Johnson Controls YJHJXH018BARR-FX, YJHJYH018BARRA-X Service Manual

Page 1
SERVICE MANUAL
Wall mounted Type
Order No.
YJHJXH018BARR-FX
FREE MATCH EK
YJHJYH018BARRA-X
indoor unit and remote controller
Page 2
Table of Contents
T
able of Contents
1. Introduction ……………………………………………………………………..1
2. List of Functions ……………………………………………………......………5
3. Specifications …………………………………………………………………...6
4. Printed Circuit Board ConnectorWiring Diagram ………………………...8
5. Functions and Control ……………….....…………..…………….…..…......13
5.1 Main functions and control specifications of indoor unit…….…….………13
5.2 Main functions and control specifications of outdoor unit …………….….21
5.3 Value of Thermistor………………..…............………..……………...……..27
6. System Configuration ……………………….…………………….….………39
6.1 System Configuration……………………..……………………...……...….39
6.2 Instruction …………….…………………………………………..………….39
7.Installations …… 50
…………………………….………….……………………....
65
9. Removal Procedure……………………………..…….…………………...….80
9.1 Removal of Indoor Unit…………………………….………………………..80
9.2 The removal procedure of outdoor……….…….……………………….....92
10.Wiring Diagrams ……………………………….……………………………105
10.1 Indoor Unit …………………………………..……………………………105
10.2 Outdoor Unit ………………………….………………………………..…106
11.Circuit Diagrams …………………………….………………………………107
12.Description of Coding rules of Unit Model ………………….…………..110
8. Error Codes and Descirption..……….……………………………………...
YJHJZH018BARRAFX-SM
Page 3
I
ntroduction
Do
mestic Air Conditioner
1. Introduction
1.1
Safety Cautions
Be
sure to read the following safety cautions before conducting repair work.
The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important
since they can lead to death or serious injury if they are not followed closely. The “Caution” items can also lead
to serious accidents under some conditions if they are not followed. Therefore, be sure to observe all the safety
caution items described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates
normally, and explain the cautions for operating the product to the customer.
1.1.
1 Caution in Repair
Warning
Be
sure to disconnect the power cable plug from the plug socket before disassembling the equipment for
a repair.
Working on the equipment that is connected to a power supply can cause an electrical shook.
If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits, do not
touch any electrically charged sections of the equipment.
I
f the refrigerant gas discharges during the repair work, do not touch the discharging refrigerant gas.The
refrigerant gas can cause frostbite.
W
hen disconnecting the suction or discharge pipe of the compressor at the welded section, release the
refrigerant gas completely at a well-ventilated place first.
If there is a gas remaining inside the compressor, the refrigerant gas or refrigerating machine oil
discharges when the pipe is disconnected, and it can cause injury.
I
f the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas can generate
toxic gases when it contacts flames.
The
step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit.
Be sure to discharge the capacitor completely before conducting repair work.A charged capacitor can
cause an electrical shock.
D
o not start or stop the air conditioner operation by plugging or unplugging the power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can cause an electrical shock or
fire.
1
YJHJZH018BARRAFX-SM
Page 4
In
troduction
Do
mestic Air Conditioner
Warning
D
o not repair the electrical components with wet hands. Working on the equipment with wet hands can
cause an electrical shock.
D
o not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical
shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical
shocks.
Be
sure to turn off the power switch and unplug the power cable when cleaning the equipment. The
internal fan rotates at a high speed, and cause injury.
D
o not tilt the unit when removing it. The water inside the unit can spill and wet the furniture and floor.
B
e sure to check that the refrigerating cycle section has cooled down sufficiently before conducting repair
work. Working on the unit when the refrigerating cycle section is hot can cause burns.
U
se the welder in a well-ventilated place. Using the welder in an enclosed room can cause oxygen
deficiency.
1.1.2 Cautions Regarding Products after Repair
Wa
rning
Be
sure to use parts listed in the service parts list of the applicable model and appropriate tools to
conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can
cause an electrical shock, excessive heat generation or fire.
W
hen relocating the equipment, make sure that the new installation site has sufficient strength to
withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation work is not conducted
securely, the equipment can fall and cause injury.
B
e sure to install the product correctly by using the provided standard installation frame.
Incorrect use of the installation frame and improper installation can cause the equipment to fall, resulting
in injury.
For
integral
units only
B
e sure to install the product securely in the installation frame mounted on a window frame.
If the unit is not securely mounted, it can fall and cause injury.
For
integral
units only
2
YJHJZH018BARRAFX-SM
Page 5
In
troduction
Do
mestic Air Conditioner
Warning
B
e sure to use an exclusive power circuit for the equipment, and follow the technical standards related to
the electrical equipment, the internal wiring regulations and the instruction manual for installation when
conducting electrical work.
Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
B
e sure to use the specified cable to connect between the indoor and outdoor units. Make the
connections securely and route the cable properly so that there is no force pulling the cable at the
connection terminals.
Improper connections can cause excessive heat generation or fire.
W
hen connecting the cable between the indoor and outdoor units, make sure that the terminal cover does
not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause an electrical shock,
excessive heat generation or fire.
D
o not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire. Placing heavy items on the
power cable, and heating or pulling the power cable can damage the cable.
D
o not mix air or gas other than the specified refrigerant (R-410A / R22) in the refrigerant system.
If air enters the refrigerating system, an excessively high pressure results, causing equipment damage
and injury.
I
f the refrigerant gas leaks, be sure to locate the leak and repair it before charging the refrigerant. After
charging refrigerant, make sure that there is no refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to perform pump-down and
close the service valve, to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself
is harmless, but it can generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
W
hen replacing the coin battery in the remote controller, be sure to disposed of the old battery to prevent
children from swallowing it.
If a child swallows the coin battery, see a doctor imm ediately.
3
Cauti
on
I
nstallation of a leakage breaker is necessary in some cases depending on the conditions of the
installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be
sure to install the packing and seal on the installation frame properly. If the packing and seal are not
installed properly, water can enter the room and wet the furniture and floor.
For
integral
units only
YJHJZH018BARRAFX-SM
Page 6
I
ntroduction
Do
mestic Air Conditioner
4
1.1.
3 Inspection after Repair
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet
all the way.
If the plug has dust or loose connection, it can cause an electrical shock or fire.
I
f the power cable and lead wires have scratches or deteriorated, be sure to replace them.
Damaged cable and wires can cause an electrical shock, excessive heat generation or fire.
Wa
rning
D
o not use a joined power cable or extension cable, or share the same power outlet with other electrical
appliances, since it can cause an electrical shock, excessive heat generation or fire.
Cauti
on
C
heck to see if the parts and wires are mounted and connected properly, and if the connections at the
soldered or crimped terminals are secure. Improper installation and connections can cause excessive
heat generation, fire or an electrical shock.
I
f the installation platform or frame has corroded, replace it. Corroded installation platform or frame can
cause the unit to fall, resulting in injury.
C
heck the grounding, and repair it if the equipment is not properly grounded. Improper grounding can
cause an electrical shock.
B
e sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 M
ohm or higher.
Faulty insulation can cause an electrical shock.
Be
sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture and floor.
YJHJZH018BARRAFX-SM
Page 7
Category
Healthy negative ion
Child lock
3D air flow
24Hour timer
Easy clean design
Intelligent air
Anti-mold filter
4 Fan setting
Auto mode
Power mode
Soft mode
Note:
Y: Holding Functions
N : No Functions
m
ake your room full of an abundance natural negative ions.
Functions
Quick cooling or heating
adjust the last fixed operation mode automatically.
Make dehumidifying in the room while keeping the constant temperature inside
lower noise operation condition
Slect the fan speed LO,MED,HI,AUTO
Constant temperature
dehumidification
Avoid the child's wrong operation on the remote controller
Sleep mode
Catches most small particles and remove unpleasant odors effectively.
With twin-blade technology ,the airflow can be adjusted not to blow directly
The 3D airflow is able to deliver the airflow horizontally and vertically.
Use the timer function to set on,or off,or from on to off,or from off to on
The panel is easy to wash and the airflow vents can be detached easily
The setting temprature and the indoor noise can be adjusted to a more comfortable level when you set the "sleep mode"during night sleep
5
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
N
AS18GN3ERA
1U18EN2ERA
YJHJZH018BARRAFX-SM
Page 8
16381
16381
163~941~2250
377~1412~2850
5.1
3.4
-
-
4.1
6.1
941
1412
4.8
4
4127
4.1
6.1
2.0
10
15
25
02
4127
12.7
AS18GN3ERA/1U18EN2ERA
7969
6.35
16.0
14.2
12.7
11.2
15.0
13.5
13.0
10.5
12.5
1016X304X360
938X187X265
55/52/48
55
3. Specifications
6
40
96
96
4.8
gnitaeHgnilooC
AS18GN3ERA
YJHJZH018BARRAFX-SM
Page 9
0.5
R410a
33
1176.5
33
1176.5
35.5
33
780X245X640
930X340X714
54
40
54
1U18EN2ERA
1.2
900
4.1
6.1
15
7
FV50S
1412
941
SNB130FGYMC-L1
98
98
Specifications
5 m
Propeller
YJHJZH018BARRAFX-SM
Page 10
Connector
Wiring Diagram
Domestic Air Conditioner
3ULQWHG&LUFXLW%RDUG&RQQHFWRU:LULQJ'LDJUDP
4.1˖Indoor
unit Connectors
Conn
ectors
PCB(1) (Control PCB) For AS18GN3ERA
1) CN26 Connector for fan motor
2) CN1 Connector for heat exchanger thermistor and Room temperature thermistor
3) CN11’ Connector for UP&DOWN STEP motor
4) CON2 Connector for power N wire
5) CON1 Connector for power L
6) CON13 Connector for power GRN
7) CN32 Connector for display board
8) CON7 Connector for communicate between the indoor board and the outdoor board
9) CN34 Connector for long-range control
Note: Other designations
PCB(1) (INdoor Control PCB)
1) SW1 Connector for Forced operation ON / OFF switch
2) SW2 1 Select remote code A or B,2 Select 25 or 35 ,3 Select room card able or disable
3) RV1 Varistor
4) FUSE1 Fuse 3.15A/250VAC
8
YJHJZH018BARRAFX-SM
Page 11
Connector Wiring Diagram
Domestic Air Conditioner
PCB(1)
CN1
1’
CN34
CN26
CON1
CN1
CON7
CN32
CO
N13
CO
N2
9
YJHJZH018BARRAFX-SM
Page 12
Connector Wiring Diagram
Domestic
Air Conditioner
4.2:
outdoor unit
Conn
ectors
PCB(1) (Control PCB) for 1U18EN2ERA
1) CN1,CN2 Connector for power N and L
2) CN3 Connector for ground
3) CN22 Connector for DC POWER 15Vand 5V to the module board
4) CN9,CN8 Connector for CN2,CN1 on the module board
5) CN21 Connector for fan motor
6) CN10 Connector for four way valve coil
7) CN17,CN18,CN19, CN20 Connector for thermistors
8)CN23 Connector for communicate between the control board and the module board
9) CN26,CN24 Connector to P and N of the module board
10) CN4 Connector for communicate between indoor and outdoor unit
11) CN16 Connector for electric expansion valves
PCB(2) (module PCB)
CN10 Connector for the DC power 5V and 15V form the control PCB
CN11 Connector for communicate between the control board and the module board
P( CN1), N(CN5) Connector for capacitance board
LI (CN7),LO(CN6) Connector for reactor CN2ˈCN3ˈCN4 Connector for the U, V, W wire of the compressor
Note: Other Designations
PCB(1) (Control PCB)
1) FUSE 1, (25A,250VAC) FUSE 2(1A,250VAC)
2)LED 1 keep light representative normal ,if keep flash interval representative trouble Alarm
3)RV1,RV2,RV3 Varistor
10
YJHJZH018BARRAFX-SM
Page 13
Connector
Wiring Diagram
Domestic Air Conditioner
PCB
(1)
11
CN1
CN2
CN3
CN2
2
CN8
CN9
CN2
1
CN1
0
CN1
7
CN1
8
CN1
9
CN2
0
CN2
3
CN2
4
CN2
6
CN4
CN1
6
CN5 CN6
YJHJZH018BARRAFX-SM
Page 14
Connector
Wiring Diagram
Domestic
Air Conditioner
PCB
(2)
CN1
CN2
CN3
CN4
CN5
CN
6
CN7
CN11
CN10
12
YJHJZH018BARRAFX-SM
Page 15
-SM
Funcitions and Control
Domestic
Air Conditioner
13
5.Funcitions and Control
5.1 Main functions and control specification of indoor unit
5.1.1 Automatic
operation
When the running mode is turned to automation after starting the system, the system will first
determine the running mode according to the current room temperature and then will run according to
the determined mode. Tr in the following selection conditions means room temperature, Ts means
setting temperature, Tp means temperature of indoor coil pipe Tr23ć Choose Cooling Mode Tr˘23ć Choose Heating Mode
After turning to the automation mode, the running mode can be switched between cooling mode,
fan mode and heating mode according to the change of the indoor ambient temperature. But the
automatic conversion between cooling mode and heating mode must be conducted after 15 minutes.
5.1.2 Cooling
operation mode
T
emperature control range: 16ć---30ć Temperature difference: r1ć * Control features: When Tr˄input airflow˅>Ts˄set temperature˅ć, the compressor will be opened,the
indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system. When Tr˄input airflow˅ Ts˄set temperature˅ć , the compressor will be opened,the indoor fan will operate
at the set speed and the mode signal will be sent to the outdoor system. The system will keep the
original status if Tr= Ts. Airflow speed control: (temperature difference 1ć) Automatic: When Tr>=Ts+3ć, high speed. When Ts+1ć=<Tr<Ts+3ć, medium speed When Tr<Ts+1ć, low speed
When the sensor is off, low speed
When the airflow speed has no delay from the high to low switching, the speed should be delayed for
3 minutes (remain at high speed for 3 minutes.) before the next switch.
Manus: When the system is operating, you can set the high, medium or low speed manually. ( When
the sensor is on or off, the system will change the speed 2 seconds after receiving the signal.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
demoisture). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM) and
the temperature of the indoor coils has been below zero centigrade for 10 seconds, the compressor
will be stopped and the malfunction will be recorded in the malfunction list. The indoor system will continue to run. When the temperature of the indoor coil is raised to 7ć, the compressor will be
restarted again (the prerequirement of 3 minutes’ delay should be satisfied.)
* timing system on/off function.
* Dormant control function.
YJHJZH018BARRAFX
Page 16
Domestic
Air Conditioner
14
5.1.3 Demoisture
mode.
* temperature control range: 16---30ć * temperature difference: r1ć
Control feature: send the demoisture signal to the outdoor system. When Tr>Ts+2ć, the compressor will be turned on, the indoor fan will operate at the set speed. When Tr is between the Ts and Ts+2ć, the outdoor system will operate at the high demoisture
frequency for 10 minutes and then at the low demoisture mode for six minutes. The indoor fan will
operate at low speed.
When Tr< Ts, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then
turned to the low speed option. All the frequency converses have a f1ć difference.
* Wind speed control: Automatic: When Tr >= Ts+ 5ć, high speed. When Ts+3ćdTr< Ts+5ć, medium speed. When Ts+2ćdTr< Ts+3ć, low speed. When Tr<Ts+2ć, light speed.
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system
will be changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for
3 minutes (remain at high speed for 3 minutes.) before the next switch. Manual: When the sensor is off or Tr< Ts+3ć, the manual operation can not be made. (obligatory
automatic operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
demoisture). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM) and
the temperature of the indoor coils has been below zero centigrade for 10 seconds, the compressor
will be stopped and the malfunction will be recorded in the malfunction list. The indoor system will continue to run. When the temperature of the indoor coil is raised to 7ć, the compressor will be
restarted again (the prerequirement of 3 minutes’ delay should be satisfied.)
* coil protection (synchronic overheating protection) are installed for the four directions latch
malfunctions when demoisturing.
* timing system on/off function.
* Dormant control functio
n.
5.1.4 Heating
operation mode.
