
10 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11 Field Wiring Disconnect - Cooling Unit With/
Without Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
12 Typical Field Wiring 24 Volt Thermostat . . . . . . . . . . . . 15
13 External Supply Connection External Shut-Off . . . . . . . 27
14 Bottom Supply Connection External Shut-Off . . . . . . . . 27
15 Vent and Combustion Air Hood . . . . . . . . . . . . . . . . . . . 29
16 Enthalpy Set Point Chart . . . . . . . . . . . . . . . . . . . . . . . . 33
17 Economizer Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
18 Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
19 Altitude/Temperature Correction Factors . . . . . . . . . . . . 35
20 Pressure Drop Across A Dry Indoor Coil Vs. Supply
Air CFM For All Unit Tonnages . . . . . . . . . . . . . . . . . . . 44
21 Gas Valve Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
22 Gas Valve and Controls . . . . . . . . . . . . . . . . . . . . . . . . . 51
23 Proper Pilot Flame Adjustment . . . . . . . . . . . . . . . . . . . 53
24 Typical Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
25 Typical Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
26 J15ZJ (15 Ton) Charging Chart . . . . . . . . . . . . . . . . . . . 54
27 J18ZJ (17.5 Ton) Charging Chart . . . . . . . . . . . . . . . . . 54
28 J20ZJ (20 Ton) Charging Chart . . . . . . . . . . . . . . . . . . . 54
29 J25ZJ (25 Ton) Charging Chart . . . . . . . . . . . . . . . . . . . 54
30 Unit Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
349218-JIM-F-0512
349218-JIM-F-0512

General

Johnson Controls Series 20 J**ZJ models are either single package air conditioners equipped with optional factory installed electric heaters, or single package gas-fired central heating furnaces with cooling unit. Both are designed for outdoor installation on a rooftop or slab.
The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require electric power, gas connection, duct connections, installation of combustion air inlet hood, flue gas outlet hoods and fixed outdoor air intake damper (units without economizer or motorized damper option only) at the point of installation.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
The supplemental electric heaters have nickel-chrome elements and utilize single point power connection.
These gas-fired heaters have aluminized-steel or optional stainless steel, tubular heat exchangers with spark ignition with proven pilot. All gas heaters are shipped from the factory equipped for natural gas use, but can be field converted to L.P./Propane with Kit Model # 1NP0418. See Gas Heat Application Data Table.
Safety Considerations
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION. DANGER indicates an imminently hazardous situation, which,
if not avoided, WARNING indicates a potentially hazardous situation, which,
if not avoided, CAUTION indicates a potentially hazardous situation, which, if
not avoided used to alert against unsafe practices and hazards involving only property damage.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified contractor, installer or service agency.
will result in death or serious injury.
could result in death or serious injury.
may result in minor or moderate injury. It is also
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury.
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS: a. Do not try to light any appliance. b. Do not touch any electrical switch; do not use any
phone in your building.
c. Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
d. If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Due to system pressure, moving parts, and electrical components, installation and servicing of air conditioning equipment can be hazardous. Only qualified, trained service personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags accompanying the equipment whenever working on air conditioning equipment. Be sure to follow all other applicable
This product must be installed in strict compliance with the installation instructions and any applicable local, state and national codes including, but not limited to building, electrical, and mechanical codes.
2 Johnson Controls Unitary Products
safety precautions and codes including ANSI Z223.1 or CSA­B149.1- latest edition.
349218-JIM-F-0512
Wear safety glasses and work gloves. Use quenching cloth and have a fire extinguisher available during brazing operations.
Inspection
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing.
