Johnson Controls Z2100 User Manual

SINGLE PIECE
INSTALLATION MANUAL
ISO 9001
Management System
VARIABLE SPEED AIR HANDLERS
MODELS: AV*(C) SERIES
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .7
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . .7
REQUIRED CONTROL SET-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
LIST OF FIGURES
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Return Duct Attachment & Component Location . . . . . . . . . . . . . . . . .3
Dimensions & Duct Connection Dimensions . . . . . . . . . . . . . . . . . . . .4
Condensate Deflector on Vertical Drain Pan . . . . . . . . . . . . . . . . . . . .4
Condensate Deflecctor on Horizontal Drain Pan Edge . . . . . . . . . . . .5
S-Clip Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Duck Work Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Typical Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
LIST OF TABLES
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Heat Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Comfort Setting Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical and Electrical Data - Cooling Only (60 Hz) . . . . . . . . . . . . . . . . 12
Electrical Data - Cooling Only (60 Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Conversion Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical Data - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
AIRFLOW AND COMFORT SETTING SELECTION . . . . . . . . . . . . 12
UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TXV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Proper Bulb Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Air Handler Control Board – Communications Connections . . . . . . . . 7
Cooling Models with and without Electric Heat Wiring . . . . . . . . . . . . 8
Two-Stage Heat Pump Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Air Handler with Communicating AC or HP . . . . . . . . . . . . . . . . . . . . 9
Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electrical Data - (For Single Source Power Supply) -
Copper Wire - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Data - (For Multi-Source Power Supply) -
Copper Wire - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Data - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical Data - (For Single Source Power Supply) -
Copper Wire - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical Data - (For Multi-Source Power Supply) -
Copper Wire - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Air Handler Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SECTION I: GENERAL
The AV single piece air handler provides the flexibility for installation in any upflow, downflow, or horizontal application.
These versatile models may be used for cooling or heat pump operation with or without electric heat.
A BRAND LABEL (available from Distribution) may be applied to the center of the blower access panel on AVG models.
The unit can be positioned for bottom return air in the upflow position, top return air in the downflow position, and right or left return in the hor­izontal position.
Top and side power wiring and control wiring, accessible screw termi­nals for control wiring, easy to install drain connections and electric heaters all combine to make the installation easy, and minimize installa­tion cost.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
.
.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. alert against unsafe practices and hazards involving only property dam­age.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assis­tance or for additional information, consult a qualified contractor, installer or service agency.
This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
FIRE OR ELECTRICAL HAZARD Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may result causing property damage, per­sonal injury or loss of life.
It is also used to
536636-UIM-D-1211
536636-UIM-D-1211
NOTICE
1. Install this air handler only in a location and position as specified in SECTION III of these instructions.
2. Always install the air handler to operate within the air handler’s intended maximum outlet air temperature. Only connect the air handler to a duct system which has an external static pressure within the allowable range, as specified on the air handler rating plate.
3. When an air handler is installed so that supply ducts carry air cir­culated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating in the space to be cooled/heated.
4. The air handler is not to be used for temporary heating of buildings or structures under construction.
5. The size of the unit should be based on an acceptable heat loss or gain calculation for the structure. ACCA, Manual J or other approved methods may be used.
SAFETY REQUIREMENTS
1. This air handler should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes.
2. Refer to the unit rating plate for the air handler model number, and then see the dimensions page of this instruction for supply air ple­num dimensions in Figure 3. The plenum must be installed accord­ing to the instructions.
3. Provide clearances from combustible materials as listed under Clearances to Combustibles.
4. Provide clearances for servicing ensuring that service access is allowed for electric heaters and blower.
5. Failure to carefully read and follow all instructions in this manual can result in air handler malfunction, death, personal injury and/or property damage.
6. Check the rating plate and power supply to be sure that the electri­cal characteristics match.
7. Air handler shall be installed so the electrical components are pro­tected from water.
8. Installing and servicing heating/cooling equipment can be hazard­ous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating/cooling equip­ment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating/cooling equipment, observe precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
9. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed.
Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping.
LIMITATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
1
Air Handler Voltage Voltage code
208/230-1-60 06 187-253
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp.°F Dry Bulb Temp. °F
Min. Max. Min. Max.
57 72 65 95
Normal Operating
Voltage Range
SECTION III: UNIT INSTALLATION
CLEARANCES
Clearances must be taken into consideration, and provided for as fol­lows:
1. Refrigerant piping and connections - minimum 12” recommended.
2. Maintenance and servicing access - minimum 36” from front of unit recommended for blower motor/coil replacement.
3. Condensate drain lines routed to clear filter and panel access.
4. Filter removal - minimum 36” recommended.
5. The ductwork and plenum connected to this unit are designed for zero clearance to combustible materials.
6. A combustible floor base accessory is available for downflow applications of this unit, if required by local code.
LOCATION
Location is usually predetermined. Check with owner’s or dealer’s installation plans. If location has not been decided, consider the follow­ing in choosing a suitable location:
1. Select a location with adequate structural support, space for ser­vice access, clearance for air return and supply duct connections.
2. Use hanging brackets to wall mount this single piece air handler unit, is not recommended.
3. Normal operating sound levels may be objectionable if the air han­dler is placed directly over some rooms such as bedrooms, study, etc.
4. Select a location that will permit installation of condensate line to an open drain or outdoors allowing condensate to drain away from structure.
The primary and secondary drain line must be trapped to allow proper drainage of condensate water. If the secondary drain line is not used, it must be capped. The coil is provided with a secondary drain. It should be piped to a location that will give the occupant a visual warn­ing that the primary drain is clogged. If the secondary drain is not used it must be capped.
5. Proper electrical supply must be available.
6. If unit is located in an area of high humidity (ie: an unconditioned garage or attic), nuisance sweating of casing may occur. On these installations, unit duct connections and other openings should be properly sealed and a wrap of 2” fiberglass insulation with vinyl vapor barrier should be used.
2 Johnson Controls Unitary Products
536636-UIM-D-1211
NOTICE
UPFLOW DOWNFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
NOTICE
FRONT VIEW
SIDE VIEW
BLOWER COMPARTMENT
VERTICAL DRAIN PAN
REFRIGERANT LINE CONNECTIONS
PRIMARY DRAIN UPFLOW 3/4” THREADED
DUCT WORK MAY BE FASTENED CAUTIOUSLY WITH SCREWS TO THE SIDES AND REAR OF UNIT
SECONDARY DRAIN UPFLOW 3/4” THREADED
COIL COMPARTMENT (Access panel removed)
HORIZONTAL DRAIN PAN
HORIZONTAL SECONDARY DRAIN
HORIZONTAL PRIMARY DRAIN
ALTERNATE DRAIN CONNECTIONS UPFLOW/DOWNFLOW
FILTER DOOR
RETURN AIR
DUCT
WHEN ATTACHING DUCT WORK WITH SCREWS - KEEP SCREWS WITHIN 5/8” OF SIDES AND BACK OF AIR HANDLER
When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes.
FIGURE 1: Typical Installation
DOWNFLOW AND HORIZONTAL CONVERSION (AV ONLY)
These air handler units are supplied ready to be installed in a upflow and right hand horizontal position. If unit requires left hand positioning, the unit must have the coil assembly repositioned.