*
temperature control range: 16---30ć
* temperature difference: r1ć
* control feature: the temperature compensation is automatically added and the system will send the
heating signals to the outdoor system.
If TrdTs, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode.
If Tr>Ts+, the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
Funcitions and Control Funcitions and Control
YJHJZH018BARRAFX-SM
Page 17
Domestic
Air Conditioner
15
If
Tr<Ts+, the outdoor system will be turned on again, the indoor fan will be at the cold air proof mode.
*Indoor fan control
manual control: You can choose high, medium, low and automatic speed control.
Automatic: When Tr<Ts, high speed.
When Ts=<Tr=<Ts+2 , medium speed.
When Tr> Ts+2,low speed.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for
3 minutes (remain at high speed for 3 minutes.) before the next switch.
*Airgate location control: the location for the airgate can be set according to your needs.
Coldair proof operation
1. The indoor operation within 4 minutes after the start up is as the following diagram, the air speed
can be raised only after the speed has reached a certain level.
2. 4 minutes after the start up of the indoor fan, the light airflow and the low airflow will be turned to the
set speed airflow.
3. In the cold air proof operation, the fan won’t stop after the start up.
4. During the cold air proof operation, the indoor system will continuously send ‘indoor high speed’
signals to the outdoor system.
* Residue heat sending. The indoor fan will send the residue heat at a low speed for 12 seconds.
If other conditions are satisified, when the compressor stops, the indoor system will operate at a light
speed. The indoor fan will stop when the coil temperature is below the ‘heat start temp 4’.
* Defrosting. When the system receives the defrosting signal from outdoors, the indoor fan will stop
and the indoor temperature display won’t change. At the time, any indoor coil malfunctions will be
neglected. When the outdoor defrosting finishes, the coil malfunction will still be neglected until the
compressor has been started up for 30 seconds. The indoor temperature display will not change and
the system operates at the cold air proof mode.
* Automatic heating temperature compensation: when the system enters the heating mode, the
temperature compensation (4) will be added. When the status is switched off, the compensation will
be erased.
5.1.5 strength
operation
a.
the system enters the mode after receiving the ‘strength signal’.
Send strength operation signal to the outdoor system.
The mode change finishes the strength operation.
Entering ‘mute’, you can have normal operation or signal control such as timing to finish the strength
operation.
Heat
start temp 1
Heat
start temp
2
Heat
start temp
3
Heat
start temp
4
Set speed
Lo
w speed
L
ight speed
Fan/of
f
Fan/off
Keep
the hig
h
speed.
The fa
n
doesn’
t stop
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 18
Domestic
Air Conditioner
16
When
the system is at the automatic option with the strength/ mute function, if the system enters the
cooling mode, the cooling strength/ mute function will be offered; if the system enters the heating
mode, then the heating strength/ mute function will be offered; if the system enters the airflow mode,
there will be no strength/ mute function.
5.1.6 Mute
operation
the
system enters the mode after receiving the ‘mute signal’.
a. Mute heating: the airflow speed is slight, the system sends the mute signal to the outdoor system.
b. mute cooling: the airflow speed is slight, the system sends the mute signal to the outdoor system.
When the compressor operates, the airflow speed is mute speed. EEPROM is adaptable.
Mute operation can not work under the demoisturing and airflow-sending operation.
5.1.7 Air
refreshing
Af
ter receiving the signal from the remote control,(HV series: the background light of the ‘health’ logo
is green. HS series: the ‘health’ indicator will be lighted). If the fan operates, the negative ion
generator operates to realize the negative sending function.
If the indoor fan stops, the negative ion generator is turned off.
When the negative ion generator is turned off, if the air refreshing system is turned on, the negative
ion generator will be turned on when the fan operates.
5.1.8 Timing.
Y
ou can set 24 hours’ on/off timing accordingly. After the setting, the timing indicator will be lightened.
Also, the light will be turning off after the timing is finished. The followings are several timing methods.
1.system /on timing: The timing indicator will be lightened and the indoor system is under the waiting
mode. The light will be turned off when the timing is finished and the rest of the system will operate
under a normal condition. The timing starts since the last reception of the timing singal. You can have
the dormacy setting under the timing mode, the order of your settings will be operated according to
the timing settings.
2.system /off timing: When the system is turned on, the timing indicator is lightened, the rest of the
system will operated under a normal condition. When set time comes, the indicator light will be turned
off and the system will be turned off. If you have set the dormant functions, the order of your settings
will be operated according to the timing settings.
3 .system /on and off timing: The settings will be completed according to the orders.
5.1.9 Dormant
operation
The dormant timing is an eight hours unadaptable one. The timing signs are shown on the V series
board. (RC series show the dormant signal, the timing light is lighted on the 6 lights board).
2.1 Under the cooling/ demoisture operation, after the setting of the dormant operation, the set
temperature will be raised for 1 centigrade after 1 hour’s operation and will be raised for 1 centigrade
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 19
Domestic
Air Conditioner
17
1
hour later. The system will keep this status for 6 hours and then close.
2.2 Under the heating mode, after the setting of the dormant operation, the et temperature will fall 2
centigrades after 1 hour’s operation and will fall 2 centigrades 1 hours later. 3 hours after the
preceding operations, the set temperature will be raised for 1 centigrade and the system will keep this
status for 3 hours and then close down.
2.3 During the dormant time, except the change of the system mode or a new press on the dormant
setting keys, the timing of the 8 hours dormancy will take the first timing as the start time, any presses
on other keys will not affect the original timing.
2.4 Indoor fan control under the dormant operation.
If the indoor fan is at the high speed before the dormant operation setting, the speed will be turned to
medium after the setting. If the fan is at the medium speed before the dormant setting, the speed will
be turned to low after the setting. If the fan is at the low speed before the dormant setting, the speed
will not change.
5.1.10 Urgent
on/off input
Press
the urgency button the buzzer will ring. The system will enter the automatic mode if you don’t
press the button for more than 5 seconds.
Under the system off mode, if you press the urgency key for 5 to 10 seconds, the system will start the
test operation.
Under the system off mode, If you press the urgency key for 10 to 15 seconds, the display screen will
show the resume of the last malfunction.
If the system is under operation, the press on the urgency key will stop it.
Under the system off mode, the display screen will show automatic running sign.
Under the system off mode, the system will not receive the remote control signal if the press on the
urgency key doesn’t last for 15 seconds or if the key is loosened.
Urgency operation: If you press the urgency key for less than 5 seconds, the buzzer will ring when you
press the on/off key. The system will enter the urgency operation when the urgency key is loosened.
The urgency operation is fully automatic.
Test operation.
The inlet temperature sensor doesn’t work, the indoor fan and the indoor air direction board motor
works synchronically. High speed airflow, cooling, outdoor system on, etc, will send the ambient
temperature 30 centigrade and coil temperature 16 centigrade information to the outdoor system.
Test operation
The defrost protection of the evaporator doesn’t work.
The temperature control doesn’t work.
The test operation will be finished in 30 minutes.
The test operation can be stopped by the relative commands from the remote control.
5.1.11
Low load protection control
In order to prevent the frosting of the indoor heat interaction device, the outdoor system will be
stopped if the indoor heat interaction temperature is below zero centigrade for 5 minutes, but the fan
will continue to operate. The outdoor system will be started again when the heat interaction
temperature is above 7 centigrade and the system has been stopped for 3 minutes. The malfunction
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 20
Domestic
Air Conditioner
18
will be stored
in the malfunction resume and will not be revealed.
5.1.12 High load protection control
The out
door system will be stopped if the coil temperature is above 65ć for 2 minutes. The indoor
fan will be controlled by the thermostat. The outdoor system can be restarted when the coil temperature is below 42ć and the system has been stopped for 3 minutes. The malfunction will be
stored in the malfunction resume and will not be revealed.
5.1.13 abnormal operation of indoor system
When the outdoor system operates, if the indoor system operation differs from the outdoor system,
the abnormal operation malfunction will be reported. 10s after the report, the indoor system will be
closed.
Outdoor system mode Indoor system mode conflicts
cooling heating yes
cooling cooling no
cooling airflow no
heating heating no
heating airflow yes
heating cooling yes
5.1.14 Malfunction list resume.
Nothing is presented if there is no
code list.
The malfunction display will automatically finish in 10 seconds.
The remote control only receives the sigals for stop. According to the signals, the malfunction resume
presentation finishes.
The resume restores after the power supply restores.
5.1.15 abnormality confirmation approaches.
1. indoor temperatu
re sensor abnormality:
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
2 .indoor heat interaction sensor abnormality:
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
3 .indoor malfunction:
Out door malfunction: When the indoor system receives the outdoor malfunction codes, it will store
the code into E2 for the malfunction list resume. The indoor system will continue to operate according
Funcitions and Control Funcitions and Control
YJHJZH018BARRAFX-SM
Page 21
Domestic
Air Conditioner
19
to the original
status, the malfunction code will not be revealed or processed.
4.transmission abnormality:
If the indoor system can’t receive the outdoor system for 8 minutes, the communication abnormality
can be confirmed and reported and the outdoor system will be stopped.
5.1.16 Single indoor system operation
* Enter
condition: First, set the high speed airflow and 30 centigrade set temperature, then press the
dormant keys for 6 times within 7 seconds, the system will feedback with 6 rings.
* After the system enters the separate indoor system operation mode, the indoor system will operate
according to the set mode and neglect the communication signals of the outdoor system. However, it
has to send signals to the outdoor system.
* Quitting condition: This mode can be quitted after receiving the quitting signal from the remote
control or urgency system. The indoor system thus can quit the single operation mode.
5.1.17
Power cut compensation.
* Entering condition: Press dormant butt
on 10 times within 7 second, the buzzer will ring 4 times and
the present system status will be stored into the EEPROM of the indoor system.
* After entering the power cut compensation mode, the processing of the indoor system should be as
the followings:
Remote control urgency singal: operate according to the remote control and the urgent conditions,
the present status will be stored into the EEPROM of the indoor system.
* Quitting conditions: Press dormant button 10 times within 7 seconds and the buzzer will ring twice.
5.1.18 Fixed frequency operation.
1. Fixed cooling: a. unde
r G code condition: high speed cooling, set 16ć, press temperature ‘-‘ key
and the set key at the same time. The system will enter the fixed frequency operation after the buzzer
rings twice.
b. The proceeding programs are as the follows:
Entering the fixed frequency operation, you can set the fixed strength location 1 and send the coolng
signal to the outdoor system. Meanwhile, you can fix the indoor system at high speed mode, the
location of the airflow directin board can be switched to the maximal position.
c. Quitting condition: The fixed frequency cooling can be quitted after receiving the remote signal, and
the system will enter the remote setting status.
2. Fixed heating: a. under G code condition: high speed heating, set 30ć, press temperature ‘+‘ key
and the set key at the same time. The system will enter the fixed frequency operation after the buzzer
rings twice.
b. The proceeding programs are as the follows:
Entering the fixed frequency operation, you can set the fixed strength location 1 and send the heating
signal to the outdoor system. Meanwhile, you can fix the indoor system at high speed mode, the
location of the airflow directin board can be switched to the maximal position.
c. Quitting condition: The fixed frequency heating can be quitted after receiving the remote signal, and
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 22
Domestic
Air Conditioner
20
the system
will enter the remote setting status.
5.1.19 Test program
First, connect the
test program terminal on the mainboard, then connect the system to the power
circuit. The test program will operate as follows.
HV series display: The buzzer rings for one time—the signal will be sent to outdoor system for 0.5
second— the violet is sent for 0.5-- the background light turns to white—the back ground light turns to
white—the background light turns to white—the background light is fully lighted for 0.5 second—LED
screen lights for 0.5 second— the step-in motor fully output for 0.5 second—then the motor doesn’t
output for 0.5 second—the motor fully output again for 0.5 second. The test program finishes.
5.1.20 Time cutting function:
con
nect the test program terminal on the mainboard after connecting the system to the power circuit.
The CPU of the main control will be 60 times faster.
Funcitions and Control
Funcitions and Control
YJHJZH018BARRAFX
Page 23
Domestic
Air Conditioner
21
5.2 The control system of outdoor unit
5.2.1˖The operation frequency of out
door unit and its control
5.2.1.1˖The operation frequency control of compressor
The operation frequency scope of compressor˖
Mode
Minimun operation frequency Maximun operation frequency
Heatin
g 20Hz 110Hz
Refrigeration 20
Hz 90Hz
5.2.1.2˖The st
arting of compressor
When the compressor i
s started for the first time, it must be kept under the conditions of
58Hz,88Hz for one minute (the overheating protection of the outdoor unit air-blowing temperature,
immediately decrease the frequency when the compressor is overflowing and releasing the pressure)ˈthen it can be operated towards the target frequency. When the machine runs normally,
there’s no such process. After starting the compressor for operation, the compressor should run
according to the calculated frequency, and every determined frequency for protection should be prior
to the calculated frequency.
5.2.1.3˖The speeds of increasing or decreasing the frequency of the compressor
The speed of increasing or decreasing the frequency rapidly 1 -----------1HZ/second
The speed of increasing or decreasing the frequency slowly 2 -----------1HZ/10seconds
5.2.1.4˖The calculation of the compressor
’s frequency
1˅ǃThe minimum/maximum frequency limitation AˊWhile refrigerating: ˢˉ˩˝˴ˉ is the maximum operation frequency of the compressor;
ˢˉ˩INˉ is the minimum operation frequency of the compressor.
BˊWhile heating: ˢˉ˩˝˴ˉ is the maximum operation frequency of the compressor; ˢˉ
˩INˉis the minimum operation frequency of the compressor.
1˅ǃThe frequency limitation which is affected by the environment temperature.
Heating mode:
Serial No. Temperature scope Frequency limitation
1
Wh_c<-12 Max_hz8 110 HZ
2
Wh_c<-8 Max_hz7 110HZ
3
Wh_c<-2 Max_hz4 110 HZ
4
Wh_c<5 Max_hz5 100HZ
5
Wh_c<10 Max_hz1 90HZ
6
Wh_c<17 Max_hz2 80 HZ
7
Wh_c<20 Max_hz2 70 HZ
8
Wh_
c
20
Max_hz6 65
HZ
Remarks: the above are the maximum
frequency limitations of the complete appliance which are
affected by the environment, and they have nothing to do with the ability of the indoor unit.
Refrigeration/dehumidification mode::
Serial No. Temperature scope Frequency limitation
1
Wh_c<28 Max_hz1 45 HZ
2
Wh_c<32 Max_hz2 80 HZ
3
Wh_c<46 Max_hz3 90 HZ
Funcitions and Control
YJHJZH018BARRAFX
Page 24
Domestic
Air Conditioner
22
4
Wh_c<50 Max_hz4 80 HZ
5
Wh_
c
50
Max_hz5 60 HZ
Remarks: the above are not only
the maximum frequency limitations of the complete appliance which
are affected by the environment, but also the maximum ability limitation of the system. When the
starting ability is not the maximum, its maximum frequency limitation is calculated by the following
equations:
The frequency limitation which is affected by the temperature and under the condition of actual ability ˙the actural running system ability*the maximum frequency which is limited by the temperature and
under the condition of maximum ability/the maximum designing ability of the system
T=ě˄Ti*Pi˅/ěPi (Ti=|Tst_i-Tnh_i the indoor environment temperature| ;Pi˙i the ability of
the indoor unit)
Refrigeration/dehumidification:
Heating mode˖
K=ěKi/the number of running machines
The calculation of the actual output frequency: when there is no healthy airflow: F =F-ED-*hPhK When the healthy airflow has been set: F =F-ED-*hPhK˄airflow speed˅hK˄healthy airflow˅ When refrigerating, it is needed to satisfy ˢˉ˩INˉ< F<ˢˉ˩˝˴ˉ When heating, it is needed to satisfy ˢˉ˩INˉr< F<ˢˉ˩˝˴ˉr
5.2.2˖The out
door fan control (exchange fan)
Whe
n the fan is changed among every airflow speed (including stop blowing), in order to avoid the
airflow speed from skipping frequently, it must be kept under each mode for over 30 seconds, and
then it can be changed to another mode (when refrigerating, the time is changed to 15 seconds).