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state and national codes including, but not limited to, building, electrical, and mechanical codes.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing at pressures in excess of 1/2 PSIG.
Pressures greater than 1/2 PSIG will cause gas valve damage resulting in a hazardous condition. If it is subjected to a pressure greater than 1/2 PSIG, the gas valve must be replaced.
The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG.
Renewal Parts
For authorized replacement parts call Johnson Controls, Inc. National Source 1 Parts outlet at 1-866-523-9670.
Approvals
Design certified by CSA as follows:
1. For use as a cooling only unit, cooling unit with
supplemental electric heat or a forced air furnace.
2. For outdoor installation only.
3. For installation on combustible material.
4. For use with natural gas (convertible to LP with kit).
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to, building, electrical, and mechanical codes.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Reference
Additional information is available in the following reference forms:
• Technical Guide - J15 thru 25 ZJ/ZR/ZF, 349690
• General Installation - J15 thru 25 ZJ, 349218
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
Johnson Controls Unitary Products 3
349218-JIM-F-0512
Nomenclature
Nominal Cooling Capacity
J15 = 15 Ton J18 = 17.5 Ton J20 = 20 Ton J25 = 25 Ton
Product Category
Z = A/C, Single Pkg., R-410A
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No field installed
N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel
E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW
A = Std. Motor B = Std. Motor/Economizer C = Std. Motor/Economizer/Power Exhaust
(Downflow Only) D = Std. Motor/Motorized Damper E = Std. Motor/Motorized Damper/Barometric Relief J = Std. Motor/Economizer/Barometric Relief N = Hi Static P = Hi Static/Economizer Q = Hi Static/Economizer/Power Exhaust
(Downflow Only) R = Hi Static/Motorized Damper K = Hi Static/Motorized Damper/Barometric Relief S = Hi Static/Economizer/Barometric Relief 2 = Low Static 3 = Low Static/Economizer 4 = Low Static/Economizer/Power Exhaust
(Downflow Only) 5 = Low Static/Motorized Damper 6 = Low Static/Motorized Damper/Barometric Relief 7 = Low Static/Economizer/Barometric Relief
Product Identifier
J = 11.0+ EER A/C
electric heat
Gas Heat Options
Electric Heat Options
Airflow
15-25 Ton Series 20 Model Number Nomenclature
ZJJ15 N24 A 2 A AA 1 0 1 2 4 A
Product Style
A = Style A
Configuration Options (not required for all units)
For valid combinations of the above; see the equipment price pages or
the Unitary Sales Tool program; all combinations are not available
Additional Options
Hinged Filter Door & Tool Free Access Cabinet
BA = Hinged Filter Door & Tool Free BB = Phase Monitor, Hinged Filter Door & Tool Free
Access Panels
BC = Coil Guard, Hinged Filter Door & Tool Free
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Tool Free Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Tool Free Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Tool Free Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Tool Free Access Panels
BH = Phase Moni
Hinged Filter Door & Tool Free Access Panels
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
Johnson UNT 1126 Controller (N2 protocol), DFS, APS
Johnson Commercial Controls System (CCS) Rtu Controller
Johnson Controller Metasys FEC-2611 (BACnet MS/TP Protocol), SAS, RAS, OAS, DFS, APS
CPC Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort II Controller
Simplicity IntelliComfort II Controller w/Simplicity™LINC
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD
Variable Air Volume, VFD and Manual Bypass
Variable Air Volume, VFD (BAS ready - for customer provided VFD controller)
Variable Air Volume, VFD and Manual Bypass (BAS ready)
Variable Air Volume, VFD Ready (for customer provided, field installed drive)
2" Pleated Filters, MERV 7
4" Pleated Filters, MERV 13
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Double Wall Construction
Product Generation
1 = First Generation
Standard Cabinet
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils EA = ElectroFin Condenser Coil EJ = ElectroFin Evaporator Coil ES = ElectroFin Cond & Evap Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A.
N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
Options
4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Access Panels
tor, Coil Guard & Dirty Filter Switch,
4 Johnson Controls Unitary Products
349218-JIM-F-0512

