Raed this manual before installation and operation
Make sure that it is well kept for later reference
0150510281
Page 2
Contents
Cautions
Safety Precautions
Parts and Functions
Operation
Maintenance
Operation Tips
Troubleshooting
Installation Procedure
Test Run
10
10
11
13
19
3
5
6
8
English
Page 3
Cautions
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air
conditioner in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable
materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old
air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of
your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to
environmental awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the
environment.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag
made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.
Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal
services nearest to your house.
Safety Instructions and Warnings
Before starting the air conditioner, read the information given in the User's Guide carefully. The User's Guide contains very
important observations relating to the assembly, operation and maintenance of the air conditioner.
The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following
instruction.
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Installation shall be done by professional people. Don't install unit by yourself.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Always grip plug firmly and pull straight out from the
outlet.
All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for
the user of the air conditoiner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes
with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts
out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and
swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
When the indoor unit is turned on, the PCB will test if swing motor is O.K., and then fan motor will start up.So there is a few
seconds to wait.
In cooling mode,the flaps will swing automatically to a fixed position for anti-condensating.
3
Page 4
Cautions
Specifications
The refrigerating circuit is leak-proof.
For all the models in this manual, the all-pole discon-nexion connection method should be applied in the power supply.
Such means for disconnection must be incorporation in the fixed wiring.
Temperature and Humidity Range
Cooling
Heating
If the air conditioner is used under higher temperature condition than those listed, the built-in protection circuit may operate
to prevent internal circuit damage. Also, during Cooling and Dry modes, if the unit is used under conditions of lower
temperature than those listed above, the heat-exchanger may freeze, leading to water leakage and other damage.
Do not use this unit for purposes other than cooling, heating, dehumidifying and ventilation of rooms in ordinary dwellings.
The wiring method should be in line with the local wiring standand.
The waste battery should be disposed properly.
If the fuse on PC board is broken, please change it with the type T 6.3A/250VAC.
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
43/26 C
18/- C
26.7 C
15/- C
23.9/18.3 C
-7/- C
4
Page 5
Safety Precautions
WARNING
The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less
3 mm. Such means for disconnection must be incorporation in the fixed wiring.
Use copper wire only. All the cables shall have got the local authentication certificate.
The power supply connects from the outdoor side. The connecting cable and the power cable are self-provided.
The parameter of connecting cable: H05RN-F 5G 0.75mm
DANGER
Do not attempt to install this air conditioner by yourself.
This unit contains no user-serviceable parts. Always consult authorized service personnel for repairs.
When moving, consult authorized service personnel for disconnection and installation of the unit.
Do not become excessively chilled by staying for lengthy periods in the direct cooling airflow.
Do not insert fingers or objects into the outlet port or intake grills.
Do not start and stop air conditioner operation by connecting and disconnecting the power supply cord and so on.
Take care not to damage the power supply cord. If the supply cord is damaged, it must be replaced by the manufacturer
or authoried service agent in order to avoid a hazard.
In the event of a malfunction (burning smell, etc.), stop operation immediately, turn off the circuit breaker, and consult
authorized service personnel.
WARNING
Provide occasional ventilation during use.
Do not direct air flow at fire places or heating apparatuses.
Do not place objects on the air conditioner or climb onto it .
Do not hang objects from the indoor unit.
Do not set flower vases or water containers on top of the air conditioner.
Do not expose the air conditioner directly to water.
Do not operate the air conditioner with wet hands.
Do not pull power supply cord.
Turn off power source when not using the unit for extended periods.
Check the condition of the installation stand for damage.
Do not place animals or plants in the direct path of the air flow.
Do not drink the water drained from the air conditioner.
Do not use in applications involving the storage of foods, plants or animals, precision equipment or art works.
Do not apply any heavy pressure to radiator fins.
Operate only with air filters installed.
Do not block or cover the intake grill and outlet port.
Ensure that any electronic equipment is at least one metre away from either the indoor or outdoor unit.