5.2.2.1˖
The outdoor fan control when refrigerating or dehumidifying
Af
ter the compressor is started for 5 seconds, the outdoor fan is started at the medium speed at first,
after 30 seconds,it begins to control the airflow speed according to the temperature conditions of the
outdoor environment.
T
<1
˙1 ˙2 ˙3
4
The pe
rcentage of the
rated frequency P
50% 70% 100% 120% 160%
T
<1
˙1 ˙2 ˙3
4
The pe
rcentage of the
rated frequency P
150% 170% 200% 220% 240%
The indoor set
airflow s
peed
Breeze Low Medium High Strong Quiet Healthy
airflow
The pe
rcentage
of the rated
frequency Ki
70ˁ
80% 90% 100% 180% 65% 65%
Funcitions and Control
YJHJZH018BARRAFX
Page 25
Domestic
Air Conditioner
23
5.2.2.2˖The outdoor fan control when heating
The temperature of the outdoor air ˄Ta ˅
Airflow speed
Ta 22ć
Low
19ćTa
< 22 ć
Keeping the speed
16ćTa
< 22 ć
Medium
14ćTa <1 6 ć
Keeping the speed
Ta <1 4 ć
High
5.2.3˖The control of the out
door electronic expansion valve
Whe
n starting the compressor: the opening size of the valve must be guaranteed to have entered into
the standard opening size, and then the compressor can be started.
When refrigeration is in vain (the machine is shut down or is in the state of retrograde operation), the
opening size of the expansion valve of the indoor unit is 5 steps;
When heating is in vain, the opening size of the expansion valve of the indoor unit is 55 steps;
When the outdoor unit is shut down, the valve is opened completely for 2 minutes, and then begin
initialization.
The scope of refrigerationg valve 90-----480 steps
The scope of heating valve 60-----480 steps The valves are adjusted according to the degree of superheat —SHaˈƸSHa.
5.2.4˖Four way control
For the det
ails of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or changed
to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the four-way
valve.
5.2.5 ˖Protection function
The temperature of the
out
door air ˄Ta˅
The temperature of the outdoor coil˄Te ˅
Airflow speed
Ta 30ć
—— High
26ćTa
< 30 ć
—— Keeping the speed
24ćTa <2 6 ć
—— Medium
23ćTa <2 4 ć
—— Keeping the speed
10ćTa <2 3 ć
—— Low
5ćTa
< 10 ć
—— Low
Ta
< 5ć 15ćTe
Low
15ć>T
e
Stop
Funcitions and Control
YJHJZH018BARRAFX
Page 26
Domestic
Air Conditioner
24
5.2.5.1˖TTC
high temperature-preventing protection
Once
the machine is started, it can run TTC overheating protection of air-blowing, but air-blowing
sensor malfunction must alarm after 4 minutes during which the compressor is started (during the
course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the
mean value of the middle 2 values), take the mean value. TTC˄ć˅
Abnormal stop
115 Decreasing the frequency rapidly˄1HZ/second˅
110
Decreasing the frequency slowly (1HZ/10seconds)
105
The frequency doesn’t change.
98 Increasing the frequency (1HZ/10second)
95 Increasing the frequency˄1HZ/1second˅ TTC>=115ć lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
5.2.5.2˖TC high temperature-preventing control of the indoor heating unit˖
Tpg_indoor
is the highest value of the effective indoor unit (start it and it is in accord with the running
state).
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the temperature is higher than 48ć, decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat exchanger is lower than 45ć, recover to the normal control.
TC
The compressor stops
Fgh_t1ˉ2
Fgh_t1 63ć
N Decreasing the frequency rapidly Fgh_t2 59ć
Fgh_t2ˉ2
P Decreasing the frequency slowly
Fgh_t3 56ć
Fgh_t3ˉ2
Q Prohibiting increasing the frequency
Fgh_t4 53ć
Fgh_t4—2 R Increasing slowly Fgh_t5 48ć
Fgh_t5—2
Normal
N˖Decreasing at the speed of 1HZ/1 s second P˖Decreasing at the speed of 1Hz/10 s seconds Q˖Continue to keep the last-time instruction cycle R˖Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
5.2.5.3 The control of preventing the overcurrent of the compressor˖
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 27
Domestic
Air Conditioner
25
During
the starting process of the compressor, if the current of the compressor is greater than 17.5A
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
During the starting process of the compressor, if the AC current is greater than 16.5A, the frequency
of the compressor decreases at the speed of 1HZ/second.
During
the starting process of the compressor, if the AC current is greater than 15.5A, the frequency
of the compressor decreases at the speed of 0.1HZ/second.
During
the starting process of the compressor, if the AC current is greater than14.5A, the frequency
of the compressor increases at the prohibited speed.
During
the starting process of the compressor, if the AC current is greater than 13.5A, the frequency
of the compressor increases at the speed of no faster than 0.1HZ/second.
5.2.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 16.5A, the frequency
of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 15.5A, the frequency
of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 14.5A, the frequency
of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 13.5A, the frequency
of the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, there’s compensation for AC current protection.
When the outdoor environment temperature is higher than 40 , AC current protection value
decreases by 25AD
When
the outdoor environment temperature is higher than 46
,AC
current protection value
decreases by 15AD
When
the outdoor environment temperature is higher than 50
,AC
current protection value
decreases by 35AD
5.2.5.5 Antifreezing
protection of the indoor heat exchanger
When
refrigerating/heating, prevent freezing.
Tpg_indoor is the minimum value of the effective indoor unit (start it and it is in accord with the running
state).
11
//ice_temp_3+5
9
i
ce_temp_3+3 Increasingslowly
8
//ice_temp_3+2
Keeping the frequency
ice_temp_3 7
6
ice_tem
p_2 5
Decreasingslowly
ice_temp_1 3
Decreasingrapidly ice_temp_1
0
Stop
When Tpg_indoor ice_temp_1 , the frequency of the compressor decreases at the speed of
1HZ/1second.
When Tpg_indoor ice_temp_2 , the frequency of the compressor decreases at the speed of
1HZ/10seconds.
Funcitions and Control
YJHJZH018BARRAFX
Page 28
Domestic
Air Conditioner
26
When
Tpg_indoor begins to rise again, and ice_temp_2İTpg_indoorİ ice_temp_3ć, the frequency
of thecompressor doesn’t change. When ice_temp_3LJTpg_indoorLJice_temp_3+3ć, the frequency of the compressor increases at the
speed of 1HZ/10seconds. For example, Tpg_indoorİ0ćˈlast for 2 minutes, and then the outdoor unit will stop, and report
underload malfunction, but don’t send malfunction report to the indoor. The compressor stops for more than 3 minutes, Tpg_indoor> ice_temp_3+2ć, the compressor
recovers.
5.2.5.6 The
frequency limitation of modification rate
In
the field which is controlled by high frequency, if the modification rate is not high enough, the
control-driven chip will enter into weak magnetic control, this will help to relieve the problem of
modification rate. If during the course of weak magnetic control, the modification rate is still not high
enough, enter into the control of decreasing frequency until the alarm of modification rate is relieved.
5.2.5.7 T
emperature protection of the outdoor refrigerating coil
When
the defrosting temperature and the sensor’s temperature are higher than 68ć, the frequency of
the compressor decreases 1hz/10seconds. Keep the frequency until it decreases to the lowest frequency. When the temperatures are lower than 68ć and higher than 61ć, keep the frequency of the compressor. When the temperatures are lower than 61ć, relieve the defrosting temperature
protection.
5.2.5.8˖Malfunction display and malfunction handling
a)ǃFor
the complete appliance’s malfunctions˖Annex 2
If there’s malfunction with the outdoor unit, the light of the outdoor unit will flash and its frequency is
1HZ, the number of times is according to the table, when a round of flashing is finished, the light
shoud be off for 5 seconds. b)ǃFor the units’ malfunctins˖Annex 1
If there’s malfunction with the units, this will not affect the run of the complete appliance, but this can
be displayed by the malfunction light, the light flashing frequency is 0.5HZ, the number of times is
according to the malfunction table of the indoor units. When a round of flashing is finished, the light shoud be off for 10 seconds. Then report according to the order : unit Aėunit Bėunit Cėunit D, that
is, if there’s malfunction with several units, then just report the indoor unit with the highest priority level.
Among the unit malfunctions, the priority level of the communication malfunction is the highest, for
others, that appears first will have the priority.
Remarks: in 3 minutes when the compressor stops, the units’ malfunctions are not displayed; the
complete appliance’s malfunctions are prior to the units’ malfunctions. Annex 1˖Malfunction codes of the whole unit
Remarks: under the mode of refrigeration, the malfunctions of each unit’s thin pipe temperature
sensor are not reported, under the mode of heating, the malfunctions of each unit’s thick pipe
temperature sensor are not reported.
Funcitions and Control
YJHJZH018BARRAFX
Page 29
Domestic
Air Conditioner
27
Room
sensor and Pipe Sensor
R25ć=10K¡f3%
B25ć/50ć=3700Kf3%
Temp.((ć))
Max.(Kȍ)
Normal(Kȍ) Min.(Kȍ)
Tolerance(ć)
-30
165.2170 147.9497 132.3678 -1.94 1.75
-29 155.5754 139.5600 125.0806 -1.93 1.74
-28
146.5609 131.7022 118.2434 -1.91 1.73
-27
138.1285 124.3392 111.8256 -1.89 1.71
-26
130.2371 117.4366 105.7989 -1.87 1.70
-25
122.8484 110.9627 100.1367 -1.85 1.69
-24
115.9272 104.8882 94.8149 -1.83 1.67
-23
109.4410 99.1858 89.8106 -1.81 1.66
-22
103.3598 93.8305 85.1031 -1.80 1.64
-21
97.6556 88.7989 80.6728 -1.78 1.63
-20
92.3028 84.0695 76.5017 -1.76 1.62
-19 87.2775 79.6222 72.5729 -1.74 1.60
-18
82.5577 75.4384 68.8710 -1.72 1.59
-17
78.1230 71.5010 65.3815 -1.70 1.57
-16
73.9543 67.7939 62.0907 -1.68 1.55
-15 70.0342 64.3023 58.9863 -1.66 1.54
-14
66.3463 61.0123 56.0565 -1.64 1.52
-13
62.8755 57.9110 53.2905 -1.62 1.51
-12
59.6076 54.9866 50.6781 -1.60 1.49
-11
56.5296 52.2278 48.2099 -1.58 1.47
-10
53.6294 49.6244 45.8771 -1.56 1.46
-9
50.8956 47.1666 43.6714 -1.54 1.44
-8 48.3178 44.8454 41.5851 -1.51 1.42
-7
45.8860 42.6525 39.6112 -1.49 1.40
Funcitions and Control
5.3
Value of Thermistor
5.3.1 int
door Unit
YJHJZH018BARRAFX-SM
Page 30
Domestic
Air Conditioner
28
-6 43.5912
40.5800 37.7429 -1.47 1.39
-5 41.4249
38.6207 35.9739 -1.45 1.37
-4 39.3792
36.7676 34.2983 -1.43 1.35
-3 37.4465
35.0144 32.7108 -1.41 1.33
-2 35.6202
33.3552 31.2062 -1.38 1.31
-1 33.8936
31.7844 29.7796 -1.36 1.29
0 32.2608
30.2968 28.4267 -1.34 1.28
1 30.7162
28.8875 27.1431 -1.32 1.26
2 29.2545
27.5519 25.9250 -1.29 1.24
3 27.8708
26.2858 24.7686 -1.27 1.22
4 26.5605
25.0851 23.6704 -1.25 1.20
5 25.3193 23.9462 22.6273 -1.23 1.18
6 24.1432
22.8656 21.6361 -1.20 1.16
7 23.0284
21.8398 20.6939 -1.18 1.14
8 21.9714
20.8659 19.7982 -1.15 1.12
9 20.9688
19.9409 18.9463 -1.13 1.09
10 20.0176
19.0621 18.1358 -1.11 1.07
11 19.1149
18.2270 17.3646 -1.08 1.05
12 18.2580
17.4331 16.6305 -1.06 1.03
13 17.4442
16.6782 15.9315 -1.03 1.01
14 16.6711
15.9601 15.2657 -1.01 0.99
15 15.9366
15.2770 14.6315 -0.98 0.96
16 15.2385 14.6268 14.0271 -0.96 0.94
17 14.5748
14.0079 13.4510 -0.93 0.92
18 13.9436 13.4185 12.9017 -0.91 0.90
19 13.3431
12.8572 12.3778 -0.88 0.87
20 12.7718
12.3223 11.8780 -0.86 0.85
21 12.2280
11.8126 11.4011 -0.83 0.83
22 11.7102
11.3267 10.9459 -0.81 0.80
23 11.2172
10.8634 10.5114 -0.78 0.78
24 10.7475
10.4216 10.0964 -0.75 0.75
25 10.3000
10.0000 9.7000 -0.75 0.75
26 9.8975
9.5974 9.2980 -0.76 0.76
27 9.5129
9.2132 8.9148 -0.80 0.80
28 9.1454
8.8465 8.5496 -0.84 0.83
29 8.7942
8.4964 8.2013 -0.87 0.86
30 8.4583 8.1621 7.8691 -0.91 0.90
31 8.1371
