Johnson Controls ZFR1812 Installation Instructions Manual

ZFR1812 Wall Mount Wireless Field Bus Router
Installation Instructions
MS-ZFR1812-x
Part No. 24-10325-45, Rev. A
Issued April 2016

Application

Use the ZFR1812 Wireless Field Bus Router only to provide an input to equipment under normal operating conditions. Where failure or malfunction of the ZFR1812 Router could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the ZFR1812 Router.
IMPORTANT: The ZFR1800 Series Wireless Field Bus System is not designed or intended for use in mission-critical or life/safety applications.
A ZFR1812 Wireless Field Bus Router is used with Advanced Application Field Equipment Controllers (FACs), Field Equipment Controllers (FECs), Input/ Output Modules (IOMs), and Variable Air Volume Modular Assembly (VMA) Series field controllers.
a field controller and the supervisory controller (b ans of a ZFR1810 Coordinator)
me
a field controller and associated WRZ Seri
Wireless Room
Additionally, the ZFR1812 Wireless Field Bus Router can be used as a repeater in WRZ-7860-0 One-to-One Wireless Room Temperature Sensing System. For more information, refer to the WRZ Series One-to-One
Wireless Room Sensing System Technical Bulletin (LIT-12011641).
Up to nine WRZ Series Sensors can be associated with a single field controller. In multi-sensor applications, the ZFR1812 Router passes all the sensor data to an FAC, FEC, IOM, or VMA controller, which can be configured to either average the sensors’ input or select the highest or lowest sensed condition for control of the target zone.
Sensors
y
es
A ZFR1812 Router is powered directly from the connected field controller’s 15 VDC output.
The ZFR812 Router is also included in the Repeater Accessory Kits, MS-ZFRRPTK-H1 or MS-ZFRRPTK­H2. These kits include a 24 VAC to 15 VDC converter power supply for stand-alone operation. As a repeater, the ZFR1812 extends the range and strengthens the wireless mesh network.
Refer to the ZFR1800 Series Wireless Field Bus
System Technical Bulletin (LIT-12011295) or the ZFR1800 Series Wireless Field Bus System Quick Reference Guide (LIT-12011630) for information on
commissioning and configuring a ZFR1800 Series Wireless Field Bus System for operation.

North American Emissions Compliance

United States

Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference an
d
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15 .21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Canada

Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada.
,
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
1

Installation

Figure 1: ZFR1812 Wireless Field Bus Router,
Physical Features and Dimensions, mm (in.)
Follow these guidelines when installing a ZFR1812 Router:
Transport the ZFR1812 Router in the original container to minimize vibration and shock damage.
Do not drop the ZFR1812 Router or subject it to physical shock.

Materials and Special Tools Needed

A 1.5 mm (1/16 in.) Allen wrench or a Johnson Controls® T- 4000-119 Allen-He ad Adjustment Tool is required for tightening or loosening the security screw

Dimensions

See Figure 1 for physical features and dimensions of the ZFR1812 Router.
The ZFR1812 can be mounted directly to drywall with drywall anchors. Both the standalone and repeater kit versions of the ZFR1812 include a 10 foot long RJ12 cable hardwired to the device. The Repeater Kit versions (the ZFRRPTK-H1 and ZFRRPTK-H2) provide additional flexibility for mounting such as a separate power supply. ZFR1812s can be flush mounted to a wall or ceiling, or mounted on a 4x4 box using a standard mudplate. When mounting the ZFR1812 Router to an enclosure, mount it to the top, bottom, or side of the enclosure. For floor mount unitary equipment, mounting on top where books or other items may be placed is not ideal. See Location Considerations.
Mounting Directly to Drywall with Drywall Anchors
- ZFR1812
1. Separate the plastic base and circuit board assembly (cover). Do not remove the security screw from the cover. See Figure 2.
IMPORTANT: The label showing the unit MAC address is on the plastic base of the unit. Be sure to keep the plastic base and circuit board assemblies together so the correct MAC address is shown.