Installation

Installation Safety Information
Read these instructions before continuing this appliance installation. This is an outdoor combination heating and cooling unit. The installer must assure that these instructions are made available to the consumer and with instructions to retain them for future reference.
1. Refer to the unit rating plate for the approved type of gas for this product.
2. Install this unit only in a location and position as specified on Page 7 of these instructions.
3. Never test for gas leaks with an open flame. Use commercially available soap solution made specifically for the detection of leaks when checking all connections, as specified on Pages 5, 28 and 52 of these instructions.
4. Always install furnace to operate within the furnace's intended temperature-rise range with the duct system and within the allowable external static pressure range, as specified on the unit name/rating plate, specified on Page 27 of these instructions.
5. This equipment is not to be used for temporary heating of buildings or structures under construction.

Limitations

These units must be installed in accordance with the following: In U.S.A.:
1. National Electrical Code, ANSI/NFPA No. 70 - Latest Edition
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. ­Latest Edition
4. Local building codes, and
5. Local gas utility requirements
In Canada:
1. Canadian Electrical Code, CSA C22.1
2. Installation Codes, CSA - B149.1.
3. Local plumbing and waste water codes, and
4. Other applicable local codes.
Refer to unit application data found in this document. After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating plate.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warning exactly could result
in serious injury, death or property damage. Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
6. If a factory option convenience outlet is installed, the weatherproof outlet cover must be field installed. The cover shall be located in the unit control box. To install the cover, remove the shipping label covering the convenience outlet, follow the instructions on the back of the weatherproof cover box, and attach the cover to the unit using the (4) screws provided.
208/230-3-60 and 380/415-3-50 units with factory installed Powered Convenience Outlet Option are wired for 230v and 415v power supply respectively. Change tap on transformer for 208-3-60 or 380-3-50 operation. See unit wiring diagram.
If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s expense.
Size of unit for proposed installation should be based on heat loss/heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings or structures under construction.
.
The control board used in this product will effectively operate the cooling system down to 0°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1­877-UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30°F.
Johnson Controls Unitary Products 5
349218-JIM-F-0512
Slide In/ Plug In
Internal Economizer
(Optional)
2” Disposable Filters
(4” Filters Optional)
Copper Tube/ Aluminum Fin
Evaporator
Coils
Thermal
Expansion
Valve
1” NPT
Condensate Drain
Filter Drier
(Solid Core)
Unit Control Board
110 Volt Convenience
Outlet (“Powered” or
“Non-Powered” Optional)
Disconnect Location
(Optional Disconnect Switch)
Bottom Power and
Control Wiring Entry
Power Ventor Motor
Electric Heater Location
(Optional Electric/Electric Units)
Location of VFD (Optional)
Location of VFD Bypass (Optional)
Belt Drive
Blower Motor
14 Gauge
Base Rails
with Lifting Holes
Outdoor Fan #2
Outdoor Fan #1
Outdoor Fan #4
Outdoor Fan #3
Copper Tube/Aluminum Fin
Condenser Coils
Compressor #4
Compressor #3
High Efficiency Scroll Compressors
Compressor #2
Compressor #1
Figure 1: J15 thru 25 ZJ Component Location
6 Johnson Controls Unitary Products
Table 1: J15 thru 25 ZJ Unit Limitations
349218-JIM-F-0512
Size
(Tons)
J15 (15)
J18
(17.5)
J20 (20)
J25 (25)
Unit Voltage
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
Applied Voltage Outdoor DB Temp
Min Max Max (°F)

Location

Use the following guidelines to select a suitable location for these units:
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.
3. Suitable for mounting on roof curb.
4. For ground level installation, use a level concrete slab with a minimum thickness of 4 inches. The length and width should be at least 6 inches greater than the unit base rails. Do not tie slab to the building foundation.
5. Roof structures must be able to support the weight of the unit and its options/accessories. Unit must be installed on a solid, level roof curb or appropriate angle iron frame.
6. Maintain level tolerance to 1/2” across the entire width and length of unit.
Unit Limitations
Clearances
All units require particular clearances for proper operation and service. Installer must make provisions for adequate combustion and ventilation air in accordance with section 5.3 of Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2,
7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) ­Latest Edition, and/or applicable provisions of the local building codes. Refer to Table 6 for clearances required for combustible construction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlets.

