Johnson Controls York Smart Equipment SC-EQUIP, York Smart Equipment SC-EQ Installation Instructions Manual

Page 1
SC-EQ
(Also Contains Relevant SC-AP Information)
INSTALLATION INSTRUCTIONS Supersedes: 450.50-N1 (1117) Form 450.50-N1 (819)
035-25087-000
YK
YVWA
YMC
YZ
2
Issue Date:
August 19, 2019
REV.8
Page 2
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
FORM 450.50-N1
ISSUE DATE: 08/19/2019
This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain com­ponents or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, instal­lation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in
which it is situated, as well as severe personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This in­dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken.
Identies a hazard which could lead to
damage to the machine, damage to other equipment and/or environmental pollu­tion if proper care is not taken or instruc­tions and are not followed.
Indicates a potentially hazardous situa­tion which will result in possible injuries or damage to equipment if proper care is not taken.
External wiring, unless specied as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specications and must be performed only by a qualied
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2
Highlights additional information useful to the technician in completing the work being performed properly.
JOHNSON CONTROLS
Page 3
FORM 450.50-N1 ISSUE DATE: 08/19/2019
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls’ policy for con­tinuous product improvement, the information con­tained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically
regarding the applicability of these documents, rig­ging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the
equipment prior to performing any work on the chiller. to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest
CHANGE BARS
Johnson Controls Service office or accessing the John­son Controls QuickLIT website at http://cgproducts.
johnsoncontrols.com.
Revisions made to this document are indicated with a
line along the left or right hand column in the area the
revision was made. These revisions are to technical in­It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these
formation and any other changes in spelling, grammar
or formatting are not included. documents to the equipment. If there is any question
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
SC-AP Installation Instructions LIT 24-10737-75
SC-AP Quick Start LIT 24-10737-87
JOHNSON CONTROLS
3
Page 4
FORM 450.50-N1
ISSUE DATE: 08/19/2019
THIS PAGE INTENTIONALLY LEFT BLANK.
4
JOHNSON CONTROLS
Page 5
FORM 450.50-N1 ISSUE DATE: 08/19/2019
TABLE OF CONTENTS
SECTION 1 - INTRODUCTION ................................................................................................................................. 9
Overview ..........................................................................................................................................................9
Emissions Compliance .................................................................................................................................. 10
SECTION 2 - INSTALLATION ................................................................................................................................ 11
Wiring ............................................................................................................................................................. 11
Protection of Communication Ports ............................................................................................................... 11
High Noise Environments ............................................................................................................................... 12
Electrical Noise Mitigation to Equipment ....................................................................................................... 12
Electrical Noise Mitigation SC-EQ to BAS ...................................................................................................... 12
Types of Communication Ports ......................................................................................................................12
Network Termination .......................................................................................................................................12
Media Access Control (MAC) Address ...........................................................................................................13
BAS Network Wiring ....................................................................................................................................... 14
Mounting ........................................................................................................................................................ 15
OptiView Panel Installation ............................................................................................................................. 15
Small Tonnage Panel Installation ...................................................................................................................16
YMAA, YCAE, and YCWE-E Panel Installation ..............................................................................................17
YVWE and YVWH Panel Installation .............................................................................................................. 20
YEWS and YGWE Single Panel Installation...................................................................................................20
Other Chiller Panel Installation ....................................................................................................................... 21
Mounting on a Micro Panel ............................................................................................................................. 22
Wall Mounting .................................................................................................................................................23
Applying Power ..............................................................................................................................................23
Equipment Configuration ................................................................................................................................ 25
Setting the Rotary Switch on Chiller Panels .................................................................................................. 25
SECTION 3 - TROUBLESHOOTING ...................................................................................................................... 33
LED Indicators ................................................................................................................................................ 33
Multimeter Checks of the BAS Port ................................................................................................................ 34
Updating the Firmware and the Software ....................................................................................................... 35
Repair Information .......................................................................................................................................... 36
SECTION 4 - SC-AP GATEWAY .............................................................................................................................37
SC-AP OptiView Mounting ............................................................................................................................37
Using the SC-AP for Troubleshooting.............................................................................................................39
E-Link Replacement ....................................................................................................................................... 40
Manually Setting the Chiller Model ................................................................................................................. 41
SECTION 5 - TECHNICAL SPECIFICATIONS ....................................................................................................... 43
SECTION 6 - LON PROTONODE ........................................................................................................................... 45
Overview ........................................................................................................................................................45
Installation ......................................................................................................................................................46
ProtoNode LED Functionality ......................................................................................................................... 49
Binding the Points Using the .XIF File ............................................................................................................ 49
Technical Specifications .................................................................................................................................50
JOHNSON CONTROLS
5
Page 6
FORM 450.50-N1
ISSUE DATE: 08/19/2019
LIST OF FIGURES
FIGURE 1 - Grounding Label .................................................................................................................................. 11
FIGURE 2 - RS-485 EOL Switches .........................................................................................................................13
FIGURE 3 - 3-Wire BAS .......................................................................................................................................... 14
FIGURE 4 - 2-Wire BAS .......................................................................................................................................... 14
FIGURE 5 - 100 Ohm Resistor Installation..............................................................................................................14
FIGURE 6 - SC-EQ Installed in OptiView (All Chillers Except YMC2) ....................................................................15
FIGURE 7 - SC-EQ Installed in YMC2 OptiView .....................................................................................................15
FIGURE 8 - SC-EQ OptiView Installation Kit (All Chillers) (YORK p/n 331-03607-000) .........................................16
FIGURE 9 - SC-EQ Screw Chiller Installation Kit Part Number 392-41228-000 ..................................................... 16
FIGURE 10 - SC-EQ Scroll Chiller Installation Kit Part Number 392-41230-001 .................................................... 16
FIGURE 11 - Scroll Chiller Panel Installation ..........................................................................................................17
FIGURE 12 - SC-EQ Installed in YMAA and YVAE ................................................................................................. 18
FIGURE 13 - SC-EQ Installed in YCAE ..................................................................................................................18
FIGURE 14 - SC-EQ Installed in YCWE-E .............................................................................................................. 18
FIGURE 15 - SC-EQ Connected in YMAA, YVAE, AND YCWE ..............................................................................18
FIGURE 16 - SC-EQ Connected in YCAE AND YCWE-E ....................................................................................... 18
FIGURE 17 - SC-EQ to YMAA, YCAE, and YCWE Connections ............................................................................19
FIGURE 18 - SC-EQ Installed in YVWE and YVWH ...............................................................................................20
FIGURE 19 - SC-EQ to YVWE and YVWH Connections ........................................................................................20
FIGURE 20 - SC-EQ Installed in YEWS and YGWE Single ....................................................................................21
FIGURE 21 - SC-EQ Installed in YEWS Tandem .................................................................................................... 21
FIGURE 22 - SC-EQ Installed in YGWE Tandem ...................................................................................................21
FIGURE 23 - SC-EQ to YEWS Connections ........................................................................................................... 21
FIGURE 24 - Mounting on the Equipment ............................................................................................................... 22
FIGURE 25 - Wall Mounting ....................................................................................................................................23
FIGURE 26 - SC-EQ in Enclosure...........................................................................................................................23
FIGURE 27 - SC-EQ Component Locations ...........................................................................................................24
FIGURE 28 - Micropanel Rotary Switch .................................................................................................................. 25
FIGURE 29 - SC-EQ Comm Card to YORKTalk II Equipment Connections ........................................................... 26
FIGURE 30 - SC-EQ COMM Card to YORKTalk II Equipment Connections .......................................................... 27
FIGURE 31 - SC-EQ Comm Card to YORKTalk II Equipment Connections ........................................................... 28
FIGURE 32 - SC-EQ COMM Card to OptiView Equipment Connections ................................................................29
FIGURE 33 - SC-EQ COMM Card Connections for Chillers with the 02478 Microboard
YCAV/YCIV/YVAA/YVWA .................................................................................................................. 30
FIGURE 34 - SC-EQ COMM Card Connections for Chillers with the 03478 Microboard
YCAV/YCIV/YVAA/YVWA/YVFA ........................................................................................................ 30
FIGURE 35 - SC-EQ COMM Card Connections for Chillers with the 02550 Microboard
YCAL/YCUL/YLAA/YLPA/YCWL/YCRL/YSAA .................................................................................. 31
FIGURE 36 - SC-EQ COMM Card Connections to YPAL (EC02) ........................................................................... 31
FIGURE 37 - SC-EQ COMM Card Connections to YEWS-D1/YEAS/YGAS ..........................................................32
FIGURE 38 - SC-EQ LEDs and USB ......................................................................................................................33
FIGURE 39 - BAS Bus Meter Checks .....................................................................................................................35
FIGURE 40 - Din Rail End Block ............................................................................................................................. 37
FIGURE 41 - SC-AP Mounted ................................................................................................................................. 37
FIGURE 42 - SC-AP Velcro Pads ............................................................................................................................37
FIGURE 43 - SC-EQ to SC-AP CABLE ................................................................................................................... 38
FIGURE 44 - SC-AP Cable Ty-Wraps ..................................................................................................................... 38
FIGURE 45 - SC-AP & SC-EQ Installed .................................................................................................................. 38
FIGURE 46 - SC-AP Device List .............................................................................................................................39
FIGURE 47 - SC-EQ Port Status and Lock In ......................................................................................................... 39
FIGURE 48 - SC-AP Device List ............................................................................................................................40
FIGURE 49 - Device Instance Mode ......................................................................................................................40
FIGURE 50 - Invalid Points ofine .......................................................................................................................... 40
FIGURE 51 - Unreliable Remote Setpoints ............................................................................................................. 40
FIGURE 52 - No Chiller Model Type Detected ........................................................................................................ 41
6
JOHNSON CONTROLS
Page 7
FORM 450.50-N1 ISSUE DATE: 08/19/2019
LIST OF FIGURES (CONT'D)
FIGURE 53 - Manually Selecting Chiller Model.......................................................................................................41
FIGURE 54 - LON ProtoNode Front View .............................................................................................................. 45
FIGURE 55 - OptiView LON ProtoNode Mounting Location ...................................................................................46
FIGURE 56 - ProtoNode to SC-EQ RS485 Wiring .................................................................................................. 47
FIGURE 57 - ProtoNode Power Wiring ...................................................................................................................47
FIGURE 58 - ProtoNode LON Network Connection ................................................................................................48
FIGURE 59 - ProtoNode Service Pin (Cover Removed) .........................................................................................48
FIGURE 60 - ProtoNode Neuron ID ........................................................................................................................48
FIGURE 61 - ProtoNode Power Wiring ...................................................................................................................49
LIST OF TABLES
TABLE 1 - SC-EQ Product Code Numbers ...............................................................................................................9
TABLE 2 - YORK Equipment Models ...................................................................................................................... 13
TABLE 3 - OptiView Wiring - SC-EQ Port J7 ..........................................................................................................15
TABLE 4 - BAS Wiring - SC-EQ Port J12 ...............................................................................................................15
TABLE 5 - BOM of YMAA SC-EQ Kit (371W06163-001) ........................................................................................ 18
TABLE 6 - BOM of YCAE SC-EQ Kit (371W06163-002) ........................................................................................ 18
TABLE 7 - BOM of YCWE-E SC-EQ Kit (371W08244-301) ...................................................................................18
TABLE 8 - Technical Specifications ........................................................................................................................ 43
TABLE 9 - LON ProtoNode Product Code Numbers ..............................................................................................46
TABLE 10 - Jumper Settings ...................................................................................................................................46
TABLE 11 - Switch Settings ....................................................................................................................................46
TABLE 12 - Power Connections .............................................................................................................................47
TABLE 13 - Diagnostic LEDs .................................................................................................................................. 49
TABLE 14 - Technical Specifications ...................................................................................................................... 50
JOHNSON CONTROLS
7
Page 8
FORM 450.50-N1
ISSUE DATE: 08/19/2019
THIS PAGE INTENTIONALLY LEFT BLANK.
8
JOHNSON CONTROLS
Page 9
FORM 450.50-N1 ISSUE DATE: 08/19/2019

SECTION 1 - INTRODUCTION

OVERVIEW

The SC-EQUIP (SC-EQ) Communication Card super­sedes the E-Link Gateway and provides BAS network connectivity for Johnson Controls® and YORK® me­chanical equipment, such as chillers and rooftop units. It is designed with four active serial ports: The J12 BAS (RS-485) port, the J7 Equipment (RS-232) port, the J8 Equipment (RS-485) port and the J11 CS port which allows equipment data to be sent to the Johnson Controls Remote Operation Center for remote chiller monitoring and diagnostics.
To simplify the installation and setup, the SC-EQ Comm Card automatically determines the BAS proto­col and Baud rate and the model of the connected chill­er or rooftop unit. The only user setting is the MAC address for the SC-EQ on the BAS network.
Several SC-EQ Comm Card models are available for connection to various types of input voltage and equipment. For chillers using the OptiView™ 02430 or 03630 microboards, the SC-EQ Comm Card consists of a single circuit board attached to four studs inside the Micro Panel, using the accessory mounting kit. The microboard supplies 12 VDC input power, eliminating the need for an external power supply. The SC-EQ plug J10-COM needs a ground wire to ground the lug on the panel.

