Johnson Controls YORK YLHA Series, YORK YLCA 120, YORK YLCA 60, YORK YLCA 80, YORK YLCA 100, YORK YLCA 150, YORK YLHA 40, YORK YLHA 50, YORK YLHA 60, YORK YLHA 80, YORK YLHA 100, YORK YLCA 40, YORK YLCA 50, YORK YLHA 120, YORK YLHA 150 Quick Installation Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Air-condensed water chillers and
heat pumps YLCA / YLHA
This document contains the necessary information for the safe and efficient transportation, assembly
and installation of the air conditioning unit. This guarantees the condition of the unit and its operating
safety.
Only an authorised company may assemble the air conditioning unit.
A T T E N T I O N
Only authorised companies with the appropriate technical resources and suitably trained personnel may
install the air conditioning unit.
C A U T I O N
The specialists responsible for installing the air conditioning unit must make sure they have all of the
information and knowledge required to correctly install, test and deliver the unit. Johnson Controls Inc.
shall not be considered responsible for any damage caused by installation of the unit that is no consistent
with that described in this document or others specifically provided with the unit.
During regular equipment installation, the fitter must pay special attention to certain situations in order
to prevent injuries or damage to the unit.
Situations that could jeopardise the safety of the fitter or that of others nearby or that could put the unit
itself at risk are clearly indicated in this manual.
A series of special symbols are used to clearly identify these situations.
Pay careful attention to these symbols and to the messages following them, as your safety and the safety
of others depends on it.
1.2 Icons used in this document
D A N G E R
•The text following this symbol contains information and instructions relating directly to your safety
and physical well-being.
•Not taking these instructions into account could lead to serious, very serious or even fatal injuries to
you and others in the proximities of the unit.
Information can also be found on safe procedures during unit handling. This will help reduce the risk of
accidents.
C A U T I O N
•The text following this symbol contains information and instructions relating directly to your safety
and physical well-being.
•Not taking these instructions into account could lead to minor injuries to you and others in the
proximities of the unit.
•Not taking these instructions into account could lead to unit damage.
Information can also be found on safe procedures during unit handling. This will help reduce the risk of
accidents.
N O T E
•The text following this symbol contains information or instructions that may be of use or that is worthy
of a more thorough explanation.
•Instructions regarding inspections to be made on unit parts or systems may also be included.
2
Quick installation guide
Instructions for storage, transport, loading and unloading of the unit1.3
1
1.3 Instructions for storage, transport, loading and unloading of
the unit
C A U T I O N
Outdoor units must be moved and stored vertically to prevent oil from leaking from the compressor.
Delivery inspection
The unit should be carefully inspected for visible damage or abnormalities as soon as it is received.
Any abnormalities or damage to the unit should be communicated to both the transportation and
insurance company in writing.
Storage instructions
The unit should be stored in a place suitable to the purpose (warehouse or similar), protected from the
weather, water, humidity and dust.
Cover the unit with a canvas of a suitable size.
The unit should be appropriately protected from knocks and dust, ensuring the protective parts it was
supplied with remain in place. Where these are not in place, establish the necessary protections and/or
barriers to keep vehicles or fork-lift trucks away.
Transport, loading and unloading of the unit
The units should only be handled by personnel from the company responsible for their installation.
Transport of the unit should be in such a manner that no damage is caused by faulty or inadequate
mooring to the bed or body of the vehicle.
Where necessary, protect all of the edges of the unit against knocks and scratches and moor it to the
bed or body of the vehicle using suitable textile belts or slings to keep it perfectly still.
Loading and unloading the unit from a truck or trailer should be on flat, solid ground using an appropriate
crane with sufficient capacity.
1.3.1 Inspection
Upon reception, inspect the goods and notify the carrier and the insurance company, in writing, of any
possible damage during transportation.
1.3.2 Disposal of packaging
The packaging is recyclable. Dispose of it in the appropriate place or take it to an appropriate collection
centre. Respect the regulations in force for this type of waste in the country where the unit is being
installed.
Packaging remains must be correctly disposed of. Improper disposal of packaging generates
environmental problems that affect human life.
3
1
2
(X4)
1
Quick installation guide
1.4Selection guide (YLCA/YLHA)
1.3.3 Hoisting points
The points designed for hoisting the unit are located
on the beams on its base.
Before hoisting the unit, check that the cables or
slings are firmly hooked to these points using
shackles -2- and make sure the crane and the cables
or slings are capable of lifting the weight.
Place spacers -1- at the top of the unit to prevent the
cables or slings from touching it.
Attach guide ropes so that the unit does not rotate
freely.
The cables or slings should be long enough to form
an angle of over 45° to the horizontal plane. Hoist the
unit keeping it in a horizontal position.
D A N G E R
There should not be onlookers within a radius of 10
m of the unit when it is being hoisted.