Rigging And Handling

Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes
Excessive exposure of this furnace to contaminated combustion air may result in equipment damage or personal injury. Typical contaminates include:
provided in the base rails. Spreader bars, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.
permanent wave solution, chlorinated waxes and cleaners, chlorine based swimming pool chemicals, water softening chemicals, carbon tetrachloride, Halogen type refrigerants, cleaning solvents (e.g. perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, cements and glues, antistatic fabric softeners for clothes dryers, masonry
If a unit is to be installed on a roof curb other than a Unitary Products roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside.
acid washing materials.
Johnson Controls Unitary Products 7
349218-JIM-F-0512
Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift, from the side only, providing an accessory skid is used.
LENGTH OF FORKS MUST BE A MINIMUM OF 90 INCHES.
All panels must be secured in place when the unit is lifted.
The condenser coils should be protected from rigging cable damage with plywood or other suitable material.
C
B
A
F
Figure 3: Unit 6 Point Load Weight
D
E
B
A
D
Figure 2: Unit 4 Point Load Weight Table 2: Weights and Dimensions
Size
(Tons)
J15ZJ
(15) J18ZJ (17.5) J20ZJ
(20) J25ZJ
(25)
Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)
Shipping Operating X Y ABCDABCDEF
2614 2609 85.25 44 467 781 852 510 287 392 568 620 428 313
2670 2665 85.25 44 477 797 870 520 293 401 580 633 437 320
2702 2697 85.05 44 485 805 878 529 298 406 585 638 443 326
2788 2783 85.25 44 498 833 908 544 306 419 606 661 457 334
X
LEFT
Y
FRONT
Figure 4: Center of Gravity
C
8 Johnson Controls Unitary Products
Table 3: J15 thru 25 ZJ Unit Accessory Weights
(C) GAS SUPPLY ENTRY
136-1/4
Weight (lbs.)
21.00
7-1/8
6-3/8
46-5/8
5-7/8
35
35-1/4
33
2-3/4
11-1/8
12-1/2
46-5/8
9-3/4
RETURN AIR
21-1/2
ECONOMIZER / MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail Y)
5
11-1/2
SUPPLY AIR
9-1/4
Unit Accessory
Shipping Operating
Economizer 165 160
Power Exhaust 90 85
Electric Heat
Gas Heat
1
2
40 40
240 240
Double Wall 260 260
Motorized Damper 150 150
Barometric Damper 50 45
Econ./Motorized Damper Rain Hood 60 55
Econ./Power Exhaust Rain Hood 95 90
Wood Skid 220 220
Roof Curb 190 185
Hot Gas Bypass 10 10
Supply Fan VFD See Table 5
1. Weight given is for the maximum heater size available (54KW).
2. Weight given is for the maximum number of tube heat exchangers available (8 tube).
BLOWER MOTOR
ACCESS (Location BLOWER COMPARTMENT ACCESS (Auxiliary)
of Optional VFD Bypass)
DOT PLUG (For pressure drop reading)
GAS OR ELECTRIC HEAT ACCESS
UNIT BASE RAILS Shown separately to illustrate Bottom Duct openings. Power and Gas Piping Connection location.
NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for proper size of the supply and return air duct connections.
VENT AIR OUTLET HOODS
COMBUSTION AIR INLET HOOD
52-5/8
BLOWER ACCESS (Location of Optional VFD)
CONTROL BOX ACCESS
(D) GAS SUPPLY ENTRY
Figure 5: J15 thru 25 ZJ Unit Dimensions Front View Table 4: Utilities Entry
Hole
A
B C 2-3/8” KO Gas Piping (Front)
D 1-11/16” Hole Gas Piping (Bottom)
1. One-inch Gas Piping NPT Required.
2. Opening in the bottom to the unit can be located by the slice in the
Note:All entry holes should be sealed to prevent rain water entry
Opening Size
Diameter
1-1/8” KO
3/4” NPS (Fem.) Bottom
3-5/8” KO
3” NPS (Fem.) Bottom
Control Wiring
Power Wiring
Used For
insulation.
into building.
Front
Front
1
1,2
Table 5: Supply Fan VFD Weights, In Lbs.
W/O Manual Bypass
W/Manual Bypass
349218-JIM-F-0512
92
DISCONNECT SWITCH LOCATION
3-3/4
(B) POWER WIRING ENTRY
5.0 hp
7.5 hp
5.0 hp
7.5 hp
COMPRESSOR ACCESS
CONDENSER COILS
(A) CONTROL WIRING ENTRY
COIL GUARD KIT
25 25 30 30 30 30 30 30 35 30 30 40
30 30 35 35 35 35 35 35 40 40 35 45
180-19/32
(B) POWER WIRING ENTRY
BOTTOM SUPPLY AND RETURN AIR OPENINGS (See Note)
8-1/8
(A) CONTROL WIRING ENTRY
9-3/4
Supply Fan Motor 230V 460V 575V
10.0 hp
15.0 hp
10.0 hp
15.0 hp
Johnson Controls Unitary Products 9
349218-JIM-F-0512
Dot Plug
(for Pressure
Drop Reading)
Evaporator
Section
40-3/8”
Supply Air
Access
Dimensions listed are for side duct flange opening; see Field Accessories
Supply
Air
Return
Air
18-5/8”
27-3/4”
5-1/8”
Return Air
Access
for Side Duct Flange Kit.
Figure 6: J15 thru 25 ZJ Unit Dimensions Rear View NOTE: Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for connecting side ducts.
For
bottom duct applications:
1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers.
2. Remove and discard the bottom duct covers. Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition.
3. Replace the side supply and return air compartment panels.
Outdoor
Air
40-1/2”
Filter
39-5/8”
Outdoor Air
Compartment
Access
Access
1” NPT Female
Cond. Drain
Connector
For side duct applications:
1. Replace the side panels on the supply and return air compartments with the accessory flange kit panels.
2. Connect ductwork to the flanges on those panels.
10 Johnson Controls Unitary Products
349218-JIM-F-0512
Economizer Motorized
Damper Rain Hood
(on Outdoor
Air Compartment)
36-5/8”
Economizer/Motorized Damper and Power Exhaust Rain Hood
Fixed
Outdoor Air Intake Hood (Located on
Return Air
Compartment)
16-1/8”
5”
Supply Air
Compartment
Power Exhaust
Rain Hood (on Return
Air Compartment)
Rear View
Detail “Y”
Unit with Rain Hoods
Figure 7: J15 thru 25 ZJ Unit Dimensions Rain Hood Table 6: J15 thru 25 ZJ Unit Clearances
Direction Distance (in.) Direction Distance (in.)
1
Top
Front 36 Bottom Rear
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
3. If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of the evaporator coil, or in the outdoor air compartment, prior to final installation.
Note:ELEC/ELEC Models: Units and ductwork are approved for zero clearance to combustible material when
equipped with electric heaters. GAS/ELEC Models: A 1" clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumulate within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).
• Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.
• Four (4) feet from electric and gas meters, regulators and relief equipment.
72 With 36 Maximum
Horizontal Overhang (For
Condenser Air Discharge)
24 (W/O Economizer)
49 (W/Economizer) 36 (W/Economizer)
Right 36
2
Left
24 (W/O Economizer)
0
1” Condensate Drain (Must be
Trapped)
92”28-3/16”
LH View
3
Johnson Controls Unitary Products 11
349218-JIM-F-0512
Figure 8: J15 thru 25 ZJ Roof Curb
25-1/4"