Mounting

Note: These instructions are for mounting new
ZFR1812s rather than retrofitting factory-mounted routers.
2. Determine where to secure the plastic base to the surface using the mounting holes and supp lie d screws. A template (Figure 11) is provided at the end of this document to help you place the mounting holes.
3. Set the DIP switches. (See
Setup and Adjustments
4. Reattach the circuit board assembly in the plastic base being careful not to pinch the a t tached RJ-12 cable.
5. Tighten the security screw to prevent tampering using a 1.5 mm (1/16 in.) Allen wrench or a Johnson Controls® T-4000-119 Allen-Head Adjustment Tool. Use caution when tightening the screw to avoid stripping the plastic threads in the ZFR1812.
Mounting the ZFRRPTK-H1
The ZFRRPTK-H1 is intended for flush wall mount or ceiling mount applications. In addition to the ZFR1812, it includes a power supply, a 10 ft RJ-12 cable for connecting the power supply, and an adapter to connect the power supply to the RJ-12 cable.
).
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
To mount the ZFRRPTK-H1:
1. Separate the plastic base and circuit board assembly (cover). Do not remove the security screw from the cover. See Figure 2.
2
IMPORTANT: The label showing the unit MAC
Figure 2: ZFR1812 Wireless Field Bus Router,
with Plastic Base and Circuit Board Assy
Separated
Figure 3: ZFR1812 Wireless Field Bus Router,
with Plastic Base Hole for Ceiling Mount
address is on the plastic base of the unit. Be sure to keep the plastic base and circuit board assemblies together so the correct MAC address is shown.
2. Decide whether you are mounting on a wall or ceiling.
a. For flush wall mount applications, determine
where to secure the plastic base to the surface using the mounting holes and supplied screws. A template (Figure 1 1) is provided at the end of this document to help you place the mounting holes.
b. For ceiling mount applications, mount the
ZFR1812 to the grid between the tiles. Ther e are a number of ceiling mounting clips available from third parties which can be used. Make sure to match the clip you purchase to the grid in the location where you are doing the installation. Ceiling grid dimensions and offsets vary, so using an incorrectly sized clip may prevent mounting the ZFR1812 flush for a professional appearance. A hole is provided in the base of the assembly for this purpose (Figure 3).
IMPORTANT: If you are using a ceiling mounting clip you must make sure that no part of the clip makes contact with the circuit board assembly when installed.
3. Assemble the external power and adapters as necessary (Figure 4).
a. The 24 VAC to 15 VDC power supply (1) uses
screw terminals to attach to a 24 volt source.
b. The adapter connects the 15 VDC output of the
power supply to an RJ12 adapter (2). Plug this adapter directly to the cable coming from the ZFR1812 through a connector (3 ).
c. This connector (3) is then used to connect to
the 10 ft RJ-12 cable which is attached to the ZFR.
Note: Any inline adapter used to extend the connection of the ZFR1812 to a controller or po wer must be a straight through adapter instead of crossover.
4. Set the DIP switches. See Setup and Adjustments
5. Reattach the circuit board assembly in the plastic base.
.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
3
6. Tighten the security screw to prevent tampering
Figure 4: Power supply and adapters
Figure 5: ZFR1812 Wireless Field Bus Router,
Wall Plate Dimensions mm (in.)
using a 1.5 mm (1/16 in.) Allen wrench or a Johnson Controls® T-4000-119 Allen-Head Adjustment Tool. Use caution when tightening the screw to avoid stripping the plastic threads in the ZFR1812.
Mounting in a Wall Plate - ZFRRPTK-H2 Note: The wall plate is intended to attach to a
mudplate rather than directly to the wall.
7. Assemble the external power and adapters as necessary (Figure 4). Note that the power supply can be secured in an electrical box with the provided two-sided tape. An electrical box is not included with the kit.
a. The 24 VAC to 15 VDC power supply (1) uses
screw terminals to attach to a 24 volt source.
b. The adapter connects the 15 VDC output of the
power supply to an RJ12 adapter (2). This adapter can be plugged directly into the RJ12 jack on the ZFR1812 or connected to a connector (3).
c. This conn e cto r (3 ) is then used to connect to
the 10ft RJ12 cable which is attached to the ZFR1812.
8. Mount the wall plate with ZFR1812 in the selected location using standard box screws. Be sure to leave enough slack in the cable so you can still pull the ZFR1812 if you need to change the DIP switches.
1. Separate the plastic base and circuit board assembly (cover). Do not remove the security screw from the cover. See Figure 2.
IMPORTANT: The label showing the unit MAC address is on the plastic base of the unit. Be sure to keep the plastic base and circuit board assemblies together so the correct MAC address is shown.
2. Attach the plastic base to the supplied wall plate. Figure 5 shows the wall plate dimensions.
3. Connect the external cable assembly to the 6-pin modular receptacle.
4. Set the DIP switches. (See
Setup and Adjustments
5. Reattach the circuit board assembly in the plastic base.
6. Tighten the security screw to prevent tampering using a 1.5 mm (1/16 in.) Allen wrench or a Johnson Controls® T-4000-119 Allen-Head Adjustment Tool. Use caution when tightening the screw to avoid stripping the plastic threads in the ZFR1812.
)
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
4
The preferred orientation for the ZFR1812 Router is in
Figure 6: ZFR1812 Mounted in Wall Plate
a horizontal orientation with the green LED at the top. If you feel that you are not able to get proper signal strength, you can rotate the device 90 degrees on its plastic wall plate. See Figure 6.