1.3.4 Disposal of the unit
When removing the unit, the components must be ecologically recovered. The cooling circuit is full of
coolant that must be extracted and delivered to the gas manufacturer for recycling.
A T T E N T I O N
The refrigerant gas contains greenhouse-effect fluorinated gas covered by the Kyoto protocol.
Please see the specifications plate for type of gas and quantity per system.
GWP (Global Warming Potential): 2088
There will be oil left in the hermetic compressor, therefore it must be delivered with the circuit sealed.
The air conditioner shall be deposited in the area established by local authorities, to facilitate its selective
recovery.
1.3.5 Handling
The unit must be moved using the metal rails provided for its installation and transport
1.4
Selection guide (YLCA/YLHA)
Necessary information
The following information is needed to select a YLCA/YLHA water cooling unit:
1. Cooling capacity needed
2. Design cold water inlet and outlet temperatures.
3. Design water flow rate, if one of the temperatures of Point 2 above is unknown.
4
Quick installation guide
Selection guide (YLCA/YLHA)1.4
4. Design inlet temperature of air to the condenser. Normally, this will be the design ambient temperature
of summer air, unless influenced by the situation or other factors.
5. Altitude above sea level.
6. Design fouling factor of the evaporator.
N O T E
Points 1, 2 and 3 should be related by means of the following formulae:
l/h cold water x differential °C
Cooling capacity kW =
860
SELECTION EXAMPLE
A cooler is required to chill water from 13 °C to 7 °C, with a cooling capacity of 119 kW.
There are also other design conditions:
•Inlet ambient air in the condenser 35 °C
•Fouling factor: 0.044 m2 °C/kW
•Altitude: Sea level
1
Taking a quick look at the table, we can see that a YLCA 120 unit gives an approximate required capacity
of 119 kW.
As the factors appearing in Tables and
will be as follows:
•Cooling capacity: 119 kW
•Power consumed: 40 kW
•Water temperature: 13 °C to 7 °C (Temp. difference of 6)
Water flow rate =
Available pressure in hydraulic circuit of a unit with pack:
•From the table we infer that the YLCA 120 TP, with a 17 056 l/h flow rate, has an available pressure
of 279 kPa.
Pressure drop in hydraulic circuit of a unit without pack:
•From the table we infer that the YLCA 120 T, with a 17 056 l/h flow, has an available pressure drop
of 23 kPa.
Pressure drop in filter:
•From Table
said filter has a pressure drop of 2.4 kPa.
YLHA selection method
1. Determine the correct size of the YLHA unit by selecting a model from Tables 3, 4 and 5 that is closest
to the cooling and heating capacities required in the design conditions of the water outlet and air inlet
temperatures.
2. Apply fouling (Table 11) and altitude (Table 12) correcting factors to the capacity and power values
that appear in the corresponding capacity tables in cool and heat. Make sure the corrected capacity
is still sufficient for your needs.
3. Using the corrected capacities of the unit, select the design temperature differential or the flow rate.
4. Check to make sure that these selections are within the YLCA/YLHA operating limits.
Pressure drop in filters, see on page 16
119 x 860
6
Altitude factors, see on page 11
= 17 056 l/h
, 2 ½" filter, we infer that with a 17 056 l/h flow,
are not applicable, the conditions
5
1
Quick installation guide
1.4Selection guide (YLCA/YLHA)
YLHA SELECTION EXAMPLE
A YLHA heat pump operating at a 35°C ambient temperature should chill water from 13°C to 7°C, with
a 112 kW cooling capacity.
A 110 kW heating capacity is required in 5 °C design ambient temperature and a hot water outlet
temperature of 40 °C.
The fouling factor is 0.044 m2 °C/kW, with the unit operating at sea level (no corrections). With a quick
glance of capacity Tables 3 and 5, we see that a YLHA 120 heat pump gives the approximate required
capacities of:
•Cooling capacity = 114 kW
•Total unit absorbed power = 43.2 kW
•Cold water temperature = 13 °C to 7 °C (Temp. diff. of 6 °C)
•Hot and cold water flow = 16 340/h
•Heating capacity = 110.1 kW
•Total unit absorbed power in heat mode = 35.8 kW
•Hot water outlet temperature = 40 °C
Hot water temp. dif‐
ferential
=
110.1 x 860
= 5.8 °C
16 340
Thus, hot water return temperature is = 34.2°C
All values are within operating limits:
•Available pressure in hydraulic circuit of a unit with pack:
•From Table 6 we infer that the YLCA 120, with a 16 340 l/h flow, has an available pressure of 289
kPa.
•Pressure drop in hydraulic circuit of a unit without pack:
–From the table we infer that the YLCA 120, with a 16 340 l/h flow, has an available pressure of 21
kPa.