Ductwork

Ductwork should be designed and sized according to the methods in Manual D of the Air Conditioning Contractors of America (ACCA) or as recommended by any other recognized authority such as ASHRAE or SMACNA.
A closed return duct system should be used. This will not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise.
The supply and return air duct systems should be designed for the CFM and static pressure requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit.
Refer to Figure 5 for bottom air duct openings. Refer to Figure 6 for side air duct openings.
NOTE: It is recommended that, in Canada, the outlet duct be
provided with a removable access panel. It is recommended that this opening be accessible when the unit is installed in service, and of a size such that smoke or reflected light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover should be attached in a manner adequate to prevent leakage.
Gasketing and mounting screws are provided in a parts bag attached to the hood assembly. Apply gasketing to the three flange surfaces on the hood prior to installing the hood. Extend gasketing 1/4 inch beyond the top and bottom of the two side flanges to insure adequate sealing.
Adjusting the damper to the desired air flow may be done before mounting the hood into position or after installation by removing the front hood panel or the screen on the bottom of the hood. Damper baffle in position 1 will allow approximately 10% outdoor air flow, position 2 approximately 15% and, to allow approximately 25%, remove the damper baffle.
On units with bottom return air application install the damper assembly over the opening in the side return air access panel. Remove and discard the opening cover and the covering over the hood mounting holes (used for shipping) before installing. Secure with the screws provided.
On units with side return air applications, install the damper assembly on the return air ductwork as close to the unit as possible. Cut an opening 16 inches high by 18 inches wide in the ductwork to accommodate the damper. Using the holes in the hood flanges as a template, drill 9/64 inch diameter (#26 drill) holes into the ductwork and secure with the screws provided.
Fixed Outdoor Air Intake Damper
This damper is shipped inside the return air compartment. It is completely assembled and ready for installation. A damper baffle inside of the hood is adjustable to provide variable amounts of outdoor air intake on units that are not provided with an economizer or a motorized damper option. Refer to the Fixed Outdoor Damper Figure 9.
12 Johnson Controls Unitary Products
If outdoor air intake will not be required on units with bottom return air applications, the damper assembly should still be mounted on the side return air access panel, per the instructions above, to insure moisture is not drawn into the unit during operation. The covering over the mounting holes only need be removed. Do not remove the opening cover.
Side Supply
Air Access
Panel
349218-JIM-F-0512
The compressor also uses a polyolester (POE oil), Mobil 3MA POE. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oil can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
Screen
Flange
*
Side Return Air
Access Panel
2
1
Rear View
Outdoor Air
Opening Cover
Damper
Baffle
Hood
* Gasketed
Figure 9: Fixed Outdoor Air Damper

Condensate Drain

Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line from the one-inch NPT female connection on the unit to an open drain.
NOTE: The condensate drain operates in a negative pressure
in the cabinet. The condensate drain line MUST be trapped to provide proper drainage. See Figure 10.
Base
Pan
Unit Condensate
Connection
3” Min.
Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the system. This type of oil is highly susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take precautions to protect roofing.
Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device or coil.
Units are shipped with compressor mountings which are factory-adjusted and ready for operation.
2”
Drain
Plug
Base Rails
Figure 10: Condensate Drain

Compressors

The scroll compressor used in this product is specifically designed to operate with R-410A Refrigerant and cannot be interchanged.
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
Do not loosen compressor mounting bolts.