Location Considerations

Follow these guidelines when locating a ZFR1812 Router within a ZFR1800 Series System.
Locate the ZFR1812 Router so that it is easily
accessible.
For best signal transmission, mount the ZFR1812
Router in an unobstructed location below (and clear of) any pipes, duct work, or other metal obstructions by at least 50 mm (2 in.).
Due to the nature of the radio frequency waves, a
wireless device may have significantly different signal strengths if its position changes relative to another wireless device or if its environment changes.
Locate the ZFR1812 Router in line-of-sight with as
many ZFR1812 Routers and WRZ Sensors as possible.
Do not mount the ZFR1812 Router in recessed
areas, metal enclosures, or shelving units.
Note: For detaile d information on location guidelines for a ZFR1800 Series system, and for estimating the number of ZFR1812 Routers needed as repeaters for extending wireless transmission range, refer to the
ZFR1800 Series Wireless Field Bus System Technical Bulletin (LIT-12011295).

Wireless Signal Transmission Considerations

Line-of-sight transmission ranges between a ZFR1810 Coordinator, ZFR1812 Router, and a WRZ Sensor can be less than the maximum distances shown in Table 1. The effective transmission range for indoor applications varies because of wireless signal absorption and reflection due to metal obstructions, walls (or floors), and furniture found in typical building interiors.
Table 1: Indoor Line-of-Sight Transmission
Ranges
Range Type Transmission Distance
ZFR1810 Coordinator, ZFR1812 Router
Recommended 15.2 m (50 ft) 15.2 m (50 ft) Maximum 76.2 m (250 ft) 30 m (98 ft)
WRZ Series Sensor

Wiring

Wiring Considerations and Guidelines

IMPORTANT: Do not connect supply power to the ZFR1812 Router before finishing wiring and checking all wiring connections. Short circuits or improperly connected wires may result in permanent damage to the Router.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations. The ZFR1812 Router is a low-voltage (less than 30 VAC) device. Do not exceed the ZFR1812 Router’s electrical ratings.
IMPORTANT: Prevent any static electric discharge to the ZFR1812 Router . Static electric discharge can damage the ZFR1812 Router and void any warranties.
IMPORT ANT: Do not connect the ZFR1812 Router to the power supply before setting the PAN OFFSET switches.