TABLE 1 - SC-EQ PRODUCT CODE NUMBERS

PRODUCT
DESCRIPTION
SC-EQ with Serial Outputs (BACnet MS/TP, Modbus Remote Terminal Unit [RTU], and N2)
SC-EQ with Serial Outputs in Enclosure
SC-EQ OptiView Panel Installation Kit 331-03607-000
SC-EQ Screw Chiller Panel Installation Kit
SC-EQ Scroll Chiller Panel Installation Kit
SC-EQ YEWS Panel Installation Kit 371W06953-132
SC-EQ YGWE Tandem Panel Installation Kit
SC-EQ YGWE Single Panel Installation Kit
SC-EQ YVWE, YVWH, and YGWH Panel Installation Kit
SC-EQ YMAA Panel Installation Kit 371W06163-001
SC-EQ YCAE Panel Installation Kit 371W06163-002
CODE
NUMBERS
SE-SCC1001-1
(031-03610-000)
YK-SCCPNL-0
392-41228-000
392-41230-001
392W41228-020
392W41228-030
39241228-010
(IPU3 BD)
The SC-EQ kit includes the SC-EQ board and the re-
lated installation accessories. The OptiVew kit does not
include the SC-EQ board.
1
For screw compressor chillers using the 02478 or 03478 microboards, the SC-EQ Comm Card is installed inside the Micro Panel, using the accessory mounting kit. The microboard supplies 12 VDC input power, eliminating the need for an external power supply.
For scroll compressor chillers using the 02050 or 02550 microboards, the SC-EQ Comm Card is installed in­side the Micro Panel and requires an additional trans­former to supply power to the SC-EQ Comm Card. The transformer is included in the SC-EQ Scroll Chiller In­stallation Kit.
For other types of chillers, the SC-EQ Comm Card is packaged in its own enclosure. In addition to the SC­EQ circuit board, a transformer is included inside the enclosure that converts a 120 VAC or 240 VAC input to 24 VAC power.
JOHNSON CONTROLS
9
Page 10
SECTION 1 - INTRODUCTION

EMISSIONS COMPLIANCE

FORM 450.50-N1
ISSUE DATE: 08/19/2019
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interfer­ence when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user is required to correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the require­ments of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
10
JOHNSON CONTROLS
Page 11
FORM 450.50-N1 ISSUE DATE: 08/19/2019

SECTION 2 - INSTALLATION

The SC-EQ is supplied as a circuit board that can be installed directly into the equipment’s enclosure, or can be supplied pre-mounted in an enclosure ready for line voltage. Accessory mounting kits are used to mount the SC-EQ Comm Card directly into OptiView, Latitude, and IPU-II based Micro Panels.
IMPORTANT: Do not install the SC-EQ Comm Card directly into an equipment’s enclosure without the use of an approved installation kit.

WIRING

Risk of Electric Shock. Disconnect or isolate all power supplies be­fore making electrical connections. More than one disconnect or isola­tion may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accor­dance with local, national, and regional regulations.
Install the wiring so it does not cause a hazard, and is protected against electrical and mechanical damage.
to the SC-EQ Comm Card. For the line voltage power
source, use a dedicated line (with a separate fuse) that
is isolated (using a control transformer) from other
equipment in the plant room that may generate Elec-
tromagnetic Interference (EMI).
Grounding
For the enclosure style, a ground wire must be connect-
ed directly to the enclosure supply power ground lug at
the point of entry. A label (Figure 1 on page 11) iden-
tifies this grounding point. This ground wire should be
connected through a continuous ground circuit to the
incoming ground at the source transformer.
GRD
LD20000

FIGURE 1 - GROUNDING LABEL

Besides providing safety protection, the ground connection plays an extremely important part in the operation of the communication circuitry.
Risk of Electric Shock. Ground the SC-EQ Enclosure according to local, na­tional, and regional regulations. Failure to ground the SC-EQ Enclosure may re­sult in electric shock and severe personal injury or death.

PROTECTION OF COMMUNICATION PORTS

2
Power
The SC-EQ circuit board is powered from either a 12 VDC, or a 24 VAC, Class 2 power source. When used with an OptiView chiller, the Micro Panel supplies low-voltage power via a power harness supplied by the OptiView installation kit. If the SC-EQ circuit board is installed in its own enclosure, a transformer is in­cluded in the enclosure. Line voltage may be supplied using an external power source, or drawn from the in­put voltage terminal strip inside the chiller panel. Be sure the capacity of the power conductors supplying the equipment is rated for the additional power (VA) required by the SC-EQ Comm Card. Use a wire that is one size larger than required for the amperage draw (maximum 400 mA) to connect the line voltage feed
JOHNSON CONTROLS
When using RS-485 technology, it is possible that elec-
trical disturbances, such as voltage spikes, can damage
a circuit board. The SC-EQ Comm Card includes reset-
table fuses and other devices on each RS-485 port to pro-
tect against damaging electrical spikes and stray voltage.
The equipment panel should also be equipped with pro-
tection against electrical disturbances. Whereas OptiView
Micro Panels are equipped with onboard tranzorbs, other
equipment panels may require the addition of an external
board. Refer to the equipment documentation for details.
The BAS Port J12 of the SC-EQ Comm Card is also elec-
trically isolated, providing a means of mitigating common
mode voltage induced problems.
11
Page 12
SECTION 2 - INSTALLATION
FORM 450.50-N1
ISSUE DATE: 08/19/2019

HIGH NOISE ENVIRONMENTS

Electrical equipment that employs high speed switching circuits (Variable Speed Drives [VSD], Solid State Start­ers [SSS], and computing equipment) generates Electro­magnetic Interference (EMI) noise and Radio Frequency Interference (RFI), which can generate transient voltage between ground points in the communication wiring. The RS-485 circuitry is designed to withstand some low transient voltage, but if this difference exceeds certain limits, it can permanently damage the RS-485 circuitry.
Ensure that the Micro Panel and the SC-EQ Comm Card are powered from a source with a true earth ground.
IMPORTANT: Do not run communication cables in close proximity to, or parallel with, high-voltage pow­er cables (maintain at least 457.2 mm [18 in.] of sepa­ration, or use a grounded metal conduit).

ELECTRICAL NOISE MITIGATION TO EQUIPMENT

The likelihood of transient voltage is greatly reduced if the SC-EQ Comm Card is close-coupled to the Mi­cro Panel. Close-coupling requires that the SC-EQ En­closure and Micro Panel share the same line voltage power source and are physically close to one another. Typically, the SC-EQ Enclosure is mounted on the Mi­cro Panel enclosure. This scenario ensures a short com­munication cable, which is usually protected entirely within the two enclosures.

ELECTRICAL NOISE MITIGATION SC-EQ TO BAS

When the SC-EQ is used in an electrically hostile envi­ronment (for example, with VSD-enabled equipment), a double-shielded cable should be used to help miti­gate the adverse effects electrical noise can have on the system. The double-shielded cable should connect the SC-EQ’s BAS port (J12) to the next controller(s) in the daisy-chained network.
The outer shield of the double-shielded cable should be grounded directly at the low noise end (the end most distant from the VSD), and ideally, indirectly through an appropriate capacitor at the high noise end (the end closest to the VSD). If a capacitor is not available, the outer shield may be left unconnected, or tied directly to ground. The best results on the site determine the specific termination strategy employed.
The inner shield of the double-shielded cable should be grounded directly at the low noise end (the end most distant from the VSD), and left open at the high noise end (the end closest to the VSD).

TYPES OF COMMUNICATION PORTS

The SC-EQ Comm Card uses two electrical commu­nication protocols to connect to other devices: RS-485 which is used for multi-drop networking, and RS-232 is primarily used for point-to-point connectivity.
RS-485
The RS-485 standard uses three conductors to con­nect network nodes: two signal wires and a third called COM which is the reference. The SC-EQ Comm Card uses either a third wire for the reference or the build­ing’s infrastructure. The wiring method depends on the port being used: an electrically isolated RS-485 BAS Port J12 typically uses a third wire, whereas the RS-485 Equipment Port J8 and the RS-485 Connect­ed Services Port J11 normally use chassis or building ground for the reference.
For BAS systems that use a 2-wire RS-485 network, connect a 100 ohm 1W resistor between SC-EQ J12 COM and J10 COM with a wire that then runs to Ground in the panel. (see Figures 4 and 5)
RS-232
The RS-232 Standard also uses three conductors to connect network nodes: two signal wires and a third called COM which is the reference. RS-232 is more susceptible to noise interference than RS-485 so proper shielding and wire routing is essential for proper op­eration. The RS-232 Standard limits the cable run to a maximum of 50 feet. The OptiView panels use RS-232 to communicate with the SC-EQ.

NETWORK TERMINATION

Terminate all End-of-Line (EOL) devices at each end of the RS-485 bus (that connect to only one set of RS-485 network wires). EOL termination provides bi­asing of the network, and assists in returning the signal to a normal state in the event of voltage transients. If the SC-EQ Comm Card happens to be an end-of-line device on the Building Automation System network, terminate the network by setting the BAS EOL switch S2 to ON.
12
JOHNSON CONTROLS
Page 13
FORM 450.50-N1
BAS Port J12
Not Terminated
Terminated
ISSUE DATE: 08/19/2019
1O
N
RS485 Port EOL
1O
N
RS485 Port EOL
LD20001

FIGURE 2 - RS-485 EOL SWITCHES

IMPORTANT: Ensure that the EOL switches are not set to the ON position for controllers that are not at the end of the BAS RS-485 network.