Filters

Two-inch filters are supplied with each unit, but units can be converted easily to four-inch filters. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Physical Data Table 9.
Make sure that panel latches are properly positioned on the unit to maintain an airtight seal.
Johnson Controls Unitary Products 13
349218-JIM-F-0512

Power And Control Wiring

Field wiring to the unit, fuses, and disconnects must conform to provisions of National Electrical Code (NEC), ANSI/NFPA No. 70 – Latest Edition (in U.S.A.), current Canadian Electrical Code C221, and/or local ordinances. The unit must be electrically grounded in accordance with NEC and CEC as specified above and/or local codes.
208/230-3-60 and 380/415-3-50 units control transformers are factory wired for 230v and 415v power supply respectively. Change tap on transformer for 208­3-60 or 380-3-50 operation. See unit wiring diagram.
Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.
The internal wiring harnesses furnished with this unit are an integral part of the design certified unit. Field alteration to comply with electrical codes should not be required. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire.
A disconnect must be utilized for these units. Factory installed disconnects are available. If installing a disconnect (field supplied or Unitary Products supplied accessory), refer to Figure 1 for the recommended mounting location.
Avoid damage to internal components if drilling holes for disconnect mounting.
NOTE: Since not all local codes allow the mounting of a
disconnect on the unit, please confirm compliance with local code before mounting a disconnect on the unit.
Electrical line must be sized properly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
Refer to Figures 11 and 12 for typical field wiring and to the appropriate unit wiring diagram mounted inside control doors for control circuit and power wiring information.
When connecting electrical power and control wiring to the unit, water-proof connectors must be used so that water or moisture cannot be drawn into the unit during normal operation. The above water-proofing conditions will also apply when installing a field supplied disconnect switch.
Power Wiring Detail
Units are factory wired for the voltage shown on the unit nameplate. Refer to Electrical Data Table 8 to size power wiring, fuses, and disconnect switch.
Power wiring is brought into the unit through the side of the unit or the basepan inside the curb.
TERMINAL BLOCK TB1
GROUND
LUG
FACTORY OR FIELD
SUPPLIED DISCONNECT
Figure 11: Field Wiring Disconnect - Cooling Unit With/Without Electric Heat
THREE
PHASE POWER SUPPLY
14 Johnson Controls Unitary Products
349218-JIM-F-0512
Thermostat Wiring
The thermostat should be located on an inside wall approximately 56 inch above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow the manufacturer's instructions enclosed with thermostat for general installation procedure. Seven (7) color-coded, insulated wires should be used to connect the thermostat to the unit. Refer to Table 7 for control wire sizing and maximum length.
CONTROL
THERMOSTAT
TERMINALS
TERMINAL
BLOCK
W1
W1
W2
Y1
1
W2
Y1
G
OCC
Y2
P
Y3
P1
Space Sensor
The space sensor, if used, should be located on an inside wall approximately 56 inches above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with sensor for general installation procedure.
Table 7: Control Wire Sizes
Wire Size Maximum Length
18 AWG 150 Feet
1. From the unit to the thermostat and back to the unit.
1
208/230-3-60 and 380/415-3-50 units control transformers are factory wired for 230v and 415v power supply respectively. Change tap on transformer for 208­3-60 or 380-3-50 operation. See unit wiring diagram.