1. Remove blower, coil, and filter access panels.
Conversion must be made before brazing the refrigerant connections to the coil.
For downflow and horizontal left installations, follow steps 2 - 8.
2. Remove tubing connection panel.
3. Remove front drain pan, hold down bracket.
4. Slide coil assembly out of air handler.
5. Rotate cabinet 180º so blower outlet is facing down.
In severe high humidity, high temperature indoor unit environments, an accessory insulation blanket is available to supplement the stan­dard cabinet insulation. Insulate with UPG Kit: 1VJ0117 for B cabi­nets, 1VJ0121 for C cabinets or 1VJ0124 on D cabinets or seal completely with adequate fiberglass insulation using vapor barrier on the outside.
6. Re-install coil assembly on downflow bracket.
7. Re-attach front drain pan, hold down bracket.
8. Re-attach tubing connection panel.
9. For horizontal applications, rotate air handler 90º into desired ori-
entation.
10. Re-position drain plugs as necessary based on air handler orienta-
tion.
11. Re-position and replace access panels.
12. For downflow installations, the cladding should be reconfigured so
that the grille and circuit breaker covers having logos and/or black coloring are at the top of the unit on the coil access panel. See below.
13. Apply branding label to air handler in recessed area provided on
blower access panel cladding. This label should be applied after the air handler is placed in its proper orientation so the label is right side up.
FIGURE 2: Return Duct Attachment & Component Location
Johnson Controls Unitary Products 3
536636-UIM-D-1211
NOTICE
10-3/8”
F
CIRCUIT
BREAKER
PANEL
BOTTOM INLET
DIMENSIONS
BLOWER COMPARTMENT
REFRIGERANT
DRAIN CONNECTIONS
FOR UPFLOW AND
DOWNFLOW APPLICATIONS
D
A
E
TOP OUTLET DIMENSIONS
18-9/32”
J
K
CLADDING
CONDENSATE
S-CLIPS (3)
VERTICAL
NOTICE
CLADDING CONFIGURATION FOR DOWNFLOW INSTALLATION (IF USED)
To reconfigure the cladding parts, remove the grille by pulling gently at the top. Once the grille is removed, the circuit breaker cover can also be removed. Remove the gray, non-branded grille and circuit breaker cover from the cladding on the coil access panel. Next, remove the black and/or branded grille and circuit breaker cover from the blower access panel. Install these pieces into the coil access panel cladding so they are at the top of the air handler. Install the gray, non-branded grille and circuit breaker cover in the blower access panel cladding.
If a heat kit with a circuit breaker is installed in the air handler, the cir­cuit breaker cover cladding must be removed to gain access to the sheet metal cover plate. Some local codes may require that the circuit breaker remain visible. If so, do not re-install circuit breaker cover cladding.
FIGURE 3: Dimensions & Duct Connection Dimensions TABLE 1:
Dimensions
Dimensions (Inches)
Models
AV
AB C
Height Width Depth Power Control Liquid Vapor
24B 46 17 1/2 36C 52 21 17-1/8 17-13/32 18-3/32 7/8” 48D 57 24 1/2 22-1/8 20-29/32 21-19/32 7/8” 60D 57 24 1/2 22-1/8 20-29/32 21-19/32 7/8’
1. Actual size (Conduit size).
21-1/2
(w/o cladding)
22-1/2
(with cladding)
SUCTION FEEDER TUBE CONDENSATE DEFLECTOR
UPFLOW OR DOWNFLOW
No action required. See Figure 4.
DEF
12-3/8 13-29/32 14-19/32
Horizontal Left or Right
Use an appropriate tool to pry out water deflector with two or three s­clips from the vertical drain pan. See Figure 4. Relocate the deflector with s-clips on the Horizontal Drain Pan lined up to the coil support brackete. See Figure 5. This positions the deflector below the feeder tubes to channel the condensate to the drain pan.
The condensate deflector should be installed in the s-clip section which is inside the drain pan edge. See Figure 6.
Wiring Knockouts
JK
7/8” (1/2”) 1 3/8” (1”)
7/8” (1/2”) 3/8”
1 23/32” (1 1/4”)
1
Refrigerant
Connections
Line Size
3/4”
FIGURE 4: Condensate Deflector on Vertical Drain Pan
4 Johnson Controls Unitary Products
FIGURE 5: Condensate Deflecctor on Horizontal Drain Pan Edge
S-CLIPS ON HORIZONTAL PAN
FEEDER
TUBES
CONDENSATE
DEFLECTOR
DEFLECTOR
S-CLIP
DRAIN PAN
WALL
SUGGESTED LOCATION OF BLOCK OFF PLATE
RECOMMENDED TRANSITION
536636-UIM-D-1211
ers and never fastened directly to the structure. This unit is not designed for non-ducted (freeblow) applications. Size outlet plenum or transition to discharge opening sizes shown in Figure 3.
Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air-Conditioning and Ventilat­ing Systems, NFPA No. 90B.
DUCT WORK TRANSITION
Duct work that is not designed to match the supply air opening can cause turbulence inside the plenum box. This turbulence can change the air flow patterns across the heat kit limit switch. If the factory sug­gested transition can not be fabricated, it is recommended a block off plate (approximately 8” in height and running the full width of the ple­num) be attached to the supply opening Please refer to Figure 7 as a visual aid. The use of this block off plate will keep better air circulation across the limit switch.
FIGURE 6: S-Clip Installation
DUCT CONNECTIONS
Use 1/2" screws to connect ductwork to bottom of unit. Longer screws will pierce the drain pan and cause leakage. If pilot holes are drilled, drill only though field duct and unit bottom flange.
Air supply and return may be handled in one of several ways best suited to the installation. See Figure 3 for dimensions for duct inlet and outlet connections.
The vast majority of problems encountered with combin ation heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an instal­lation that the duct system be properly designed and installed.
Use flexible duct collars to minimize the transmission of vibration/noise into the conditioned space. If electric heat is used, non-flammable material must be used.
Where return air duct is short, or where sound may be a problem, sound absorbing glass fiber should be used inside the duct. Insulation of duct work is a must where it runs through an unheated space during the heating season or through an uncooled space during the cooling season. The use of a vapor barrier is recommended to prevent absorp­tion of moisture from the surrounding air into the insulation.
The supply air duct should be properly sized by use of a transition to match unit opening. All ducts should be suspended using flexible hang-
FIGURE 7: Duck Work Transition The above suggestions will not alleviate problems caused by improper
installation. When receiving intermittent fault codes pertaining to the limit switch, always double check your airflow CFM, motor speed and static pressures.
AIR FILTERS
Air filters must be field supplied. A 1" filter access rack has been built into the unit. See Figure 3. Remove filter access cover shown. Install proper size filter. Standard 1" size permanent or throw away filter may be used, or, permanent washable filters are available using model num­bers: 1PF0601, 602, 603BK. See Table 8 for filter size.
Equipment should never be operated without filters.