MEDIA ACCESS CONTROL (MAC) ADDRESS

The SC-EQ Comm Card’s network hardware address is set on a single 8-way DIP switch. Switch 8 is not used. The switches are binary weighted allowing the setting of addresses from 1 to 127. The address must be provided by the BAS contractor. If an address is not provided at chiller commissioning, leave the MAC ad­dress set to 0 (all switches OFF) and leave a copy of the last page of this manual taped on the chiller panel for the controls contractor. The last page explains how to set the MAC address. The SC-EQ automatically de­termines what BAS protocol is present and what chiller is connected except older Yorktalk2 chillers requires that the chiller model manually be set using an SC-AP as explained in the SC-AP section of this manual. This should eliminate the need for a chiller technician to have to return to site after the chiller has been com­missioned just to set the BAS Network MAC Address.
IMPORTANT: The SC-EQ Comm Card is intended to provide an input to equipment under normal operat­ing conditions. Use this SC-EQ Comm Card only as an operating control. Where failure or malfunction of the SC-EQ Comm Card could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other de­vices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the SC-EQ Comm Card.
SECTION 2 - INSTALLATION

TABLE 2 - YORK EQUIPMENT MODELS

MICROBOARD
NUMBER
031-02550 031-02050
031-01095
031-02478 031-03478
031-01065
031-02430
031-03630
331-02496
025W43786-022
(XS09
Display BD)
025W43786-025
(XS09
Display BD)
025W43786-079
(XS09
Display BD)
331W03325-107
331W03325-106
331W03325-110
(IPU3 BD)
331W03325-101
331W03325-104
331W03325-105
331W03325-109
1
SC-EQ/
INSTALL KIT
392-41230-001
KIT includes
SC-EQ
YK-SCCPNL-0
N/A
392-41228-000
KIT includes
SC-EQ
YK-SCCPNL-0
N/A
031-03610-000 331-03607-000
YK-SCCPNL-0
N/A
031-03610-000
371W06953-132
031-03610-000
371W06953-132
031-03610-000
392W41228-020
031-03610-000
392W41228-030
031-03610-000
392W41228-010
031-03610-000
392W41228-010
031-03610-000
371W06163-001
031-03610-000
371W06163-002
031-03610-000
371W06163-002
031-03610-000
371W06163-002
EQUIPMENT
YCWL, YCUL, YCAL, YLAA, YCRL, YLPA, YSAA
YCAS, YCWS, YCRS
YVWA,YVAA, YCIV, YCAV, YVFA
YIA, YPC, YG, YB
YK, YT, YS, YR, YST, YD, YKEP, YMC
YK, YT, YS, YR, YST, YD, YKEP, YMC
YPAL
YEWS Single, YEWS250-E Tandem
YEWS Tandem
YGWE Single
YGWE Tandem
YVWE
YVWH, YGWH
YMAA, YMPA, YVAE-X
YCAE130C, YCAE130D
YCAE130XH
YCAE-X, YCAE-G (Tier2)
MODEL
2
2
2
JOHNSON CONTROLS
1. Installing technician must verify board number in unit prior to installation.
2. Software edition of YEWS-D1 (RHSYEWSD1) V1.08 or later), YEAS (RHMASB V1.06 or later), YGAS (RHMYGAS V1.03 or later) are supported.
3. Models with Native communications do not require a SC-EQ or SC-AP when only connecting to a BAS and Connected Services is NOT installed.
4. OM and Competitive Retrot available in future release 3.
13
Page 14
SECTION 2 - INSTALLATION

BAS NETWORK WIRING

FORM 450.50-N1
ISSUE DATE: 08/19/2019
BAS SYSTEM
-
COM
SHLD
+
SC-EQ #1 SC-EQ #2 SC-EQ #3
SHLD
-
COM
+
SHLD
-
COM
+
SHLD
COM
­+
Ground
Screw
LD29264

FIGURE 3 - 3-WIRE BAS

NOTES:
1. The shield terminal on the SC-EQ is not connected to ground. It provides a convenient place to connect shields in two daisy chain seg­ments.
2. Do not set the EOL switch ON if the unit is not at the end of the segments.
3. Set the EOL switch to ON for the right end of the unit.
4. Ground only one end of the shielded cable.
BAS SYSTEM
-
SHLD
+
SC-EQ #1 SC-EQ #2
-
SHLD
COM
+
SHLD
COM
­+
Ground
Screw

FIGURE 4 - 2-WIRE BAS

NOTES:
1. Set the EOL switch to ON for the right end of the unit.
2. Ground only one end of the shielded cable.
24 VAC
J10

FIGURE 5 - 100 OHM RESISTOR INSTALLATION

NOTES:
1. Ground all SC-EGs.
2. Only 2-wire BAS need 100 Ohm resistor.
100Ω
1W
100Ω
1W
See Figure 5See Figure 5
-
SHLD
COM
+
J12
100Ω
Resistor
LD29328
LD29326
14
JOHNSON CONTROLS
Page 15
FORM 450.50-N1 ISSUE DATE: 08/19/2019

MOUNTING

Risk of Electric Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Con­tact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.

OPTIVIEW PANEL INSTALLATION

1. Attach the SC-EQ Comm Card board to the studs provided inside the chiller enclosure (Fig- ure 6 on page 15 or Figure 7 on page 15), using the four screws and washers provided in the OptiView/Latitude installation kit.
2. Connect the appropriate communications ca­ble (included with the kit) based on the SC-EQ mounting location, from Port J7 (RS-232) on the SC-EQ Comm Card to J2 on the OptiView Micro Panel. Ensure that wires are connected according to Table 3 on page 15.
3. Check for stray wire strands, which could cause short circuits, and ensure all components are secure.
4. Connect the BAS network to J12 (RS-485) on the SC-EQ board.
For BAS systems with 2-wire RS-485 net­work cables remember to install the 100 ohm resistor as shown in Figures 4 and 5.
5. Connect the appropriate length power harness (in­cluded with the kit) from J9 on the SC-EQ Comm Card to J21 on the Optiview Micro Panel (see Fig- ure 8 on page 16).
SECTION 2 - INSTALLATION
SC-EQ Comm Card
U35
U38
Washer
Screw
OptiView
Micro Panel
LD19583

FIGURE 6 - SC-EQ INSTALLED IN OPTIVIEW (ALL CHILLERS EXCEPT YMC2)

SC-EQ Gateway
371-05568-xxx 371-06985-xxx
Panel
SC-EQ Gateway 371-05619-xxx 371-06698-xxx 371-06986-xxx Panel
Washer
Screw
OptiView
Micro Panel
Screw
U3
5
U38
Washer
U38
5 3 U
LD19582a

FIGURE 7 - SC-EQ INSTALLED IN YMC2 OPTIVIEW

2
6. Set the desired BAS network address for the SC­EQ using the SW-1 MAC Address Switches.
When the SC-EQ and the OptiView panel are pow­ered up, the SC-EQ automatically sets itself to the BAS protocol, baud rate and chiller model. This may take up to 120 seconds.

TABLE 3 - OPTIVIEW WIRING - SC-EQ PORT J7

SC-EQ PORT J7 OPTIVIEW PORT J2 WIRE COLOR
RX GTX Black
TX GRX Red
REF N/A Shield/Drain
JOHNSON CONTROLS

TABLE 4 - BAS WIRING - SC-EQ PORT J12

SC-EQ PORT J12 BAS WIRE COLOR
+ + White
- - Blue
REF REF Black
When replacing an E-Link with a SC­EQ, the BAS wiring MUST be changed since the plug terminal locations are not the same!
15
Page 16
SECTION 2 - INSTALLATION
Power Harness
(OptiView)
4 Position
Connector
Communication Cable
(OptiView / Latitude)
4 #8 Nylon
Washers
(OptiView /
Lattitude)
3/8 in. Screw
8 x32
(OptiView)
Primary
Power Wiring
Harness
FORM 450.50-N1
ISSUE DATE: 08/19/2019
Primary
120 VAC
Secondary
24 VAC
24 VAC
Power
Transformer
YMC2 Power
Harness (OptiView)
4 Position Connector
YMC2 Communication
Cable (OptiView)
100 OHM
Resistor
LD20002

FIGURE 8 - SC-EQ OPTIVIEW INSTALLATION KIT (ALL CHILLERS) (YORK P/N 331-03607-000)

Power Harness
(Latitude)
2 Position
Connector
4 Position
Resister
Connector
Communication Wiring Harness
100 OHM
Tie
Wrap
Secondary
Power Wiring
100 OHM
Resister
Tie
Wrap
Sheet Metal
Screw
Harness
Expansion
Nut
Communication
Wiring Harness
Expansion Nut Screw
LD20004

FIGURE 10 - SC-EQ SCROLL CHILLER INSTALLATION KIT PART NUMBER 392-41230-001

SMALL TONNAGE PANEL INSTALLATION

1. Attach the SC-EQ Comm Card board to the panel in the upper right side of the enclosure using the four expansion screws and nuts provided in the IPU-II Panel Installation Kit (see Figure 11 on page 17).
Sheet Metal Screw
Expansion
Nut
Expansion Nut Screw
LD20003

FIGURE 9 - SC-EQ SCREW CHILLER INSTALLATION KIT PART NUMBER 392-41228-000

16
2. Attach the 24 VAC transformer to the panel to the left of the SC-EQ board using two screws (Figure 10 on page 16).
3. Connect the communications cable (included with the kit) between the SC-EQ board J8 (RS-
485) and the IPU-II Micro board TB1.
4. Connect the transformer to the terminal block.
5. Connect the transformer to SC-EQ J10 and secure the wiring with tie-wraps.
6. For RS-485 2-wire operation, connect a 100 ohm 1W resistor between SC-EQ J12 COM and J10 COM with a wire then run to Ground in the panel. (see Figure 4 on page 14 and Figure 5 on page
14)
JOHNSON CONTROLS
Page 17
FORM 450.50-N1 ISSUE DATE: 08/19/2019
SECTION 2 - INSTALLATION
7. Connect the communications cable shielded ground to the ground screw.
8. Set the desired BAS network address for the SC­EQ using the SW-1 MAC Address Switches.
Primary Power Wiring Harness
Terminal block location
The Resister is used for BAS
RS485 2 Wire Connection.
Connect one end of the
Resistor to the COM of TB5
(24 VAC) and the other to
Port 1 COM.
Use this resistor only if the BAS
wiring utilizes a 2 Wire
communication trunk
Communication Wiring Harness:
Connect to Micro Board
TB1 as Follows:
Wire Color / Terminal
Red / +
Black / -
for YCAL-C, YCWL,
and YCUL-C.
Transformer
Secondary
TB1 RS485
SHLD REF - +
Ground
Secondary
Power Wiring
Harness
TB2
TB5
Tie
Wrap
When the SC-EQ and the control panel are powered up, the SC-EQ automatically sets itself to the BAS pro­tocol, baud rate and chiller model. This may take up to 120 seconds.
Sheet Metal Screw
24 VAC
Transformer
Expansion
Nut
TB5
Resistor
Communication Wiring Harness
MicroBoard
TB5
TB1
TB2
Expansion Nut Screw
Com
Ground
SC-EQ
2
Terminal Block Location
For YCAL-D, YCAL-E, and YLAA.

FIGURE 11 - SCROLL CHILLER PANEL INSTALLATION

YMAA, YCAE, AND YCWE-E PANEL INSTALLATION

To install the panel on YMAA, YCAE, or YCWE-E chillers, complete the following steps:
1. Install the SC-EQ to the bracket using plastic sup­port. Attach the bracket to the studs provided in­side the chiller enclosure. See Figure 12, Figure 13, or Figure 14.
2. Install the 12 VDC switch power supply to the bracket using M3 screws. Attach the bracket to the studs provided inside the chiller enclosure. This step is only for YCAE and YCWE chillers. See Figure 13 or Figure 14.
3. Connect the appropriate communications cable based on the SC-EQ mounting location, from Port J8 (RS-485) on the SC-EQ to CON205 on the YMAA, YCAE, or YCWE control board. Ensure that wires are correct. See Figure 15, Figure 16, or Figure 17
LD20005
4. Check for stray wire strands, which could cause short circuits. Ensure all components are secure.
5. Connect the BAS network to J12 (RS-485) on the SC-EQ board.
6. Connect the appropriate length of power har­ness from J9 on the SC-EQ to XTB2, as shown in Figure 15, or to 12 VDC switch power supply, as shown in Figure 16. The power harness is in­cluded in the kit.
7. Set the required BAS network address for the SC­EQ using the SW-1 MAC address switches.
When the SC-EQ and the control board are powered up, the SC-EQ automatically sets itself to the BAS pro­tocol, baud rate, and chiller model. This may take up to 120 s.
JOHNSON CONTROLS
17
Page 18
SECTION 2 - INSTALLATION
LD29244
BOARD
PLASTIC
BRACKET
SC-EQ
GROUNDING
LD29245
PLASTIC
SUPPORT
SWITCH POWER SUPPLY
LD29246
PLASTIC
SWITCH POWER
SUPPLY AND BRACKET
LD29247
FORM 450.50-N1
ISSUE DATE: 08/19/2019
SCREW
CONTROL
SUPPORT
PANEL
XTB2

FIGURE 12 - SC-EQ INSTALLED IN YMAA AND YVAE

TABLE 5 - BOM OF YMAA SC-EQ KIT (371W06163-
001)
LEVEL ITEM P/N DESCRIPTION QTY
1 1 031-03610-000
1 10 371W06163-101
Gateway
SC-EQ Board
Kit, Installation,
SC-EQ, YMPA
1
1
SUPPORT
BRACKET
SC-EQ
CONTROL
BOARD
PANEL

FIGURE 14 - SC-EQ INSTALLED IN YCWE-E

TABLE 7 - BOM OF YCWE-E SC-EQ KIT
(371W08244-301)
LEVEL ITEM P/N DESCRIPTION QTY
1 1 031-03610-000
1 10 371W08244-302
Gateway SC-
EQ Board
Kit, Installation,
SC-EQ,
YCWE-E
1
1
BRACKET CONTROL