Y4
G
Y2
X
R
3
RC
OCC
R
C
4
5
X
SD
C
EXPANSION
BOARD
TERMINAL
BLOCK
Y3
Y4
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
Figure 12: Typical Field Wiring 24 Volt Thermostat
1
Second stage heating not required on single stage heating units.
2
Jumper is required if there is no S moke Detect or circuit.
3
Jumper is required for any combination of R, RC, or RH.
4
OCC is an output from the thermostat to in dicate the Occup ied condition.
5
X is an input to the thermostat to display Error Status conditions.
R
SD
SD
C
Smoke
Detector
Jumper
2
24 VAC Class 2
Johnson Controls Unitary Products 15
349218-JIM-F-0512
Table 8: Electrical Data J15 thru 25 ZJ - Standard Drive Without Powered Convenience Outlet
Size
(Tons)
(17.5)
Volt
208-3-60 14.7 115 23.0 2.1 15.4 0.0
230-3-60 14.7 115 23.0 2.1 14.4 0.0
J15
(15)
460-3-60 7.7 50 12.0 1.1 7.2 0.0
575-3-60 6.4 40 10.0 0.9 5.9 0.0
208-3-60 16.7 120 26.0 2.1 15.4 0.0
230-3-60 16.7 120 26.0 2.1 14.4 0.0
J18
460-3-60 8.7 60 15.5 1.1 7.2 0.0
575-3-60 6.7 42 10.5 0.9 5.9 0.0
208-3-60 17.9 120 28.0 3.7 15.4 0.0
230-3-60 17.9 120 28.0 3.7 14.4 0.0
J20 (20)
460-3-60 9.6 70 15.0 1.9 7.2 0.0
575-3-60 7.4 53 11.5 1.5 5.9 0.0
Compressors
(each)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
OD Fan
Motors
(each)
Supply Blower
Motor
Pwr
Conv
Outlet
Max Fuse2/
Electric Heat Option
None - - - 86.5 100
E18 13.5 1 37.5 86.5 100 E36 27.0 2 74.9 112.9 125 E54 40.6 2 112.7 160.1 175 E72 54.1 2 150.2 169.4 200
None - - - 85.3 90
E18 18.0 1 43.3 85.3 90 E36 36.0 2 86.6 126.3 150 E54 54.0 2 129.9 147.9 175 E72 72.0 2 173.2 191.2 225
None - - - 44.3 50
E18 18.0 1 21.7 44.3 50 E36 36.0 2 43.3 63.1 70 E54 54.0 2 65.0 74.0 90 E72 72.0 2 86.6 95.6 110
None - - - 36.7 40
E18 18.0 1 17.3 36.7 40 E36 36.0 2 34.6 50.7 60 E54 54.0 2 52.0 59.3 70 E72 72.0 2 69.3 76.7 90
None - - - 94.8 110
E18 13.5 1 37.5 94.8 110 E36 27.0 2 74.9 112.9 125 E54 40.6 2 112.7 160.1 175 E72 54.1 2 150.2 169.4 200
None - - - 93.8 110
E18 18.0 1 43.3 93.8 110 E36 36.0 2 86.6 126.3 150 E54 54.0 2 129.9 147.9 175 E72 72.0 2 173.2 191.2 225
None - - - 48.6 50
E18 18.0 1 21.7 48.6 50 E36 36.0 2 43.3 63.1 70 E54 54.0 2 65.0 74.0 90 E72 72.0 2 86.6 95.6 110
None - - - 38.0 40
E18 18.0 1 17.3 38.0 40 E36 36.0 2 34.6 50.7 60 E54 54.0 2 52.0 59.3 70 E72 72.0 2 69.3 76.7 90
None - - - 106.3 110
E18 13.5 1 37.5 106.3 110 E36 27.0 2 74.9 112.9 125 E54 40.6 2 112.7 160.1 175 E72 54.1 2 150.2 169.4 200
None - - - 105.3 110
E18 18.0 1 43.3 105.3 110 E36 36.0 2 86.6 126.3 150 E54 54.0 2 129.9 147.9 175 E72 72.0 2 173.2 191.2 225
None - - - 55.6 60
E18 18.0 1 21.7 55.6 60 E36 36.0 2 43.3 63.1 70 E54 54.0 2 65.0 74.0 90 E72 72.0 2 86.6 95.6 110
None - - - 43.4 50
E18 18.0 1 17.3 43.4 50 E36 36.0 2 34.6 50.7 60 E54 54.0 2 52.0 59.3 70 E72 72.0 2 69.3 76.7 90
MCA
(Amps)
1
Breaker
Size
(Amps)
3
16 Johnson Controls Unitary Products
J15 thru 25 ZJ - Standard Drive Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
208-3-60 23.0 160 31.5 3.7 28.0 0.0
230-3-60 23.0 160 31.5 3.7 26.0 0.0
J25 (25)
460-3-60 12.2 87 17.1 1.9 13.0 0.0
575-3-60 8.7 62 13.5 1.5 10.3 0.0
Compressors
(each)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
OD Fan
Motors
(each)
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Supply Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
None - - - 141.8 150
E18 13.5 1 37.5 141.8 150 E36 27.0 2 74.9 141.8 150 E54 40.6 2 112.7 175.9 200 E72 54.1 2 150.2 185.2 200
None - - - 139.3 150
E18 18.0 1 43.3 139.3 150 E36 36.0 2 86.6 140.8 150 E54 54.0 2 129.9 162.4 175 E72 72.0 2 173.2 205.7 225