HORIZONTAL SUSPENSION (AV ONLY)
For suspension of these units in horizontal applications, it is recom­mended to use angle steel support brackets with threaded rods, sup­porting the units from the bottom, at the locations shown in Figure 8.
When an evaporator coil is installed in an attic or above a finished ceil­ing, an auxiliary drain pan should be provided under the air handler as is specified by most local building codes.
Johnson Controls Unitary Products 5
536636-UIM-D-1211
WW
XX
SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS
2
1-1/2
MIN. 1-1/2” x 1-1/2” Angle Recommended length 26” minimum with 2” clearance on both sides of Air Handler
MIN. 3/8”
THREADED ROD
YY
VAPOR LINE
THERMAL EXPANSION VALVE BULB (Required insulation not shown for clarity)
THERMAL EXPANSION VALV E
DISTRIBUTOR BODY
LIQUID LINE
TXV EQUALIZER LINE
TXV BULB (Cover completely with insulation)
SCREW
CLAMP
NUT
SUCTION LINE
NOTICE
NOTICE
Units
(Nominal Tons)
WW XX 24B 20 46 36C 24 52
AV*48D, 60D 28 57
FIGURE 8: Typical Horizontal Installation
Dimension
TXV METERING DEVICES
If the model (C) number is of the following format: 4F, 4G, 4H, 4J, and 4K will have the coil with R410A TXV metering device installed at the factory.
If the model (C) number is of the 3X model series:
The coil will require an orifice or R410A TXV to be installed in the field. Refer to installation manual with TXV kit. It is recommended to install a orifice or TXV kit prior to brazing line sets.
COIL UNDER PRESSURE. Relieve pressure by depressing schrader core. Coil may have factory
installed TXV or may require orifice or TXV to be added. See outdoor unit documentation for correct orifice or TXV to be used. Refer t o coil nameplate for TXV identification for this unit.
The coil should be open to the air for no more than 2 minutes to keep moisture and contaminates from entering the system. If the coil can­not be installed into the refrigeration system in that time, the ends should be temporarily closed or plugged. For a short term delay, use masking tape over the ends of the copper tubing to close the tube to the air. For a longer term delay, use plugs or caps. There is no need to purge the coil if this procedure is followed.
REFRIGERANT LINE CONNECTION
Coil is under inert gas pressure. Relieve pressure from coil by depressing schrader core.
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
Connect lines as follows:
FIGURE 9: TXV Please refer to Outdoor Unit Tech Guide to verify which metering device
is installed in this coil and that this is a valid system match for the AC or HP unit installed.
The temperature sensing bulb is attached to the coil suction header line.
FIGURE 10: Proper Bulb Location
Route the refrigerant lines to the coil in a manner that will not obstruct service access to the coil, air handling system, or filter.
1. Suction and liquid line connections are made outside the cabinet. Leave the tubing connection panel attached to the cabinet with the tubes protruding through it. Coil access panel should be removed for brazing. The lines are swedged to receive the field line set tubes.
2. Cut the end of the suction tube using a tube cutter. Place the tube cutter as close as possible to the end of the tube to allow more space for the connection and brazing of the suction line.
3. Remove the heat shield from the Customer Packet, soak in water, and install over coil tubing to prevent overheating of cabinet.
4. Wrap a water soaked rag around the coil connection tubes inside the cabinet to avoid damaging the TXV bulb.
5. Remove grommets where tubes exit the cabinet to prevent burning them during brazing.
6. Purge refrigerant lines with dry nitrogen. Follow outdoor unit braz­ing instructions.
7. Braze the suction and liquid lines.
8. Remove the heat shield.
9. Re-attach the grommets to the lines carefully to prevent air leak­age.
10. Attach the coil access panel to the cabinet.
Refer to Outdoor unit Installation Manual for evacuation, leak check and charging instructions.
Lines should be sound isolated by using appropriate hangers or strap­ping.
All evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder.
6 Johnson Controls Unitary Products
536636-UIM-D-1211
NOTICE
NOTICE
SPARE JUMPER
HEAT ENABLE JUMPER
HUMIDIFIER OUT PUT
EAC OUTPUT
THERMOSTAT CONNECTIONS
CONTINUOUS FAN JUMPER
BLOWER SPEED JUMPERS
HUMIDSTAT JUMPER
AC/HP JUMPER
DRAIN CONNECTIONS
All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.
Threaded drain connection should be hand-tightened, plus no more than 1/16 turn.
Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. See Figures 2 and 3 for drain connection locations.
When the coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil if specified by local building codes.
Coils should be installed level or pitched slightly toward the drain end. Suggested pitch should not exceed 1/4 inch per foot of coil.
The coil is provided with a secondary drain that should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped. When an exterior secondary drain pan is used that secondary drain should br piped to a location that will give the occupant a visual warning that the primary drain is clogged.The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. Use 3/4" PVC or steel threaded pipe. Since the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines.
DO NOT use teflon tape, “pipe dope” or other sealants. The use of a sealant may cause damage and premature failure of hte drain pan
SECTION IV: ELECTRIC HEATER INSTALLATION
If the air handler requires electric heat, install the electric heat kit according to the installation instructions included with the kit. After installing the kit, mark the air handler nameplate to designate the heater kit that was installed. If no heater is installed, mark the name plate appropriately to indicate that no heat kit is installed.
The HEAT/ENABLE jumper (See Figure 10) must be moved to the HEAT position to enable operation of the heater.
Use only 4HK heater kits, as listed on Air Handler name plate and in these instructions. Use data from Tables 10 and 13 for information on required minimum motor speed tap to be used for heating operation, maximum over-current protection device required and minimum electri­cal supply wiring size required – for listed combination of Air Handler and Heater Kit.
For Upflow, Downflow and Horizontal right hand applications the kits can be installed without modification.
Field modification is required for Horizontal left hand airflow application only. Follow instructions with heater kits for modification.
If a heat kit with a circuit breaker is installed in the air handler, the cir­cuit breaker cover cladding must be removed to gain access to the sheet metal cover plate. Some local codes may require that the circuit breaker remain visible. If so, do not re-install circuit breaker cover cladding.
SECTION V: LOW VOLTAGE CONTROL CONNECTIONS
This air handler can be connected to the wall thermostat and outdoor air conditioner or heat pump using either conventional low voltage (24 VAC) thermostat wiring OR using four-wire digital communications wir­ing. To use conventional low voltage wiring, see the section below enti­tled “Conventional Low Voltage Control Wiring”. To use four-wire communications control wiring, see the section below entitled “Control Wiring using Communicating Controls”.
The Communicating System consists of several intelligent communicat­ing components including the Communicating Thermostat Control (touch-screen wall thermostat), variable speed air handler, air condi­tioner (15 and 18 SEER premium air conditioners) or heat pump (13, 15 and 18 SEER premium heat pumps), which continually communicate with each other via a four-wire connection called the A-R-Gnd or C-B bus. Commands, operating conditions, and other data are passed con­tinually between components over the A-R-Gnd or C-B bus. See Figure
13. The result is a new level of comfort, versatility, and simplicity. In order to use this air handler in full communications (COMM) mode, it
MUST be installed with the matching touch-screen Communicating Control (wall thermostat) and an outdoor air conditioner or heat pump with a fully communicating control.