FIGURE 13 - SC-EQ INSTALLED IN YCAE

TABLE 6 - BOM OF YCAE SC-EQ KIT (371W06163-
002)
LEVEL ITEM P/N DESCRIPTION QTY
1 1 031-03610-000
1 10 371W06163-102
PANEL SC-EQ
BOARD
AND BRACKET
GROUNDING
SCREW
Gateway SC-
EQ Board
Kit, Installation,
SC-EQ,
YCAE-X

FIGURE 15 - SC-EQ CONNECTED IN YMAA, YVAE, AND YCWE

LD29248
1

FIGURE 16 - SC-EQ CONNECTED IN YCAE AND YCWE-E

1
18
JOHNSON CONTROLS
Page 19
FORM 450.50-N1 ISSUE DATE: 08/19/2019
SECTION 2 - INSTALLATION
2

FIGURE 17 - SC-EQ TO YMAA, YCAE, AND YCWE CONNECTIONS

JOHNSON CONTROLS
LD29249
19
Page 20
SECTION 2 - INSTALLATION
LD29250
CONTROL
LD29251

YVWE AND YVWH PANEL INSTALLATION

To install the panel on YVWE or YVWH chillers, com­plete the following steps:
1. Install the SC-EQ on the door inside of the control panel using M3 screws. See Figure 18.
2. Connect the appropriate communications cable from Port J8 (RS-485) on the SC-EQ to XTB3, which is factory-connected to the control board. Ensure all wires are correct. See Figure 19.
FORM 450.50-N1
ISSUE DATE: 08/19/2019

FIGURE 19 - SC-EQ TO YVWE AND YVWH CONNECTIONS

3. Check for stray wire strands, which could cause short circuits. Ensure all components are secure.
4. Connect the BAS network to J12 (RS-485) on the SC-EQ board.
5. Connect the appropriate length of power harness from J10 on the SC-EQ to XTB3. See Figure 19. The power harness is included in the kit.
6. Set the required BAS network address for the SC­EQ using the SW-1 MAC address switches.
When the SC-EQ and the control board are powered up, the SC-EQ automatically sets itself to the BAS pro­tocol, baud rate, and chiller model. This may take up to 120 s.
SC-AP
HMI
BOARD

YEWS AND YGWE SINGLE PANEL INSTALLATION

To install the panel on YEWS or YGWE chillers, com­plete the following steps:
1. Install the switch power supply to the DIN35 lead rail. See Figure 20, Figure 21, or Figure 22.
2. Install the SC-EQ on the standoffs of the panel using M3 screws. See Figure 20 for YEWS and YGWE Single, Figure 21 for YEWS Tandem, or Figure 22 for YGWE Tandem.
3. Connect the appropriate communications cable from Port J8 (RS-485) on the SC-EQ to XTB2 (A4/B4) in the panel. Ensure all wires are correct. This step is only for YEWS and YGWE Single. See Figure 23.
4. Connect the appropriate communications cable from the XS-09 display (RS485-1, only for the unit using York-003 board) or IPU3 control board (TB4:A4/B4, which is factory-connected) to XTB2 (A4/B4) in the panel. Ensure all wires are correct. See Figure 20, Figure 21, or Figure 22.
SC-EQ

FIGURE 18 - SC-EQ INSTALLED IN YVWE AND YVWH

20
GROUNDING
SCREW
XTB3
5. Check for stray wire strands, which could cause short circuits. Ensure all components are secure.
6. Connect the BAS network to J12 (RS-485) on the SC-EQ board.
7. Connect the appropriate length of power harness from J9 on the SC-EQ to 12 VDC terminals of switch power supply. See Figure 20, Figure 21, or Figure 22 and Figure 23.
8. Set the required BAS network address for the SC­EQ using the SW-1 MAC address switches.
When the SC-EQ and the control board are powered up, the SC-EQ automatically sets itself to the BAS pro­tocol, baud rate, and chiller model. This may take up to 120 s.
JOHNSON CONTROLS
Page 21
FORM 450.50-N1
SWITCH
XS09
POWER
XS09
LD29254
CONTROL
POWER
LD29255
ISSUE DATE: 08/19/2019
SECTION 2 - INSTALLATION
XTB2
POWER
SC-EQ PANEL
DISPLAY

FIGURE 20 - SC-EQ INSTALLED IN YEWS AND YGWE SINGLE

YORK-003 BD
DISPLAY
LD29252
2

FIGURE 23 - SC-EQ TO YEWS CONNECTIONS

OTHER CHILLER PANEL INSTALLATION

For all other applications, the SC-EQ Comm Card in­cludes an optional enclosure. The optional enclosure does not include communication cables due to the vari­ety of types and lengths that may be required.
Never install the SC-EQ Comm Card outside the con­fines of a building unless within another enclosure rated IP 65/NEMA 4x or higher.
The SC-EQ Comm Card can be mounted as a stand­alone enclosure either on the outside surface of the chiller Micro Panel (close coupled), or on a smooth surface within close proximity of the chiller panel en­closure.
XTB2 SC-EQ PANEL
SWITCH
LD29253

FIGURE 21 - SC-EQ INSTALLED IN YEWS TANDEM

PANEL
XTB2
BOARD
SWITCH
SC-EQ
For mounting on a Micro Panel, the line voltage power is supplied by a power source in the Micro Panel.
IMPORTANT: Make sure that the cover is securely fastened to the enclosure and the internal ground wire is attached before placing the SC-EQ in operation. These steps help to minimize Radio Frequency Inter­ference (RFI) from being generated and picked up.

FIGURE 22 - SC-EQ INSTALLED IN YGWE TANDEM

JOHNSON CONTROLS
21
Page 22
SECTION 2 - INSTALLATION

MOUNTING ON A MICRO PANEL

Risk of Electric Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Con­tact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
SC-EQ
Enclosure
YORK Chiller
Micro Panel
FORM 450.50-N1
ISSUE DATE: 08/19/2019
ISN
MicroGateway
177.8mm (7 in.)
IMPORTANT: When attaching the SC-EQ Enclosure to a Micro Panel, ensure the SC-EQ Enclosure does not impede access to other components.
To mount the SC-EQ Enclosure on a Micro Panel:
1. Disconnect power to the chiller Micro Panel.
2. Make sure the SC-EQ Enclosure ts properly and that no obstructions, such as internal boards, switches, or external conduit, prevent mounting or servicing of the panel. See Figure 23 on page 21 for examples of good mounting locations.
3. Locate and remove the two plastic caps in the bot­tom of the SC-EQ Enclosure.
4. Mark an appropriate place on the enclosure for a matching set of knock out holes. Mark and drill, or punch, two holes in the Micro Panel.Using two bulkhead pipe couplers, attach the SC-EQ Enclo­sure to the Micro Panel.
5. Complete wiring as described in the Applying Power section in this document.
Drill or punch 19mm (3/4 in.) Diamerter 2x
ISN
MicroGateway
ISN
MicroGateway
Alternative Mounting
Locations
LD20006

FIGURE 24 - MOUNTING ON THE EQUIPMENT

IMPORTANT: Be careful not to damage the SC-EQ or Micro Panel’s circuit boards during the installation. Protect all circuit boards from metal chips, which may cause short circuits if left on the boards at startup.
Use of bulkhead pipe couplers provides
sufcient clearance to allow removal of
the SC-EQ Encloser cover.
22
JOHNSON CONTROLS
Page 23
FORM 450.50-N1 ISSUE DATE: 08/19/2019
SECTION 2 - INSTALLATION

WALL MOUNTING

To mount the SC-EQ Enclosure on a wall:
When wall mounting, make sure there is no interference with other components in the near vicinity. Use appropriate conduit to connect the power and communications wiring.
1. Check for proper clearances for the necessary electrical and communications cable runs.
2. Ensure that power and communications wiring is in compliance with all local, national, and region­al codes, and customer requirements.
3. Select a suitable location and mark the anchor points. Ensure that the enclosure is level. See Fig- ure 25 on page 23 for an example.
4. Drill the appropriate holes in accordance with the type of wall anchor used.
5. Install the enclosure on the wall.
6. Check that the mounting is secure and the wir­ing connections are correct and tight. Check that no loose wire strands or other metal objects that could cause a short circuit are on the circuit board.

APPLYING POWER

When using an enclosure type of SC-EQ, power can be supplied from either a separate power supply or the main terminal strip in the chiller panel. Locate the power source within 0.9 m (3 ft) of the SC-EQ En­closure, and protect it with a suitable fuse or circuit breaker. Ensure the power is supplied from a dedicated source and not controlled by a programmed switch.
If the enclosure is mounted on a wall, the wiring from the power source to the SC-EQ Enclosure must always run in a suitable conduit. To obtain the best Electromag­netic Interference (EMI) and Electromagnetic Compat­ibility (EMC) performance, ensure that the conduit is bonded to the metal of both enclosures. Scraping the paint around the knockouts usually helps provide a bet­ter electrical connection between the joining parts.
Risk of Electric Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Con­tact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
2
7. Complete wiring as described in the Applying Power section.
YORK Chiller Mirco Panel

FIGURE 25 - WALL MOUNTING

Conduit
ISN
MicroGateway
241.3mm (9-1/2 in.)
SC-EQ
Enclosure
Template for Mounting
on a wall
136.5mm (5-3/8 in.)
LD20007
120 VAC
or
240 VAC
Power
J10
24 VAC
Power
LD19996
JOHNSON CONTROLS

FIGURE 26 - SC-EQ IN ENCLOSURE

23
Page 24
SECTION 2 - INSTALLATION
FORM 450.50-N1
ISSUE DATE: 08/19/2019
Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
1. Connect a 1.29-1.02 mm (16-18 AWG) wire from a reliable ground reference to the SC-EQ Gate­way’s incoming power ground lug. Do not re­move the existing wire that connects the ground lug to the enclosure cover.
24 VAC
Power
+12 VDC
Power
2. On 120 VAC applications, connect the Hot wire to TB-BLK and the Neutral wire to TB-WHT. Con­nect the ground wire to the ground lug.
On 240 VAC applications, connect the Hot wire to TB-YEL and the Neutral wire to TB-WHT. Con­nect the ground wire to the ground lug.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the SC-EQ Gateway’s electrical ratings.
MAC Address Switch
BAS Port J12
EQ 485 Port
COM
SHD
EQ 232 Port
COM
SHD
LEDs Power
USB Port
+
-
TX
RX
CS BUS BS BUS EQ BUS
Fault
Equipment RX Equipment TX
BAS RX BAS TX
BAS RJ

FIGURE 27 - SC-EQ COMPONENT LOCATIONS

24
Connected Service
Port J11
CS RJ
LD19992a
JOHNSON CONTROLS
Page 25
FORM 450.50-N1
Chiller Rotary Switch
YT Address = Rotary Switch +1
1
0
23
4
5
87
96
ISSUE DATE: 08/19/2019
SECTION 2 - INSTALLATION

EQUIPMENT CONFIGURATION

Different pieces of equipment sometimes require a spe­cific hardware configuration (jumper, switch or soft­ware setting) to enable communication with the SC­EQ Communication Card. Refer to the equipment’s installation literature for details on the proper configu­ration settings. The following diagrams summarize what these requirements are and the wiring interfaces for each of the different types of microboards.
LD20009

FIGURE 28 - MICROPANEL ROTARY SWITCH

SETTING THE ROTARY SWITCH ON CHILLER PANELS

Some Micro Panels use a rotary switch to set their YORK Talk II address (YORK Talk address = Rotary Switch setting + 1). Since the SC-EQ uses a one-to­one relationship with the chiller panel, this switch is normally set to 0 (YORK Talk address 1). However, when two microboards are used in a BACnet MS/TP configuration, set the master microboard rotary switch to 0, and the subordinate microboard is set to 1. If the chiller microboard is not equipped with a rotary switch, the YORK Talk address is set using the Micro Panel keypad and display. In most cases, you can configure the setting, but some models are fixed and cannot be changed (refer to the equipment documentation for specific details).
2
JOHNSON CONTROLS
25
Page 26
SECTION 2 - INSTALLATION
S1
23
1
4
0
5
96
87
031-01065-xxx
U17
EPROM
MODEM
JP56
JP58
EMS
TB7
GND
RS485
RS232
BLACK
(Open)
RED
SHIELD
Equipment Cable
York Talk 2
RS485
(1200 baud)
ISSUE DATE: 08/19/2019
SC-EQ
EQ 485 Port J8
-
+
COM
RED
BLACK
GRD
FORM 450.50-N1
SHLD
Rotary Switch (Chiller ID=0)
Jumper
V25
TB1
SHD
TB6
GND
SHD
031-01314-000
Note: If the EPROM used in the board is dated prior to 11/2000, the chiller ID is fixed at 0. If the EPROM used is dated after 11/2000, the chiller ID is software selectable through the micro panel.
GND
V25
TB1
031-02050-000
SHD GND
RED
(Open)
BLACK
SHIELD
Equipment Cable
York Talk 2
RS485
(1200/4800 baud)
BLUE
WHITE
SHIELD
Equipment Cable
York Talk 2
RS485
(4800 baud)
RED
BLUE
SC-EQ
EQ 485 Port J8
-
+
COM
BLACK
GRD
SC-EQ
EQ 485 Port J8
-
+
COM
WHITE
GRD
SC-EQ
EQ 485 Port J8
SHLD
SHLD
Note: The chiller ID is software-selectable through the micro panel keypad. Set the Chiller ID to 0 to make network address to 1.
NOTE: See Table 2 on page 13 for board cross-reference.