Avoid installing the air conditioner near a fireplace or other heating apparatuses.
When installing the indoor and outdoor unit, take precautions to prevent access to infants.
Do not use inflammable gases near the air conditioner.
For the wired control type unit, the unit state should be checked by the wired controller, instead of the remote receiver.
And if you set the TIMER function, the TIMER LED on the remote receiver will not be on.
6
Page 7
Parts and Functions
Base Operation
Remote controller
SPEED
1. Unit start
Press ON/OFF on the remote controller, unit starts.
2.Select operation mode
Press MODE button. For each press, operation mode
changes as follows:
Remote controller:
AUTO COOLDRYFANHEAT
3.Select temp.setting
/
Pressbutton
TEMP+
TEMP+
Every time the button is pressed, temp.setting
increase 1
TEMP-
o
C,if kept depressed, it will increase
rapidly
TEMP-
Every time the button is pressed, temp.setting
decrease 1
o
C,if kept depressed, it will decrease
rapidly
Select a desired temperature.
4.Fan speed selection
Press FAN SPEED button. For each press, fan speed
changes as
Remote controller:
Air conditioner is running under displayed fan speed.
When FAN is set to AUTO, the air conditioner
automatically adjusts the fan speed according to room
temperature.
Operation
Mode
AUTO
COOL
DRY
FAN
follows:
etomeR
Display
Board
rellortnoC
LOW
MED
Under the mode of auto operation, air conditioner will
automatically select Cool or Heat operation according
to room temperature.
air conditioner
according to room
In DRY mode, when room temperature becomes
lower than temp.setting+2
at LOW speed regardless of FAN setting.
In FAN operation mode, the unit will not operate in
COOL or HEAT mode but only in FAN mode ,AUTO is
not available in FAN mode.And temp.setting is disabled.
In FAN mode,SLEEP operation is not available.
HI
Note
When FAN is set to AUTO, the
automatically adjusts the fan speed
temperature.
AUTO
o
C,unit will run intermittently
HEAT
7
Page 8
Operation
Sleep Operation
Before going to bed,you can simply press the SLEEP
button and unit will operate in SLEEP mode and bring
you a sound sleep.
Use of SLEEP function
After the unit starts,set the operation status,
then press SLEEP button before which the
clock must be adjusted and time being set.
Operation Mode
1. In COOL,DRY mode
1 hours after SLEEP mode starts,temp.will become
O
1 higher than temp.setting.After another 1 hours,
C
temp.rises by 1 futher.The unit will run for further
6 hours then stops Temp. is higher than temp.
setting so that room temperature won
for your sleep.
be too low
SLEEP operation startsSLEEP operation stops
O
C
Approx.6hrs
In AUTO mode
3.
The unit operaters in corresponding sleep mode
adapted to the automatically selected operation
mode.
4. In FAN mode
It has no SLEEP function.
5.Set the wind speed change when sleeping
If the wind speed is high or middle before
setting for the sleep, set for lowing the wind
speed after sleeping.
If it is low wind, no change.
Note
When TIMER function is set, the sleeping function
can't be set up .After the sleeping function is set up
,
if user resets TIMER function, the sleeping function
will be cancelled;the machine will be in the state of
timing-on.
POWER/SOFT Operation
(1)
POWER Operation
When you need rapid heating or cooling, you can use this
function.
high speed of AUTO fan mode. In HEAT mode, fan speed
automatically takes medial speed of AUTO fan mode.
(2)
You can use this function when silence is needed for
rest or reading. In SOFT operation mode, fan speed
automatically takes low speed of AUTO fan mode.
In COOL mode, fan speed automatically takes
SOFT Operation
Rises 1
Rises 1OC
O
C
Unit stop
1 hr
1 hr
Temp.setting
In COOL, DRY mode
In HEAT mode
2.