7.8428 7.5522 -0.95 0.93
32 7.8299 7.5377 7.2498 -0.98 0.97
33 7.5359
7.2461 6.9611 -1.02 1.00
34 7.2546 6.9673 6.6854 -1.06 1.04
35 6.9852
6.7008 6.4222 -1.10 1.07
36 6.7273
6.4459 6.1707 -1.13 1.11
37 6.4803
6.2021 5.9304 -1.17 1.14
38 6.2437
5.9687 5.7007 -1.21 1.18
Funcitions and Control
YJHJZH018BARRAFX
Page 31
Domestic
Air Conditioner
29
39 6.0170
5.7454 5.4812 -1.25 1.22
40 5.7997
5.5316 5.2712 -1.29 1.25
41 5.5914
5.3269 5.0704 -1.33 1.29
42 5.3916
5.1308 4.8783 -1.37 1.33
43 5.2001
4.9430 4.6944 -1.41 1.36
44 5.0163
4.7630 4.5185 -1.45 1.40
45 4.8400
4.5905 4.3500 -1.49 1.44
46 4.6708
4.4252 4.1887 -1.53 1.47
47 4.5083
4.2666 4.0342 -1.57 1.51
48 4.3524
4.1145 3.8862 -1.61 1.55
49 4.2026
3.9686 3.7443 -1.65 1.59
50 4.0588 3.8287 3.6084 -1.70 1.62
51 3.9206
3.6943 3.4780 -1.74 1.66
52 3.7878
3.5654 3.3531 -1.78 1.70
53 3.6601
3.4416 3.2332 -1.82 1.74
54 3.5374
3.3227 3.1183 -1.87 1.78
55 3.4195
3.2085 3.0079 -1.91 1.82
56 3.3060
3.0989 2.9021 -1.95 1.85
57 3.1969
2.9935 2.8005 -2.00 1.89
58 3.0919
2.8922 2.7029 -2.04 1.93
59 2.9909
2.7948 2.6092 -2.08 1.97
60 2.8936
2.7012 2.5193 -2.13 2.01
61 2.8000 2.6112 2.4328 -2.17 2.05
62 2.7099
2.5246 2.3498 -2.22 2.09
63 2.6232 2.4413 2.2700 -2.26 2.13
64 2.5396
2.3611 2.1932 -2.31 2.17
65 2.4591
2.2840 2.1195 -2.36 2.21
66 2.3815
2.2098 2.0486 -2.40 2.25
67 2.3068
2.1383 1.9803 -2.45 2.29
68 2.2347
2.0695 1.9147 -2.49 2.34
69 2.1652
2.0032 1.8516 -2.54 2.38
70 2.0983
1.9393 1.7908 -2.59 2.42
71 2.0337
1.8778 1.7324 -2.63 2.46
72 1.9714
1.8186 1.6761 -2.68 2.50
73 1.9113
1.7614 1.6219 -2.73 2.54
74 1.8533
1.7064 1.5697 -2.78 2.58
75 1.7974 1.6533 1.5194 -2.83 2.63
76 1.7434
1.6021 1.4710 -2.88 2.67
77 1.6913 1.5528 1.4243 -2.92 2.71
78 1.6409
1.5051 1.3794 -2.97 2.75
79 1.5923 1.4592 1.3360 -3.02 2.80
80 1.5454
1.4149 1.2942 -3.07 2.84
81 1.5000
1.3721 1.2540 -3.12 2.88
82 1.4562
1.3308 1.2151 -3.17 2.93
83 1.4139
1.2910 1.1776 -3.22 2.97
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 32
Domestic
Air Conditioner
30
84 1.3730
1.2525 1.1415 -3.27 3.01
85 1.3335
1.2153 1.1066 -3.32 3.06
86 1.2953
1.1794 1.0730 -3.38 3.10
87 1.2583
1.1448 1.0405 -3.43 3.15
88 1.2226
1.1113 1.0092 -3.48 3.19
89 1.1880
1.0789 0.9789 -3.53 3.24
90 1.1546
1.0476 0.9497 -3.58 3.28
91 1.1223
1.0174 0.9215 -3.64 3.33
92 1.0910
0.9882 0.8942 -3.69 3.37
93 1.0607
0.9599 0.8679 -3.74 3.42
94 1.0314
0.9326 0.8424 -3.80 3.46
95 1.0030 0.9061 0.8179 -3.85 3.51
96 0.9756
0.8806 0.7941 -3.90 3.55
97 0.9490
0.8558 0.7711 -3.96 3.60
98 0.9232
0.8319 0.7489 -4.01 3.64
99 0.8983
0.8088 0.7275 -4.07 3.69
100 0.8741
0.7863 0.7067 -4.12 3.74
101 0.8507
0.7646 0.6867 -4.18 3.78
102 0.8281
0.7436 0.6672 -4.23 3.83
103 0.8061
0.7233 0.6484 -4.29 3.88
104 0.7848
0.7036 0.6303 -4.34 3.92
105 0.7641
0.6845 0.6127 -4.40 3.97
106 0.7441 0.6661 0.5957 -4.46 4.02
107 0.7247
0.6482 0.5792 -4.51 4.07
108 0.7059 0.6308 0.5632 -4.57 4.12
109 0.6877
0.6140 0.5478 -4.63 4.16
110 0.6700
0.5977 0.5328 -4.69 4.21
111 0.6528
0.5820 0.5183 -4.74 4.26
112 0.6361
0.5667 0.5043 -4.80 4.31
113 0.6200
0.5518 0.4907 -4.86 4.36
114 0.6043
0.5374 0.4775 -4.92 4.41
115 0.5891
0.5235 0.4648 -4.98 4.45
116 0.5743
0.5100 0.4524 -5.04 4.50
117 0.5600
0.4968 0.4404 -5.10 4.55
118 0.5460
0.4841 0.4288 -5.16 4.60
119 0.5325
0.4717 0.4175 -5.22 4.65
120 0.5194 0.4597 0.4066 -5.28 4.70
5.3.2 Outdoor Unit
Ambient Sensor
, Defrosting Sensor, Pipe sensor
R25ć=10K¡f3% B25ć/50ć=3700Kf3%
Temp.(ć)
Max.(Kȍ) Normal(Kȍ) Min.(Kȍ)
Tolerance(ć)
-30 165.2170
147.9497 132.3678 -1.94 1.75
-29 155.5754
139.5600 125.0806 -1.93 1.74
-28 146.5609
131.7022 118.2434 -1.91 1.73
-27 138.1285
124.3392 111.8256 -1.89 1.71
Funcitions and Control
YJHJZH018BARRAFX
Page 33
Domestic
Air Conditioner
31
-26 130.2371
117.4366 105.7989 -1.87 1.70
-25 122.8484
110.9627 100.1367 -1.85 1.69
-24 115.9272
104.8882 94.8149 -1.83 1.67
-23 109.4410
99.1858 89.8106 -1.81 1.66
-22 103.3598
93.8305 85.1031 -1.80 1.64
-21 97.6556
88.7989 80.6728 -1.78 1.63
-20 92.3028
84.0695 76.5017 -1.76 1.62
-19 87.2775
79.6222 72.5729 -1.74 1.60
-18 82.5577
75.4384 68.8710 -1.72 1.59
-17 78.1230
71.5010 65.3815 -1.70 1.57
-16 73.9543
67.7939 62.0907 -1.68 1.55
-15 70.0342 64.3023 58.9863 -1.66 1.54
-14 66.3463
61.0123 56.0565 -1.64 1.52
-13 62.8755
57.9110 53.2905 -1.62 1.51
-12 59.6076
54.9866 50.6781 -1.60 1.49
-11 56.5296
52.2278 48.2099 -1.58 1.47
-10 53.6294
49.6244 45.8771 -1.56 1.46
-9 50.8956
47.1666 43.6714 -1.54 1.44
-8 48.3178
44.8454 41.5851 -1.51 1.42
-7 45.8860
42.6525 39.6112 -1.49 1.40
-6 43.5912
40.5800 37.7429 -1.47 1.39
-5 41.4249
38.6207 35.9739 -1.45 1.37
-4 39.3792 36.7676 34.2983 -1.43 1.35
-3 37.4465
35.0144 32.7108 -1.41 1.33
-2 35.6202 33.3552 31.2062 -1.38 1.31
-1 33.8936
31.7844 29.7796 -1.36 1.29
0 32.2608
30.2968 28.4267 -1.34 1.28
1 30.7162
28.8875 27.1431 -1.32 1.26
2 29.2545
27.5519 25.9250 -1.29 1.24
3 27.8708
26.2858 24.7686 -1.27 1.22
4 26.5605
25.0851 23.6704 -1.25 1.20
5 25.3193
23.9462 22.6273 -1.23 1.18
6 24.1432
22.8656 21.6361 -1.20 1.16
7 23.0284
21.8398 20.6939 -1.18 1.14
8 21.9714
20.8659 19.7982 -1.15 1.12
9 20.9688
19.9409 18.9463 -1.13 1.09
10 20.0176 19.0621 18.1358 -1.11 1.07
11 19.1149
18.2270 17.3646 -1.08 1.05
12 18.2580 17.4331 16.6305 -1.06 1.03
13 17.4442
16.6782 15.9315 -1.03 1.01
14 16.6711 15.9601 15.2657 -1.01 0.99
15 15.9366
15.2770 14.6315 -0.98 0.96
16 15.2385
14.6268 14.0271 -0.96 0.94
17 14.5748
14.0079 13.4510 -0.93 0.92
18 13.9436
13.4185 12.9017 -0.91 0.90
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 34
Domestic
Air Conditioner
32
19 13.3431
12.8572 12.3778 -0.88 0.87
20 12.7718
12.3223 11.8780 -0.86 0.85
21 12.2280
11.8126 11.4011 -0.83 0.83
22 11.7102
11.3267 10.9459 -0.81 0.80
23 11.2172
10.8634 10.5114 -0.78 0.78
24 10.7475
10.4216 10.0964 -0.75 0.75
25 10.3000
10.0000 9.7000 -0.75 0.75
26 9.8975
9.5974 9.2980 -0.76 0.76
27 9.5129
9.2132 8.9148 -0.80 0.80
28 9.1454
8.8465 8.5496 -0.84 0.83
29 8.7942
8.4964 8.2013 -0.87 0.86
30 8.4583 8.1621 7.8691 -0.91 0.90
31 8.1371
7.8428 7.5522 -0.95 0.93
32 7.8299
7.5377 7.2498 -0.98 0.97
33 7.5359
7.2461 6.9611 -1.02 1.00
34 7.2546
6.9673 6.6854 -1.06 1.04
35 6.9852
6.7008 6.4222 -1.10 1.07
36 6.7273
6.4459 6.1707 -1.13 1.11
37 6.4803
6.2021 5.9304 -1.17 1.14
38 6.2437
5.9687 5.7007 -1.21 1.18
39 6.0170
5.7454 5.4812 -1.25 1.22
40 5.7997
5.5316 5.2712 -1.29 1.25
41 5.5914 5.3269 5.0704 -1.33 1.29
42 5.3916
5.1308 4.8783 -1.37 1.33
43 5.2001 4.9430 4.6944 -1.41 1.36
44 5.0163
4.7630 4.5185 -1.45 1.40
45 4.8400
4.5905 4.3500 -1.49 1.44
46 4.6708
4.4252 4.1887 -1.53 1.47
47 4.5083
4.2666 4.0342 -1.57 1.51
48 4.3524
4.1145 3.8862 -1.61 1.55
49 4.2026
3.9686 3.7443 -1.65 1.59
50 4.0588
3.8287 3.6084 -1.70 1.62
51 3.9206
3.6943 3.4780 -1.74 1.66
52 3.7878
3.5654 3.3531 -1.78 1.70
53 3.6601
3.4416 3.2332 -1.82 1.74
54 3.5374
3.3227 3.1183 -1.87 1.78
55 3.4195 3.2085 3.0079 -1.91 1.82
56 3.3060
3.0989 2.9021 -1.95 1.85
57 3.1969 2.9935 2.8005 -2.00 1.89
58 3.0919
2.8922 2.7029 -2.04 1.93
59 2.9909 2.7948 2.6092 -2.08 1.97
60 2.8936
2.7012 2.5193 -2.13 2.01
61 2.8000
2.6112 2.4328 -2.17 2.05
62 2.7099
2.5246 2.3498 -2.22 2.09
63 2.6232
2.4413 2.2700 -2.26 2.13
Funcitions and Control
YJHJZH018BARRAFX-SM
Page 35
Domestic
Air Conditioner
33
64 2.5396
2.3611 2.1932 -2.31 2.17
65 2.4591
2.2840 2.1195 -2.36 2.21
66 2.3815
2.2098 2.0486 -2.40 2.25
67 2.3068
2.1383 1.9803 -2.45 2.29
68 2.2347
2.0695 1.9147 -2.49 2.34
69 2.1652
2.0032 1.8516 -2.54 2.38
70 2.0983
1.9393 1.7908 -2.59 2.42
71 2.0337
1.8778 1.7324 -2.63 2.46
72 1.9714
1.8186 1.6761 -2.68 2.50
73 1.9113
1.7614 1.6219 -2.73 2.54
74 1.8533
1.7064 1.5697 -2.78 2.58
75 1.7974 1.6533 1.5194 -2.83 2.63
76 1.7434
1.6021 1.4710 -2.88 2.67
77 1.6913
1.5528 1.4243 -2.92 2.71
78 1.6409
1.5051 1.3794 -2.97 2.75
79 1.5923
1.4592 1.3360 -3.02 2.80
80 1.5454
1.4149 1.2942 -3.07 2.84
81 1.5000
1.3721 1.2540 -3.12 2.88
82 1.4562
1.3308 1.2151 -3.17 2.93
83 1.4139
1.2910 1.1776 -3.22 2.97
84 1.3730
1.2525 1.1415 -3.27 3.01
85 1.3335
1.2153 1.1066 -3.32 3.06
86 1.2953 1.1794 1.0730 -3.38 3.10
87 1.2583
1.1448 1.0405 -3.43 3.15
88 1.2226 1.1113 1.0092 -3.48 3.19
89 1.1880
1.0789 0.9789 -3.53 3.24
90 1.1546
1.0476 0.9497 -3.58 3.28
91 1.1223
1.0174 0.9215 -3.64 3.33
92 1.0910
0.9882 0.8942 -3.69 3.37
93 1.0607
0.9599 0.8679 -3.74 3.42
94 1.0314
0.9326 0.8424 -3.80 3.46
95 1.0030
0.9061 0.8179 -3.85 3.51
96 0.9756
0.8806 0.7941 -3.90 3.55
97 0.9490
0.8558 0.7711 -3.96 3.60
98 0.9232
0.8319 0.7489 -4.01 3.64
99 0.8983
0.8088 0.7275 -4.07 3.69
100 0.8741 0.7863 0.7067 -4.12 3.74
101 0.8507
0.7646 0.6867 -4.18 3.78
102 0.8281 0.7436 0.6672 -4.23 3.83
103 0.8061
0.7233 0.6484 -4.29 3.88
104 0.7848 0.7036 0.6303 -4.34 3.92
105 0.7641
0.6845 0.6127 -4.40 3.97
106 0.7441
0.6661 0.5957 -4.46 4.02
107 0.7247
0.6482 0.5792 -4.51 4.07
108 0.7059
0.6308 0.5632 -4.57 4.12
Funcitions and Control
YJHJZH018BARRAFX
Page 36
Domestic
Air Conditioner
34
109 0.6877
0.6140 0.5478 -4.63 4.16
110 0.6700
0.5977 0.5328 -4.69 4.21
111 0.6528
0.5820 0.5183 -4.74 4.26
112 0.6361
0.5667 0.5043 -4.80 4.31
113 0.6200
0.5518 0.4907 -4.86 4.36
114 0.6043
0.5374 0.4775 -4.92 4.41
115 0.5891
0.5235 0.4648 -4.98 4.45
116 0.5743
0.5100 0.4524 -5.04 4.50
117 0.5600
0.4968 0.4404 -5.10 4.55
118 0.5460
0.4841 0.4288 -5.16 4.60
119 0.5325
0.4717 0.4175 -5.22 4.65
120 0.5194 0.4597 0.4066 -5.28 4.70
Discharging Sensor
R80ć=50K¡f3% B25/80ć=44
50Kf3%
Temp.((ć))
Max.(Kȍ) Normal(Kȍ) Min.(Kȍ)
Tolerance(ć)
-30
14646.0505 12061.7438 9924.4999 -2.96 2.45
-29
13654.1707 11267.8730 9290.2526 -2.95 2.44
-28
12735.8378 10531.3695 8700.6388 -2.93 2.44
-27
11885.1336 9847.7240 8152.2338 -2.92 2.43
-26 11096.6531 9212.8101 7641.8972 -2.91 2.42
-25
10365.4565 8622.8491 7166.7474 -2.90 2.42
-24
9687.0270 8074.3787 6724.1389 -2.88 2.41
-23
9057.2314 7564.2244 6311.6413 -2.87 2.41
-22
8472.2852 7089.4741 5927.0206 -2.86 2.40
-21 7928.7217 6647.4547 5568.2222 -2.84 2.39
-20
7423.3626 6235.7109 5233.3554 -2.83 2.39
-19
6953.2930 5851.9864 4920.6791 -2.82 2.38
-18
6515.8375 5494.2064 4628.5894 -2.80 2.37
-17
6108.5393 5160.4621 4355.6078 -2.79 2.37
-16
5729.1413 4848.9963 4100.3708 -2.77 2.36
-15
5375.5683 4558.1906 3861.6201 -2.76 2.35
-14
5045.9114 4286.5535 3638.1938 -2.75 2.34
-13
4738.4141 4032.7098 3429.0191 -2.73 2.34
-12
4451.4586 3795.3910 3233.1039 -2.72 2.33
-11
4183.5548 3573.4260 3049.5312 -2.70 2.32
-10 3933.3289 3365.7336 2877.4527 -2.69 2.31
-9
3699.5139 3171.3148 2716.0828 -2.67 2.30
-8 3480.9407 2989.2460 2564.6945 -2.66 2.29
-7
3276.5302 2818.6731 2422.6139 -2.64 2.28
-6
3085.2854 2658.8058 2289.2164 -2.63 2.28
-5
2906.2851 2508.9126 2163.9230 -2.61 2.27
-4
2738.6777 2368.3158 2046.1961 -2.60 2.26
-3
2581.6752 2236.3876 1935.5371 -2.58 2.25
Funcitions and Control
YJHJZH018BARRAFX
Page 37
Domestic
Air Conditioner
35
-2
2434.5487 2112.5459 1831.4826 -2.56 2.24
-1
2296.6230 1996.2509 1733.6024 -2.55 2.23
0
2167.2730 1887.0018 1641.4966 -2.53 2.22
1
2045.9191 1784.3336 1554.7931 -2.52 2.21
2
1932.0242 1687.8144 1473.1460 -2.50 2.20
3
1825.0899 1597.0431 1396.2333 -2.48 2.19
4
1724.6540 1511.6468 1323.7551 -2.47 2.17
5
1630.2870 1431.2787 1255.4324 -2.45 2.16
6
1541.5904 1355.6163 1191.0048 -2.43 2.15
7
1458.1938 1284.3593 1130.2298 -2.41 2.14
8
1379.7528 1217.2282 1072.8813 -2.40 2.13
9 1305.9472 1153.9626 1018.7481 -2.38 2.12
10
1236.4792 1094.3200 967.6334 -2.36 2.11
11
1171.0715 1038.0743 919.3533 -2.35 2.09
12
1109.4661 985.0146 873.7359 -2.33 2.08
13
1051.4226 934.9440 830.6210 -2.31 2.07
14
996.7169 887.6792 789.8583 -2.29 2.06
15
945.1404 843.0486 751.3077 -2.27 2.04
16
896.4981 800.8922 714.8380 -2.26 2.03
17
850.6086 761.0603 680.3265 -2.24 2.02
18
807.3024 723.4134 647.6580 -2.22 2.00
19
766.4212 687.8205 616.7252 -2.20 1.99
20 727.8172 654.1596 587.4271 -2.18 1.98
21
691.3524 622.3161 559.6694 -2.16 1.96