FIGURE 29 - SC-EQ COMM CARD TO YORKTALK II EQUIPMENT CONNECTIONS

26
-
+
COM
SHLD
LD20010
JOHNSON CONTROLS
Page 27
FORM 450.50-N1 ISSUE DATE: 08/19/2019
Rotary Switch
(Chiller ID=0)
Jumper
031-01095-xxx
S1
(MASTER)
23
4
1
5
0
96
87
JP19
TB7
RS485
RS232
TB8
BAS +
BAS -
GND
SHLD
485-
485+
BAS +
RED
(Open)
BLACK
SHIELD
Equipment Cable
York Talk 2
RS485
(4800 baud)
EQ 485 Port J8
RED
EQ 485 Port J8
+
+
SC-EQ
-
BLACK
SC-EQ
-
COM
GRD
COM
SECTION 2 - INSTALLATION
SHLD
2
SHLD
Rotary Switch
(Chiller ID=0)
Jumper
Rotary Switch
(Chiller ID=0)
Jumper
Rotary Switch
(Chiller ID=0)
031-01095-xxx
S1
(MASTER)
23
4
1
5
0
96
87
JP19
TB7
RS485
RS232
TB8
BAS +
BAS -
GND
SHLD
485-
485+
BAS +
RED
BLACK
RED
RED
(Open)
SHIELD
Equipment Cable
York Talk 2
RS485
(4800 baud)
Equipment
SHIELD
TB6
TB1
Slave Micro
Board Cable
BLACK
SHD
GND
SHD
GND
031-01095-xxx
S1
23
4
1
5
0
96
87
(SLAVE)
TB7
JP19
RS485
RS232
TB8
031-01793-000
or
031-02050-000
(Slave)
BAS +
BAS -
GND
SHLD
485-
485+
BAS +
RED
V25
Note: The 1793 slave chiller ID is always set to the master address +1.
031-01095-xxx
S1
23
4
1
5
0
96
87
(Master)
JP19
TB7
RS485
RS232
BAS +
BAS -
GND
SHLD
485-
485+
BAS +
BLACK
RED
Equipment Slave
Micro Board
TB8
RED
SHIELD
Cable
BLACK
RED
BLACK
BLACK
GRD
EQ 485 Port J8
+
(Open)
SHIELD
SC-EQ
-
SHLD
COM
SC-EQ
EQ 485 Port J8
+
RED
Equipment Cable
York Talk 2
RS485
(4800 baud)
­COM
BLACK
GRD
SHLD
Jumper
NOTE: See Table 2 on page 13 for board cross-reference.

FIGURE 30 - SC-EQ COMM CARD TO YORKTALK II EQUIPMENT CONNECTIONS

JOHNSON CONTROLS
LD20011
27
Page 28
SECTION 2 - INSTALLATION
P3 Keypad
P6 Keyboard
I/O COM DC Power Temp Sensor
P4
Frick Q2 Board
Floppy DRV
J90
J64
Hard DRV
COM 1
COM 2
J89
P10
P11
P12
FORM 450.50-N1
ISSUE DATE: 08/19/2019
SC-EQ
EQ 485 Port J8
-
+
BLACK
1­2+
3 4
5
6
RED
7
8
(Open)
SHIELD
RED
BLACK
COM
GRD
SHLD
F1
P5 DISP
P4 INV
P3 KYPD
P2 DC POW
P6
VR1
P1
640D0061H01
VGA
HEAT SINK
Frick Q3 Board
PL20 COM 1
PL18
P12
PL7
BAT
DP1
1 8
Open
P1
COM2
RS232
LK19
BAT
PL7
FLASH MEMORY SOCKET
8 1
DIAG
COM1
COM3
P2
BLACK
RED
Jumper
(Open)
SHIELD
Jumpers
Equipment Cable
York Talk 2
RS485
(4800 baud)
SC-EQ
EQ 485 Port J8
-
+
RED
BLACK
Equipment Cable
York Talk 2
RS485
(4800 baud)
SC-EQ
EQ 485 Port J8
-
+
COM
GRD
COM
SHLD
SHLD
Port 2 Port 1
U5 U4
RED
+RX
4
-RX
5
+TX
8
-RX
9
GND
Connect to Port 1 (9 Pin Connector)
BLACK
3 1
Jumpers
6
2 7
Jumpers
RED
(Open)
SHIELD
Equipment Cable
York Talk 2
RS485
(4800 baud)
RWBII Rev. B and Lower
Frick RWBII Plus
+RX
Note: Requires ISN EPROMs in locations U4 and U5.
The transfer rate on the chiller must be set to 4800 baud.
Connect to Port 1 (5 Pin Connector)
RED
BLACK
Jumpers
RED
(Open)
SHIELD
RWBII Rev. C and Higher
NOTE: See Table 2 on page 13 for board cross-reference.

FIGURE 31 - SC-EQ COMM CARD TO YORKTALK II EQUIPMENT CONNECTIONS

BLACK
GRD
SC-EQ
EQ 485 Port J8
-
+
COM
BLACK
GRD
Equipment Cable
York Talk 2
RS485
(4800 baud)
SHLD
LD20012
28
JOHNSON CONTROLS
Page 29
FORM 450.50-N1 ISSUE DATE: 08/19/2019
J7
J22
J6
J5
SW1
1 2 3 4
Program Switches
OPEN
J18
Optiview Microboard
031-02430-XXX
J21
FLASH
CARD
Program Download Connector
BOOT-UP LED Status Display
J4
J8
BRAM
J19
J9
LEDS
BIOS
JP27
EPROM
LEDS
F2
F1
J20
J10
J11
J12
J13
J2
J15
J1
RED
NC GND GND
GTX
GRX
DTR1
TXD1 RXD1 DSR1
NC
BLACK
SHIELD
J2
RED
RED
(Open)
Power Harness
(+12 v DC)
Equipment Cable
York Ta lk 3
RS232
BLACK
(Open)
SHIELD
E-Link
PORT 2B RS232
TX RX COMSHLD
BLACK
GRD
SC-EQ J9
+12 VDC
SECTION 2 - INSTALLATION
SC-EQ
EQ 232 Port J7
TX RXCOMSHLD
2
J22
Optiview Microboard
J9
F2
J1
J10
031-03630-XXX
J21
J6
F1
J11
J12
SMARC CARD
J5
LEDS
SW1
OPEN
Program Switches
J13
1 2 3 4
J2
LED
BOOT-UP LED Status Display
J18
J19
J15
J20
RS-232. On the 03630 this port is dedicated to RS-232.
Equipment Cable
GND
GTX
GRX
DTR
TX1 RX1 DSR
GND
BLACK
RED
SHIELD
Power Harness
J2
(Open)
(+12 v DC)
BLACK
RED
SHIELD
EQ 232 Port J7
TX RX COM SHLD
RED
York Ta lk 3
RS232
(Open)
SC-EQ
BLACK
SX-EQ J9
+12 VDC
SC-EQ
EQ 232 Port J7
TX RXCOMSHLD
GRD
LD28299
Note: There is no JP27 jumper to set Com 4 port to

FIGURE 32 - SC-EQ COMM CARD TO OPTIVIEW EQUIPMENT CONNECTIONS

JOHNSON CONTROLS
29
Page 30
SECTION 2 - INSTALLATION
FORM 450.50-N1
ISSUE DATE: 08/19/2019
Note: JP1 on the 031-02478-xxx board must be set to the RS485 position when the SC-EQ BAS communication is required.
031-02478-xxx
J16
Equipment Cable
York Talk 2
RS485
(4800 baud)
SC-EQ J9
+12 VDC
SC-EQ
EQ 485 Port J8
+ - COM SHLD
SC-EQ
Power
GND
+5V
RS485
NOTE: Enabling any part of PRINT functions will disrupt BAS/SC-EQ communications. See YORK Equipment form 201.21-NMx in the installation, Operation & Maintenance (IOM) Air-Cooled Screw Liquid Chillers manual for more information.
Shld
P3+
P3-
4
231
5
JP1
BLACK
RED
(Open)
Power Harness
(+12v DC)
GRD
SHIELD
SC-EQ
EQ 485 Port J8
+ - COM SHLD
BLACK
RED
LD20014a

FIGURE 33 - SC-EQ COMM CARD CONNECTIONS FOR CHILLERS WITH THE 02478 MICROBOARD YCAV/ YCIV/YVAA/YVWA

031-03478-xxx
J16
SC-EQ
Power
GND
+5V
RS485
NOTE: The default settings of the 03478 allow the board to communicate with the SC-EQ. If communication does not occur, check the chiller panel settings to ensure that Port 2 (TB-2) is set for DE Instance = -1 and Chiller ID set = 0.
Shld
+
-
4
231
5
TB2
Equipment Cable
SC-EQ J9
+12 VDC
RED
BLACK
TB3 Native Comms
+ - COM SHLD
York Talk 2
RS485
(4800 baud)
Power Harness
(+12v DC)
GRD
SHIELD
(Open)
EQ 485 Port J8
+ - COM SHLD
SC-EQ
EQ 485 Port J8 + - COM SHLD
BLACK
RED
SC-EQ
LD20015a

FIGURE 34 - SC-EQ COMM CARD CONNECTIONS FOR CHILLERS WITH THE 03478 MICROBOARD YCAV/ YCIV/YVAA/YVWA/YVFA

30
JOHNSON CONTROLS
Page 31
FORM 450.50-N1
LD20016
ISSUE DATE: 08/19/2019
SECTION 2 - INSTALLATION
RS485
TB1
031-02550-xxx (I/O Board)
031-02630-xxx
Red
Black
(Open)
SHIELD
SHLD
REF
-
+
Red
SC-EQ
EQ 485 Port J8
COM SHLD
-
+
Black
(IPU II Board)
Communication Wiring Harnes
(Part of Installation Kit) Wired from SC-EQ EQ 485
Port to Microboard TB1 (RS-485, 4800 baud)
IPU-ll P1 Setup for York Talk 2: DE Modifier Address set to -1. DE Modifier Offset set to -1. P1 Protocol set to API. P1 Manual MAC Address set to -1. Some panel programs may not allow the -1 setting in which case it should be set to 0. P1 Baud Rate set to 4800. P1 Parity set to Odd. Cycle power to the IPU-ll NOTE: The IPU ll Chiller address defaults to 0, which is the Yorktalk equivalent of an ID of 1. Do not change this default ID. If you believe
this has been modified, reset it to 0. Also, set the Chiller Local/Remote setting to Remote to send commands to the chiller.