1 hours after SLEEP mode starts,temp will
become 2 lower than temp.setting.After
another 1 hours,temp decrease by 2
O
C
O
C
futher.After more another 3hours,temp.rises
O
C
by 1 futher.The unit will run for further 3
hours then stops.Temp.is lower than temp.
setting so that room temperature won
too high for your sleep.
be
Temp.setting
1 hr
1 hr
SLEEP
operation starts
Decreases 2OC
Decreases 2
3 hrs
Unit stop
O
C
3 hrs
Rises 1OC
SLEEP
operation stops
In HEAT mode
Note
£”
During POWER operation, in rapid HEAT or COOL
mode ,
distribution. Long period SOFT operation will cause
effect of not too cool or not too warm.
To cancel POWER or SOFT operation
Press POWER/SOFT button again ,POWER or SOFT
disappear
s.
NOTE:
Cooling only unit do not have displays and functions
related with heating.
8
Page 9
Operation
Timer On/Off On-Off Operation
Set clock correctly before starting TIMER operation.
1.After unit starts, select your desired operation mode.
2.Press TIMER button to change TIMER mode. Every
time the button is pressed, display changes as follows:
Remote controller:
BLANK
TIMER ON TIMER OFFTIMER ON-OFF
Then select your desired TIMER mode (TIMER ON or
TIMER OFF or TIMER ON-OFF). " "or " "will flash.
3.Press TIME+ /TIME- button to set time.
It can be adjusted within 24 hours.
4.After setting correct time, press SET button to confirm
" "or" " on the remote controller stops flashing.
5.Cancel TIMER mode
Just press TIMER button several times until TIMER mode
disappears.
Hints:
After replacing batteries or a power failure happens, time
setting should be reset.
Remote controller possesses memory function,when use
TIMER mode next time, just press SET button after mode
selecting if time setting is the same as previous one.
According to the Time setting sequence of TIMER ON or
TIMER OFF, either Start-Stop or Stop-Start can be
achieved.
Healthy airflow Operation
1.Press ON/OFF to starting
Setting the comfort work conditions.
2.The setting of healthy airflow function
1).Press the button of healthy airflow
display
blows direct to the body.
2).Press the button of healthy airflow again, appears on
the displa
blows direct to the body.
3.The cancel of the healthy airflow function
Press the button of healthy airflow again,
working under the condition before the setting of healthy
airflow function.
Notice: Do not direct the flap by hand. Otherwise, the
grille will run incorrectly. If the grille is not run correctly, stop
. Horizontal airflow sending.
. Downward airflow sending.
y
for a minute and then start, adjusting by remote
controller.
Note:
1.After setting the healthy airflow function, the position
grill is fixed.
2.In heating, it is better to select the
3.In cooling, it is better to select the
4.In cooling and dry, using the air conditioner for a long
time under the high air humidity, condensate water may
occur at the grille .
, appears on the
Avoid the airflow
Avoid the airflow
the unit
mode.
mode.
goes on
9
Page 10
Maintenance
Clean the air filter
1.
Pull the filters upward to remove them from the Intake Grill.
2.
Clean the air filter: Remove the dust from the filters by vacuum cleaner or washing
them. After washing, allow the air filters to dry thoroughly in an area protected from
sunlight.
3.
Re-attach the air filters to the Intake Grill. Press the two buttons on the filters until
you hear a sound of click.
Maintenace of indoor units
When used for extended periods, the unit may accumulate dirt inside, which reduces its performance. We recommend
that the unit is inspected regularly, in addition to your own cleaning and care. For more information, consult authorized
service personnel.
When cleaning the unit's body, do not use water hotter than 40 C, harsh abrasive cleansers, or volatile agents like
benzene or thinner.
Do not expose the unit body to liquid insecticides or hairsprays.
When shutting down the unit for one month or more, first allow the Fan mode to operate continuously for about half a
day to allow internal parts to dry thoroughly.
Operation tips
Instructions relating to heating are applicable only to "HEAT & COOL TYPE"
Heating Performance
This air conditioner operates on the heat-pump principle, absorbing heat from outdoor air and transferring that heat indoors.