This air handler may also be used along with the Communicating Ther­mostat Control and a non-communicating outdoor air conditioner through the addition of a communicating Outdoor Aux Control board to the outdoor unit. This system allows full communication between the air handler and thermostat and limited communication to the outdoor unit.
This air handler may also be used along with the Communicating Ther­mostat Control and a non-communicating outdoor air conditioner or heat pump using COMM between the air handler and thermostat and conventional 24V wiring to the outdoor unit. This system allows full communication between the air handler and thermostat but no digital communication with the outdoor unit. See Figure 14.
FIGURE 11: Air Handler Control Board – Communications Connections
Johnson Controls Unitary Products 7
536636-UIM-D-1211
NOTICE
NOTICE
Air Handler Control Wiring
Typical A/C - Cooling only Applications
THERMOSTAT
AIR HANDLER
BOARD
1-STAGE
AIR CONDITIONING
RR
G
Y
W1
W2
C
G
W1
W2
Y
C
Y/Y2
Y1
O
HUM
X/L
COM
HUMIDISTAT
*
THERMOSTAT
AIR HANDLER
BOARD
1-STAGE
AIR CONDITIONING
RR
G
Y
W1
W2
C
G
W1
W2
Y
C
Y/Y2
Y1
O
HUM
X/L
COM
HUMIDISTAT
*
Air Handler Control Wiring
Typical A/C with Electric Heat Applications
CONVENTIONAL LOW VOLTAGE CONTROL WIRING (24 VAC)
The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models, However, if the unit is con­nected to a 208 volt power supply, the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label.
Field supplied low voltage wiring can exit the unit on the top right hand corner or the right hand side panel. Refer to Figure 3.
Remove desired knockout and pierce foil faced insulation to allow wir­ing to pass through. Use as small of a hole as possible to minimize air leakage.
Install a 7/8” plastic bushing in the selected hole and keep low voltage wiring as short as possible inside the control box.
To further minimize air leakage, seal the wiring entry point at the outside of the unit.
The field wiring is to be connected at the screw terminals of the control board. Refer to Figure 11 and 12.
.All wiring must comply with local and national electrical code require­ments. Read and heed all unit caution labels.
It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump. Standard wiring will only bring on the first stage of electric heat during defrost. See Heat Output and Limit Connections and Table 5 for additional information on heat during defrost cycle.
TABLE 2:
Low Voltage Connections
Terminal Signal Comment
R 24 VAC power (fused) G Continuous Fan operation
Y/Y2
HUM Humidity switch input
COM 24 VAC common
Second or full stage compressor operation
First stage compressor
Y1
operation W2 Second stage heat operation W1 First stage heat operation
O Reversing valve operation
Connection point for X/L
heat pump fault indicator
Not used with outdoor units having one stage compressors.
24 VAC will be present at this terminal when the MODE jumper is in the AC position. This is normal.
24 VAC will be present at this terminal when the HUM STAT jumper is in the NO position. This is normal.
This terminal is a connection point only and does not affect air handler control operation.
The low voltage connections may be connected to the screw terminals or the quick connect terminals. The screw terminals and the quick con­nect terminals are physically connected on the control board.
FIGURE 12: Cooling Models with and without Electric Heat Wiring
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
8 Johnson Controls Unitary Products
536636-UIM-D-1211
CONTROL WIRING - Air Handler & UPG HP Systems
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”
Conventional Application - Not Hot Heat Pump
THERMOSTAT
AIR HANDLER
BOARD
2 - STAGE SCROLL
HEAT PUMP
RR R
GG
Y2
E
W
W
O O
O
X / L X / L X / L
C
C
Y/Y2
Y1
Y1
Y2 OUT
Y2
W2 OUT
W1 OUT
BS
W2
W1
HUM
COM
HUMIDISTAT
*
Y1
A+
R
C
B-
A+
R
C
B-
A+
R
C
B-
R
G
Y/Y2
Y1
W2
W1
O
HUM
X/L
COM
Touch Screen
Communicating
Control
Air Handler
Communicating
Control
Air Conditioner/Heat Pump
Communicating Control
NOTICE
NOTICE
.
FIGURE 13: Two-Stage Heat Pump Wiring
* Optional dehumidification humidistat switch contacts open on humidity rise. NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board
CONTROL WIRING USING COMMUNICATING CONTROLS
Use the wiring diagram below to connect the air handler control, Com­municating Control (wall thermostat) and communicating outdoor unit. Be sure that all of the “A” terminals are connected together, all of the “B” terminals are connected together, all of the “GND” or “C” terminals are connected together and all of the “R” terminals are connected together. See Figure 13. When using a fully communicating system, the large screw terminals (C, G, R, etc.) on the air handler control are not used. The four small screw terminals in the terminal block on the end of the air handler control should be used.
FIGURE 14: Air Handler with Communicating AC or HP
Johnson Controls Unitary Products 9
HUMIDITY SWITCH INPUT
The air handler control is designed to work with a humidity control that closes when the humidity is below the set-point. The control is open when the humidity is above the set-point. This humidity control may be referred to as a humidistat or a dehumidistat.
The humidity switch controls both humidification and de-humidification operation of the control. The control provides humidification using the HUM OUT relay output and de-humidification by lowering the blower speed. This is accomplished using the de-humidification input of the motor for variable speed models. The humidity switch should be con­nected to the R and HUM terminals of the control. See Figures 11 and
12. The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models, However, if the unit is con­nected to a 208 volt power supply, the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label.
Field supplied low voltage wiring can exit the unit on the top right hand corner or the right hand side panel. Refer to Figure 3.
Remove desired knockout and pierce foil faced insulation to allow wir­ing to pass through. Use as small of a hole as possible to minimize air leakage.
Install a 7/8” plastic bushing in the selected hole and keep low voltage wiring as short as possible inside the control box.
To further minimize air leakage, seal the wiring entry point at the outside of the unit.
The field wiring is to be connected at the screw terminals of the control board. Refer to Figures 11 or 12.
All wiring must comply with local and national electrical code require­ments. Read and heed all unit caution labels.
It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump. Standard wiring will only bring on the first stage of electric heat during defrost. See Heat Output and Limit Connections and Table 5 for additional information on heat during defrost cycle.
536636-UIM-D-1211
The low voltage connections may be connected to the screw terminals or the quick connect terminals. The screw terminals and the quick con­nect terminals are physically connected on the control board.
TABLE 3:
Low Voltage Connections
Terminal Signal Comment
R 24 VAC power (fused) G Continuous Fan operation
Y/Y2
Y1
W2 Second stage heat operation W1 First stage heat operation
O Reversing valve operation
HUM Humidity switch input
X/L
COM 24 VAC common
Second or full stage
compressor operation
First stage compressor
operation
Connection point for
heat pump fault indicator
Not used with outdoor units
having one stage compressors.
24 VAC will be present at this
terminal when the MODE
jumper is in the AC position.
This is normal.
24 VAC will be present at this
terminal when the HUM STAT
jumper is in the NO position.
This is normal.
This terminal is a connection
point only and does not affect
air handler control operation.