FIGURE 35 - SC-EQ COMM CARD CONNECTIONS FOR CHILLERS WITH THE 02550 MICROBOARD YCAL/ YCUL/YLAA/YLPA/YCWL/YCRL/YSAA

2
YPAL
031-02497-xxx (I/O Board)
331-02496-101
(IPU I Board)
J4
P3 P3
GND
+5V
5
4
+
3
-
2
1
Equipment Cable
BACnet
MS/TP
(38400 baud)
RED
(Open)
BLACK
SHIELD
RED
SC-EQ
EQ 485 Port J8
COM SHLD
-
+
BLACK
GRD
SC-EQ
EQ 485 Port J8
-
+
COM
SHLD
YPAL Setup for MS/TP Bus: DE Modifier Address set to 50. DE Modifier Offset set to -1. P1 Protocol set to BACnet. P1 Manual MAC Address set to -1. P1 Baud Rate set to 38400. P1 Parity set to None. P1 Stop Bits set to 1. MAC Address Switch (SW2) set 1 ON, all others OFF. NOTE: Do not set the Chiller address and the SC-EQ address to the same value. This causes a conflict on the MS/TP Bus resulting in no
communication between the chiller IPU I board and the E-Link Gateway.
LD20017a

FIGURE 36 - SC-EQ COMM CARD CONNECTIONS TO YPAL (EC02)

JOHNSON CONTROLS
31
Page 32
SECTION 2 - INSTALLATION
FORM 450.50-N1
ISSUE DATE: 08/19/2019
XS08-10
Black
Green
Yellow
Red
-
12V
OV
B1
A1
B0
A0
10-24V
0V
(Open)
Green
Black
Equipment Cable
MODBUS
RTU
(9600 baud)
White
Blue
Shield
SC-EQ
EQ 485 Port J8
-
COM
+
SHLD
GRD
SC-EQ
EQ 485 Port J8
-
+
COMSHLD
YORK-003
System-1
B
A
+
For node address setting,
please refer to Chiller Installation Manual
220 VAC
220 VAC
50 Hz
50 Hz
12V
­+
220 VAC
50 Hz
Green
Black
YORK-003
System-2
B
A

FIGURE 37 - SC-EQ COMM CARD CONNECTIONS TO YEWS-D1/YEAS/YGAS

32
LD20018
JOHNSON CONTROLS
Page 33
FORM 450.50-N1 ISSUE DATE: 08/19/2019

SECTION 3 - TROUBLESHOOTING

LED INDICATORS

There are 9 LEDs on the SC-EQ Comm Card to indi­cate the operational status of the SC-EQ and the 3 com­munication ports. The LEDs on the SC-EQ and related communication LEDs on the chiller microboard should be observed to help diagnose communication problems.
LEDs/ USB
BAS Network
BS BUS - A Green LED that indicates the communi­cation activity on the BAS communication port. The LED illumination has two variations depending upon the protocol present on the BAS port.
BACnet MS/TP - The LED is OFF when there are no active BACnet communications on the network. It is also OFF when it is initially auto-bauding and waiting for a master device to poll on the network. The LED illuminates ON when the SC-EQ sees any communica­tions on the network.
N2 and Modbus RTU - SC-EQ receives a request from the Master to the SC-EQ network address. The LED then illuminates while the SC-EQ is transmitting the response message.
There are two additional LEDs on the BAS Port to aid in diagnosing BAS Network Integration problems.
BRX - A Green LED that illuminates when the SC-EQ is Receiving data on the BAS Network Port.
3

FIGURE 38 - SC-EQ LEDS AND USB

LD19992a
Power
A Green LED that is ON whenever power is applied to the SC-EQ Comm Card either by the 24 VAC (20.4 to 30 VAC) input or the +12 VDC (+12 VDC +or- 10%) input. The Power LED should always be illuminated. If not then a digital multimeter should be used to verify the power source to the SC-EQ is present or not. If the power source is present at the SC-EQ power terminals (J9 +12 VDC (Red wire + Black wire - ) or J10 24 VAC as applicable) and the Power LED is not illuminated then the SC-EQ is faulty.
Connected Services Network
CS BUS - A Green LED that indicates the commu­nication activity on the Connected Services commu­nication port. It blinks ON and OFF every 500ms to indicate that communications is established with the SC-AP. The LED is ON solid when there are no com­muncations established with the SC-AP and the SC-EQ CS port is therfore polling for a Master. If the LED is OFF continuously then the SC-EQ is waiting for the SC-AP to start polling the SC-EQ.
BTX - A Red LED that illuminates when the SC-EQ is Transmitting data on the BAS Network Port.
Normal Sequence - The Green BRX LED illuminates whenever there is a data packet sent on the BAS net­work to Any address. If this LED illuminates for a short period of time then it indicates that the BAS Port RS-485 receive circuitry is functioning. If the BRX illuminates solid, then the + and - RS-485 wires are probably swapped and should be corrected. If the data message address matches the SC-EQ address then the SC-EQ responds with the requested data and the Red BTX LED illuminates during the response. If the BAS system is polling the SC-EQ but the SC-EQ is not re­sponding then the MAC address should be checked to see if it is set to the desired address.
JOHNSON CONTROLS
33
Page 34
SECTION 3 - TROUBLESHOOTING
FORM 450.50-N1
ISSUE DATE: 08/19/2019
Equipment Network
EQ BUS - A Green LED that indicates the commu­nication activity between the SC-EQ and the chiller Microboard. The SC-EQ acts as the Master in this net­work and issues data requests to the chiller Microboard. The EQ BUS LED blinks as it receives a valid response from the chiller Microboard. The data is requested one parameter at a time so the blink rate is almost constant.
There are two additional LEDs on the Equipment Port to aid in diagnosing communication problems with the microboard.
ERX - A Green LED that illuminates when the SC-EQ is Receiving data from the microboard.
ETX - A Red LED that illuminates when the SC-EQ is Transmittinging data to the microboard.
Normal Sequence - The Red ETX LED is illuminate when the SC-EQ sends a request for data to the chiller microboard. The microboard Receive LED should then illuminate. The microboard should then illuminate it's Transmit LED as it sends the requested data and the Green ERX LED on the SC-EQ should illuminate.
If the SC-EQ ETX light illuminates and the micoboard Receive LED illuminates but no response is transmit­ted from the microboard check that the chiller address is set to 1. For microboards with a rotary switch set to 0 which is interpreted as a 1. If the address is set in the software, then it should be set to 1.
Fault
A Red LED that indicates a problem with the SC-EQ Firmware or indicates the status during a program update.
Power-Up - The LED blinks while the SC-EQ is ini­tializing and perfroming self checks.
Normal Operation - The LED should normally be OFF.
Firmware Update - The LED blinks at a 100 ms cycle
while the Firmware is updating.
Unable to Load Firmware - The LED blinks at a 500ms cycle to indicate that the SC-EQ could not load a firmware update. Try loading the firmware update on to another USB thumb drive and perform the update again.
Firmware Validation Failure - The LED blinks at a 1 second cycle whenever the SC-EQ fails to validate the firmware at intial power up or after a firmware up­grade. Try cycling power to the SC-EQ and updating the firmware again.
Firmware Programming Required - The LED is ON solid indicating no firmware is present. A firmware up­date should be performed to remedy this.

MULTIMETER CHECKS OF THE BAS PORT

If the SC-EQ board is connected to a BAS bus but the BS BUS LED is off steady then the SC-EQ board is not likely seeing any valid communications occurring on the BAS bus. Simple voltage measurements with a DC voltmeter can be made on the SC-EQ board and BAS communication bus to help diagnose the problem.
1. Remove the BAS plug from the SC-EQ J12.
2. Note the position of the BAS End Of Line (EOL) Switch S2. (If the SC-EQ is not the EOL device, the EOL switch must be OFF) If it is the EOL then set the EOL to ON temporarily for these tests.
3. Measure the voltage between the + and – pins on the BAS Bus Terminal Block as shown in the top portion of Figure 39 on page 35. The positive lead of the voltmeter should be on the + pin of the block and the negative lead of the voltmeter on the – pin of the block. The voltage reading can fall in the range of (0.38 VDC to 0.47 VDC). The reading should be steady and only changing by a couple of millivolts at the most. If the reading is within the range of (+0.38 VDC to +0.47 VDC) that is an indication that the BAS transceiver on the SC-EQ board is not damaged. If the volt­age reading is out of the range given by a large amount, the transceiver or its associated circuitry may be damaged. Again verify that switch S2
(BAS EOL) is in the “ON” position during the measurement otherwise the voltage readings are out of the given range.
4. If the reading in step 3 is within the given voltage range then return switch S2 (BAS EOL) to its prop­er position and connect the BAS terminal block plug back into the BAS terminal block J12 on the SC-EQ board. Take another VDC voltage reading now on the BAS plug between the + and –wire con­nections as shown in the bottom portion of Figure 39 on page 35. If the BAS bus is connected to a JCI BAS bus with proper EOL terminations set then the voltage range should be steady and in the (0.38 VDC to 0.47 VDC) voltage range if NO
34
JOHNSON CONTROLS
Page 35
FORM 450.50-N1 ISSUE DATE: 08/19/2019
SECTION 3 - TROUBLESHOOTING
communications are occurring on the BAS bus. If the voltage reading is steady but out of the (0.38 VDC to 0.47 VDC) voltage range then the issue could be improper EOL terminations, issues with wiring or some other issue. If the BAS trunk is connected to a third party BAS then the voltage readings could be acceptable anywhere between (0.25 VDC to 0.5 VDC).
5. If communications are occurring onthe BAS Bus then the voltage measured in step 4 should uc­tuate generally in the range of (0.1 VDC to 0.5 VDC) if the bus is properly terminated. The volt­age readings may vary somewhat out of this range depending on bus loading and the type of voltme-
ter used. If the voltage readings are uctuating in
the approximate range of (1.5 VDC to 3.5 VDC) then it is likely there is no End of Line (EOL) ter­mination set on the bus and that should be cor­rected at the EOL device.
-
COM
+
BAS Bus Terminal Block
SHLD

UPDATING THE FIRMWARE AND THE SOFTWARE

As new chiller data maps become available, it is neces­sary to update the SC-EQ firmware and software. The following procedure should be followed to perform a firmware and software update.
3
Updating the Firmware
To update the firmware, complete the following steps:
1. Format the USB thumb drive to FAT32.
2. Copy the current rmware.pkg from the CHASE site.
There cannot be other les on the
USB thumb drive.
3. Download the current rmware.pkg le. If the chiller is running, put it in the local mode, so the SC-EQ does not affect the chiller operation dur-
ing the rmware update.
-
-
COM
SH
LD

FIGURE 39 - BAS BUS METER CHECKS

+
V
+
V
BAS Bus Terminal Block
-
+
Plug
The meter checks detailed for the BAS port can also be used for the CS and EQ ports.
LD19997
4. Insert the USB thumb drive into the J3 port on
the SC-EQ board. The rmware update starts au­tomatically and the fault LED ashes quickly dur-
ing the update process.
5. If it does not start automatically, cycle power to the SC-EQ board by removing and reconnecting the power plug on the SC-EQ board.
6. When rmware update is completed, the SC-EQ reboots. All LEDs go out and then on again. A typical update takes more than 5 min.
7. When the SC-EQ Fault LED is off for 30 s, the
rmware upgrade is complete. The USB thumb
drive can be removed.
JOHNSON CONTROLS
35
Page 36
SECTION 3 - TROUBLESHOOTING
Updating the Software
To update the software, complete the following steps:
FORM 450.50-N1
ISSUE DATE: 08/19/2019
1. Format the USB thumb drive to FAT32.
2. Copy the current software.pkg le on a USB thumb drive.
There cannot be other les on the
USB thumb drive.
3. Download the current software.pkg le. If the chiller is running, put it in the local mode, so the SC-EQ does not affect the chiller operation during the software update.
4. Insert the USB thumb drive into the J3 port on the SC-EQ board. The software update starts au­tomatically and the fault LED ashes quickly dur­ing the update process.
5. If it does not start automatically, cycle power to the SC-EQ board by removing and reconnecting the power plug on the SC-EQ board.
6. When the software update is completed, the SC­EQ reboots. All LEDs go out and then on again. A typical update takes more than 5 minutes.
7. When the SC-EQ Fault LED is off for 30 s, the
rmware upgrade is complete. The USB thumb
drive may can removed.