22 656.8979 592.1831 533.3634 -2.14 1.95
23
624.3328 563.6604 508.4261 -2.12 1.93
24
593.5446 536.6540 484.7796 -2.10 1.92
25
564.4275 511.0760 462.3510 -2.09 1.90
26
536.9865 486.9352 441.1516 -2.07 1.89
27
511.0105 464.0500 421.0258 -2.05 1.87
28
486.4151 442.3499 401.9146 -2.03 1.86
29
463.1208 421.7683 383.7626 -2.01 1.84
30
441.0535 402.2430 366.5175 -1.99 1.83
31
420.1431 383.7151 350.1301 -1.97 1.81
32
400.3242 366.1295 334.5542 -1.95 1.80
33
381.5350 349.4341 319.7460 -1.93 1.78
34 363.7176 333.5801 305.6645 -1.90 1.76
35
346.8176 318.5216 292.2709 -1.88 1.75
36 330.7839 304.2151 279.5286 -1.86 1.73
37
315.5682 290.6199 267.4031 -1.84 1.71
38 301.1254 277.6976 255.8620 -1.82 1.70
39
287.4128 265.4119 244.8745 -1.80 1.68
40
274.3905 253.7288 234.4118 -1.78 1.66
41
262.0206 242.6161 224.4465 -1.76 1.64
42
250.2676 232.0436 214.9529 -1.74 1.63
Funcitions and Control
YJHJZH018BARRAFX
Page 38
Domestic
Air Conditioner
36
43
239.0983 221.9825 205.9065 -1.71 1.61
44
228.4809 212.4060 197.2844 -1.69 1.59
45
218.3860 203.2887 189.0648 -1.67 1.57
46
208.7855 194.6066 181.2273 -1.65 1.55
47
199.6531 186.3369 173.7524 -1.63 1.54
48
190.9639 178.4584 166.6217 -1.60 1.52
49
182.6945 170.9508 159.8181 -1.58 1.50
50
174.8228 163.7951 153.3249 -1.56 1.48
51
167.3280 156.9733 147.1268 -1.53 1.46
52
160.1904 150.4683 141.2090 -1.51 1.44
53
153.3914 144.2641 135.5577 -1.49 1.42
54 146.9136 138.3454 130.1598 -1.47 1.40
55
140.7403 132.6980 125.0027 -1.44 1.38
56
134.8559 127.3081 120.0746 -1.42 1.36
57
129.2457 122.1630 115.3645 -1.40 1.34
58
123.8956 117.2504 110.8618 -1.37 1.32
59
118.7926 112.5589 106.5564 -1.35 1.30
60
113.9241 108.0776 102.4388 -1.32 1.28
61
109.2784 103.7961 98.5000 -1.30 1.26
62
104.8443 99.7046 94.7315 -1.28 1.23
63
100.6112 95.7939 91.1253 -1.25 1.21
64
96.5692 92.0553 87.6735 -1.23 1.19
65 92.7088 88.4805 84.3690 -1.20 1.17
66
89.0211 85.0614 81.2048 -1.18 1.15
67 85.4976 81.7908 78.1744 -1.15 1.12
68
82.1303 78.6615 75.2715 -1.13 1.10
69
78.9116 75.6668 72.4902 -1.10 1.08
70
75.8343 72.8004 69.8249 -1.08 1.06
71
72.8916 70.0561 67.2703 -1.05 1.03
72
70.0770 67.4283 64.8213 -1.03 1.01
73
67.3844 64.9115 62.4731 -1.00 0.99
74
64.8080 62.5006 60.2211 -0.98 0.96
75
62.3423 60.1906 58.0609 -0.95 0.94
76
59.9821 57.9770 55.9885 -0.92 0.92
77
57.7223 55.8552 53.9998 -0.90 0.89
78
55.5583 53.8210 52.0912 -0.87 0.87
79 53.4856 51.8706 50.2591 -0.85 0.84
80
51.5000 50.0000 48.5000 -0.85 0.84
81 49.7063 48.2057 46.7083 -0.85 0.85
82
47.9835 46.4842 44.9911 -0.89 0.89
83 46.3286 44.8323 43.3452 -0.93 0.92
84
44.7385 43.2468 41.7672 -0.96 0.95
85
43.2105 41.7248 40.2540 -1.00 0.99
86
41.7386 40.2604 38.7996 -1.03 1.02
87
40.3241 38.8545 37.4048 -1.07 1.06
Funcitions and Control
YJHJZH018BARRAFX
Page 39
Domestic
Air Conditioner
37
88
38.9643 37.5045 36.0668 -1.11 1.09
89
37.6569 36.2078 34.7831 -1.14 1.13
90
36.3996 34.9622 33.5513 -1.18 1.16
91
35.1903 33.7653 32.3689 -1.22 1.19
92
34.0269 32.6151 31.2338 -1.26 1.23
93
32.9075 31.5096 30.1438 -1.30 1.27
94
31.8302 30.4467 29.0970 -1.33 1.30
95
30.7933 29.4246 28.0915 -1.37 1.34
96
29.7950 28.4417 27.1254 -1.41 1.37
97
28.8337 27.4961 26.1970 -1.45 1.41
98
27.9078 26.5864 25.3048 -1.49 1.44
99 27.0160 25.7110 24.4470 -1.53 1.48
100
26.1569 24.8685 23.6222 -1.57 1.52
101
25.3290 24.0574 22.8291 -1.61 1.55
102
24.5311 23.2765 22.0662 -1.65 1.59
103
23.7620 22.5245 21.3323 -1.69 1.63
104
23.0205 21.8002 20.6261 -1.73 1.66
105
22.3055 21.1025 19.9465 -1.77 1.70
106
21.6159 20.4303 19.2924 -1.81 1.74
107
20.9508 19.7825 18.6626 -1.85 1.77
108
20.3091 19.1582 18.0563 -1.89 1.81
109
19.6899 18.5564 17.4723 -1.93 1.85
110 19.0924 17.9761 16.9098 -1.98 1.89
111
18.5157 17.4166 16.3680 -2.02 1.93
112 17.9590 16.8769 15.8458 -2.06 1.96
113
17.4214 16.3564 15.3427 -2.10 2.00
114
16.9023 15.8542 14.8577 -2.15 2.04
115
16.4010 15.3696 14.3902 -2.19 2.08
116
15.9167 14.9020 13.9394 -2.23 2.12
117
15.4489 14.4506 13.5047 -2.27 2.16
118
14.9968 14.0149 13.0855 -2.32 2.19
119
14.5599 13.5942 12.6811 -2.36 2.23
120
14.1376 13.1879 12.2909 -2.41 2.27
121
13.7294 12.7955 11.9144 -2.45 2.31
122
13.3347 12.4165 11.5510 -2.50 2.35
123
12.9531 12.0503 11.2003 -2.54 2.39
124 12.5840 11.6965 10.8617 -2.58 2.43
125
12.2270 11.3545 10.5348 -2.63 2.47
126 11.8817 11.0240 10.2191 -2.68 2.51
127
11.5475 10.7046 9.9142 -2.72 2.55
128 11.2242 10.3957 9.6197 -2.77 2.59
129
10.9112 10.0970 9.3352 -2.81 2.63
130
10.6084 9.8082 9.0602 -2.86 2.67
131
10.3151 9.5288 8.7945 -2.91 2.71
132
10.0312 9.2586 8.5378 -2.95 2.75
Funcitions and Control
YJHJZH018BARRAFX
Page 40
Domestic
Air Conditioner
38
133
9.7563 8.9971 8.2895 -3.00 2.80
134
9.4901 8.7441 8.0495 -3.05 2.84
135
9.2322 8.4993 7.8175 -3.09 2.88
136
8.9824 8.2623 7.5931 -3.14 2.92
137
8.7404 8.0329 7.3760 -3.19 2.96
138
8.5059 7.8108 7.1660 -3.24 3.00
139
8.2787 7.5958 6.9629 -3.29 3.04
140
8.0584 7.3875 6.7664 -3.33 3.09
Funcitions and Control
YJHJZH018BARRAFX
Page 41
39
YJHJZH018BARRAFX-SM
Page 42
Domestic
Air Conditioner
0
System Configration
YJHJYH018BARRAFX-SM
1
2
3
5
6
4
7
4
POWER/SOFT button is not available for 07k09k12k.
Page 43
Domestic
Air Conditioner
1
System Configration
YJHJYH018BARRAFX-SM
Operation
next time,just press ON/OFF button and unit will run in previous status.
Remote controller can memorize each operation status. When starting it
AUTO
COOL DRY FAN
2.Select operation mode
Press
FAN SPEED button. For each press, fan speed
follows:
Press MODE button. For each press, operation mode changes as follows: Remote controller:
Remote controller:
Press button
Every time the button is pressed, temp.setting increase 1
o
C,if kept depressed, it will increase
rapidly
Every time the button is pressed, temp.setting
decrease
1
o
C,if kept depressed, it will decrease
rapidly
Select a desired temperature.
4.Fan speed selection
3.Select temp.setting
Air conditioner is running under displayed fan speed. When
FAN is set to AUTO, the air conditioner automatically adjusts the fan speed according to room temperature.
LOW
MED
HI
AUTO
1.
Unit start
Press ON/OFF on the remote controller, unit star
ts.
TEMP+
TEMP-
TEMP+
TEMP-
B
ase Operation
Remote controller
Air Flow Direction Adjustment
V
ertical flap
Po
s.1
Pos.2
Pos.3
Pos.4
Pos.5
(Auto
swing)
1.Status displa
y of air flow
When restart after remote turning off, the remote
memorize the previous
Move the vertical blade by a knob on air
to adjust left and right direction
referring to Fig.
2.Left and right air flow adjustment
(manual)
Cautions:
When adjusting the flap by hand,turn off the unit.
When humidity is high,condensate water might occur
adjusted to left or
It is advisable not to keep horizontal flap at downward position for a long time in COOLor DRY
otherwise, condensate water might occur.
conditioner
Emergency Operation:
temperature is below 16
o
C, do not use it in the
T
est operation:
Use this switch in the test operation when the room
normal operation.
your finger from the switch: the cooling
Continue to press the test operation
switch for more than 5 seconds . After
you hear the "Pi" sound twice,
release
T
est operation switch is the same as emergency switch.
operation starts with the air flow speed "Hi".
Emergency operation and test operation
Use this operation only when the remote controller is de
fective or lost. When the emergency operation switch is pressed,the" Pi "sound is heard once
, which
the start of this operation.
In this operation, the system automatically selects
the
operation modes
,cooling or fan or heat,
according to the room temperature.
.
It is not possible to operate in dry mode.
Room
temperature
Operation
mode
Designated temperature
Timer
mode
Air flow
ABOVE 23
O
C
BELOW 23
O
C
COOLING
HEAT
23
O
C
26
O
C
NO
NO
AUTOMATIC
AUTOMATIC
(C
ooling only uint˅
Room temperature
Operation
mode
Designated temperature
Timer mode
Air flow
BELOW 23
O
C
FAN
26
O
C
NO
AUTOMATIC
at air outlet if all vertical louvers are
right.
mode ,
controller will automatically
Note:
set swing position.
means
changes as
Pi
Pi
Pi
SPEED
Operation
Mode
AUTO
e
tomeR
rellortn o C
Note
COOL
DRY
FAN
In DR
Y mode, when room temperature becomes
lower than temp.setting+2
o
C,unit will r
un intermittently
at LOW speed regardless of FAN setting.
Under the mode of auto oper
ation, air conditioner will automatically select Cool or Heat operation according to room temperature. air conditioner
automatically adjusts the fan speed
temperature.
When FAN is set to AUTO, the
according to room
In
FAN operation mode, the unit will not operate in COOL or HEAT mode but only in FAN mode ,AUTO is not available in FAN mode.And temp.setting is disabled. In FAN mode,SLEEP operation is not available.
Display
Board
Page 44
Operation
Sleep Operation
If the wind speed is high or middle before setting for the sleep, set for lowing the wind speed after sleeping.
If it is low wind, no change.
5.Set the wind speed change when sleeping
Operation Mode
1. In COOL,DR
Y mode
SLEEP oper
ation starts SLEEP operation stops
SLEEP oper
ation starts
SLEEP operation stops
Appro
x.6hrs
1 hr
1 hr
1 hr
3 hrs
3 hrs
Rises 1OC
Rises 1
O
C
Rises 1OC
Temp.setting
T
emp.setting
Unit stop
Unit stop
In COOL, DRY mode
In HEAT mode
Decreases 2OC
Decreases 2
O
C
1 hr
2.
3.
In HEA
T mode
In AUTO mode
4. In FAN mode
It has no SLEEP function.
Note
When TIMER function is set, the sleeping function can’t be set up .After the sleeping function is set u
p
,
TIMER function, the sleeping function will be cancelled; the machine will be in the state of
timing-on.
PO
WER/QUIET Operation
1 hours after SLEEP
mode starts,temp.will become higher than temp.setting.After another 1 hours,temp.rises by 1 futher.The unit will run for further
6 hours then stops Temp. is higher than temp.setting so that room temperature won’t be too low for your sleep.
1 hours after SLEEP mode starts,temp will become 2 lower than temp.setting.After another 1 hours,temp decrease by 2 rises
by 1 futher.The unit will run for further 3 hours then stops.Temp.is lower than temp. setting so that room temperature won’t be
too high for your sleep.
The unit operaters in corresponding sleep mode adapted to the automatically selected operation
mode.
O
C
O
C futher.After more another 3 hours,temp.
O
C
1
O
C
O
C
if user resets
Press button to enter additional options, when cycle display to , will flash.
And then press
enter to sleep function.
(1)
PO
WER Operation
(2)
QUIET Operation
N
ote ˖
When you need rapid heating or cooling, you can use this function.
You can use this function when silence is needed for rest or reading.
During POWER operation, in rapid HEAT or COOL mode
,
the room will show inhomogeneous temperature distribution.
Long period QUIET operation will cause effect of not too
cool or not too warm.
Press QUIET
button, the remote controller will show ,
and then achieve to the quiet function. Press again this
QUIET button , the quiet function will be cancelled.
Press button to enter additional options, when cycle display to , will flashand then press ,enter to
power function. When cancel the function, please enter
additional options again and to cancel power function.
Parts and Functions
42
Domestic Air
Conditioner
YJHJZH018BARRAFX-SM
Page 45
Operation
1.After unit starts, select your desired operation mode.
2.Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows: Remote controller:
BLANK
TIMER ON
TIMER OFF TIMER ON-OFF
Then select your desired TIMER mode (TIMER ON or TIMER OFF or TIMER ON-OFF). " "or " "will flash.
3.Press /
button to set time.
It can be adjusted within 24 hours.
Hints: After replacing batteries or a power failure happens, time setting should be reset.
According to the Time setting sequence of TIMER ON or TIMER OFF, either Start-Stop or Stop-Start can be achieved.