Wiring with an FEC or VMA16 Series Field Controller

Connect the ZFR1812 Router to the field controller as shown in Table 2. This connection provides both power and communication to the ZFR1812 Router.
Note: When using a field controller in a wireless field bus network, ensure that the DIP switch for Address 128 is set to the ON position.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
5
Figure 7: Pin Number Assignments for
RJ-12 Jack
(15 VDC)
SA or FC Bus
-
Bus and Power Common
Power
(15 VDC)
(RJ-12 Mod ul ar Jack)
Bus and Power Common
p
Table 2: Connecting the ZFR1812 Router to a Field Controller
Field Controller Model
Plug the ZFR1812 Router Connector Cable into the Following Jack on the Field Controller:
Connection Points for the Bluetooth® CVT Commissioning Interface
and Other SA Bus Products
Use This Communications Port between WEFC and
1
Wired IOMs, WRZ Sensors, or VFDs:
FAC26 FC Bus RJ-12 Jack SA Bus RJ-12 Jack SA Bus Terminals FAC36 FC Bus RJ-12 Jack SA Bus RJ-12 Jack SA Bus Terminals FEC16 FC Bus RJ-12 Jack SA Bus RJ-12 Jack SA Bus Terminals FEC26 FC Bus RJ-12 Jack SA Bus RJ-12 Jack SA Bus Terminals
2,3
IOM17
2,3
IOM27
2,3
IOM37
IOM472,
VMA1615/30 FC Bus RJ-12 Jack SA Bus RJ-12 Jack SA Bus Terminals
1. SA Bus Products include the DIS1710 Local Controller Display, the MS-BTCVT-1 Wireless Commissioning Converter, and the NS Series (hard-wired) Network Sensors, Balancing Sensors, and Discharge Air Temperature Sensors.
2. IOMs cannot be used in wireless mode to extend the IO of a field controller. You must always hardwire IOMs to their host field controller.
3. Do not connect any device to the SA Bus/FC Bus terminal block when using the IOM with a ZFR1812.
SA/FC Bus RJ-12 Jack Not available in wireless mode.
Use CCT with ZFR Dongle.
SA/FC Bus RJ-12 Jack Not available in wireless mode.
Use CCT with ZFR Dongle.
SA/FC Bus RJ-12 Jack Not available in wireless mode.
3
SA/FC Bus RJ-12 Jack Not available in wireless mode.
Use CCT with ZFR Dongle.
Use CCT with ZFR Dongle.
N/A
N/A
N/A
N/A
For further information on how to set up a field controller to work with the ZFR1812 Router, refer to the following documents:
FAC3611 Advanced Application Field Equipment Controller Installation Instructions (Part No. 24­10143-470)
FEC16 Field Equipment Controller Installation Instructions (Part No. 24-10143-136)
FEC26 Field Equipment Controller Installation Instructions (Part No. 24-10143-144)
IOM17 and IOM27 Input/Output Modules Installation Instructions (Part No. 24-1044-76)
IOM37 Input/Output Module Installation Instructions (Part No. 24-1044-84)
IOM47 Input/Output Module Installation Instructions (Part No. 24-1044-92)
VMA16 Series Variable Air Volume Controllers Installation Instructions (Part No. 24-10143-20)
Sensor, SA Bus, or FC Bus Port
Power
6 5 4 3 2 1
SA or FC Bus +
FIG:RJ_
inout
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
6
The value equals the sum of the numbers set to ON.
Figure 8: Connecting an IOM to a
Wireless-Enabled VMA1615/1630 Field Controller
Figure 9: Wiring a Discharge Air Net sensor , Zone
Netsensor with Terminal Block, or IOM to a
Wireless-Enabled VMA1615/1630 Field
Controller
For example, if the DIP switches labeled 1, 4, and 8 are set to ON, the PAN Offset value is 13 (1 + 4 + 8 = 13).
When selecting a PAN Offset value for a wireless system:
Use a unique PAN Offset value for each wireless mesh network at a job site.
Use the same PAN Offset value for each wireless device in a wireless mesh network—the ZFR1810 Coordinator and each associated ZFR1812 Router and WRZ Sensor.
If, after setting the PAN Offset value you find that you are unable to communicate with the desired network, it may help to toggle the DIP switches to ensure a good connection. Power down the ZFR1812 and toggle the switches (all off, then all on) and then set the switches to the desired PAN. Restore power to the ZFR1812 and see that it joins the correct network.
If the ZFR1812 misread the dip switches, it might become the child of another network and use up an available child slot in a device you did not expect. If this situation occurred, a reform on the incorrect network should clear up the now unusable child address.

Setup and Adjustments

IMPORTANT: Ensure that the PAN OFFSET
switches are set to the same value for each ZFR1810 Coordinator, ZFR1812 Router, and WRZ Sensor in a mesh network.
IMPORT ANT: Do not connect the ZFR1812 Router to the power supply before setting the PAN OFFSET switches.
IMPORTANT: On the MS/TP Address switch block of the associated FEC/IOM/VMA16 Field Controller, set switch 128 to ON for use with a ZFR1812 Router.
Set the P AN Offset value of the ZFR1812 Router using the DIP switches (located on the back of the cover) to configure the ZFR1812 Router to communicate on the wireless mesh network. See Figure 1 and Figure 10.
Note: On some date code labels, the switch position numbers on the bottom of the DIP switch are reversed. In either case, the switch positions are always read right to left.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
7
Figure 10: Sample DIP Switch Settings
Wireless transmissions between ZFR1810 Coordinators and ZFR1812 Routers occur as needed. Wireless transmissions between ZFR1812 Routers and WRZ Sensors occur approximately every 60 seconds or when the occupancy button on the WRZ Sensor is pressed. Refer to the WRZ Series Wireless
Room Temperature Sensors Installation Instructions (Part No. 24-10332-2) for more information.
Approximately once every 10 seconds, the Signal Strength LED flashes to indicate the strength of the signal received from neighboring devices. See Table 3.
Note: The Signal Strength LEDs on all the ZFR1812 routers in a network extinguish after approximately 2 hours of normal operation, making the ZFR1812 less distracting when installed in an open area. To re-enable the ZFR1812 LEDs for troubleshooting purposes, perform a scan using the ZFR Checkout Tool (ZCT). Alternatively, push the Network Optimize/Reform Push Button on the ZFR1810 coordinator for 0 to 5 seconds. Note that if you press this button more than 5 seconds, a Network Optimize or Reform is initiated.
Refer to the ZFR1800 Series Wireless Field Bus System Technical Bulletin (LIT-12011295) for more information on determining the signal strength between ZFR1800 Series devices in your application.