REPAIR INFORMATION

There are no user replaceable parts in the SC-EQ. If the SC-EQ Comm Card fails to operate within its speci­fications, replace the unit. For a replacement SC-EQ Comm Card, contact the nearest Johnson Controls rep­resentative.
36
JOHNSON CONTROLS
Page 37
FORM 450.50-N1
LD20431
LD20433
ISSUE DATE: 08/19/2019

SECTION 4 - SC-AP GATEWAY

SC-AP OPTIVIEW MOUNTING

The SC-AP Installation Kit (p/n 331-03608-000) contains all of the materials needed to install the SC­AP into the OptiView chiller control panel using a DIN rail in new panels or velcro for older panels.
OptiView DIN Rail Panel Mount
1. New production panels have 3" piece of DIN rail installed to mount the SC-AP. The SC-AP instal­lation kit contains two DIN rail end blocks to hold the SC-AP in place on the DIN rail.
2. Install one end block (p/n 025-29189-000) to the back end of the DIN rail, as shown in Figure 40 on page 37.
3. Pull the SC-AP case bottom mounting bracket clip outwards from the case.
4. Hang the SC-AP on the DIN rail and push the bot­tom mounting bracket clip upwards to secure the SC-AP to the DIN rail.
5. Install the second Din rail end block (p/n 025­29189-000) to the front end of the DIN rail, as shown in Figure 41 on page 37.
OptiView Velcro Panel Mount
1. On older panels that do not have a DIN rail mount­ed, the SC-AP should be mounted using the velcro
parts of the Installation Kit.

FIGURE 40 - DIN RAIL END BLOCK

FIGURE 41 - SC-AP MOUNTED

4
LD20432
2. Install the four round velcro fasteners (p/n 025­47586-000) to the four mounting holes on the back of the mounting bracket using four screws (p/n 021-34098-000), as shown in Figure 42 on page 37.
3. Stick one of the four square velcro pieces (p/n 025-47587-000) on to each of the four round vel­cro fasteners.
4. Remove the protective backing from the square velcro pieces, and carefully stick the SC-AP in the desired mounting location.
JOHNSON CONTROLS

FIGURE 42 - SC-AP VELCRO PADS

37
Page 38
SECTION 4 - SC-AP GATEWAY
DIN RAIL & Velco Panel Mount (Cont'd)
5. Install one ty-wrap mount (p/n 025-25155-000) above the ribbon cables and one below to retain the coiled cable using two ty-wraps (p/n 025­18167-000), as shown in Figure 44 on page 38.
6. Install the coiled SC-AP cable by plugging one end into the SC-EQ CS RJ Port J1 and the oth­er end into the SC-AP 6-pin RJ-12 connector. Caution: Do not plug the SC-AP cable in to the SC-EQ BAS RJ jack as this exposes the wrong equipment to the SC-AP.
7. Install the two ty-wraps in the ty-wrap mounts to hold the coiled cable, loosely tighten the ty-wrap and trim off the excess ty-wrap ends.
8. The installed SC-AP and SC-EQ should look sim­ilar to Figure 45 on page 38
FORM 450.50-N1
ISSUE DATE: 08/19/2019
LD20434

FIGURE 44 - SC-AP CABLE TY-WRAPS

FIGURE 43 - SC-EQ TO SC-AP CABLE

38
LD21043
LD20435

FIGURE 45 - SC-AP & SC-EQ INSTALLED

JOHNSON CONTROLS
Page 39
FORM 450.50-N1 ISSUE DATE: 08/19/2019

USING THE SC-AP FOR TROUBLESHOOTING

SECTION 4 - SC-AP GATEWAY
The SC-AP is a device that interfaces with Johnson Controls Connected Chillers service. This device can also be used to troubleshoot connectivity issues.
If an SC-AP is installed as part of a Connected Servic­es installation, or if an SC-AP is available otherwise, connecting it to the SC-EQ allows the technician to view the port activity to aid in communication prob­lem diagnosis. It is also required to manually set the Chiller Model on older YorkTalk2 chillers that do not auto-discover. Refer to page 34 for instructions on how to manually set the chiller model. For more detailed information on the SC-AP refer to SC-AP Installation
Instructions (Lit 24-10737-75) and SC-AP Quick Start (Lit 24-10737-75).
The first screen displayed on the SC-AP after login is the Device List screen, as shown in Figure 46 on page 39). The example shows two devices, the SC­AP, and the SC-EQ, as well as their MAC address. The
SC-AP is always MAC address three. In the example below, the SC-EQ has MAC address four. The Device List can be used to help troubleshoot issues where the BAS is not connecting to the SC-EQ.
Selecting the SC-EQ Data tab displays the data for the SC-EQ. Four of the parameters in the SC-EQ Data tab display the three communication port settings and the Online/Offline status of the ports. Refer to Figure 47 on page 39.
The SC-EQ Port Status shows that the Equipment Port is communicating using YorkTalk 3 and the BAS is Modbus. The CS port is always BACnet MSTP. If ei­ther the BAS or the EQ port are not active for a short period of time, the status is displayed as "Offline." If the communications is not present for a few minutes, the status is displayed as "No Protocol." The SC-EQ continually tries to connect to the absent ports.
4

FIGURE 46 - SC-AP DEVICE LIST

FIGURE 47 - SC-EQ PORT STATUS AND LOCK IN

JOHNSON CONTROLS
LD19990
LD29237
39
Page 40
SECTION 4 - SC-AP GATEWAY
LD29329
LD29330
To Change the Device Instance
The SC-EQ automatically creates the Device Instance as 5000 plus the MAC Address switch setting. For ex­ample, if the MAC address DIP switches are set to a value of 6, the Device Instance is 5006. Some custom­ers require the Device Instance to be something other than the automatically generated 5000 series address. The SC-AP can be used to change the Device Instance to the customer desired address. Connect the SC-AP to the SC-EQ and log on to the SC-AP using a WiFi interface either from a Smartphone, a Laptop or Tablet PC. Refer to SC-AP Installation (Lit 24-10737-75) and SC-AP Quick Start (Lit 24-10737-87) for more infor­mation on the SC-AP.
Note that any MAP 4.0 device may be used to connect to the SC-EQ to change the Device Instance and to also look at the communication port status. It is not able to communicate with the Cloud though. When you first click on a MAP 4.0 device, the Home page loads and displays a "spinner" that never stops since it is looking to connect to a Simplicity SE or a RTU controller and can not find them. The user must just proceed to click on a menu item on the left-hand side to view informa­tion.
The MAP1810 device uses two MAC address of 2. So a temporary change of the SC-EQ mac/node address 2 allows a CS port port mac/node# change as shown in Figure 48. The virtual MAC address is separate from BMS. When it finishes, the address can return to 2.
1. Select the SC-EQ Device then select the SC-EQ Data tab.
FORM 450.50-N1
ISSUE DATE: 08/19/2019

FIGURE 49 - DEVICE INSTANCE MODE

3. Next, select the SC-EQUIP BACNET INSTANCE ID and change it to the desired value. (Must be a number from 1 to 4914302).
LD19998

E-LINK REPLACEMENT

In BACnet autodiscovery, the E-Link transferred a list of all possible chiller parameters to the BAS. Even ones that did not apply. For example, if you had an Electro-Mechanical starter, the parameters for a VSD starter were shared by the E-Link and auto-discovered by the BAS. The SC-EQ discovers what type of chiller is connected and the chiller features and then exposes only the relevant points to the BAS. If an E-Link is replaced by an SC-EQ, the BAS shows the points that were non relevant previously as Offline. To resolve this you either need to delete the E-Link and re-discover the SC-EQ or delete each of the inappropriate Offline points.

FIGURE 48 - SC-AP DEVICE LIST

A list of parameters is shown on the right side of your WiFi Smartphone or PC screen.
2. Select the BACNET DEVICE INSTANCE MODE and change it from AUTO to MANUAL. Then select SAVE.
40

FIGURE 50 - INVALID POINTS OFFLINE

LD19994
BAS Commands
Points that are commandable show as Unreliable until the BAS sends the setpoints.
LD19993

FIGURE 51 - UNRELIABLE REMOTE SETPOINTS

JOHNSON CONTROLS
Page 41
FORM 450.50-N1 ISSUE DATE: 08/19/2019

MANUALLY SETTING THE CHILLER MODEL

Some of the older YorkTalk2 chillers do not have pro­gramming in place to tell the SC-EQ their chiller mod­el. In these instances, a SC-AP needs to be used to tell the SC-EQ what chiller is present.
On the SC-AP SC-EQUIP DATA screen, when the Auto Detected Chiller Protocol is displayed as YorkTalk2
SECTION 4 - SC-AP GATEWAY
but the Auto Detected Chiller Model is NONE, an ad­ditional field is displayed named MANUALLY SE­LECTED CHILLER MODE. See Figure 52 on page
41. Clicking on this field allows the user to select the chiller model that the SC-EQ is connected to. See Figure 53 on page 41. Field 46 allows manual EQ Port starting point after a power loss.
4

FIGURE 52 - NO CHILLER MODEL TYPE DETECTED

LD29331

FIGURE 53 - MANUALLY SELECTING CHILLER MODEL

JOHNSON CONTROLS
LD21042
41
Page 42
FORM 450.50-N1
ISSUE DATE: 08/19/2019
THIS PAGE INTENTIONALLY LEFT BLANK.
42
JOHNSON CONTROLS
Page 43
FORM 450.50-N1 ISSUE DATE: 08/19/2019

SECTION 5 - TECHNICAL SPECIFICATIONS

TABLE 8 - TECHNICAL SPECIFICATIONS

External to Equipment (Inside Enclosure): 120/240 VAC Primary 50/60 Hz, 24
Power Requirements
Addressing
Installation Environment Protected, Dry
Ambient Operating Conditions Temperature: -40 to 65°C; (-40 to 149°F) Humidity: 0% to 95% Noncondensing
Ambient Storage Conditions Temperature: -40 to 85°C (-40 to 185°F) Humidity: 0 to 95% RH, Noncondensing
Power
Communication Wiring Terminations
Wiring
Materials
Mounting
Dimensions
Shipping Weight
Compliance United States UL Listed 916/FCC Part 15 Conducted and Radiated
Europe
BTL B-ASC (BTL-24317)
VAC Secondary Transformer (+10%/-15%), 400 mA, Nominal 12 VA Internal to Equipment SC-EQ Comm Card Assembly: 24 VAC (±15%), 50/60 Hz, 400 mA, Nominal 12 VA, 12 VDC (+50%/-2%), 400 mA, Nominal 12 VA
Addressing is selectable by the MAC Address Switch – 8 Position DIP Switch using Switches 1 through 7.
• BACnet MS/TP Addressing Range 1 to 127
• Modbus RTU Addressing Range 1 to 127
• N2 Addressing Range1 to 127
External to Equipment (Inside Enclosure): One 3-Position Terminal Block for 120/240 VAC Supply Power Internal to Equipment SC-EQ Comm Card Assembly: Removable Terminal Plug for 24 VAC Supply Power and Removable Terminal Plug for 12 VDC Supply Power
BAS Protocol is automatically detected BAS Port J12: RS-485 BAS Port Supporting BACnet MS/TP, Modbus RTU and
N2 Protocols With Available EOL Termination Switch
Equipment Protocol and Model are automatically detected EQ 485 Port J8: RS-485 Equipment Port Supporting BACnet MS/TP and YORK
Talk II Protocols with Available EOL Termination Switch EQ 232 Port J7: RS-232 Equipment Port Supporting YORK Talk 3 Protocol
Connected Services CS Port J11: RS-485 BAS Port Supporting BACnet MS/TP Protocol With
Available EOL Termination Switch
Network Cable: 0.51 mm (24 AWG) (3 Cores Plus Shield) Power Cable: 1.02 mm (18 AWG) Copper Wire Rated for 10 Amperes Per Core at
250 VAC
External to Equipment:
Metal Enclosure with Removable Lid, SC-EQ Comm Card Assembly, Power Transformer
Internal to Equipment E-Link Board Assembly: SC-EQ Comm Card Assembly
External to Equipment: Screw Mount Enclosure Internal to Equipment: SC-EQ OptiView/Latitude and IPU-II installation kit
External to Equipment: 241.3 x 136.5 x 63 mm (9 1/2 x 5 3/8 x 2 1/2 in.) Internal to Equipment: 102 x 152 x 25.4 mm (4 x 6 x 1 in.)
External to Equipment: 2 kg (4.5 lb) Internal to Equipment: 227 g (8 oz)
CE Mark - Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.
5
NOTE: The performance specications are nominal and conform to acceptable industry standards. for application of conditions beyond these specications, consult the local Johnson Controls ofce. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
JOHNSON CONTROLS
43
Page 44
FORM 450.50-N1
ISSUE DATE: 08/19/2019
THIS PAGE INTENTIONALLY LEFT BLANK.
44
JOHNSON CONTROLS
Page 45
FORM 450.50-N1
LD29256
ISSUE DATE: 08/19/2019