Timer On/Off On-Off Operation
CE
All the products are in conformity with the following European provision:
- Low Voltage Directive 73/23/EEC
- Low Voltage Directive 2006/95/EC
-Electomagnetic CompatibilitY 89/336/EEC
-Electomagnetic CompatibilitY 2004/108/EC
ROHS
The products are fulfilled with the requirements in the directive 2002/95/EEC of the European p
arliament and of council on the Restriction of the use of Certain Hazardous Substances in Electrical and Electronic Equipment (EU RoHS Directive)
WEEE
DISPOSAL
REQUIREMENTS:
Your air conditioning product is marked with this symbol.This means that electrical and electronic
products shall not be mixed with unsorted household waste. Do not try to dismantle the system yourself : the dismantling of the air
EUROPEAN
REGULATIONS
CONFORMITY FOR THE MODELS
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A GWP* value:1975 GWP=global warming potential Please fill in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
IMPOR
TANT INFORMATION REGA-
RDING THE REFRIGERANT USED
In accordance with the directive
2002/96/CE
of the European
parliament, herewith we inform the consumer about the dis­posal requirements of the electrical and electronic products.
conditioning system,treatment of the refrigerant, of oil and of other part must be done by a qualified installer in
accordance
with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative cons­equences for the environment and humen health. Please contact the installer or local authority for more information. Battery must be removed from the remote controller and dis­posed of separately in accordance with relevant local and nationl legislation.
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
Healthy airflow Operation
1.Press to starting
Setting the comf
ort work conditions.
2.The setting of healthy airflow function
Note:
1.After setting the healthy airflow function, the position
grill is fixed.
4.In cooling and dry, using the air conditioner for a long time under the high air humidity, condensate water may occur at the grille .
3.The cancel of the healthy airflow function
Notice: Do not direct the flap by hand. Otherwise, the grille will run incorrectly. If the grille is not run correctly, stop
for a minute and then start, adjusting by remote controller.
2.In heating, it is better to select the
3.In cooling, it is better to select the
mode. mode.
TIMER OFF-ON
0.5h
0.5h
0.5h
0.5h
Press the button for each time, setting time in the first 12 hours increased by 0.5 hour every time, after 12 hours,increased by 1 hour every time.
Press the button for each time, settiing time in the first 12 hours decreased by 0.5 hour every time, after 12 hours,decreased by 1 hour every time.
After adjust the time,press button and confirm the time ON or OFF button will not flash any more.
4.Confirm timer setting
5.Cancel timer setting Press the timer button by times until the time display eliminated.
Press button to enter additional options,Press this button continuously
, the louvers location will cycle between in the following three locations, to choose the swing location what you needed,and then press button to confirm.
Press button to enter additional options,Press this button continuously, the louvers location will cycle between in the following three locations again,and then press button to cancel.
Healthy airflow upwarder
Healthy airflow downwarder
Present position
Parts and Functions
43
Domestic Air
Conditioner
YJHJZH018BARRAFX-SM
Page 46
Maintenance
Setting of proper room temperature
Close doors and windows during operation
If the unit is not to be used for a long time, turn off the power supply main switch.
Use the timer eff
ectively
Use the lou
vers effectively
Do not block the air inlet or outlet
Proper
temperature
During cooling operation
prevent the penetration of
direct sunlight with
curtain or blind
OFF
Remote Controller
Indoor Body
1.Open the lnlet G
rille
2.Detach the standard air filter
3.Attach Air Purifying Filter
4.Attach the standard air filter
(Necessar
y installation)
5.Close the Inlet Gr
ille
Close the G
rille surely
Slide the knob slightly up
ward to
release the filter, then withdraw it.
Put air purifying filter appliances into the
right and left filter frames.
N
OTE:
The photocatalyst air purifying filter will be solarized in fixed
time. In normal family,
it will be solarized every 6 months.
Prop up the inlet grille by using a
small device named grille-support
ATTENTION:
Please keep the bacteria-killing medium air purifying filter in
avoid
long time directly sunshine
when you stop using it,or its ability of sterilization will
be
reduced.
The bacteria-killing medium air purifying filter will be used for a long time,no need for replacement. But in the period of using them ,you should remove the dust frequently by
which located in the right side of
the indoor unit.
using vacuum cleaner or flaping them lightly,otherwise ,
its performance will be affected.
the cool and dry conditions
For Smar
t Use of The Air Conditioner
Replacement of Air Purifying Filter
The white side of the photocatalyst air purifying filter face outside,and the black side face the unit
The green side of the bacteria-killing medium air purifying filter face outside,and the white side face the unit.
Do not usewater,wipe the controller with a dry cloth.Do not use glass
cleaner or chemical cloth.
wipe the air conditioner by using a soft and dry cloth.For serious stains,
use a neutral detergent diluted with water.Wring the water out of the cloth before wiping,then wipe off the detergent completely.
Air Filter cleaning
Open the inlet
grille by pulling it upward.
Remove the filter.
Clean the filter.
Attach the filter.
Close the inlet grille.
Push up the filter's center tab slightly until it is
from the stopper, and remove the filter do
wnw
ard.
Use a vacuum cleaner to remove dust, or wash the filter with water.After washing, dry the filter completely in the shade.
Attach the filter correctly so that the "FRONT" indication
facing to the front.Make sure that the filter is
fixed behind the stopper.If the right
attached correctly, that
Do not use the
following for cleaning
Gasoline,benzine, thinner or cleanser
ay
damage the coating of the unit.
Hot water over 40
O
C(104OF) m
ay
discoloring or deformation.
Once every two weeks
m
cause
released
is
completely and left filters are not
may cause defects.
Detach old Air Pu
rifying Filter
Installation
44
Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 47
the power supply cord and so on.
2.
Do not install in the place where there is any
possibility of inflammable gas leakage around the unit.
3.Do not
get the unit exposed
to vapor or oil steam.
Cautions
Please call Sales/Service Shop for the Installation.
Do not attempt to install the air conditioner by yourself because improper works may cause electric shock, fire, water leakage.
Connect the earth cable.
ear
thing
W
ARNING
When abnormality such as burnt-small found, immediately stop the operation button and contact sales shop.
OFF
Use an exclusive power source with a circuit breaker
ENFORCEMENT
Connect power supply cord to the outlet completely
Use the proper voltage
Do not use power supply cord in a bundle.
Take care not to damage
the power supply cord.
1.Do not use power supply cord extended or connected in halfway
STRICT
ENFORCEMENT
STRICT
STRICT
ENFORCEMENT
PROHIBITION
PROHIBITION
PROHIBITION
PROHIBITION
Do not start or stop the
operation by disconnecting
Do not channel the air flow directly at people, especially at infants or the aged.
Do not try to repair or reconstruct by yourself.
Do not use for the purpose of storage of food, art work, precise equipment, breeding, or cultivation.
CAUTION
Take fresh air occasionally especially when gas appliance is running at the same time.
PROHIBITION
STRICT
ENFORCEMENT
Do not operate the switch with wet hand.
PROHIBITION
PROHIBITION
PROHIBITION
PROHIBITION
PROHIBITION
Do not install the unit near a fireplace or other heating apparatus.
Check good condition of the installation stand
Do not pour water onto the unit for cleaning
PROHIBITION
Do not place animals or plants in the direct path of the air flow
Do not place any objects on or climb on the unit.
Do not place flower vase or water containers on the top of the unit.
Do not insert objects into the air inlet or outlet.
PROHIBITION
PROHIBITION
PROHIBITION
STRICT ENFORCEMENT
Check proper installation of the drainage securely
W
ARNING
Installation
45
Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 48
Trouble shooting
Normal Performance inspection
Noise is heard
Phenomenon
Cause or check points
The system
i
mmediately.
Smells are generated.
Mist or steam are
Multiple
check
Poor cooling
When unit is stopped, it won't restart
elapsed to protect the system. When the electric plug is pulled out
and reinserted, the protection circuit
During unit operation or at stop, a swishing or gurgling noise may
(This noise is generated by
refrigerant flowing in the system.)
During unit operation, a cracking noise may be heard.This noise is
temperature changes.
Should there be a big noise from
filter may be too dirty.
This is because the system circulates smells from the interior
During COOL or DRY operation,
This is due to the sudden cooling
Is power plug inserted? Is there a power failure? Is fuse blownout?
Is the air filter dirty?
Are there any obstacles before
Is temperature set correctly? Are there some doors or
Is there any direct sunlight through the window during the
Are there too much heat sources or too many people in the room
In dry mode,
fan speed can’t be changed.
In DRY mode, when room temperature
setting+2
o
C,unit will run
regardless of FAN setting.
during cooling operation?
cooling operation?(Use curtain)
windows left open?
inlet and outlet?
Normally it should be cleaned every 15 days.
intermittently at LOW speed
becomes
lower than temp.
indoor unit may blow out mist.
of indoor air.
air such as the smell of furniture, paint, cigarettes.
air flow in unit operation, air
generated by the casing expanding
or shrinking because of
be heard.At first 2-3 minutes after
unit start, this noise is more noticeable.
will work for 3 minutes to protect the
air conditioner.
immediately until 3 minutes have
Cautions
3. If the fuse of indoor unit on PC board is it with the type of
T
. 3.15A/ 250V
outdoor
broken,change it with the type of
T.25A/250V
Do not obstruct or c
over the ventilation
conditoner.Do not put fingers
inlet/outlet and
swing louver.
Do not allow children to play with the air
conditioner
case should children be
allowed to sit on the outdoor unit.
The refrigerating circuit is leak-proo f.
1.Applicable ambient temperature range:
Specifications
The ma
chine is adaptive in following
situation
The power plug and connecting cable
acquired the local
2. If the power supply cord is damaged, it
must be replaced
manufacturer
qualified
person.
4. The wiring method should be in line with
the local wiring
5. After installation, the power plug should
be easily reached.
6. The waste battery should be disposed
properly.
7. The appliance is not intended for use persons
without supervision.
8. Young children should be supervised
with
the appliance.
9. Please employ the proper power plug,
cord.
11.In order to protect the units,please turn 30 seconds
later, cutting off the power.
10.
Cooling
Indoor
Maxim
um:D.B/W.B
Maximum:D.B/W.B
D.B
Maximum:D.B
D.B
Minimum:D.B/W.B
Maximum:D.B/W.B Minimum:D.B/W.B
Outdoor
Indoor
Outdoor
Heating
32oC/23oC
24
o
C/18oC
o
C/-8oC
46
o
C/26oC
18
o
C
27
o
C
21
o
C/15oC
Outdoor
Maxim
um:D.B/W.B
Minimum:D.B
24
o
C/18oC
-15
o
C
(INVER
TER)
o
C
7
-
Minim
um:
Minimum:
g
rille of the air
or any other things into the
.In no
or its service agent or a similar
broken,please
. If the fuse of
standard.
by young children or
to ensure that th
ey
which fit into the
must have
off the A/C first,
Before asking for service, check the following first.
blown out.
does not restart
b
y the
change
unit is
infirm
do not play
p
ower supply
attestation.
and at least
15
Installation
46
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 49
Indoor Unit Installaion
D
riverƽ
Torque wrench
ƽ
(17mm,22mm,26mm)
Nipperƽ
Reamerƽ
Hacksawƽ
Pipe cutterƽ
Gasleakagedetectororƽ soap-and-water solution
Hole core drillƽ
Flaring toolƽ
Spanner(17,19 and 26mm)ƽ
Knifeƽ Measuring tapeƽ
NecessaryTools for Installation
Power Source
Be
fore inserting power
into receptacle, check the voltage without fail. The power
supply is the same as the
corresponding name plate.
Install an exclusive branch circuit of the power.
A receptacle shall be set up in a distance where the power cable can
be
reached.
Donotextendthecablebycuttingit.
Selection of Installation Place
Pla
ce, robust not causing vibration, where the body can be
supported suf¿ciently.
ƽ
Plac
e, not affected by heat or steam generated in the vicinity,
where inlet and outlet of the
unit are not disturbed.
ƽ
Plac
e, possible to drain easily, where piping can be conne-
cted with the outdoor unit.
ƽ
P
lace,wherecoldaircanbespreadin a roomentirely.
ƽ
Plac
e, nearby a power receptacle, with enough space around.
ƽ
Plac
e where the distance of more than lm from televisions,
radios, wireless apparatuses
a
nd Àuorescent lamps can be
left.
ƽ
I
n the case of ¿xing the remote controller on a wall, place
where the indoor unit can
receive signals when the Àuore-
scent
ƽ
lamps
in
the room are lightened.
ƽ
ƽ
ƽ
The distance between
theindoorunitandthe
Àoorshouldbemore
than 2m.
T
hemodelsadoptHFCfreerefrigerantR410A
more
than
10cm
more than 15cm
more
than 10cm
A
rrangement of piping
directions
Rear left
Left
Rear right
Right
Below
Attention must be paid to
the rising up of drain hose
R
emote controller (1)
R-
03 dry battery (2)
Mounting plate (1)
D
rain hose (1)
Ø4
X25 Screw
(4)
Plastic cap (4)
Accessory Parts
FOR 07K 09K 12K
FOR 18K
FOR 24K
Selection of Pipe
Drawing for the installation of indoor units
ƽ
Air purifying filter(Optional)
(1)
Please be subject to the actual product purchased,the above picture is just for your reference.
Installation
47
Domestic Air
Conditioner
YJHJZH018BARRAFX-SM
Page 50
Indoor Unit Installation
Fix to side bar and lintel a mounting bar, Which is separately sold, and
then
fas
ten the plate to the
xed mounting bar.
Ref
er to the previousarticle, “ When the mounting plate is
position o
f wall hole.
Make a hole of 70 mm in diameter, slightly descendingto outside the wall I
nstall piping hole cover and seal it off with putty after installation
1. Carry out, based on the neighboring p
illars or lintels, a
to be
xed ag
ainst the wall, then temporarily fasten the plate
with
one steel nail.
2. Make sure once more the proper level of the plate, by
hanging a thread
with a
weight from the central top of the plate, then fasten securely the
plate with
the
attachment steel nail.
3. Find the wall hole location A using a measuring tape
Wh
en the mounting plate is
xed side b
ar and lintel
Fitting of the Mounting Pla
te and
Positioning of the wall Hole
Lid for rig
ht
piping
Lid for under piping pipe
Fix with adhesive tape
L
id for left piping
Indoor/outdoor electric cableand drain hose must be bound with
efri
gerant
p
iping by protecting tape.
[ Other direction piping ]
Cut away,with a nipper, the lid for piping according to the piping
direction
and
then bend the pipe accord
ing to theposition of wall
hole. When bending, be
careful not to crash
pipes.
Connect beforehand the indoor/outdoor electric cable,and then
pull out the
connected to the heat insulation of connecting part
specially.
p
roper leveling
for
the plate
rst xed “,
f
or the
Makin
g a Hole on the Wall and Fitting the Piping Hole Cover
Drawing of pipe
Installat
ion of the Indoor Unit
[ Rear pi
ping ]
Draw pipes and the drain ho
se, then fasten them with the adhesive tape
[ Left·Left-r
ear piping ]
In case o
f left side piping, cut away, with a nipper, the lid for left
piping.
In case of left-re
ar piping, bend the pipes according to the piping
direction to
the mark of hole for left-rear pipingwhich is marked on
heat
insulation materials.
1. I
nsert the drain hose into the dent of heat insulationmaterials of
indoor
unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit,
and pul
l it
out on the front side, then connect them.
3. Coat the
ari
ng seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materialsclosely, and
make sure
x
ing with adhesive tape
Hang surely the unit body onto the upper
notches of the
mounting plate. Move the body
f
rom
side to side to verify its
securexing.
In order to
x the body onto t
he mounting
plate,hold up
the body aslant from the
u
nderside and
then put it down
perpendicularly.