As a result, the operating performance is reduced as outdoor air temperature drops. If you feel that insufficient heating
perfomance is being produced, we recommend you use this air conditioner in conjunction with another kind of heating
appliance.
Heat-pump air conditioners heat your entire room by recirculating air throughout the room, with the result that some time
may be required after first starting the air conditioner until the room is heated.
Microcomputer-controlled Automatic Defrosting
When using the Heating mode under conditions of low outdoor air temperature high humidity, frost may form on the
outdoor unit, resulting in reduced operating performance.
In order to prevent this kind of reduced performance, this unit is equipped with a Microcomputer-controlled Automatic
Defrosting function. If frost forms, the air conditioner will temporarily stop, and the defrosting circuit will operate briefly
(for about 7 to 15 minutes).
10
Page 11
Troubleshooting
Followings are not problems
Sound of water flowing is not a problem.
Sound of cracking is heard.
Smell are generated.
During operation, white fog or steam
comes out from the indoor unit.
In cooling operation, unit switches to
blowing operation.
Unit will not restart after stop.
Won't start?
No outlet air or fan speed can't be changed
in dry mode.
During unit operation or at stop, a swishing or gurgling noise may be heard.
This noise is generated by refrigerant flowing in the system.
During unit operation, a cracking noise may be heard.
This noise is generated by the casing expanding or shrinking because of
temperature changes.
This is because the system circulates smells from the interior air such as
the smell of cigarettes or the painting on the furniture.
When unit is running at places like restaurant, etc. where dense edible oil
fumes always exist, this will happen.
To prevent frost from accumulating on indoor heat exchanger, unit will switch
to blowing operation for a while then resume cooling operation.
Though ON/OFF button is set to ON, the unit won't
resume cooling, dry or heating operation in 3 min
after it is stopped, this is because of
3-min-delay protection circuit.
Please wait 3 minutes
Unit will reduce fan speed repeatedly and automatically if room temp. is
too low in dry operation.
In heating operation, water or steam
are blown out of outdoor unit.
In heating operation, indoor fan won't stop
even if unit is stopped.
This occurs when frost accumulated on the outdoor unit is removed.
(during defrosting operation)
After unit stop, indoor fan will go on running until indoor unit cools down.
11
Page 12
Troubleshooting
Before ask for services, please first check your unit against the following.
Air conditioner won't start.
Is power supply switch turned on?
Power supply switch is not set at ON.
Are operation control adjusted
correctly as specified?
Proper
temp
Are horizontal louvers at up position
(in heating mode)?
Is city power supply normal?Is leakage current breaker activated?
Power
failure?
This is very dangerous, please
disconnect power supply immediately
and contact your dealer.
Poor cooling or heating
Is air filter too dirty?Are there any obstacles in inlet or
outlet grill?
Any doors or windows left open?
Poor cooling
Is there any direct sunlight in the room?If there are unexpected heat sources
Too many people in the room?
in the room?
Cold air blows out (in heating mode). Is air conditioner in standby condition in heating mode?
If your unit still can't work properly after above mentioned checks, or following problems occur, please stop it immediately
and contact your dealer.
Fuses or circuit breakers often blow out.
Water comes out in cooling/dry operation.
Operation is abnormal or sound is heard.
Diagnosis for models
Failure DescriptionPossible CauseLED on PCB flash times
1
2
3
4
5
10
indoor ambient temp sensor failure.
indoor coil temp.sensor failure
over voltage/under voltage
outdoor until abnormal
EEPROM abnormalEEPROM data missing.
indoor drainage failure
Sensor broken down or short circuit
for more than 2min continuously.
Sensor broken down or short circuit
for more than 2min continuously.
power supply over voltage or under
voltage.
outdoor until abnormal can not
resume.
Float switch broken down for more
than 10min continuously
.
12
Page 13
Installation Procedure
Please ask the dealer or specialist to install, never try by the users themselves. After the installation please be sure of the
following conditions.