OVERVIEW

SECTION 6 - LON PROTONODE

The LON ProtoNode in conjunction with the SC-EQ communication interface card provides YORK® chill­ers LON network connectivity. It is designed with two active serial ports:
• A LON port, which is used to connect to a LON FTT10 network.
• An RS485 port, which connects to the BACnet MS/TP BAS port J12 on the SC-EQ.
The ProtoNode also contains an Ethernet port that can be used for troubleshooting or to update the ProtoNode firmware, if needed.
To simplify the installation and setup, the LON Proto­Node comes preconfigured. The switches and internal jumpers are preset at the factory for the correct node ID, baud rate, and configuration file type. There are no user switch settings required in the field. The Proto­Node polls the SC-EQ and chiller micro board to deter­mine what model chiller and what points are available.
LONWORKS
SERVICE PIN
This is based upon the options installed and configu­ration of the chiller. The ProtoNode then dynamically creates the LON points list. One ProtoNode part num­ber covers all the various chiller models.
If a firmware update is needed, the user can add the new ProtoNode firmware through the Ethernet port. A LON interface file named fserver.xif is also available from this port. The .xif file allows the LON Integra­tor to engineer and bind the chiller points offline. This file is automatically generated based upon the chiller model and options installed.
The LON ProtoNode consists of a single module mounted inside the chiller control panel. In most cases, the chiller control panel supplies 24 VAC input power, eliminating the need for an external power supply.
For YS OptiView panels, 24 VAC is not provided. For YS OptiView panels the +12 VDC power to the SC-EQ board is extended to the ProtoNode.
6
ETHERNET
PORT

FIGURE 54 - LON PROTONODE FRONT VIEW

JOHNSON CONTROLS
RS-485 24 VAC
POWER
45
Page 46
SECTION 6 - LON PROTONODE
LD29257
WASHER
OPTIVIEW

INSTALLATION

FORM 450.50-N1
ISSUE DATE: 08/19/2019
The LON ProtoNode can be installed directly into the chiller control panel of indoor and outdoor chillers. The ambient operating range is -40°F to 167°F, 5% to 90% RH Non-Condensing. An accessory mounting kit, P/N 371-06580-000, is used to mount the LON Proto­Node directly into the chiller control panel.
TABLE 9 - LON PROTONODE PRODUCT CODE
NUMBERS
DESCRIPTION PART NUMBER
LON ProtoNode 025-46015-000
OptiView Panel Installation Kit 371-06580-000
Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize the equipment. Contact with components carrying hazardous voltage can cause electric shock and result in severe per­sonal injury or death.
Make all wiring connections in accor­dance with local, national, and regional regulations. Install the wiring, so it does not cause a hazard and is protected against electrical and mechanical dam­age.
To install the ProtoNode into the chiller control panel, complete the following steps:
1. All switch and jumper settings must remain at the factory settings shown in Table 10 and Table 11. The unit ships with a label covering the externally accessible switches. This label indicates the set­tings shown below. No user settings are required for any of the switches or jumpers and the default settings are included only for informational pur­poses.

TABLE 10 - JUMPER SETTINGS

Bias OFF
Termination OFF
A B Pin 1 and Pin 2
2. Attach the LON ProtoNode to the location shown in Figure 55 using the adhesive fasteners, P/N 025-47587-000, included in the installation kit.
MICROPANEL
FIGURE 55 - OPTIVIEW LON PROTONODE
MOUNTING LOCATION
3. Connect the LON ProtoNode to the BAS port J12 on the SC-EQ using the communications cable, P/N 571-06580-402, included in the installation kit. Connect the wires as shown in Figure 56. Trim the cable to the required length.

TABLE 11 - SWITCH SETTINGS

A0 A1 A2 A3 A4 A5 A6 A7 B0 B1 B2 B3 S0 S1 S2 S3
ON ON OFF OFF OFF OFF OFF OFF ON ON OFF ON OFF OFF OFF OFF
46
JOHNSON CONTROLS
Page 47
FORM 450.50-N1
PROTONODE
LD29258
LD29259
PWR+ PWR-
ISSUE DATE: 08/19/2019
WHITE
BLACK
RED

FIGURE 56 - PROTONODE TO SC-EQ RS485 WIRING

SECTION 6 - LON PROTONODE
SC-EQ
6
4. For all OptiView panels (except on YS chillers), complete the following steps:
1. Connect the power harness from the + PWR and – PWR terminals on the JCI LON Proto­Node to the locations as shown in Table 12. The power harness, P/N 571-06580-401, is included in the installation kit.
2. Connect the Frame GND on the ProtoNode to a ground using the green/yellow wire, P/N 571-06580-403, included in the installation kit.
3. Trim each of the cables to the required length.
4. Secure the power and communication cables using wire ties and adhesive mounts provid­ed in the installation kit.

TABLE 12 - POWER CONNECTIONS

CHILLER MODEL PWR+ PWR-
YK OptiView TB6-162 TB6-5
YZ OptiView TB7-162 TB7-5
YMC2 OptiView TB7-162 TB7-5
YD OptiView TB6-118 TB6-5
YKEP OptiView TB6-118 TB6-5
YT OptiView TB1-162 TB6-5
YR OptiView TB1-162 TB6-5
YST OptiView TB7-321 TB7-322
For YS OptiView panels, complete the following steps:
1. Remove the power cable installed between the micro board and the SC-EQ board.
2. Install the cable, P/N 571-08936-001, as fol­lows:
• connect P21 to J21 on the micro board
• connect P9 to J9 on the SC-EQ board
• connect the wire end to the ProtoNode (red wire to PWR+, black wire to PWR-)
3. Trim the cable to the required length at the ProtoNode end, if needed.
4. Install the Frame GND wire as described previously in step 4.
JOHNSON CONTROLS
GND

FIGURE 57 - PROTONODE POWER WIRING

47
Page 48
SECTION 6 - LON PROTONODE
LD29260
LD29262
5. Connect the ProtoNode to the LON FTT10 net­work using the non-shielded twisted pair network cable. There is no polarity on the LON FTT10 network, so you can connect either wire to either terminal.
FORM 450.50-N1
ISSUE DATE: 08/19/2019
SERVICE
PIN
LD29261
FIGURE 59 - PROTONODE SERVICE PIN (COVER
REMOVED)
NETWORK
CONNECTION
FIGURE 58 - PROTONODE LON NETWORK
CONNECTION
6. To discover the ProtoNode automatically, com­plete the following steps:
1. Power up the chiller panel and the Proto­Node.
2. Insert a small screwdriver into the Service Pin hole.
3. Tilt the screwdriver towards the LonWorks connector to depress the Service Pin switch. The Service Pin switch faces towards the LON port connector as shown in Figure 59.
7. Use the unique 12 character LON Neuron ID in lieu of the service pin to bind the ProtoNode to the network. The ID address is printed on a label on the back of the ProtoNode.
FIGURE 60 - PROTONODE NEURON ID
48
JOHNSON CONTROLS
Page 49
FORM 450.50-N1
LD29263
ISSUE DATE: 08/19/2019

PROTONODE LED FUNCTIONALITY

The ProtoNode LEDs indicate functionality as shown in.
DIAGNOSTIC LEDS

FIGURE 61 - PROTONODE POWER WIRING

SECTION 6 - LON PROTONODE
6

TABLE 13 - DIAGNOSTIC LEDS

TAG DESCRIPTION
SPL
RUN The RUN LED starts ashing 20 seconds after the power indicates normal operation.
ERR
RX
TX
PWR THE PWR LED is the power light and shows steady green at all times when the unit is powered.
The SPL LED lights up if the unit is not getting a response from one or more of the congured devices.
For LonWorks units, LED lights up until the unit is commissioned on the LonWorks network.
The SYS ERR LED lights up 15 seconds after powering up. It turns off after 5 seconds. A steady red light indicates if there is a system error on the unit. If this occurs, immediately report the related system error shown in the error screen of the GUI to support for evaluation.
If the socket protocol is serial, the RX LED ashes when the host port receives a message.
If the socket protocol is Ethernet, the RX LED is not used.
If the socket protocol is serial, the TX LED ashes when a message is sent on the host port.
If the socket protocol is Ethernet, the TX LED is not used.

BINDING THE POINTS USING THE .XIF FILE

If you want to bind the points using the .XIF file, complete the following steps the retrieve it from the ProtoNode:
1. Connect a CAT 5 Ethernet cable (Straight-Thru or Cross-Over) from the PC to the ProtoNode.
3. Set the PC to a static IP address 192.168.1.11, Subnet Mask 255.255.255.0.
4. Open the Internet Browser and navigate to the Pro-
toNode address for the .xif le: 192.168.1.24/ fserver.xif.
2. Turn off the Wi-Fi on the PC, so it does not try to connect to a network.
JOHNSON CONTROLS
5. Save the .xif le to the PC.
49
Page 50
SECTION 6 - LON PROTONODE

TECHNICAL SPECIFICATIONS

TABLE 14 - TECHNICAL SPECIFICATIONS

Electrical Connections
Approvals
Power Requirements 9VDC to 30 VDC or 12 VAC to 24 VAC
Physical Dimensions
(Lenght x Width x Height)
Weight 0.2 kg (0.4 lb)
Operating Temperature 40°C to 75°C (-40°F to 167°F)
Surge Supression EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity 5% to 90% RH (non-condensing)
Note: Specications subject to change without notice.
One 6-pin Phoenix connector, one RS-485 +/- ground port, power +/- frame ground port One Ethernet 10/100 BaseT port, One FTT-10 LonWorks port
CE Certied; TUV approved to UL 916, EN 60950-1, EN 50491-3 and CSA C22-2 standards;
FCC Class A Part 15; DNP3 Conformance Tested; RoHS Compliant; CSA 205 Approved
LonMark Certied
11.5 cm x 8.3 cm x 4.1 cm (4.5 in. x 3.2 in. x 1.6 in.)
FORM 450.50-N1
ISSUE DATE: 08/19/2019
50
JOHNSON CONTROLS
Page 51
FORM 450.50-N1 ISSUE DATE: 08/19/2019
NOTE: The information below can be shared with the technician responsible for the BAS network.
INSTRUCTIONS FOR THE BAS CONTRACTOR
The SC-EQ Communication Card has the ability to au­tomatically determine the BAS network protocol and communication parameters and set its communication parameters to match the installed BAS system.
If the chiller was already commissioned, there is no need for a chiller technician to return to the site to con­nect the BAS wiring and set the MAC address since these are standard tasks that a BAS contractor routinely performs.
The instructions on this page assist you with these steps.
BAS Wiring Connections
The BAS port J12 is the blue pluggable connector shown below. It is an RS-485 port with + - COM and SHLD marked. The SHLD (shield) terminal is not con­nected to any circuitry or ground and provides a con­venient location to connect the shields of two daisy­chained segments. On some BAS systems the COM is called REF.
Setting the MAC Address
The SC-EQ Communication Card Media Access Con­trol (MAC) network hardware address is set on a single 8-way DIP switch. Switch 8 is not used. The switches are binary weighted allowing the setting of addresses from 1 to 127.
Once the DIP switches are set for the correct MAC ad­dress, cycle the power to the SC-EQ by momentari­ly unplugging the 24 VAC or +12 VDC power plug (depending upon how the SC-EQ is being powered). The SC-EQ Communication Card then boots up and establish communications. This may take up to 120 s.
JOHNSON CONTROLS
51
Page 52
5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 1-800-524-1330 Subject to change without notice. Printed in USA Copyright © by Johnson Controls 2019 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 450.50-N1 (819) Issue Date: August 19, 2019 Supersedes: 450.50-N1 (1117)
Loading...