SECTION VI: REQUIRED CONTROL SET-UP
The following steps must be taken at the time of installation to insure proper system operation.
1. Consult system wiring diagram to determine proper thermostat wiring for your system.
2. If heat kit is installed, change HEAT/NO HEAT jumper from NO HEAT to HEAT position.
3. If a humidistat is installed, change HUM STAT jumper from NO to YES.
4. Set the MODE jumper to A/C (Air Conditioner) or HP (Heat Pump) position depending on the outdoor unit included with the system.
5. Set airflow and comfort setting jumper to proper positions.
FUNCTIONALITY AND OPERATION
Jumper Positions
HEAT/NO HEAT Jumper
The HEAT/NO HEAT jumper configures the control for heat kit opera­tion. The jumper must be in the HEAT position if a heat kit is installed with the air handler.
With the jumper in the NO HEAT position, the control will not energize the heat relay outputs or sense the limit switch input.
If the jumper is not present, the control will operate as if the jumper is in the HEAT position. If the jumper is not present and a heat kit is not pres­ent, the control will sense an open limit condition and the blower will run continuously.
Hum Stat Jumper
The HUM STAT jumper configures the control to monitor the humidity switch input. With the jumper in the NO position, the control will ener­gize the HUM terminal with 24 VAC continually. With the jumper in the YES position, the control will monitor the HUM input to control the HUM OUT output to control an external humidifier.
If the jumper is not present, the control will operate as if the jumper is in the YES position.
Mode Jumper
The MODE jumper configures the control to operate properly with an air conditioner (AC position) or heat pump (HP position). With the jumper in the AC position, the control will energize the O terminal with 24 VAC continually. With the jumper in the HP position, the O input signal is received from the room thermostat.
If the jumper is not present, the control will operate as if the jumper is in the HP position.
SPARE Jumper
The control includes a spare jumper that can be used if a jumper is lost. The SPARE jumper does not have any effect on the operation of the control.
Airflow and Comfort Setting Jumpers
See separate section.
Status and Fault Codes
The control includes an LED that displays status and fault codes. These codes are shown in Table 4. The control will display the fault codes until power is removed from the control or the fault condition is no longer present.
TABLE 4:
Fault Codes
Fault or Status Condition
LED1 (RED)
Flash Code
Status
No power to control OFF Normal operation 2s ON/2s OFF Control in test mode Rapid Flash Control failure ON
Limit Faults
Limit switch currently open (not in lockout) 1 Multiple limit openings with no call for heat 2 Multiple limit openings during one call for heat 3 Single long duration limit opening 4 Multiple long duration limit openings 5 Fan failure 6
Wiring Related Faults
Simultaneous call for heating and cooling 7
Internal Control Faults
Control recovered from internal event 9
External Relay Outputs
The control includes two outputs to drive external relays having 24 VAC coils. The outputs have a maximum rating of 1.0 Amp pilot duty at 24 VAC.
HUM OUT
The HUM OUT output can be used to drive an external relay or solenoid (24 VAC coil) to control a humidifier. The output is energized when the HUM input is energized, the HUM STAT is in the YES position, and the control has a thermostat call for heating (heat pump or electric heat).
EAC
The EAC output can be used to drive an external relay (24 VAC coil) to control an electronic air cleaner. The output is energized whenever the blower relay on the control is energized.
Heat Output and Limit Connections
The control is connected to the heater relays and limit switch using the 6-pin connector. The relay outputs and the limit switch signal are 24 VDC.
The control energizes the heat relays and senses the limit switch input as shown in Table 5 when the HEAT ENABLE jumper is in the HEAT position.
10 Johnson Controls Unitary Products
536636-UIM-D-1211
ELECTRIC HEAT
WITHOUT CIRCUIT BREAKER
SINGLE SOURCE (2.5 - 10 KW)
GND. LUG
POWER SUPPLY
GND. LUG
ELECTRIC HEAT
WITHOUT CIRCUIT BREAKER
3 PHASE (10 - 15 KW)
GND. LUG
POWER SUPPLY
GND. LUG
1 PHASE ELECTRIC HEAT
WITH CIRCUIT BREAKER
AS SHIPPED FROM FACTORY
SINGLE SOURCE
(2.5 - 25 KW) - 25 KW SHOWN
GND. LUG
POWER SUPPLY
GND. LUG
1 PHASE ELECTRIC HEAT
WITH CIRCUIT BREAKER
& BREAKER BAR REMOVED
MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN
GND. LUG
POWER SUPPLY 1
GND. LUG
POWER SUPPLY 2
POWER SUPPLY 3
TYPICAL WIRING WITHOUT ELECTRIC HEAT
GND. LUG
POWER SUPPLY
GND. LUG
POWER WIRING (208/230-1-60)
TERMINAL BLOCK
TERMINAL BLOCK
MAY BE 1, 2, OR 3 CIRCUIT BREAKERS
MAY BE 1, 2, OR 3 CIRCUIT BREAKERS
(JUMPER BAR)
CONNECT TRANSFORMER LEADS WITH WIRE NUTS (TYPICAL ALL HEAT KITS)
TABLE 5:
Heat Relays
Input Heat Relay Output
W1 HT1 W2 HT1 and HT2
W1 and W2 HT1 and HT2 and HT3
The control energizes the first stage of electric heat immediately, the second stage 10 seconds after the call for second stage heat, and the third stage 20 seconds after the call for third stage heat.
Depending on the heat kit installed in the air handler, the control pro­vides the flexibility to configure the amount of heat delivered with the first stage heating call. As an example, when the control’s W1 input is connected to the room thermostat’s first stage heat signal, a call for first stage heat will energize one heating element (HT1). If the control’s W2 input is connected to the room thermostat’s first stage heat signal, a call for first stage heat will energize two heating elements (HT1 and HT2). With either configuration, the control will energize three heating ele­ments (HT1, HT2, and HT3) when it receives a first and second stage heat input from the thermostat.
Limit Switch and Lockout Operation
Limit Switch Operation
If the HEAT ENABLE jumper is in the HEAT position and the limit switch opens (fault code 1), the control will immediately de-energize all electric heat relay outputs and energize the blower (if it wasn’t already ener­gized). When the limit switch closes, the control will re-energize electric heat according to the thermostat inputs using normal timings.
Fan On Lock Condition
If the limit switch opens multiple times during a single call for electric heat (fault code 3) or if the limit switch opens for a long duration (fault code 4), the control will energize the blower until power is removed from the control. The control will cycle the heat outputs on and off as the limit re-closes and opens. The constant fan operation will signal the home­owner that a problem has occurred and a service call is required.
Soft Lockout
If the limit switch opens for a second long duration period during a sin­gle call for heat (fault code 5), the control will keep the blower locked on and lock out the heat outputs for one hour. The control will only reset this one hour lockout when the power is removed from the control. After the one hour period has passed, the control will re-energize electric heat according to the thermostat inputs using normal timings. The blower will remain locked on from the first long duration limit opening.
Hard Lockout
The control has a hard lockout condition during which the control will keep all heat outputs de-energized until power is removed from the con­trol. The control de-energizes the blower five minutes after entering the hard lockout condition.
