Johnson Controls YICS015B21S, HICS030B21S, HICS015B21S, HICS036B21S, YICS024B21S Installation And Maintenance Manual

...
Page 1
Installation
and
Maintenance
Manual
INVERTER-DRIVEN
MULTI-SPLIT SYSTEM
HEAT PUMP
Type Model
(H,Y,C)ICS015B21S
Ceiling Suspended
(H,Y,C)ICS024B21S (H,Y,C)ICS030B21S (H,Y,C)ICS036B21S
IMPORTANT:
READ AND UNDERSTAND THIS MANUAL BEFORE INSTALLING THIS HEAT PUMP AIR CONDITIONER. KEEP THIS MANUAL FOR FUTURE REFERENCE.
P5417058
Page 2
ATTENTION
Each model number and all matching model numbers within a system must have the same version of software.
Follow these steps to verify that your product model numbers have the same version of software.
• Access the main printed circuit board in each product.
• Locate a white sticker with a P-XXXX number or
• Connect a service checker and locate the ROM number.
For further assistance, please contact our Technical Support Center at 1 (844)
873-4445 and select Option 2.
Page 3
Important Notice
Johnson Controls, Inc. pursues a policy of continuing improvement in design and performance in its products. As such, Johnson Controls reserves the right to make changes at any time without prior notice.
Johnson Controls cannot anticipate every possible circumstance that might involve a potential hazard.
This heat pump air conditioning unit is designed for standard air conditioning applications only. Do not use this unit for anything other than the purposes for which it was intended.
The installer and system specialist shall safeguard against leakage in accordance with local
pipetter and electrical codes. The following standards may be applicable, if local regulations are
not available. International Organization for Standardization: (ISO 5149 or European Standard, EN
378). No part of this manual may be reproduced in any way without the expressed written consent of Johnson Controls.
This heat pump air conditioning unit is operated and serviced in the United States of America and comes with a full complement of the appropriate Safety, Dangers, Cautions, and Warnings.
If you have questions, please contact your distributor or dealer.
This manual provides common descriptions, basic and advanced information to maintain and service this heat pump air conditioning unit which you operate as well for other models.
This heat pump air conditioning unit has been designed for a specic temperature range. For optimum performance and long life, operate this unit within the range limits according to the table below.
Temperature
Maximum Minimum
Cooling Operation
Heating Operation
DB: Dry Bulb, WB: Wet Bulb
* The temperature may change depending on the outdoor unit.
Indoor 89
Outdoor 118
Indoor 80
Outdoor 59
o
F DB/73oF WB (32oC DB/23oC WB) 69oF DB/59oF WB (21oC DB/15oC WB)
o
F DB (48oC DB) * 14oF DB (-10oC DB) *
o
F DB (27oC DB) 59oF DB ( 15oC DB)
o
F WB (15oC WB) * -4oF WB (-20oC WB) *
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment.
Product Inspection upon Arrival
1. Upon receiving this product, inspect it for any damages incurred in transit. Claims for damage, either
apparent or concealed, should be led immediately with the shipping company.
2. Check the model number, electrical characteristics (power supply, voltage, and frequency rating), and any accessories to determine if they agree with the purchase order.
3. The standard utilization for this unit is explained in these instructions. Use of this equipment for purposes other than what it is designed for is not recommended.
4. Please contact your local agent or contractor as any issues involving installation, performance, or
maintenance arise. Liability does not cover defects originating from unauthorized modications
performed by a customer without the written consent of Johnson Controls, Inc. Performing any mechanical alterations on this product without the consent of the manufacturer will render your warranty null and void.
P5417058-rev.1
i
Page 4
TABLE OF CONTENTS
1. Introduction ........................................................................................................................................................... 1
2. Safety Instructions ................................................................................................................................................ 1
3. Before Installation ................................................................................................................................................. 8
3.1 Combinations of Outdoor Unit and Indoor Unit ............................................................................................ 8
3.2 Transportation and Handling ........................................................................................................................ 8
3.3 Factory-Supplied Accessories ...................................................................................................................... 9
4. Installation Work ................................................................................................................................................. 12
4.1 Position of Suspension Bolts ...................................................................................................................... 12
4.2 Installation of Suspension Bolts ................................................................................................................. 12
4.3 Mounting Indoor Unit .................................................................................................................................. 13
4.4 Installation of Wired Controller ................................................................................................................... 14
5. Refrigerant Piping Work ...................................................................................................................................... 15
5.1 Piping Materials .......................................................................................................................................... 15
5.2 Piping Connection ...................................................................................................................................... 15
5.3 Piping Connection Work ............................................................................................................................. 17
5.3.1 Position of Piping Connection ........................................................................................................... 17
5.3.2 Access of Piping Connection ............................................................................................................ 18
6. Condensate Piping .............................................................................................................................................. 19
7. Electrical Wiring .................................................................................................................................................. 22
7.1 General Check ........................................................................................................................................... 22
7.2 Electrical Wiring Capacity ........................................................................................................................... 22
7.2.1 Field Minimum Wire Sizes for Power Supply .................................................................................... 22
7.2.2 Details of Electrical Wiring Connection ............................................................................................. 23
7.3 Position of Electrical Wiring Connection ..................................................................................................... 24
7.4 Caution for Electrical Wiring ....................................................................................................................... 26
7.5 Wiring Connections .................................................................................................................................... 27
7.6 DIP Switch Settings .................................................................................................................................... 28
7.7 Function Selection by Wired Controller ...................................................................................................... 30
7.8 Setback Operation ...................................................................................................................................... 31
8. Test Run .............................................................................................................................................................. 32
8.1 Before Test Run .......................................................................................................................................... 32
8.2 Test Run ..................................................................................................................................................... 32
8.3 Alarm Codes ............................................................................................................................................... 36
ii
P5417058-rev.1
Page 5
1. Introduction
Read following sections carefully before installing this product.