WARNING
Please call dealer to install the air-conditioner. Incorrect installation may cause water leaking, shock and fire
hazard.
CAUTION
Air-conditioner can't be installed in the environment with inflammable gases because the inflammable gases
near air-conditioner may cause fire hazard.
Installed electrical-leaking circuit breaker.
It easily cause electrical shock without circuit breaker.
Connect earthing wire.
Earthing wire should not be connected to the gas pipe, water pipe, lightning rod or phone line, incorrect earthing
may cause shock.
Use discharge pipe correctly to ensure efficient discharge.
Incorrect pipe use may cause water leaking.
Wiring
Air-conditioner should be equipped with special power supply wire.
Location
Air-conditioner should be located in well-vented and easily accessible place.
Air-conditioner should not be located in the following places:
(1) Places with machine oils or other oil vapours.
(2) Seaside with high salt content in the air.
(3) Near hot spring with high content of sulfide gases.
(4) Area with frequent fluctuation of voltage e.g. factory, etc.
(5) In vehicles or ships.
(6) Kitchen with heavy oil vapour or humidity.
(7) Near the machine emitting electric-magnetic waves.
(8) Places with acid, alkali vapour.
Choose the following locations:
(1) Capable of supporting air conditioner weight. Don't increase operating noise and vibration.
(2) Hot vapour from outdoor unit outlet and operating noise don't disturb neighbour.
(3) No obstacles around the outdoor unit outlet.
TV, radio, acoustic appliances etc. are at least 1 m far away from the indoor unit, outdoor unit, power supply wire,
connecting wire, pipes, otherwise images may be disturbed or noises be created.
As required, take measures against heavy snow.
Installation Precaution
Earthing
For authorized sevice personnel only
WARNING
(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation manual.
(2) Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our standard
parts. This installation manual describes for the correct connections so that the installation set available from our
standard parts should be used.
(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(4) Never cut the power cord, lengthen or shorten the cord, or change the plug. Do not use an extension cord.
(5) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(6) Do not turn on the power until all installation work is done.
CAUTION
(1) Be careful not to scratch the room air conditioner when handing it.
(2) After installation, explain correct operation to the customer, according to the operating manual.
(3) Let the customer keep this installation manual because it will be used when the room air conditioner is serviced or moved.
13
Page 14
Installation Procedure
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor unit and install it positively so that the unit will not topple or
fall.
CAUTION
Do not install the unit where there is the danger of combustible gas leakage.
Do not install near heat sources.
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Decide the mounting position with the customer as follows.
(1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed, and the air should be able to blow all over the room.
(3) Do not install the unit where it will be exposed to direct sunlight
(4) Install the unit where connection to the outdoor unit is easy.
(5) Install the unit where the drain pipe can be easily installed.
(6) Take servicing, etc. into consideration and leave the spaces shown in "Maintenace space dimension" .
(7) Install the unit where the filter can be removed
ACCESSORIES FOR INSTALLATION
The following installation parts are optional parts. Use them as required.
Optional parts
Adhesive tape
Saddle (L.S) with screws
Drain hose
Heat insulation material
Piping hole cover
Putty
Plastic clamp
MAINTENANCE SPACE DIMENSION
For ceiling installation
Ceiling
INDOOR UNIT
>3"(80mm)>6"(150mm)
>0.4"(10mm)
For half concealed installation
INDOOR UNIT
>3"(80mm)
Ceiling panel
>6"(150mm)
Ceiling panel
>0.4"(10mm)
14
Page 15
Installation Procedure
INSTALLING THE INDOOR UNIT
Connection pipe requirement
Model
Liquid sideGas side
Diameter
Maximum
length
Maximum height
(between indoor
and outdoor)
YHFFXC(H)036BBA-FX
YHFFXC(H)048BBA-FX
YHFFXC(H)060BBA-FX
9.52 mm19.05mm20 m
9.52 mm19.05mm30 m15m
12.7 mm22.22mm30 m
10m
15m
Install the room air conditioner as follows
1. Remove the intake grill and side cover
(1) Remove the Air filters
(2) Remove the intake grilles
(3) Remove the Side cover (Right and left side)
(4) This air conditioner can be set up to intake fresh air. The information about how to install for fresh-air intake, refer to
"Fresh air intake".