None - - - 72.7 80
E18 18.0 1 21.7 72.7 80 E36 36.0 2 43.3 72.7 80 E54 54.0 2 65.0 81.2 90 E72 72.0 2 86.6 102.9 110
None - - - 53.7 60
E18 18.0 1 17.3 53.7 60 E36 36.0 2 34.6 56.2 60 E54 54.0 2 52.0 64.8 70 E72 72.0 2 69.3 82.2 90
MCA
(Amps)
Max Fuse2/
1
Breaker
Size
(Amps)
349218-JIM-F-0512
3
Johnson Controls Unitary Products 17
349218-JIM-F-0512
J15 thru 25 ZJ - Standard Drive With Powered Convenience Outlet
Size
(Tons)
(17.5)
Volt
208-3-60 14.7 115 23.0 2.1 15.4 10.0
230-3-60 14.7 115 23.0 2.1 14.4 10.0
J15 (15)
460-3-60 7.7 50 12.0 1.1 7.2 5.0
575-3-60 6.4 40 10.0 0.9 5.9 4.0
208-3-60 16.7 120 26.0 2.1 15.4 10.0
230-3-60 16.7 120 26.0 2.1 14.4 10.0
J18
460-3-60 8.7 60 15.5 1.1 7.2 5.0
575-3-60 6.7 42 10.5 0.9 5.9 4.0
208-3-60 17.9 120 28.0 3.7 15.4 10.0
230-3-60 17.9 120 28.0 3.7 14.4 10.0
J20 (20)
460-3-60 9.6 70 15.0 1.9 7.2 5.0
575-3-60 7.4 53 11.5 1.5 5.9 4.0
Compressors
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
(each)
OD Fan
Motors
(each)
Supply Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
None - - - 96.5 110
E18 13.5 1 37.5 96.5 110 E36 27.0 2 74.9 125.4 150 E54 40.6 2 112.7 172.6 175 E72 54.1 2 150.2 181.9 200
None - - - 95.3 100
E18 18.0 1 43.3 95.3 100 E36 36.0 2 86.6 138.8 150 E54 54.0 2 129.9 160.4 175 E72 72.0 2 173.2 203.7 225
None - - - 49.3 50
E18 18.0 1 21.7 49.3 50 E36 36.0 2 43.3 69.4 70 E54 54.0 2 65.0 80.2 90 E72 72.0 2 86.6 101.9 110
None - - - 40.7 45
E18 18.0 1 17.3 40.7 45 E36 36.0 2 34.6 55.7 60 E54 54.0 2 52.0 64.3 70 E72 72.0 2 69.3 81.7 90
None - - - 104.8 110
E18 13.5 1 37.5 104.8 110 E36 27.0 2 74.9 125.4 150 E54 40.6 2 112.7 172.6 175 E72 54.1 2 150.2 181.9 200
None - - - 103.8 110
E18 18.0 1 43.3 103.8 110 E36 36.0 2 86.6 138.8 150 E54 54.0 2 129.9 160.4 175 E72 72.0 2 173.2 203.7 225
None - - - 53.6 60
E18 18.0 1 21.7 53.6 60 E36 36.0 2 43.3 69.4 70 E54 54.0 2 65.0 80.2 90 E72 72.0 2 86.6 101.9 110
None - - - 42.0 45
E18 18.0 1 17.3 42.0 45 E36 36.0 2 34.6 55.7 60 E54 54.0 2 52.0 64.3 70 E72 72.0 2 69.3 81.7 90
None - - - 116.3 125
E18 13.5 1 37.5 116.3 125 E36 27.0 2 74.9 125.4 150 E54 40.6 2 112.7 172.6 175 E72 54.1 2 150.2 181.9 200
None - - - 115.3 125
E18 18.0 1 43.3 115.3 125 E36 36.0 2 86.6 138.8 150 E54 54.0 2 129.9 160.4 175 E72 72.0 2 173.2 203.7 225
None - - - 60.6 70
E18 18.0 1 21.7 60.6 70 E36 36.0 2 43.3 69.4 70 E54 54.0 2 65.0 80.2 90 E72 72.0 2 86.6 101.9 110
None - - - 47.4 50
E18 18.0 1 17.3 47.4 50 E36 36.0 2 34.6 55.7 60 E54 54.0 2 52.0 64.3 70 E72 72.0 2 69.3 81.7 90
MCA
(Amps)
1
Max Fuse
Breaker
Size
(Amps)
2
/
3
18 Johnson Controls Unitary Products
J15 thru 25 ZJ - Standard Drive With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
208-3-60 23.0 160 31.5 3.7 28.0 10.0
230-3-60 23.0 160 31.5 3.7 26.0 10.0
J25 (25)
460-3-60 12.2 87 17.1 1.9 13.0 5.0
575-3-60 8.7 62 13.5 1.5 10.3 4.0
Compressors
(each)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
OD Fan
Motors
(each)
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Supply Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
None - - - 151.8 175
E18 13.5 1 37.5 151.8 175 E36 27.0 2 74.9 151.8 175 E54 40.6 2 112.7 188.4 200 E72 54.1 2 150.2 197.7 200
None - - - 149.3 175
E18 18.0 1 43.3 149.3 175 E36 36.0 2 86.6 153.3 175 E54 54.0 2 129.9 174.9 175 E72 72.0 2 173.2 218.2 225
None - - - 77.7 90
E18 18.0 1 21.7 77.7 90 E36 36.0 2 43.3 77.7 90 E54 54.0 2 65.0 87.5 90 E72 72.0 2 86.6 109.1 110
None - - - 57.7 60
E18 18.0 1 17.3 57.7 60 E36 36.0 2 34.6 61.2 70 E54 54.0 2 52.0 69.8 70 E72 72.0 2 69.3 87.2 90
MCA
(Amps)
1
Max Fuse2/
Breaker
Size
(Amps)
349218-JIM-F-0512
3
Johnson Controls Unitary Products 19
Loading...
+ 44 hidden pages