Read over the "Installation and Maintenance Manual" for the outdoor unit as well.
Forward this information, and the warranty to all installers and users. Ask end users to maintain copies for future reference.
(Refrigerant Piping Work) (Electrical Wiring Work) (Ref. Charge Work) (Test Run) (User)
● For details on wiring between the indoor unit and the outdoor unit, refer to the "Installation and Maintenance Manual" for the outdoor unit.
● For details on the optional controller, refer to the "Installation and Maintenance Manual" for that optional
controller module.
● For details on each optional part, refer to the "Installation and Maintenance Manual" for each optional part.
● For central controller, refer to the "Installation and Maintenance Manual" for the central controller.
2. Safety Instructions
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions
This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be
qualied according to local, state and national building and safety codes and regulations. Incorrect installation could cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance requirements are specied, the appropriate measures should be taken during installation to guard
against possible damage or injury that might occur in an earthquake if the unit is not installed correctly, injuries may occur due to a falling unit. Suspend pipes at certain points and reinforce against earthquakes so that they will not be damaged by an external force. Check local codes and regulations.
Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and, where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
for electrical operation purposes. Keep a wet cloth and a re extinguisher nearby during brazing. Use
care in handling, rigging, and setting of bulky equipment.
When transporting, be careful when picking up, moving and installing these units. Although the unit may be packed using plastic straps, do not use them for transporting the unit from one location to another. Do not stand on, or put any material on, the unit. Get a partner to help, and bend with
your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum ns on the air conditioner can cut ngers, so wear protective gloves.
thoroughly and follow all warnings or cautions included in all manuals that accompanied the product and are attached to the unit. Refer back to
these safety instructions as needed.
P5417058-rev.1
1
Page 6
Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features, disengagement, and interlocks must be in place and functioning correctly before the equipment is put into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident can occur. Never bypass or jump-out any safety device or switch.
Before servicing, turn-OFF the power supply and use accepted lockout and tag out procedures at all main switches.
This unit is a pressurized system. Never loosen threaded joints while the system is under pressure and never open pressurized system parts.
Johnson Controls will not assume any liability for injuries or damage caused by not following steps
outlined or described in this manual. Unauthorized modications to Johnson Controls' products are
prohibited as they…
May create hazards that could result in death, serious injury or equipment damage. Will void product warranties. May invalidate product regulatory certications. May violate OSHA standards.
Take the following precautions to reduce the risk of property damage.
Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant system during installation work. Foreign matter could damage internal components or cause blockages.
If air lters are required on this unit, do not operate the unit without the air lter set in place. If the air
lter is not installed, dust may accumulate and breakdown may result.
Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules attach themselves to the surface of the heat exchanger, the nned surfaces repel water. As a result, any amount of drainage moisture condensate can overow from the condensate pan and could run
inside of the electrical box, possibly causing electrical failures.
When installing the unit in a hospital or other facility where electromagnetic waves are generated from nearby medical and/or electronic devices, be prepared for noise and electromagnetic interference (EMI). Do not install where the waves can directly radiate into the electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment, and radio communications equipment may cause the unit to malfunction. The operation of the unit may also adversely affect these same devices. Install the unit at least 10 ft. (3m) away from such devices.
When a wireless controller is used, locate at a distance of at least 3.3 ft. (1m) between the indoor unit
and electric lighting. Otherwise, the receiver part of the unit may have difculty receiving operation
commands.
If the wired controller is installed in a location where electromagnetic radiation is generated, make sure that the wired controller is shielded and cables are sleeved inside conduit tubing.
If there is a source of electrical interference near the power source, install noise suppression
equipment (lter).