Air filter
Intake grille
Side cover A (Right side) Side cover A (Left side)
2. Location of ceiling supension bolts
30mm
Suspension bolt pitch Amm
30mm
Dimensions (Space Required for
installation)
10mm
155mm
INDOOR UNIT (TOP VIEW)
Suspension bolt should
extend outward 30 to 50mm.
For half-concealed installation
Supension-bolt pitch should be as shown below
Ceiling Opening:Amm40mm40mm
Ceiling Opening
640mm
Model
YHFFXC(H)036BBA-FX
YHFFXC(H)048BBA-FX
YHFFXC(H)060BBA-FX
15mm
Ceiling panel
Dimensions
A(mm)
1248
1530
300mm
Ceiling panel
Suspension bolt should
extend outward 30 to 50mm.
15
Page 16
Installation Procedure
3. Drilling the holes and attaching the suspension bolts
Ceiling panel
Special nut A (included)
(1) Drill 25mm holes at the suspension-bolt locations. The two special nuts are
provided with the unit. The M10 nut must be obtained locally.
(2) Install the bolts, then temporarily attach Special nuts A and B and a normal
M10 nut to each bolt.
Bolt strength: 980 to 1470 N (100 TO 150 kgf)
10 to 15 mm
Special nut B (included)
M10 nut (Obtained locally)
If using anchor bolts
(1) Drill holes for anchor bolts at the locations at which you will set the suspension bolts. Note that anchor bolts must be
obtained locally.
(2) Install the anchor bolts, then temporarily attach special nut "B" (included) and a locally-procured M10 nut to each of
the bolts.
Anchor-bolt strength: 980 to 1470 N (100 TO 150 kgf)
Special nut B(included)
M10 Nut
(Obtaied locally)
4.Installing the indoor unit
10 to 15 mm
M10 Nut (Obtaied locally)
Ceiling
Ceiling panel
(1) Lift unit so that suspension bolts pass through suspension fittings at
the sides (four places),and slide the unit back.
Wall
(2) Fasten the indoor unit into place by tightening-up the special "B" bolts
and the M10 nuts. Make sure that unit is secure and will not shift
Wall
back and forth.
For half-concealed installation
When installing the indoor unit in a semi-concealed orientation, make
Glass wool insulate
(10 to 20mm thick )
sure to reinforce the insulation of the unit on all sides. Drops of water
may fall from the unit if it is not thoroughly insulated.
Indoor unit
CAUTION
(Top view)
In order to check the drainage, be sure to use a level during installation
of the indoor unit. If the installation site of the indoor unit is not level,
water leakage may occur.
Ceiling panel
Wall
5.Installing the coupler heat insulation
After checking for gas leaks, insulate by wrapping insulation around the two parts (large and small) of the indoor unit
coupling, using the coupler heat insulation. After installling the coupler heat insulation, wrap both ends with vinyl tape so
that there is no gap. Secure both ends of the heat insulation material using nylon fasteners.
Indoor unit
Coupler heat insulation(large)
Coupler pipe (large)
Coupler pipe (small)
Coupler heat insulation(small)
Indoor unit
Nylon fastener (large)
No gap
Coupler heat
insulation
Nylon fastener (small)
When using an auxiliary pipe, make sure that the fastener used is insulated in the same way.
Note:
When installing the unit on the floor, fix the four rubber base feet in the accessories on the bottom plate of the unit with
four 4x16 screws and 4 flat washers, as the position in the figure.
A
The bottom plate of the unit.
