Post start check list ....................................................20
Shut down ..................................................................21
Installation, Operation and Maintenance Manual : 036-1011(0806)
Page 2
GENERAL
RENEWAL PARTS
YORK Saber units are single package air conditioners
equipped with optional factory installed electric heaters and
designed for outdoor installation on a rooftop or steel
structure.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and
electrical wiring is factory installed and tested. The units
require electric power, duct connections and drain piping
connections at the point of installation.
The supplemental electric heaters have nickel-chrome
elements and utilize single point power connection.
SAFETY CONSIDERATIONS
Due to system pressure, moving parts and electrical
components, installation and servicing of air conditioning
equipment can be hazardous. Only qualified, trained, service
personnel should install, repair, maintain or service this
equipment.
Observe all precautions in the literature, on labels and tags
accompanying the equipment whenever working on air
conditioning equipment. Be sure to follow all other safety
precautions that apply.
Wear safety glasses and work gloves, and follow all safety
codes. Use a quenching cloth and have a fire extinguisher
available for all brazing operations.
INSPECTION
Refer to York USER’S MAINTENANCE and SERVICE
INFORMATION MANUAL. It is strongly suggested that only
genuine YORK Spare Parts are used to ensure efficient
working of the unit and safety.
CAUTION
THIS PRODUCT MUST BE INST ALLED IN STRICT COMPLIANCE
WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND
ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES
INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL,
AND MECHANICAL CODES.
WARNING
IMPROPER INSTALLATION MAY CREATE A CONDITION
WHERE THE OPERATION OF THE PRODUCT COULD CAUSE
PERSONAL INJURY OR PROPERTY DAMAGE.
Installer should pay particular attention to the words :
NOTE, CAUTION and WARNING.
NOTES are intended to clarify or make the installation easier.
CAUTIONS are given to prevent equipment damage.
WARNINGS are given to alert installer that personal injury
and/or equipment damage may result if installation
procedure is not handled properly.
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident, the
extent of the damage should be noted on the carrier’s freight
bill.
TYPICAL UNIT CONFIGURATION
FIGURE 1 : TYPICAL UNIT CONFIGURATION
Installation, Operation and Maintenance Manual : 036-1011(0806)
Page 3
NOMENCLATURE
INSTALLATION
Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and
cooling unit. The installer must assure that these instructions
are made available to the consumer and with instructions to
retain them for future reference.
Installation, Operation and Maintenance Manual : 036-1011(0806)
LIMITATIONS
These units must be installed in accordance with the
applicable national and local safety codes. (Refer to Unit
Application Data table).
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or the customer’s
expense. Size of unit for proposed installation should be
based on heat loss/heat gain calculation.
TABLE 1 : UNIT APPLICATION DATA
Page 4
LOCATION
Use the following guidelines to select a suitable location for
these units :
1. Unit are designed for outdoor installation only.
WARNING
BEFORE LIFTING A UNIT, MAKE SURE THAT ALL PANELS ARE
IN PLACE AND THAT ITS WEIGHT IS DISTRIBUTED EQUALLY
ON ALL CABLES SO IT WILL LIFT EVENLY.
2. Condenser coils must have an unlimited supply of air.
3. Where a choice of location is possible, position the unit
on either north or east side of building.
4. For ground level installation, use a level concrete slab.
The length and width should be at least 6 inches greater
than the unit base rails. Do not tie slab to the building
foundation.
5. Roof structures must be able to support the weight of the
unit and its options and/or accessories. Unit must be
installed on a solid level roof curb.
6. Maintain level tolerance to 1/2 inch maximum across the
entire length or width of the unit.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the round lifting
holes provided in the base rails. Spreaders, whose length
exceeds the largest dimension across the unit, MUST BE
USED. Refer to Figure 2. Units may also be moved or lifted
with a forklift, from the side only, provided that an accessory
skid is used.
CLEARANCES
All units require certain clearances for proper operation and
service. Installer must make provisions for adequate
ventilation air in accordance with applicable provisions of the
local building codes. Refer to Dimensions and Clearances.
Refer Figure 8 for the clearances required for servicing, and
proper unit operation.
WARNING
DO NOT PERMIT OVERHANGING STRUCTURES OR SHRUBS
TO OBSTRUCT OUTDOOR AIR DISCHARGE OUTLET.
DUCTWORK
A closed return duct system should be used. This should not
preclude use of outdoor fresh air intake.
The supply and return air duct connections at the unit should
be made with flexible joints to minimize noise. The supply
and return air duct systems should be designed for the CFM
and static requirements of the job. They should NOT be
sized to match the dimensions of the duct connections on the
unit.
LENGTH OF FORKS MUST BE A MINIMUM OF 90”. Refer
to the Product Data Table 5 for unit weights.
WARNING
WHEN FASTENING DUCTWORK TO SIDE DUCT FLANGES ON
UNIT, INSERT SCREWS THROUGH DUCT FLANGES ONLY. DO
NOT INSERT SCREWS THROUGH CASING. OUTDOOR
DUCTWORK MUST BE INSULATED AND WATERPROOFED.
Refer to Dimensions and Clearances Figure 7 for information
concerning supply and return air duct openings.
FIXED OUTDOOR AIR INTAKE DAMPER
This damper is shipped inside the return air compartment. It
is completely assembled and ready for installation. Refer to
the Fixed Outdoor Damper Figure 3.