•Pressure drop in filter.
–From Table
flow rate, said filter has a pressure drop of 2.2 kPa.
Pressure drop in filters, see on page 16
, 2 1/2" filter, we infer that with a 16 340 l/h
1.4.1 Selection guide with glycol (cooling units only)
Necessary information
The following information is needed to select a YLCA cooling unit:
1. Cooling capacity needed
2. Design cold water/glycol inlet and outlet temperatures.
3. Design water/glycol flow rate.
4. Design inlet temperature of air to the condenser. Normally, this will be the design ambient temperature
of summer air, unless influenced by the situation or other factors.
5. Altitude above sea level.
6. Design fouling factor of the evaporator.
N O T E
Points 1, 2 and 3 should be related by means of the following formulae:
(Recommended ethylene glycol concentrations) for ethylene glycol or (Recommended propylene
glycol concentrations) for propylene glycol. For design outlet temperature, please see the recommended
glycol concentration and the glycol factor in this concentration. This is the minimum concentration to be
used for design outlet temperature. If a greater concentration is required, the glycol factor can be
determined by means of
in other concentrations) or (Propylene glycol in other concentrations).
Selection method
1. Determine the correct cooler model by selecting the one that is closest to the capacities required by
the design conditions of the glycol outlet and air inlet temperatures.
2. Apply the fouling correcting factors that correspond to the fouling, altitude and glycol concentration
factor, to the capacity and power values in the capacity tables. Make sure the corrected capacity is
still sufficient for your needs.
3. Using the corrected capacities of the cooler, set the design temperature range, or the flow rate, to
balance the formulae appearing in
4. Always recheck to make sure these selections are within the specified design limits.
Selection example
A cooler is required to chill ethylene glycol from 1 to ‑4 °C, with an output of 75 kW.
The following design conditions are applicable:
•Fouling factor: 0,088m °C/kW
•Altitude: 1 200m
•Ambient air: 25℃
•Glycol concentration: 30% w/w
Glycol concentration and correcting tables, see on page 9
Glycol concentration and correcting tables, see on page
(Ethylene glycol
Selection guide (YLCA/YLHA), see on page 4
.
For a ‑4 °C ethylene glycol outlet, the concentration recommended in Figure 1 is 30%. Therefore, the
specified concentration is appropriate.
From Table
YLCA-120 unit, at the established design conditions, gives a capacity of 76.8 kW and a consumption of
28.8 kW.
With the design fouling factor, use the capacity correcting factors x 0.987 and power x 0.995 (see
factors, see on page 8
On design altitude, apply the capacity correcting factors x 9.973 and power x 1.020 (see
factors, see on page 11
On design glycol concentration, apply the capacity correcting factors x 1.015 and power x 1.005 (see
Correcting factors for other glycol concentrations, see on page 11
Applying these factors to the selection: YLCA ‑120
Capacity = 76.8 x 0.987 x 0.973 x 1.015 = 74.9 kW
Comp. power = 28.8 x 0.995 x 1.020 x 1.005 = 29.4 kW
For the specified glycol concentration and an outlet temperature of ‑4°C, figure 3 shows a glycol factor
of 0.248. Therefore, the flow rate can be determined with the formula indicated in section
(YLCA/YLHA), see on page 4
74.9 [kW] =
Cooling capacities YLCA 40 ÷ 150 (35% ethylene glycol), see on page 32
).
).
).
.
(1 ‑ (-4)) x Flow rate [l / s]
0,248
, we infer that a
Fouling
Altitude
Selection guide
Flow rate =
74.9 x 0.248
5
This covers the Limits of Use.
= 3.71 [l / s] or 13374 [l / h]
7
1Quick installation guide
1.5Technical data
The evaporating unit pressure drop can be determined by taking the water pressure drop value for a
YLCA 120 unit and multiplying it by the correcting factor (see
tables, see on page 9
1 + (-4)
-1.5 °C=
16 kPa x 1.22 = 19.5 kPa.
) for a 30% concentration and an average temperature of ‑1.5 °C, i.e.:
2
Glycol concentration and correcting
1.5 Technical data
1.5.1 Limits of use
Voltage limits
Model
YLCA
YLHA-10 (4)203050(2)
(1)
(2)50 °C if the inlet air is 0 ºC.
(3)From a water temperature of 0 °C or lower, glycol-type antifreeze mixtures must be used.
(4)
Prior to final approval of the installation
Check:
•Voltage remains between 342 ‑ 436 V.
•Power supply cable cross-section is at least as indicated in the corresponding wiring diagrams. The
cable used for the unit power supply must be H05 RN-F or H07 RN ‑ F.
•Operating instructions have been given to the user.
•The warranty card has been filled out.
•Maintenance instructions have been given, or a regular maintenance contract has been signed.