Troubleshooting

Use the Status LED (see Figure 1) along with the information in Table 3 to troubleshoot the ZFR1812 Router.

Wireless Signal Strength

A wireless signal strength indication LED displays the reception strength of the transmissions between the ZFR1810 Coordinators, ZFR1812 Routers, and the WRZ Series Sensors. This LED helps determine the network connectivity status when selecting locations for the devices during system installation.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
8

WRZ-SST-120 Wireless Sensing System Tool

Use the WRZ-SST-12 0 Wireless Sensing System Tool with a WRZ Series Sensor as a site survey tool to determine the wireless signal strength between a ZFR1810 Coordinator and a ZFR1812 Router or between two ZFR1812 Routers. Refer to the
WRZ-SST-120 Wireless Sensing System Tool Installation Instructions (Part No. 24-10563-12) for
more information on testing signal strength in your application.
Table 3: ZFR1812 Router Status LED
Name Visual
Descriptions
Indication of:
General Operation
Signal Strength
Indication
Network Reform
Network Ping
Normal operation
Wireless signal strength
1
Operation during network reform
Wireless node function in the network
OFF Steady = No power (or normal operation for more than 2 hours). OFF Steady with 1 Flash every 10 seconds = ZFR1812 Router is not a member of a
wireless network, invalid PAN OFFSET setting, no ZFR1810 Coordinators or ZFR1812 Routers in area.
ON Steady with Signal Strength displayed once every 10 seconds = ZFR1812 Router is a member of a wireless network.
OFF Steady with Signal Strength displayed once every 10 seconds = Wireless network is actively communicating, but ZFR1810 Coordinator cannot be reached (for example, coordinator lost power).
3 Flashes - Excellent 2 Flashes - Good 1 Flash - Weak OFF for 3 seconds - None
Rapid Flashes for 5 minutes = rapid flashes occur for up to 5 minutes:
• when the Reform Network option is initiated to the network, the ZFR1812 Router disconnects itself from the network
• when the PAN OFFSET is changed on the ZFR1812 Router
• when the PAN OFFSET is changed on the ZFR1812 Router after it has already joined another PAN
• when the Channel Mask in the ZFR1810 is changed from CCT
Network pings provide a means of physically locating connected devices. There are two methods with different use cases:
1) Use ZFR Checkout T ool (ZCT) to ping an address. The LED on the connected ZFR1812
blinks, indicating the device mapped to that specific MS/TP address.
2) Press the Occupancy push button on a WRZ Network Sensor. The ZFR1812 connected
to the paired device blinks. This blinking response can be used to validate switch settings on the sensor during installation.
1. The Signal Strength LEDs on all the ZFR1812 Routers in a network extinguish after approximately 2 hours of normal operation, making the ZFR1812 less distracting when installed in an open area. To re-enable the ZFR1812 LEDs for troubleshooting purposes, perform a scan using the ZCT or push the Network Optimize/Reform Push Button on the ZFR1810 Coordinator.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
9

Repair Information

If the ZFR1812 Wireless Field Bus Router fails to operate within its specifications, replace the unit. For a replacement ZFR1812 Route r, contact the nearest Johnson Controls® representative.