If the limit switch closes and re-opens during the one hour soft lockout period, the control will enter a hard lockout condition and continue to indicate a fault code 5.
If the limit switch opens twice when no call for electric heat is present (fault code 2), the control will enter a hard lockout condition.
If the limit switch opens multiple times soon after a soft lockout reset (fault code 6), the control will enter a hard lockout condition.
Wiring Related Faults
If the control receives a simultaneous call for heating and cooling (fault code 7), the control will perform both heating and cooling operations.
SECTION VII: LINE POWER CONNECTIONS
Power may be brought into the unit through the supply air end of the unit (top when unit is vertical) or the left side panel. Use the hole appro­priate to the unit’s orientation in each installation to bring conduit from the disconnect. The power lead conduit should be terminated at the electrical control box. Refer to Tables 11, 12, 14 and 15 to determine proper wire sizing. T o minimize air leakage, seal the wiring entry point at the outside of the unit.
All electrical connections to air handlers must be made with copper con­ductors. Direct connection of aluminum wiring to air handlers is
not approved.
If aluminum conductors are present, all applicable local and national codes must be followed when converting from aluminum to copper con­ductors prior to connection to the air handler.
If wire other than uncoated (non-plated), 75° C ambient, copper wire is used, consult applicable tables of the National Electic Code (ANSI/ NFPA 70). The chosen condutor and connections all must meet or exceed the amperage rating of the overcurrent protector (circuit breaker or fuse) in the circuit.
Additionally, existing aluminum wire within the structure must be sized correctly for the application according to National Electric Code and local codes. Caution must be used when sizing aluminum rather than copper conductors, as aluminum conductors are rated for less current than copper conductors of the same size.
FIGURE 15: Line Power Connections
Johnson Controls Unitary Products 11
536636-UIM-D-1211
NOTICE
SECTION VIII: AIRFLOW AND COMFORT SETTING SELECTION
AIRFLOW SELECTION
The airflow and comfort setting selection jumpers must be set properly at the time of installation for proper system operation. Place jumpers in the proper locations based on the information shown in Table 16 and Figure 11. Inputs to air handler control board are passed to the motor which deter­mines the target CFM to be delivered. The following inputs will produce the CFM per the appropriate table and selected tap settings.
Incorrect airflow and comfort settings may result in decreased system efficiency and performance.
These variable speed air handlers are designed to deliver constant air­flow (CFM) regardless of the external static pressure (ESP) in the duct­work. Therefore, if too many supply registers are closed, a filter becomes clogged, or there is a restriction in the ductwork, the motor will automatically operate at a higher speed to compensate for the highe r ESP. This may result in a higher operating sound level.
To Set Cooling Airflow: Refer to the outdoor unit technical guide for the recommended airflow
with the matching evaporator coil. Refer to Table 16 for the possible high speed cooling and heat pump airflow selections.
Find the recommended system airflow in Table 16 for the installed air handler model.
Select the COOL airflow you need from Table 16. Set the COOL and ADJUST Jumpers on the control as indicated in Table 16.
To Set Heat Pump Airflow: The heat pump airflow setting is the same as the cooling airflow setting.
No additional airflow setting is required. However, you must set the MODE jumper to the HP position for proper system operation (See Fig­ure 11).
To Set Electric W1 Heat Airflow: The blower speed required for 1st stage electric heat is different than
cooling. Refer to Table 16 for the possible CFM selections. Refer to Table10 for the minimum required airflow for the electric heater installed. Find the desired airflow in T able 16 for low heat. Set the HEAT jumper on the control as indicated in Table 16.
To Set W2 Electric Heat Airflow: Airflow for any W2 input, which is for Stages 2 & 3 of electric heat, is the
indicated CFM for high heat tap selection on Table 16.
DO NOT change the ADJUST tap position on the control as this will change your cooling airflow previously selected.
Fan Only CFM: When the connection is made from "R" to "G", the fan only mode is acti-
vated. In this mode, the airflow will depend on the position of the CONT Fan jumper. In the “H” position, the blower will deliver 85-90% of full capacity. In the “M” position, the blower will deliver 60-65% of full capacity . In the “L” position, the blower will deliver 30-35% of full cap ac­ity.
Blower Ramp-Up /Ramp-Down To minimize the sound made by the blower when it speeds up or slows
down, the blower will slowly ramp up or down from one speed to another. Changes in blower speed during A/C or heat pump heating can take up to 30 seconds. Changes in blower speed during electric strip heating can take up to 15 seconds.
:
COMFORT SETTINGS
TABLE 6:
Comfort Setting Selection
DELAY TAP COMFORT SETTING
ANormal BHumid CDry D Temperate
Normal
The normal setting provides a ramp-up from zero airflow to full capacity and a ramp-down from full capacity back to zero airflow.
Humid
The humid setting is best-suited for installations where the humidity is frequently very high during cooling season, such as in the southern part of the country. On a call for cooling, the blower will ramp up to 50% of full capacity and will stay there for two minutes, then will ramp up to 82% of full capacity and will stay there for five minutes, and then will ramp up to full capacity , where it will st ay until the wall thermostat is sat­isfied.
Dry
The dry setting is best suited to parts of the country where excessive humidity is not generally a problem, where the summer months are usu­ally dry. On a call for cooling the motor will ramp up to full capacity and will stay there until the thermostat is satisfied. At the end of the cooling cycle, the blower will ramp down to 50% of full capacity where it will stay for 60 seconds. Then it will ramp down to zero.
Temperate
The temperate setting is best suited for most of the country, where nei­ther excessive humidity nor extremely dry conditions are the norm. On a call for cooling, the motor will ramp up to 63% of full capacity and will stay there for 90 seconds, then will ramp up to full capacity. At the end of the cooling cycle, the motor will ramp down to 63% of full capacity and will stay there for 30 seconds, then will ramp down to zero.
SECTION IX: UNIT DATA
TABLE 7:
Models 24B 36C 48D 60D
Blower - Diameter x Width 10 x 7 10 x 7 10 x 10 10 x 10 Motor Voltage 230
Amps Full Load (230) 2.8 4.3 5.5 7.0
Filter
Shipping/Operating Weight (lbs.) 140/134 170/164 AV - 196/185 AV - 199/188
1. Field Supplied.
12 Johnson Controls Unitary Products
Physical and Electrical Data - Cooling Only (60 Hz)
HP 1/3 1/2 3/4 1 Nominal RPM 1200 1200 1200 1200
1
Type DISPOSABLE OR PERMANENT Size 16 x 20 x1 20 x 20 x1 22 x 20 x1 22 x 20 x1 Permanent Type Kit 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK
536636-UIM-D-1211
TABLE 8:
Electrical Data - Cooling Only (60 Hz)
Total Motor Amps Minimum Circuit Ampacity
Models
60 Hertz 60 Hertz
208V 230V 208V 230V
Max. O.C.P.