Nominal at
400
Mini‐
mum
At lower water temperatures, it is advisable to use glycol-type antifreeze mixtures. Minimum
temp. with glycol ‑5 °C
If the outdoor air temperature is lower than ‑5 °C or the water temperature is 0 °C or lower, it is
advisable to use the 2.5 ‑ 4 bar low pressure switch.
Maxi‐
mum
342436-18 (4)
Inlet air temperature to the coil
DB
Operating cycleOperating cycle
Minimum °CMaximum °CMinimum °CMaximum °C
ColdHeatColdHeatColdHeatColdHeat
46
-
Water outlet temperature
5(1)
(3)(4)
15
Temperature
difference be‐
tween water
outlet and in‐
Mini‐
mum
°C
-
let
Maxi‐
mum
°C
37
1.5.2 Correcting Factors
Fouling factors
Fouling Factor m2 °C/kWCapacity factor
0,04411
0,0880,9870,995
0,1760,9640,985
0,3520,9260,962
8
Evaporator
compressor absorbed
power factor
Glycol concentration and correcting tables
A
a
b
c
C
B
AC
B
a
b
c
Recommended ethylene glycol concentrations
Quick installation guide1
Technical data1.5
A% in weighta
Outlet liquid tempera‐
B
ture °C
Glycol factor L/S °C/kW
C
in recommended
concentrations
Recommended concen‐
tration % in weight
bFreeze point
Glycol factor in recom‐
c
mended concentrations
Ethylene glycol in other concentrations.
AGlycol factor
BOutlet liquid temperature °C
CGlycol factor
Recommended propylene glycol concentrations
A% in weighta
Outlet liquid tempera‐
B
ture °C
Glycol factor L/S °C/
C
kW in recommended
concentrations
Recommended concen‐
tration % in weight
bFreeze point
Glycol factor in recom‐
c
mended concentrations
9
AC
B
AC
B
AC
B
1Quick installation guide
1.5Technical data
Propylene glycol in other concentrations
AGlycol factor
BOutlet liquid temperature °C
CGlycol factor
Ethylene glycol pressure drop correcting factor
ACorrecting Factor
BAverage liquid temperature °C
CGlycol concentration P/P
Propylene glycol pressure drop correcting factor
A
Correcting Factor
BAverage liquid temperature °C
CGlycol concentration P/P
10
Correcting factors for other glycol concentrations
Quick installation guide1
Technical data1.5
% in weight
CapacityAbsorbed powerCapacityAbsorbed power
101,0611,0251,0971,033
201,0361,0151,0671,023
301,0151,0051,0261,008
351111
400,9850,9950,9740,992
500,9540'9850,9230,977
If it is necessary to select different glycol percentages, correct the capacity and absorbed power
capacities of tables 2 and 4 (35% ethylene glycol), multiplying them by the coefficients indicated in the
table.
Ethylene glycolPropylene glycol
Altitude factors
AltitudeCapacity factorcompressor absorbed power factor
011
6000,9871,01
12000,9731,02
18000,9581,029
24000,9431,038
11
1Quick installation guide
1.5Technical data
Pressure drop in the YLCA/YLHA 40 ÷ 150 hydraulic circuit without pack
(no filter fitted)
YLCA-YLHA modelFlow rate l/hkPa
4750
550019
625026
700033
40
50
60
775042
850050
925061
1000071
1075084
6500
700028
750031
800034
850037
900040
950044
1000048
1050052
1100057
1150062
1200067
1250072
1300077
1350083
1400089
1450095
7500
800038
850040,5
900043
950045,5
1000048
1050051
1100054
1150057
1200060
1250064
1300068
1350072
1400076
1450081
1500086
1550090,5
1600095
16500100
17000105
13
25
36
YLCA-YLHA modelFlow rate l/hkPa
9500
1000043
1100048
1200053
1300059
1400065
80
100
120
1500072
1600079
1700087
1800096
19000107
20000119
21000132
22000145
12000
1300046
1400047,5
1500049,5
1600052
1700055
1800060
1900065
2000070
2100075
2200080
2300085
2400092
--
--
--
--
15000
1600020
1700023
1800025,5
1900028
2000031
2100034
2200037
2300040
2400043
2500046
2600049
2700052,5
2800056,5
2900060
3000063
3100067
3200070,5
3300074,5
3400078
40
45
18
12
YLCA-YLHA modelFlow rate l/hkPa
1800012,5
1900014
2000015,5
2100017,5
2200019,5
2300021,5
2400023,5
2500025,5
2600027,5
2700030
2800032,5
2900035
150
3000037,5
3100040
3200043
3300046
3400049
3500052
3600055
3700058
3800061
3900064
4000067
4100070
4200073
Quick installation guide1
Technical data1.5
13
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.