Accessories

See Table 4 for information on accessories for the ZFR1812 Router . Use the ZFRRPT -H1/H2 repeater kits for below ceiling repeater applications where the router is in visible space. Mounting the repeater in an open or visible space increases the transmission distances for improved wireless coverage.
Table 4: Accessories
Product Code
Product Description
Number
MS-ZFRRPT-0 Optional Repeater Accessory for use with ZFR1811 Routers as a repeater. Includes power supply
MS-ZFRRPTK-H1 ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24 VAC to 15 VDC power supply,
MS-ZFRRPTK-H2 ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24 VAC to 15 VDC power supply,
WRZ-SST-120 Wireless Sensing System Tool. Requires WRZ Series Sensor to function as a site survey tool for
ZFR-USBHA-0 USB Dongle with ZFR Driver provides a wireless connection through the CCT to allow wireless
(20 to 28 VAC or 16 to 30 VDC input power and 12 VDC output power). The ZFRRPT-0 with ZFR1811-1 combination is used for above ceiling repeater applications or
wherever mounting of the ZFR router is better facilitated using a ½ Inch conduit EMT connector.
RJ-12 cable for power extension, and mounting hardware. Use the ZFRRPT-H1 for flush wall mount or ceiling mount applications.
RJ-12 cable for power extension, mounting hardware, and mounting plate for electrical box. Use the ZFRRPT-H2 for mounting directly to a single or double gang electrical box. The electrical box is
not included with the kit.
ZFR1800 Wireless Field Bus System, or for WRZ-7860-0 One-to-One Room Temperature Sensing System.
commissioning of the wireless-enabled FAC, FEC, IOM, and VMA16 controllers. The USB ZFR Dongle is also used with the ZFR Checkout To ol used to troubleshoot and validate ZFR wireless meshes using a laptop computer.
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
10

Technical Specifications

ZFR1812 Wireless Field Bus Router (Part 1 of 2)

Product Code Number MS-ZFR1812-0: Field Equipment, Wireless Interface, Surface Mount, includes
hardwired 10 foot RJ-12 cable. MS-ZFRRPTK-H1: ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24
VA C to 15 VDC power supply, RJ-12 cable for power extension, and mounting hardware. MS-ZFRRPTK-H2: ZFR1812-0 wireless router repeater kit. Includes ZFR1812 router, 24
VA C to 15 VDC power supply , RJ-12 cable for power extension, mounting hardware, and mounting plate.
Power Supply Input 8 to 18 VDC, 15 VDC Nominal. Provided from the FC/SA BUS RJ-12 jack on the FEC or
VMA16 controller or from 24 VAC to 15 VDC power supply. The power converter for the repeater power supply has a flexible input power range and
provides regulated 12 VDC output. Input power:
• 20–28 VAC at 78–62 mA (maximum)
• 16–30 VDC at 45–28 mA (maximum)
• Output power: 12 VDC regulated at 500 mA maximum.
Current Consumption 90 mA maximum Addressing DIP Switches, Field Adjustable. Wireless Band Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Bands Transmission Power 10 mW Maximum Transmission Range 76.2 m (250 ft) Maximum Indoor Line-of-Sight
15 m (50 ft) Recommended Indoor
Ambient Conditions Operating: 0 to 50°C (32 to 122°F), less than 90% RH, Noncondensing
Non-Operating (Storage): -40 to 80°C (-40 to 176°F), less than 95% RH,
Noncondensing
Maximum Dew Point Temperature: 30°C (86°F)
Condensation: Recovers after 30 minute dry time Materials White PC/ABS Cycoloy Terminations RJ-12 plug for connection to FEC or VMA16 FC/SA Bus jack Dimensions 61 x 100 x 20.5 mm (5-3/8 x 3-15/16 x 3/4 in.) Mounting Hardware Screw mounted Shipping Weights ZFR1812: 0.113 kg (.25 lb)
Repeaters: 227 kg (.50 lb)
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
11
ZFR1812 Wireless Field Bus Router (Part 2 of 2)
Compliance United States:
Intended for Connection to an NEC Class 2 Power Source;
UL 916 Energy Management
Plenum rated per UL1995 UL94-5VB Flammability Rating
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters
Transmitter Identification ZFR1812-0: FCC: TFB-MATRIXL;
Transmitter Identification ZFR1812-1: FCC: OEJ-WRZRADIO;
Canada:
CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada (IC) Compliant to Canadian ICES-003, Class B Limits
Industry Canada (IC) RSS-210
Transmitter Identification ZFR1810-0: 5969A-MATRIXLP
Transmitter Identification ZFR1810-1: 279A-WRZRADIO
Australia and New Zealand:
RCM Mark, Australia/NZ Emissions Compliant
Europe:
CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the RED Directive.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MIL WAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
12
ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Figure 11: ZFR18 12 Mounting Template - Scale 1.000
Published in U.S.A. www.johnsoncontrols.com
13
Loading...