Amps/Type
24B 3.2 2.8 4.0 3.5 15 14 36C 4.7 4.3 5.9 5.4 15 14 48D 6.1 5.0 7.6 6.9 15 14 60D 7.8 7.0 9.7 8.8 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
TABLE 9:
Conversion Table
kW & MBH Conversions - for Total Power Input Requirement
208V
FOR
230V 240V .918
OPERATION MULTIPLY
240V
.751
TABULATED kW & MBH BY
220V 240V .840
TABLE 10:
Electrical Data - 208/230-1-60
Models
Heater
Models*
Max.
Static
Min.
Speed Tap
Total Heat
1
kW MBH W1 Only W2 Only W1 & W2
208v 230v 208v 230v 208v 230v 208v 230v 208v 230v 4HK*6500206 0.5 Heat-D 1.9 2.5 6.4 8.5 1.9 2.5 1.9 2.5 1.9 2.5 4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8
24B
4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5 4HK*6501006 0.5 Heat-B 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6 4HK16501306 0.5 Heat A 9.8 13 33.3 44.4 3.3 4.3 6.5 8.7 9.8 13
4HK165N1506 0.5 Heat-A 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4
4HK*6500506 0.5 Heat-C 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8 4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5
36C
4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
4HK16501306 0.5 Heat C 9.8 13 33.3 44.4 3.3 4.3 6.5 8.7 9.8 13 4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4 4HK16501806 0.5 Heat-A 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8 4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5 4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
48D
4HK16501306 0.5 Heat C 9.8 13 33.3 44.4 3.3 4.3 6.5 8.7 9.8 13 4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4 4HK16501806 0.5 Heat-B 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6 4HK16502006 0.5 Heat-B 14.4 19.2 49.2 65.5 3.6 4.8 7.2 9.6 14.4 19.2 4HK16502506 0.5 Heat-B 18.0 24.0 61.5 81.9 3.6 4.8 10.8 14.4 18.0 24
4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8 4HK*6500806 0.5 Heat-D 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5 4HK*6501006 0.5 Heat-C 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6
60D
4HK16501306 0.5 Heat C 9.8 13 33.3 44.4 3.3 4.3 6.5 8.7 9.8 13 4HK16501506 0.5 Heat-C 10.8 14.4 36.9 49.1 3.6 4.8 7.2 9.6 10.8 14.4 4HK16501806 0.5 Heat-C 13.2 17.6 45.1 60.1 3.3 4.4 6.6 8.8 13.2 17.6 4HK16502006 0.5 Heat-C 14.4 19.2 49.2 65.5 3.6 4.8 7.2 9.6 14.4 19.2 4HK16502506 0.5 Heat-C 18.0 24.0 61.5 81.9 3.6 4.8 10.8 14.4 18.0 24.0
1. See conversion Table 9. * May be 0 (no breaker) or 1 (with breaker).
1
Minimum Wire
Size A.W.G.
kW Staging
Johnson Controls Unitary Products 13
536636-UIM-D-1211
TABLE 11:
Electrical Data - (For
Models
Single Source
Heater
Models*
Power Supply) - Copper Wire - 208/230-1-60
Heater
Amps
240V
Min. Circuit Ampacity
208V 230V 208V 230V 208V 230V
4HK*6500206 10.4 15.28 16.53 20 20 12 12 4HK*6500506 20.0 25.67 28.50 30 30 10 10
24B
4HK*6500806 31.3 37.85 42.63 45 45 8 8
4HK*6501006 40.0 47.33 53.50 50 60 8 6 4HK16501306 54.2 62.6 71.3 70 80 4 2 4HK165N1506 60.0 69.00 78.50 70 90 4 3
4HK*6500506 20.0 27.54 30.38 30 35 10 10
4HK*6500806 31.3 39.73 44.50 45 45 8 8
36C
4HK*6501006 40.0 49.21 55.38 50 60 8 6 4HK16501306 54.2 64 72.8 70 80 4 2 4HK16501506 60.0 70.88 80.38 70 90 4 3 4HK16501806 73.3 85.32 97.00 90 100 4 3
4HK*6500506 20.0 29.29 31.88 35 35 8 8
4HK*6500806 31.3 41.48 46.00 45 50 8 8
4HK*6501006 40.0 50.96 56.88 60 60 6 6
48D
4HK16501306 54.2 66.4 75.2 70 80 4 2 4HK16501506 60.0 72.63 81.88 90 90 3 3 4HK16501806 73.3 87.07 98.50 90 100 3 2 4HK16502006 80.0 94.29 106.88 100 125 3 1 4HK16502506 100.0 115.96 131.88 125 150 1 1/0
4HK*6500506 20.0 31.42 33.75 35 35 8 8
4HK*6500806 31.3 43.60 47.88 45 50 8 8
4HK*6501006 40.0 53.08 58.75 60 60 6 6
60D
4HK16501306 54.2 68.4 77.2 70 80 4 2 4HK16501506 60.0 74.75 83.75 90 90 3 3 4HK16501806 73.3 89.19 100.38 90 110 3 2 4HK16502006 80.0 96.42 108.75 100 125 3 1 4HK16502506 100.0 118.08 133.75 125 150 1 1/0
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no breaker) or 1 (with breaker).
Field Wiring
Max. O.C.P.
Amps/Type
1
75°C Wire Size - AWG
TABLE 12:
Electrical Data - (For
Models
Heater
Models
Multi-Source
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
Power Supply) - Copper Wire - 208/230-1-60
Min. Circuit Ampacity
Circuit Circuit Circuit
Max. O.C.P.
Amps/Type
1
75°C Wire Size - AWG
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
24B
4HK16501306 43.1/48.6 19.5/22.5 45/50 20/25 6/6 12/10
4HK165N1506 47.5/53.5 21.7/25.0 50/60 25/25 8/6 10/10
4HK16501306 41.7/47.9 22.4/25.0 50/50 30/30 6/6 12/10
36C
4HK16501506 48.5/55.4 21.7/25.0 50/60 25/25 8/6 10/10 – 4HK16501806 44.9/51.2 39.8/45.8 45/60 40/50 8/8 8/8 – 4HK16501306 42.9/49.1 23.6/26.2 50/50 30/30 6/6 12/10 – 4HK16501506 51.0/56.9 21.7/25.0 60/60 25/25 6/6 10/10
48D
4HK16501806 47.4/52.7 39.8/45.8 50/60 40/60 6/6 8/6 – 4HK16502006 51.0/56.9 43.4/50.0 60//60 45/50 6/6 8/8 – 4HK16502506 51.0/56.9 43.4/50.0 21.7/25.0 60/60 45/50 25/25 6/6 8/8 10/10 4HK16501306 43.9/50.1 24.6/27.2 50/60 30/30 6/6 10/10 – 4HK16501506 53.1/58.8 21.7/25.0 60/60 25/25 6/6 10/10
60D
4HK16501806 49.5/54.6 39.8/45.8 50/60 40/60 6/6 8/6 – 4HK16502006 53.1/58.8 43.4/50.0 60/60 45/50 6/6 8/8 – 4HK16502506 53.1/58.8 43.4/50.0 21.7/25.0 60/60 45/50 25/25 6/6 8/8 10/10
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
14 Johnson Controls Unitary Products
536636-UIM-D-1211
TABLE 13:
Electrical Data - 208/230-3-60
Models
Heat Kit -
Three Phase
Max.