R
emove terminal cover at rig
ht bottom corner of
indoor unit, then take
off wiri
ng cover by removing
its screws.
mounting plate
When you unload the indoor unit,please use your hand to arise
slightly and lift the unit aslant until it leaves the mounting plate.
agraffe
mounting plate
the body to leave agraffe,then lift the bottom of the body outward
Heat i
nsulation
material
Drain hose
Piping
Pipe supporting plate
Indoor/outdoor electric cable
I
ndoor side
Outdoor side
Ø
70mm
Wall hole
Thickness of wall
(Section o
f wall hole)
Piping hole pipe
G
When t
he mounting plate is
rst xed
Fixing the indoor unit body
Unloading of indoor unit body
Con
necting the indoor/outdoor Electric Cable
Removing the wiring cover
A=145mm
30mm
B=
70mm
Ø
A=150mm
B= 70mm
35mm
A=145mm
B=
70mm
Ø
30mm
Installation
48
Domestic Air Conditioner
AS18GN3ERA
YJHJZH018BARRAFX-SM
Page 51
1. Insert from outside the room cable into left side of the wall
hole,inwhichthepipehasalreadyexisted.
2.Pulloutthecableonthefrontside,andconnectthecable making a loop.
When connecting the cable, con¿rm the terminal number of indoor and outdoor units carefully. If wiring is not correct, proper operation can not
becarriedoutandwillcausedefect.
I
nsertthecablefromtheback
ƽ
s
ide of the u nit, t hen p ull it o ut
on the front side.
Loosen the screws and insert
ƽ
th
e cable ends fully into
terminal block, then
tighten the screw s.
Pull the cable slightly to
ƽ
make sure the cables have
been properly inserted and
tightened.
After the cable connection,
ƽ
n
everfailtofastentheconnectedcablewiththe
wiring cover.
W
hen connecting the cable after installing the indoor unit
When
connecting the cable before installing the indoor unit
Note:
1
.Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturerorits
service agent or a similar quali¿ed person. The type of connecting wire is H05RN-F
or H07RN-F.
2.IfthefuseonPCboardisbrokenpleasechangeitwiththe
type of
3.Thewiringmethodshouldbeinlinewiththelocalwiringstandard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into ¿ xedwiring.Thebreakershouldbe all-pole
switch and the distance between its two contactsshouldbenotless
than 3mm.
T.3.15A/250VAC (Indoor).
To Outdoor unit
Model
Connecting wiring
4G0.75mm
2
T
he power source must be exclusively used for air
ƽ
c
onditioner.
In the case of installing an air conditioner in a moist place,
ƽ
please install
an ea
For installation in other places, use a circuit breaker as far
ƽ
as
possible.
Pipecuttingiscarriedoutwith a pipecutterandbursmust beremoved.
After inserting the Àare nut, Àaring work is carried out.
Power Source Installation
Cut
ting and Flaring Work of Piping
Flare
tool for R410A Conventional Àare tool
Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A 0~ 0.5mm 1.0~1.5mm 1.5 ~2.0mm
rt
h leakage breaker.
Lean
Damage of Àare Partial Too outside
Co
rrect Incorrect
On Dra
inage
It
becomes
high midway.
The gap with the
ground is too small.
There is the bad smell from a ditch
It waves.
Theendisimm­ersedinwater.
P
leaseinstallthedrainhosesoastobedownwardslopewithoutfail.
Please don’t do the drainage as shown below.
ƽ
ƽ
Please
pour water in the drain pan of the indoor unit, and
ƽ
is
carried out surely to outdoor.
In case that the attached drain hose is in a room, please
ƽ
apply
heat
insulation
to
Less
than
5cm
co
n¿rm that
drainage
it without fail.
Crac
k
Indoor unit
Chec
k Items for Test Run
G
asleakfrompipeconnecting? Heat insulation of pipe connecting? Are the connecting wirings of indoor and outdoor ¿rmly
Is the connecting wiring of indoor and outdoor ¿rmly ¿xed? Is
drainage securely carried out?
Is
the earth line securely connected?
Is
the indoor unit securely ¿xed?
I
spowersourcevoltageabidedbythecode?
Is
there any noise?
I
s the lamp normally lighting? Are cooling and heating (when in heat pump) performed normally? I
s the operation of room temperature regulator normal?
Please
kindly explain to our customers how to
operate
throughtheinstructionmanual.
ins
erted to the terminal block?
Ƶ
Put
check mark
in
boxes
Flare
tooling die
1.Cut pipe
2.Remove burs
3.Insert the Àare nut
4.Flare pipe
ƽ
ƽ
On Dra
inage
Check for Installation and Test Run
Co
de
ind ic a tio n
Trouble description
Analyze and diagnose
E1
E2
E4
E7
E14
Indoor fan motor malfunction
Heat-exchange sensor failure
Indoor EE PRO M error
Com munication fault between indoor and outdoor units
Indoor fan motor malfunction
Operation halt due to breaking of w ire inside the fan motor; Operation halt due to breaking of the fan m oto r lea d wire s ; De te c tion erro r d ue to fau lty indoor unit P CB;
Indoor unit- outdoor unit
signal transmission error due to wiring error; Faulty PCB;
Faulty E EPRO M data; Faulty E EPRO M; Faulty PCB;
Faulty connector connection; Faulty thermistor; Faulty P CB;
Installation
renoitidnoC riA citsemoD94
YJHJZH018BARRAFX-SM
Page 52
Domestic air conditioner
50
Installation
Installation Manual of Room Air Conditioner
CE
All the products are in conformity with the following European provision:
- Low Voltage Directive 73/23/EEC
- Low Voltage Directive 2006/95/EC
-Electomagnetic CompatibilitY 89/336/EEC
-Electomagnetic CompatibilitY 2004/108/EC
ROHS
The products are fulfilled with the requirements in the directive 2002/95/EEC of the European p
arliament and of council on the Restriction of the use of Certain Hazardous Substances in Electrical and Electronic Equipment (EU RoHS Directive)
WEEE
DISPOSAL REQUIREMENTS:
Your air conditioning product is marked with this symbol.This means that electrical and electronic
products shall not be mixed with unsorted household waste. Do not try to dismantle the system yourself : the dismantling of the air
EUROPEAN
REGULATIONS
CONFORMITY FOR THE MODELS
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop value
A contains fluorinated greenhouse gases covered by the Kyoto
Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
IMPORTANT INFORMATION REGA­RDING THE REFRIGERANT USED
In accordance with the directive
2002/96/CE
of the European parliament, herewith we inform the consumer about the dis­posal requirements of the electrical and electronic products.
conditioning system,treatment of the refrigerant, of oil and of other part must be done by a qualified installer in
accordance
with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for reuse,
recycling and recovery. By ensuring this product is disposed
of correctly, you will help to prevent potential negative cons­equences for the environment and humen health. Please contact the installer or local authority for more information. Battery must be removed from the remote controller and dis­posed of separately in accordance with relevant local and
nationl legislation.
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
cover).
7.Installation
YJHJZH018BARRAFX-SM
Page 53
Please
be subject to the actual product purchased.
The above indoor and outdoor units’ picture is just for your reference.
F
A
C
E
D
O
ptional parts for piping
Non
-adhesive tape
Adhesive tape
Saddle(L.S)withscrews
Connecting electric cable
for indoor and outdoor
Drain hose
Heating insulating material
Piping hole cover
Fixing of outdoor unit
Fi
x the unit to concrete or block
ƽ
with
bolts (10mm) and nuts ¿rmly
and horizontally.
When ¿tting the unit to wall
ƽ
s
urface,rooforrooftop,¿x
asupportersurelywithnails
or wires in consideration of
earthquake and strong wind.
If vibration may affect the
ƽ
house
, ¿x the unit by attaching a
vibration-proof mat.
The
marks from to
in the ¿gure are the parts numbers. Thedistancebetween theindoorunitandthe Àoor should be more than 2m.
ThemodelsadoptHFCfreerefrigerantR410A.
more than 10cm
more than 15cm
more than 10cm
more than 20cm
more than 20cm
more than 25cm
more than
60cm
A
G
ƽ
ƽ
A
F
C
E
D
G
B
A
rrangement of piping
directions
Rear left
Left
Rear right
Right
Below
G
Attention must be paid to
the rising up of drain hose
For installation of the indoor units,refer to the installation manual which was provided with the units. (The diagram shows a wall-mounted indoor unit.)
AIR OUTLET
AIR INLET
CONNECTING PIPING
AND ELECTRICAL WIRING
DRAIN HOSE
4
ƽ
Compressor(Inside of Unit)
Installation
Domestic Air Conditioner
51
Indoor/Outdoor Unit Installa
tion Drawings
YJHJZH018BARRAFX-SM
Page 54
WARNING
CAUTION
Installation
Domestic air conditioner
52
Safety Precautions
YJHJZH018BARRAFX-SM
Page 55
Installation
Domestic Air Conditioner
53
Safety Precautions
YJHJZH018BARRAFX-SM
Page 56
Installation
Domestic Air Conditioner
54
Safety Precautions
Precautions for Handing Units for with R410A
YJHJZH018BARRAFX-SM
Page 57
Installation
55
Domestic
Air Conditioner
Safety Precautions
YJHJZH018BARRAFX-SM
Page 58
Installation
Domestic Air Conditioner
56
Read Before Installation
YJHJZH018BARRAFX-SM
Page 59
Installation
Domestic Air Conditioner
57
Read Before Installation
YJHJZH018BARRAFX-SM
Page 60
Installation
Domestic Air Conditioner
58
Read Before Installation
YJHJZH018BARRAFX-SM
Page 61
NO
Wind direction
Air outlet
Cushion rubber
4.Installation dimension(Unit:mm)
Installation
Domestic Air Conditioner
59
Installation Procedure
1U18EN2ERA
Model
1U09BS2ERA
1U12BS2ERA
W
D
H
L1
L2 L3
Power Wiring T
erminal
Power Wiring Distribution
YJHJZH018BARRAFX-SM
Page 62
1U09BS2ERA 1U12BS2ERA
1U18EN2ERA
1.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
T
obend a pipe,givetheroundnessaslargeaspossiblenottocrushthepipe,
ƽ
a
ndthebendingradiusshouldbe30to40
mm or longer.
Connecting the pipe of gas side ¿rst makes working easier.
ƽ
TheconnectionpipeisspecializedforR410A.
ƽ
Ha
lf union
Flare nut
Torque wrench
CA
UTION
Be
careful that matters, such as wastes of sand
s,water,
,etc.shallnotenterthepipe.
ThestandardpipelengthisCm.IfitisoverDm,thefunctionoftheunitwillbeaffected.Ifthepipe
has
tobelengthened,therefrigerantshouldbecharged,
according to E g/m. But the charge of refrigerant
must
beconductedbyprofes
sional air conditioner engineer. Before adding additional refrigerant,
perform
air
purgingfromtherefrigerantpipesandindoorunitusing a vacuumpump,then
Spanner
F
orced fastening without careful centering may
damagethethreadsandcause a leakageofgas.
Pip
e Diameter(Ǜ)Fasteningtorque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gasside12.7mm(1/2") 55N.m
Gasside15.88mm(5/8") 60N.m
Ma
x.Elevation:
Ɣ
In
case the elevation A is more
Ɣ
th
an 5m, oil trap shoud be installed every 5~7 Max. Length:
Ɣ
In
case the pipe length B is
Ɣ
more
thanDm, the refrigerant should be charged, according to E g/m.
C
onnection of pipes
charg
e
additional refrigerant.
Am
ax
Bmax
2.
Installation
Domestic air conditioner
60
1U18EN2ERA
Installation Procedure
Outdoor Unit
Amax
Bmax
C
D
E
1U09BS2ERA
1U12BS2ERA
10
15
5
7
20
10
15
5
7
20
10
15
5
7
20
YJHJZH018BARRAFX-SM
Page 63
Installation
Domestic Air Conditioner
61
Installation Procedure
Air
Tightness Test
YJHJZH018BARRAFX-SM
Page 64
(e.g.1U18EN2ERA)
Installation
Domestic air conditioner
62
YJHJZH018BARRAFX-SM
Page 65
1U09BS2ERA 1U12BS2ERA
1U18EN2ERA
T 25A/250V.
3
2
1
)
( N
)(
L
)(
C
3
2
1
)
( N
)
( L
)
(
C
To
Indoor unit
1U09BS2ERA 1U12BS2ERA
Model
Connecting wiring
Power cable
3G2.5mm
2
3G1.5mm
2
4G0.75mm
2
4G0.75mm
2
N
(
1
3
)
)C(
L(
2
)
{
L
N
POWER
Outdoor uni
t
To
Indoor unit
Outdoor uni
t
POWER
FOR 09K 12K
FOR 18K
Installation
Domestic air conditioner
63
1U18EN2ERA
YJHJZH018BARRAFX-SM
Page 66
15
Outdoor Unit
2
9
15
8
12
10
5
13
19
1
18
4
11
6
25
25
25
11
0
Suction temperature sensor failure
When the The wiring of compressor is wrong or the connection is poor
17
16
15
Lack of refrigerant
Check if there is leakage in the unit.
m
Installation
Domestic air conditioner
64
YJHJZH018BARRAFX-SM
Page 67
Service
Diagnosis
65
8.Service Diagnosis
8.1 Caution for Diagnosis
The operation lamp flashes when any of the following errors is detected.
1.When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions,
disabling equipment operation.
2.When a signal transmission error occurs between the indoor and outdoor units.In either case, conduct the
diagnostic procedure described in the following pages.
8.2.Problem Symptoms and Measures
Sy
mptR
m
C
heck Item Details of Measure
Check
the power supply. Check to make sure that the rated voltage is supplied.
None
of the units
operates
Check the indoor PCB Check to make sure that the indoor PCB is broken
Operation
sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles can stop air conditioner
operation.
Check
for faulty operation
of the electronic
expansion valve.
Set the units to cooling operation, and compare the
temperatures of the liquid side connection pipes of the
connection section among rooms to check the opening and
closing operation of the electronic expansion valves of the
individual units.
Equipment operates
but does not cool, or does not heat (only for heat pump)
Diagnosis by service port
pressure and operating
current.
Check for insufficient gas.
Large
operating noise and vibrations
Check the installation condition.
Check to make sure that the required spaces for installation (specified in the Technical Guide, etc.) are provided.
Domestic Air
Conditioner
YJHJZH018BARRAFX-SM
Page 68
66
8.4.Error Codes and Description indoor display
Service Diagnosis
Domestic Air Conditioner
Code indication
Indoor
displaying
panel code
indication
Outdoor
(LED1 flash
times)
fault description
Reference
Page
Indoor and Outdoor
E7 15
Communication fault between indoor and outdoor units
Page .76
E1 -- Room temperature sensor failure Page .67 E2 -- Heat-exchange sensor failure Page .67
86. egaP rorre MORPEE roodnI -- 4E
Indoor Malfunction
E14 -- Indoor fan motor malfunction Page .69
86. egaP rorre MORPEE roodtuO 1 21F
F1
2
17. egaP MPI fo noitcetorp ehT
F22
3 Overcurrent protection of AC electricity
for the outdoor model
Page .72
F3 4
Communication fault between the IPM and outdoor PCB
Page 73
F19 6 Power voltage is too high or low Page .74 F27 7 Compressor is lockrotor or stopt momentary -------
F4 8 Overheat protection for exhaust temperature Page .75 F8 9 Outdoor fan motor malfunction Page .72
F21 10 Frost-removing temperature sensor failure Page .74
F7 11 Suction temperature sensor failure Page .69 F6 12 Ambient temperature sensor failure Page .74
F25 13 Exhaust temperature sensor failure Page .74
F11 18 deviate from the normal
for the compressor Page .78
F28 19 Loop
of the station detect error Page .78
F2 24 Overcurrent of
the compressor Page .72
O
utdoor
Malfunction
F23 25
Overcurrent protection for single-phase of the compressor
Page .72
YJHJZH018BARRAFX-SM
Page 69
Service
Diagnosis
67
8.
4.1
Thermistor
or Related Abnormality
Indoor Display E1: Room temperature sensor failure
E2: Heat-exchange sensor failure
outdoor display LED1 flash 10 times
Frost-removing
temperature sensor failure
LED1 flash 11 times
Suction
temperature sensor failure LED1 flash 12 timesAmbient temperature sensor failure LED1 flash 13 times
Ex
haust temperature sensor failure
Method of The temperatures detected by the thermistors are used to determine thermistor errors Malfunction Detection
Malfunction when the thermistor input is more than 4.92V or less than 0.08V during compressor
.noitareponoisiceD
Conditions
Note:
The values vary slightly in some models
Supposed
Faulty
connector connection
Causes Faulty thermistor
Faulty
PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Thermistor resistance check method: Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester.The relationship between normal temperature and resistance is shown in the value of indoor thermistor.