Gasketing and mounting screws are provided in a parts bag.
Adjusting the damper to the desired air flow may be done
after installation by opening or closing dampers with handle.
Damper provides maximum of 25% fresh air when fully
opened.
FIGURE 2 : TYPICAL RIGGING
Installation, Operation and Maintenance Manual : 036-1011(0806)
Page 5
FIGURE 3 : FIXED OUTDOOR AIR DAMPER
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a
sealing compound on male pipe threads.
Install a condensate drain line from the
one-inch FPT female connection on the unit to
an open drain.
NOTE : The condensate drain operates in a
negative pressure in the cabinet. The
condensate drain line MUST be trapped to
provide proper drainage. See Figure 4.
FIGURE 4 : RECOMMENDED DRAIN PIPING
FIGURE 5 : LOADING POINTS
Installation, Operation and Maintenance Manual : 036-1011(0806)
Page 6
COMPRESSORS
Units are shipped with factory adjusted compressor
mountings and ready for operation.
the tabulated rating, with a short circuit capacity of 10K or
more, for the unit. The switch must be separate from all other
circuits. Wire entry at knockout openings require conduit
fittings to comply with local codes. Refer to the Dimensions
and Clearances Figure 7 for installation location.
CAUTION
DO NOT LOOSEN COMPRESSOR MOUNTING BOLTS.
REMOVE COMPRESSOR SHIPPING BRACKETS BEFORE
START-UP.
FILTERS
Two inch filters can be supplied with each unit. Filters must
always be installed ahead of the evaporator coil and must be
kept clean or replaced with same size and type. Dirty filters
will reduce the capacity of the unit and will result in frosted
coils or safety shutdown. Minimum filter area and required
sizes are shown in Product Data Table 4.
SERVICE ACCESS
The following removable panels provide access to all
serviceable components :
• Compressor compartment
• Electric Heat compartment
• Blower compartment
• Main control box
• Filter compartment
Refer to the Dimensions and Clearances Figure 7 for
location of these access panels.
If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram and the same minimum gauge as the replaced wire.
Electrical line must be sized properly to carry the load. Use
copper conductors only. Each unit must be wired with a
separate branch circuit fed directly from the meter panel and
properly fused.
Emergency stop button should be field installed as per wiring
diagram. The activator should be red in colour with a yellow
outline background, and should be easily accessible. The
device should be self latching type and contacts must be of
positive opening operation, certified to EN60947 - 5 - 1.
CAUTION
WHEN CONNECTING ELECTRICAL POWER AND CONTROL
WIRING TO THE UNIT, WATERPROOF TYPE CONNECTORS
MUST BE USED SO THAT WATER OR MOISTURE CANNOT BE
DRAWN INTO THE UNIT DURING NORMAL OPERATION. THE
ABOVE WATERPROOFING CONDITIONS WILL ALSO APPLY
WHEN INSTALLING A FIELD SUPPLIED DISCONNECT SWITCH.
Refer to Typical Wiring Diagram, Figure 7 and to the
appropriate unit wiring diagram for control circuit and power
wiring information.
THERMOSTAT
4 Stage Cooling
The room thermostat should be located on an inside wall
approximately 56 inches above the floor where it will not be
subject to drafts, sun exposure or heat from electrical
fixtures or appliances. Follow manufacturers instructions
enclosed with thermostat for general installation procedure.
A minimum of seven color coded insulated wires (#18 AWG)
should be used to connect thermostat to unit.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the
National Electrical Code and/or local ordinances. The unit
must be electrically grounded in accordance with NEC
and/or local codes.
Voltage tolerances, which must be maintained at the
compressor terminals, during starting and running
conditions, are indicated on the unit Rating Plate and the
Unit Application Data table.
A fused disconnect switch should be field provided based on
TABLE 2 : CONTROL WIRE SIZES
OPTIONAL ELECTRIC HEAT
The factory installed heaters are wired for single point power
supply. Power supply need only be brought into the single
point terminal block and thermostat wiring to the low voltage
terminal strip located in the upper portion of the unit control
box.
These heaters are located within the supply air chamber.
Refer to Figure 8 for access panel location. Fuses are
supplied by the factory. Refer to Table 3 for minimum CFM
limitations and to Table 5 for electrical data.
TABLE 3 : MINIMUM CFM LIMITATION
Installation, Operation and Maintenance Manual : 036-1011(0806)
Page 7
FIGURE 6 : TYPICAL FIELD WIRING SCHEMATIC
PHASING
YORK Saber units are properly phased at the factory . Check
for proper compressor rotation. If the blower or compressors
rotate in the wrong direction at start up, the electrical
connection to the unit is mis-phased. Change the incoming
line connection phasing to obtain proper rotation. (Scroll
compressors operate in only one direction. If the scroll is
drawing low amperage, has similar suction and discharge
pressures, or producing a high noise level, the scroll is
mis-phased).
CAUTION
SCROLL COMPRESSORS REQUIRE PROPER ROTATION TO
OPERATE CORRECTLY. UNITS ARE PROPERLY PHASED AT
THE FACTORY. DO NOT CHANGE THE INTERNAL WIRING TO
MAKE THE BLOWER, CONDENSER FANS, OR COMPRESSOR
ROTATE CORRECTLY.
Installation, Operation and Maintenance Manual : 036-1011(0806)
Page 8
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.