Static
Min.
Speed
Tap
Total Heat
kW MBH W1 Only W2 Only W1 + W2
208V 230V 208V 230V 208V 230V 208V 230V 208V 230V
24B 4HK06501025 0.5 Heat-B 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 36C
4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6
48D
4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK06501825 0.5 Heat-B 12.9 17.2 44.7 58.7 12.9 17.2 12.9 17.2 12.9 17.2 4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6
60D
4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK06501825 0.5 Heat-B 12.9 17.2 44.7 58.7 12.9 17.2 12.9 17.2 12.9 17.2 4HK16502525 0.5 Heat-C 18.0 24.0 61.4 81.4 9.0 12.0 18.0 24.0 18.0 24.0
1. See conversion Table 9.
TABLE 14:
Electrical Data - (For
Models
Single Source
Heat Kit -
Three Phase
Power Supply) - Copper Wire - 208/230-3-60
Heater
Amps
240V
Min. Circuit Ampacity
208V 230V 208V 230V 208V 230V
24B 4HK06501025 23.1 28.5 32.4 30 35 10 8 36C
4HK06501025 23.1 30.4 34.3 30 35 10 8 4HK06501525 34.7 42.9 48.8 45 50 8 8 4HK06501025 23.1 31.3 35.1 35 35 8 8
48D
4HK06501525 34.7 43.8 49.6 45 50 8 8 4HK06501825 41.4 51.0 58.0 60 60 6 6 4HK06501025 23.1 33.8 37.6 35 40 8 8
60D
4HK06501825 41.4 48.8 56.9 50 60 8 6 4HK06501525 34.7 46.3 52.1 50 60 8 6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
1
Max. O.C.P.
Field Wiring
1
Amps/Type
kW Staging
75°C Wire Size - AWG
TABLE 15:
Electrical Data - (For
Models
Heater
Model
Multi-Source
Power Supply) - Copper Wire - 208/230-3-60
Minimum Circuit Ampacity
Max. O.C.P.
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
60D
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
4HK06501825 32.5/36.0 22.4/25.9 35/40 25/30 8/8 10/10 – 4HK16502525 41.0/44.9 31.3/36.1 45/45 35/40 8/8 8/8
Circuit
1
Amps/Type
75°C Wire Size - AWG
Johnson Controls Unitary Products 15
536636-UIM-D-1211
TABLE 16:
Air Handler Air Flow Data
HIGH/LOW SPEED COOLING AND HEAT PUMP AIRFLOW
CFM
24B 36C 24B 36C
High Low High Low High Low High Low COOL Tap ADJ Tap
1088 707 1387 905 30.8 20.0 39.3 25.6 A B
830 542 1151 753 23.5 15.3 32.6 21.3 B B 948 617 1201 783 26.8 17.5 34.0 22.2 A A 716 465 1009 657 20.3 13.2 28.6 18.6 B A 854 556 1086 703 24.2 15.7 30.7 19.9 A C 612 462 953 622 17.3 13.1 27.0 17.6 C B 637 460 901 588 18.0 13.0 25.5 16.6 B C 531 460 754 493 15.0 13.0 21.3 14.0 D B 542 462 831 540 15.3 13.1 23.5 15.3 C A 462 462 657 460 13.1 13.1 18.6 13.0 D A 474 460 751 494 13.4 13.0 21.3 14.0 C C 461 464 588 461 13.1 13.1 16.6 13.1 D C
48D 60D 48D 60D JUMPER SETTINGS
High Low High Low High Low High Low COOL Tap ADJ Tap 2138 1442 2364 1545 60.5 40.8 66.9 43.7 A B 1759 1162 1962 1271 49.8 32.9 55.5 36.0 B B 2009 1311 2123 1374 56.9 37.1 60.1 38.9 A A 1612 1052 1763 1146 45.6 29.8 49.9 32.4 B A 1773 1166 1905 1237 50.2 33.0 53.9 35.0 A C 1530 989 1777 1158 43.3 28.0 50.3 32.8 C B 1459 947 1580 1021 41.3 26.8 44.7 28.9 B C 1359 886 1596 1030 38.5 25.1 45.2 29.2 D B 1388 904 1583 1019 39.3 25.6 44.8 28.8 C A 1221 806 1413 929 34.6 22.8 40.0 26.3 D A 1244 808 1412 926 35.2 22.9 40.0 26.2 C C 1118 715 1277 841 31.6 20.2 36.2 23.8 D C
3
m
/min
JUMPER SETTINGS
HIGH/LOW SPEED ELECTRIC HEAT AIRFLOW
CFM
24B 36C 24B 36C
High Low High Low High Low High Low HEAT Tap ADJ Tap 1088 828 1387 908 30.8 23.4 39.3 25.7 A Any
954 714 1228 804 27.0 20.2 34.8 22.8 B Any 829 614 1151 756 23.5 17.4 32.6 21.4 C Any 678 523 923 609 19.2 14.8 26.1 17.2 D
48D 60D 48D 60D JUMPER SETTINGS
High Low High Low High Low High Low HEAT Tap ADJ Tap 2111 1417 2363 1488 59.8 40.1 66.9 42.1 A Any 1858 1252 2174 1252 52.6 35.4 61.5 35.4 B Any 1480 985 1868 1061 41.9 27.9 52.9 30.0 C Any 1250 840 1387 823 35.4 23.8 39.3 23.3 D Any
1. Airflow at nominal voltage, bottom return at 0.5 external static pressure, tested without filter installed, dry coil conditions.
2. These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure
3. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static.
4. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
5. Both the COOL and the ADJUST tap must be set to obtain the cooling airflow desired (CFM).
6. The ADJ tap does not affect the HEAT tap setting.
7. Low speed cooling used only with two stage outdoor units. (Speed is preset to 65% of high speed).
8. Dehumidification speed is 85% of jumper selected COOL tap and ADJUST tap.
9. When operating in both heat pump and electric heat modes, the airflow (CFM) will be per HEAT Tap CFM values only.
10. At some settings, LOW COOL and/or LOW HEA T airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.
11. Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (i.e.: 12 Flashes is 1200 CFM) – blinks are approximate +/- 10% of actual CFM.
3
m
/min
JUMPER SETTINGS
16 Johnson Controls Unitary Products
536636-UIM-D-1211
SECTION X: MAINTENANCE
Filters must be cleaned or replaced when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high.
COIL CLEANING
If the coil needs to be cleaned or replaced, it should be washed with Calgon CalClean (mix one part CalClean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted sur­faces.
LUBRICATION
The bearings of the blower motor are permanently lubricated.
CONDENSATE DRAINS
During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary drain but not from the sec­ondary drain. If condensate ever flows from the secondary drain the unit should be promptly shut off and the condensate pan and drains cleaned to insure a free flowing primary drain.
Johnson Controls Unitary Products 17
SECTION XI: WIRING DIAGRAM
FIGURE 16: Wiring Diagram
Subject to change without notice. Published in U.S.A. 536636-UIM-D-1211 Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 536636- UIM-C-1010
Johnson Controls Unitar y Prod uc ts
5005 York Drive
Norman, OK 73069
Loading...