A
4:1
rubber base foot
4x16 screw
flat washer
16
Page 17
Installation Procedure
INSTALLING THE DRAIN HOSE
Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) (outside diameter 38 mm)
During installation of the drain pipe, be careful to avoid applying pressure to the drain point of the unit.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate (8mm or over thick) the indoor side of the drain pipe.
GOOD
Supporter
BAD
5 to 6.5 ft
(1.5 to 2m)
BAD
(1) Install insulation for the drain pipe
Cut the included insulation material to an appropriate size and adhere it to the pipe.
Drain pipe
Insulation for Drain pipe
(To be obtained locally.
Length should be at least 8mm.)
Drain pipe insulation (accessories)
Indoor unit (drain port)
Indoor unit
(2) When drain pipe is put in the right rear position
Fasten the drain pipe with cable VT so that there is a proper slope for drain pipe to
exit from the indoor unit.
No gap
Drain pipe insulation
Drain pipe
10mm or over
Cable VT
drain pipe
(3) Throttle pipe should be installed between indoor unit and connecting pipe. When
connect with 12.7mm liquid pipe and 22.22 gas pipe, should do installation in
following way. The throttle pipe was put in accessory bag in indoor unit
Note:
When welding the pipe ,please blow nitrogen to prevent oxidation,with about 0.02MPa pressure of nitrogen
flow .otherwise , the oxide can damage the outdoor unit.
17
Page 18
Installation Procedure
ELECTRICAL WIRING
Connect wiring to the terminals
A.For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 15/16"(25mm) to expose the
solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighthen securely with the terminal screw using a
screwdriver.
B.For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 3/8"(10mm) to expose the
solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.
A. Solid wire
Insulation
Strip 15/16"(25mm)
Loop
B. Strand wire
Strip 3/8"(10mm)
Round
terminal
Round
terminal
Wire
Fix connection cord and power cable at the cord clamp
After passing the connection cord and power cable through the insulation tube,
fasten it with the cord clamp.
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Screw with
special washer
Terminal
board
Wire
Insulation tube
Screw with
special washer
Round
terminal
Cord clamp
Connect indoor unit and outdoor unit
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the dimensions shown in wiring diagram.
(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the connection cord with a cord clamp.
(5) Fasten the end of the connection cord with the screw.
WARNING
The power cable and connecting cable are self-provided.
Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.
Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and
has an isolation distance of at least 3mm between the contacts of each pole.
Perform wiring work in accordance with standards so that the room air conditioner can be operated safely and positively.
Install a leakage circuit breaker in accordance with the related laws and regulations and electric company standards.
CAUTION
The power source capacity must be the sum of the room air conditioner current and the current of other electrical
appliances. When the current contracted capacity is insufficient, change the contracted capacity.
When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage raised.
18
Page 19
Installation Procedure
FRESH AIR INTAKE
1. Open up the knockout hole for the fresh air intake. If using half-concealed
installation, open up the top knockout hole instead.
CAUTION
When removing the cabinet (iron plate), be careful not to damage the indoor
unit internal parts and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injury yourself
with burrs,etc.
2. Fasten the round flange (optional) to the fresh air intake. If using half concealed installation, attach to the top.
3. Connect the duct to the round flange.
4. Seal with a band and vinyl tape,etc. so that air does not leak from the
connection.
For half-concealed
Round duct (option part)
Duct
Test Run
Check items
1. Indoor unit
Is operation of each button on the remote control unit normal?
Does each lamp light normally?
Do not air flow direction louvers operate normally?
Is the drain normal?
2. Outdoor unit
Is there any abnormal noise and vibration during operation?
Will noise, wind, or drain water from the unit disturb the neighbors?
Is there any gas leakage?
Customer guidance
Explain the following to the customer in accordance with the operation manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air flow switching, and other remote
control unit operations.
(2) Air filter removal and cleaning, and how to use air louvers.
(3) Give the operation and installation manuals to the customer.
19
Page 20
2010 Johnson Controls, Inc.
Johnson Controls reserve the right to change product features without prior notice.
www.johnsoncontrols.co m AHFFXCBA--120831
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.