Thermistor resistance check
Is
it normal?
Ye
s
NO
Ye
s
Is it normal?
NO
Check
the connector onnection.
Replace
the thermistor
Replace
the indoor unit PCB
Correct
the connection
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 70
Service
Diagnosis
68
8.4.2
EEPROM abnormal
Indoor
Display E4: indoor EEPROM error
Indoor display F12: Outdoor EEPROM error ;Outdoor LED1 flash 1 times
Method of The Data detected by the EEPROM are used to determine MCU Malfunction Detection Malfunction when the data of EEPROM is error or the EEPROM is damaged Decision Conditions
Supposed Ŷ Faulty EEPROM data Causes Ŷ Faulty EEPROM
Ŷ Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Replace
the indoor or outdoor mainboard
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 71
Service
Diagnosis
69
8.4.3
Indoor fan motor malfunction
Indoor Display
E14
Method of
The
rotation speed detected by the Hall IC during fan motor operation is used to determine
Malfunction
abnormal
fan motor operation Detection Malfunction
when
the detected rotation feedback singal don’t receiced in 2 minutes Decision Conditio
ns
Supposed
Ŷ Operation
halt due to breaking of wire inside the fan motor .
Causes
Ŷ Fan motor overheat protection
Ŷ Operation halt due to breaking of the fan motor lead wires Ŷ Detection error due to faulty indoor unit PCB
Troubleshooting
*
Caution
Be
sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Domestic Air Conditioner
Check
whether terminals
on indoor
p
cb
is well ?
Electrify
the machine again and turn it on in the cooling operation,
Measure voltage between the positions 1and 3 of Terminal CN5
on the indoor PCB
the
voltage is about 90-220vac
check
whether motor can run
when turn on the unit
the
indoor motor is damaged and need replace
Ye s
12
12
<HV
Measure
whether there is voltage pulse(0-5VDC)
between the positions middle wire and black wire
of Terminal CN2 on the indoor PCB
12
the indoor pcb is damaged and
need replace
Pull
out the terminals on the indoor
mainboard and reinsert them.
1R
<HV
Is
it ok?
<HV
YJHJZH018BARRAFX-SM
Page 72
Service
Diagnosis
8.4.4
Outdoor DC fan motor fault
Check
whether Terminal on the outdoor
mainboard is well inserted.
Is
it normal?
Ye
s
NO
Reins
ert the terminals
Electrify
the machine again and turn
itonintheCoolstatewiththeremote
controller. check whether motor can
run
Ye
s
Measure the voltage between 3 and 6 of
the terminal about 0-5v.
Is
it normal?
N0
the
motor of the outdoor unit is damaged
and needs replacing.
Measure the voltage between 1 and 3 of the terminal of
fan motor on the mainboard about DC310V,Measure
the voltage between 3 and 4 of the terminal about
DC15V. Measure the voltage between 5 and 3 of the
terminal about 1-6v.
NO
Is
it normal?
Th
e mainboard of the outdoor unit is
damaged and needs replacing
N0
Ye
s
Yes
renoitidnoCriAcitsemoD07
Out
door display LED1 flash 9 times
Method of DC fan motor is detected by checking the fan running condition and so on
Malfunction Detection
Malfunction when the data of EEPROM is error or the EEPROM is damaged
Decision
Conditions Supposed Ƶ DC fan motor protection dues to the DC fan motor faulty
Causes Ƶ DC fan motor protection dues to faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage
may be occurred.
YJHJZH018BARRAFX-SM
Page 73
Service
Diagnosis
8.4.5
IPM protection
Outdoor
display LED1 flash 2 times
Method of
IPM
protection is detected by checking the compressor running condition and so on Malfunction Detection
Malfunction
Ŷ The
system leads to IPM protection due to over current
Decision
Ŷ The
compressor faulty leads to IPM protection
Conditions
Ŷ circuit
component of IPM is broken and led to IPM protection
Supposed
Ŷ IPM protection dues to the compressor faulty
C
auses
Ŷ IPM
protection dues to faulty PCB of IPM module
Ŷ Compressor wiring disconnected
Troubleshooting
*C
aution
Be
sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on
with the remote controller,If malfunctions
are reported before or upon the
compressor being started up,
IPM
Module is damaged and
needs replacing.
1ǃThe
system may have been over or under charged with gas, which can be judged through the pressure of the
measuring system.
2ǃThe shaft of compressor is seized and the compressor needs replacing.
YE
S
NO
The
compressor is started normally, but
malfunctions are reported after it has run for
some time.
Malfunction
unsolved
71
Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 74
Service
Diagnosis
8.4.6
Over-current of the compressor
Out
door Display LED1 flash 3 or 24 or 25 times
Method of The current of the compressor is too high Malfunction Detection
Malfunction when the IPM Module is damaged Decision or the compressor is damaged Conditions power supply. voltage is too low or too high
Supposed Ŷ Faulty IPM Module Causes Ŷ Faulty compressor
Ŷ Faulty power supply
T
roubleshooting
*
Caution
Be
sure to turn off power switch before connect or disconnect connector, or
parts damage may be occurred.
Electrify the machine again and turn it on
with the remote controller,If malfunctions
are reported before or upon the
compressor being started up,
IPM
Module is damaged and
needs replacing.
Repair
the power supply
the
system may have been over or under
charged with gas, which can be judged through
the pressure of the measuring system.
YES
NO
Ye
s
NO
The
compressor is started normally,
but malfunctions are reported after it
has run for some time. Check the
power supply is too low or too high
NO
72
Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 75
Service
Diagnosis
8.4.7 The communication fault between IPM and outdoor PCB
Out
door displayLED1 flash 4 times
Method of
Communication
is detected by checking the IPM module and the outdoor PCB Malfunction Detection
Malfunction Ŷ
The
outdoor PCB broken leads to communication fault
Decision
Ŷ
The
IPM module broken leads to communication fault
Conditions
Supposed Ŷ
The outdoor PCB is broken
C
auses Ŷ
The
IPM module is broken
Ŷ
Communication wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else parts damage may be occurred.
1)
Check whether Terminal CN23 and CN24 on the outdoor mainboard
CN10 and CN11 on IPM module
2) Check whether the connected wire between IPM and outdoor
Are the
y good?
Electrif
y the machine again and turn it
on, Check whether the voltage between
1 and 2 of Terminal CN23 is about
DC5V, Check whether the voltage
between2 and 3 of Terminal CN23 is
about DC15V,
Replace the out
door mainboard with a new one
Replace
the outdoor IPM module
with a new one.
YE
S
NO
NO
YE
S
Malfunction
unsolved
1) Pull out and re
insert the terminals.
2) Replace connected wire
73 Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 76
Service
Diagnosis
8.4.8
Power Supply Over or under voltagve fault
out
door display: LED1 flash 6 times The power supply is over voltage
Method of
An
abnormal voltage rise or fall is detected by checking the specified voltage detection circuit. Malfunction Detection
Malfunction
An
voltage signal is fed from the voltage detection circuit to the microcomputer Decision Conditions
Supposed Ŷ
Supply
voltage not as specified
C
auses Ŷ
the
IPM module is broken
Ŷ
the
outdoor PCB is broken
Troubleshooting
*
Caution
Be
sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Electr
ify the machine again and turn it on with
the remote controller. Check whether the
compressor is started normall
y
Is
it ok?
Ye
s
May
be there is some disturbance
NO
No
~230 is ok?
Yes
Ye
s
This
question may be caused by the power.Repair
the power supply.
NO
Chan
ge the IPM module
Change
the IPM module
T
est the outdoor power supply
(+310VDC) with a multimeter.
check whether the power is
>150 V or <390V?
74
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 77
Service
Diagnosis
8.4.9
Overheat Protection For Exhaust Temperature
out
door display LED1 flash 8 times
Method of
The
exhaust temperature control is checked with the temperature being detected
Malfunction
by
the exhaust pipe thermistor Detection Malfunction
when
the compressor discharge temperature is above 110ć
Decision Conditions Supposed Ŷ
Electroni
c expansion valve defective
C
auses Ŷ
Faulty
thermistor
Ŷ
Faulty
PCB
Troubleshooting
*
Caution
Be
sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify
the machine again and turn it on with the remote controller,
then measure the temperature at the exhaust temperature sensor of
the compressor on the outdoor unit
the
temperature exceeds
110 ć shortly after the
machine starts u
p
?
1)
The cryogen may have been leaked during
installation, or there may be leakage in the piping
system.
2) There may be other causes to make the exhaust
temperature too high.
Malfunctions
occur after running for some time even
though the measured temperature is below 110ć. Pull
out the exhaust sensor and measure its resistance at
standard temperatures according to the
resistance-temperature table
the
results deviate
much?
The
sensor is damaged. Replace the sensor
with a new one.
The
outdoor mainboard is damaged and needs be
re
p
laced
YE
S
NO
NO
YES
75
Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 78
Service
Diagnosis
8.4.10 The co
mmunication fault between indoor and outdoor
Indo
or display
E7
outdoor display
LED1 flash 15 times
Method of
Communication
is detected by checking the indoor PCB and the outdoor PCB Malfunction Detection
Malfunction Ŷ
The
outdoor PCB broken leads to communication fault
Decision
Ŷ
The
indoor PCB broken leads to communication fault
Conditio
ns
Supposed Ŷ Communication wiring disconnected Causes Ŷ
The
indoor PCB is broken
Ŷ
The
outdoor PCB is broken
Ŷ
The
Module PCB is broken
Troubleshooting
*C
aution
Be
sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
NO
˄A˅
Ye
s
NO
Yes
No
YES
Rest
art the a/c and it
becomes normally.
If
starting up normally, but
malfunction occurs again after a
while
Check
whether the linking cable
between the indoor and outdoor is well
connected or whether its core wires are
well insulated.
The out
door mainboard needs
dehumidification.
The out
door mainboard needs
dedust.
1.
Reconnect the linking cable;
2. Replace the linking cable with new
one.
76
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 79
Service
Diagnosis
˄A˅
NO
YES
Yes
No
If the voltage is of a constant
value of 0V DCto5V DC
YES
measure
the voltage between Jumpers 3 and
4 of IC1 on the indoor mainboard with a
multimeter.
NO
The out
door mainboard is damaged;
Replace them with a new one.
measure
the AC voltage between positions 1
and 3 on the terminal of outdoor unit with a
multimeter.
If 230V
AC is available but 310DC not,
the power module is damaged, replace it
with a new one.
T
est the outdoor power supply (230VAC
and +310VDC) with a multimeter.
The out
door mainboard is damaged; replace
it with a new one.
The
indoor mainboard is damaged; replace
it with a new one.
If
the value varies between 0 and 80 VAC, the
outdoor mainboard is damaged, replace it
with a new one.
If
the value is constant at about 30V, the
indoor mainboard is damaged, replace it with
a new one.
If both 230V
AC and 310DC are
available,measure +12V(from7805)
is available.
77
Domestic
Air Conditioner
Check the indoor mainboard
YJHJZH018BARRAFX-SM
Page 80
8.4.11Loss
of synchronism detection
Inverter
side current detection is abnoraml
Outdoor Display
LED1 flash 18 times
LED1 flash 19 times
Met
hod of The position of the compressor rotor can not detected normally Malfunction Detection
Malfunction when the wiring of compressor is wrong or the connection is poor;
Decision or the compressor is damaged
Conditions
Supposed Ŷ Faulty The wiring of compressor Causes Ŷ Faulty compressor
Ƶ
Faulty
PCB
T
roubleshooting
*
Caution
Be
sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Within
3 minutes after the machine is supplied with power and turned on with the remote controller,check whethe
r
the compressor can stard up
1.
The wiring of compressor is incorrect
or the connection is poor;
2. The compressor is damaged
At
frist, the compressor start up ,soon the
compressor stopped with the LED1 on the outdoor PCB blinks˄1Hz˅19/18 times
IPM
Module is damaged and needs
replacing.
the
Malfunctions exist also, the compressor is damaged replace a new one
YE
S
NO
YE
S
Malfunction
unsolved
Ma
ybe there is some disturbance
Service Diagnosis
78
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 81
8.4.12
High work-intense protection
Outdoor display LED1 flash 21 times
Method of
High work-intense control is activated in the heating mode if the temperature
Malfunction
being
sensed by the heat exchanger thermistor exceeds the limit.
Detection
Malfunction
Activated
when the temperature being sensed by the heat exchanger
Decision
rises
above 65ć twices in 30 minutes.
Conditio
ns
Supposed Ŷ
Faulty
electronic expansion valve
C
auses Ŷ
Dirt
y heat exchanger
Ƶ
Faulty
heat-exchange sensor
Ƶ
Insuf
ficient gas
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify
the machine again and turn it on with the
remote controller, check whether the wind temperature is below 65ć
the malfunction is reported after the machine has run for some time?
1 ǃ Ch
eck room temperature and
pipe temperature sensor. 2ǃthe temperature monitoring circuit of the indoor mainboard
the
indoor unit blows poorly due to blocked filters or poor condition of the fan?
1) Clean the filters
2) Reinstall the fan.
Use
some tools to measure the pressure of systemˈ
YE
S
NO
YES
NO
Service Diagnosis
79
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 82
Remova
l Procedure
Removal of indoorunit
80
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 83
81
Domestic
Air Condiioner
YJHJZH018BARRAFX-SM
Page 84
Please close the panels before start the removal procedure of front grille.
Slide the front panel from one side to another to release each axis.
Open the front panel until it is on the horizontal position, and then release the pivots on both sides of the unit to remove the front panel.
Remova
l Procedure
82
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 85
three
two
Remova
l Procedure
HOOKS
83
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 86
flap
flap
flap
flap
Removal
Procedure
84
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 87
Removal
Procedure
85
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 88
Removal
Procedure
86
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 89
Removal
Procedure
87
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 90
Removal
Procedure
88
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 91
Removal
Procedure
89
Domestic Air Conditioner
YJHJZH018BARRAFX-SM
Page 92
Removal
Procedure
90
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 93
Removal
Procedure
91
Domestic
Air Conditioner
YJHJZH018BARRAFX-SM
Page 94
92
Domestic air conditioner
Removal of procedure
9.2 The removal procedure of outdoor
9.2.1 Removal of Outdoor panel
stnioPerudecorPpetS
1. Features 1 Loosen the service
cover screw and
remove the service
cover.
Be careful not to
YJHJZH018BARRAFX-SM
Page 95
93
Domestic air conditioner
Removal of procedure
stnioPerudecorPpetS
2. Remove the panels.
1
Loosen the 4 screws
and lift the top panel
2
Loosen the screws
of the panel.
3
Pull and remove
the front panel.
YJHJZH018BARRAFX-SM
Page 96
94
Domestic air conditioner
Removal of procedure
9.2.2 Romoval of Electrcal Box
stnioPerudecorPpetS
screws, then lift
the electrical box
YJHJZH018BARRAFX-SM
Page 97
95
Domestic air conditioner
Removal of procedure
9.2.3 Romoval of the Side panel
stnioPerudecorPpetS
1
screws and remove
the side panel.
YJHJZH018BARRAFX-SM
Page 98
96
Domestic air conditioner
Removal of procedure
stnioPerudecorPpetS
2
Remove the
3 screws and remove
the side panel.
YJHJZH018BARRAFX-SM
Page 99
97
Domestic air conditioner
Removal of procedure
stnioPerudecorPpetS
1
Loosen the
remove the fan
Put the lead wire
of motor when
the propeller fan)
9.2.4 Removal of fan and fan motor
YJHJZH018BARRAFX-SM
Page 100
98
Domestic air conditioner
Removal of procedure
stnioPerudecorPpetS
2
screws and lift
the fan motor
.
YJHJZH018BARRAFX-SM
Loading...