Do not install the unit in any location where animals and plants can come into direct contact with the outlet air stream. Exposure could adversely affect the animals and plants.
Do not install the unit with any downward slope to the side of the drain adapter. If you do, you may
have condensate water owing back, which may cause leaks.
Be sure the condensate hose discharges water properly. If connected incorrectly, it may cause leaks.
Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These specialized oil-resistant units can be ordered for such applications. However, in places where large quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used. These products should not be installed in such locations.
2
P5417058-rev.1
Page 7
Installation Precautions
To reduce the risk of serious injury or death, the following installation precautions must be followed.
When installing the unit into…
A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and oors.
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable wind bafe.
A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow.
Provide snow protection hood.
Do not install the unit in the following places. Doing so can result in an explosion, re, deformation, corrosion, or product failure.
Explosive or ammable atmosphere Where a re, oil, steam or powder can directly enter the unit, such as nearby or above a kitchen
stove. Where oil (including machinery oil) may be present. Where corrosive gases such as chlorine, bromine, or sulde can accumulate, such as near a hot
tub or a hot spring. Where dense, salt-laden airow is heavy, such as in coastal regions. Where the air quality is of high acidity. Where harmful gases can be generated from decomposition.
Do not install the motion sensor kit in the following places. It may cause failure or deterioration of the sensor.
Ambient temperature changes drastically. Where excessive force or vibration is applied to the sensor. Where static electricity or electromagnetic waves may generate. Where interference of infrared light such as glasses or mist is in the detecting area. Where the lens for sensor is exposed in high temperature and humidity for a long time. Where uid and corrosive gas exist. Where light such as sunlight or direct light affects the sensor. Where hot air from a heater, or something similar directly affects the sensor. Where the airow bounces back to the sensor by hitting obstacles such as shelf or locker. Where blower devices such as a ceiling fan or ventilating fan affect the airow from the indoor
unit. Where weather directly affects the surface of the sensor. Where the lens surface may smudge or be damaged from something like a dusty environment.
Detecting function decreases, if the lens sensor has smudges.
In this case, wipe off smudges using a cotton swab soaked with alcohol or a soft cloth. Isopropyl
alcohol is recommended. (When wiping off smudges on the lens sensor, do not apply excessive
force. If excessive force is applied, the resin lens may be damaged and this may cause
malfunctions such as misdetection or undetectable motion.)
Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause respiratory injuries. If the condensate pipe is installed incorrectly, water leakage and damage to the
ceiling, oor, furniture, or other possessions may result. If the condensate pipe becomes clogged,
water may drip from the indoor unit. Do not install the indoor unit where such dripping can cause moisture damage such as uneven locations. Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the unit to prevent water damage and abnormal vibration.
P5417058-rev.1
3
Page 8
Before performing any brazing work, be sure that there are no ammable materials or open ames nearby.
Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective
devices must be in place while the compressor/unit is operating. During the test run, keep ngers and
clothing away from any moving parts.
Clean up the site when nished, remembering to check that no metal scraps or bits of wiring have been left inside the unit being installed.
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use and maintenance of this unit to the customer according to the information in all manuals that came with the system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant precautions must be followed.
As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls. uses only refrigerants that have been approved for use in the unit’s intended home country or market. Johnson Controls' distributors similarly are only authorized to provide refrigerants that
have been approved for use in the countries or markets they serve. The refrigerant used in this unit
is identied on the unit’s faceplate and/or in the associated manuals. Any additions of refrigerant into this unit must comply with the country’s requirements with regard to refrigerant use and should be obtained from Johnson Controls' distributors. Use of any non-approved refrigerant substitutes will void
the warranty and will increase the potential risk of injury or death.
If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum allowable concentration in the event that refrigerant gases should escape. The installation should meet the requirements in ASHRAE Standards 15 and 34. If refrigerant gas has leaked during the installation work, ventilate the room immediately.
Check the design pressure for this product is 601 psi (4.15MPa). The pressure of the refrigerant R410A is 1.4 times higher than that of the refrigerant R22. Therefore, the refrigerant piping for
R410A shall be thicker than that for R22. Make sure to use the specied refrigerant piping. If not, the
refrigerant piping may rupture due to an excessive refrigerant pressure. Besides, pay attention to the piping thickness when using copper refrigerant piping. The thickness of copper refrigerant piping differs depending on its material.
The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
as moisture, oxide lm, (or fat). Perform the installation work with care to prevent moisture, dust, or
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the cycle from such parts as expansion valve and the operation may be unavailable.
To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the sizes of the charging connections have been changed from R407C type and R22 type. It is necessary to prepare the following tools listed in Section 3 before performing the installation work. Use refrigerant pipes and joints that are approved for use with R410A.
Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open ames and contact your service contractor. Refrigerant (uorocarbon) for this unit is odorless. If the refrigerant should leak and come into contact with open ames, toxic gas could be generated. Also, because the uorocarbons are heavier than air, they settle to the oor, which could cause asphyxiation.
When installing the unit, and connecting refrigerant piping, keep all piping runs as short as possible, and make sure to securely connect the refrigerant piping before the compressor starts operating. If the refrigerant piping is not connected, and the compressor activates with the stop valve opened, the
refrigerant system is subjected to extremely high pressure, which can cause an explosion or re.
Tighten the are nut with a torque wrench in the specied manner. Do not apply excessive force to the are nut when tightening. If you do, the are nut can crack and refrigerant leakage may occur.
4
P5417058-rev.1
Page 9
A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is under pressure and never open pressurized system parts.
When maintaining, relocating, or disposing of the unit, dismantle the refrigerant piping after the compressor stops.
When pipes are removed from under the piping cover, after the insulation work is completed, cover
the gap between the piping cover and pipes using a packing (eld-supplied). If the gap is not covered,
the unit may be damaged if snow, rain water or small animals enter the unit.
Do not apply an excessive force to the stop valve at the end of opening. Otherwise, the stop valve
ies out due to refrigerant pressure. At the test run, fully open the gas and liquid valves. Otherwise,
these devices become damaged. (It is closed before shipment.)
If the arrangement for outdoor units is incorrect, it may cause owback of the refrigerant and result in failure of the outdoor unit.
o
The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15
.
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, re or
explosion resulting in serious injury or death.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause serious injury or death.
Perform all electrical work in strict accordance with this installation and maintenance manual and all relevant regulatory standards.
Do not open the service cover or access panel to indoor or outdoor units without turning OFF the main power supply. Before servicing, open and tag all disconnect switches. Never assume electrical power is disconnected. Check with a meter and equipment.
Only use electrical protection equipment and tools suited for this installation.
Use specied cables between units.
Do not run the relay wiring for the motion sensor and power supply wiring in parallel. Electromagnetic Interference (EMI) may cause malfunction of the sensor.
Communication cable should be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper. Shielded cable must be considered for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors. When shielded cable is applied, proper bonding and termination of the cable shield is required as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be considered per application and local code requirements.
Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
Be sure to install circuit breakers (ground fault interrupter, isolating switch, molded case circuit
breaker and so on), with the specied capacity. Ensure that the wiring terminals are tightened securely to recommended torque specications. If a circuit breaker or fuse is frequently activated,
shut down the system and contact your service contractor.
The polarity of the input terminals is important, so be sure to match the polarity when using contacts that have polarity.
Before installing the controller or remote devices, ensure the indoor and outdoor unit operation has
been stopped. Further, be sure to wait at least ve minutes before turning OFF the main power switch
to the indoor or outdoor units. Otherwise, water leakage or electrical breakdown may result.
Clamp electrical wires securely with a cable band after all wiring is connected to the terminal block. In addition, run wires securely through the wiring access channel.
When installing the power lines, do not apply tension to the cables. Secure the suspended cables at regular intervals, but not too tightly.
Make sure that the terminals do not come into contact with the surface of the electrical box. If the terminals are too close to the surface, it may lead to failures at the terminal connection.
P5417058-rev.1
5
Page 10
Turn OFF and disconnect the unit from the power supply when handling the service connector. Do not open the service cover or access panel to the indoor or outdoor units without turning OFF the main power supply.
After stopping operation, be sure to wait at least ve minutes before turning off the main power switch. Otherwise, water leakage or electrical breakdown may result. Disconnect the power supply
completely before attempting any maintenance for electrical parts. Conrm that no residual voltage is
present after disconnecting the power supply.
Do not clean with, or pour water into, the controller as it could cause electric shock and/or damage the unit. Do not use strong detergent such as a solvent. Clean with a soft cloth.
Check that the ground wiring is securely connected. Do not connect ground wiring to gas piping, water piping, lighting conductor, or telephone ground wiring.
If a circuit breaker or fuse is frequently activated, shut down the system and contact your service contractor.
This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized measure for added protection to a properly grounded unit. Install appropriate sized breakers / fuses / overcurrent protection switches, and wiring in accordance with local, state and NEC codes and requirements. The equipment installer is responsible for understanding and abiding by applicable codes and requirements.
6
P5417058-rev.1
Page 11
● Proper handling of this unit requires two people. Safe handling and installation of the indoor unit requires
NOTICE
the strength of two people. Mounting the unit alone may cause injury due to a fall of the unit. Although the
unit may be girded with steel banding, do not use it for transportation. Avoid contact with nned surfaces of the heat exchanger as sharp edges can cause severe injury to hands and ngers. Use appropriate
work gloves for the job.
● Check to ensure that the condensate hose discharges moisture properly. If connected incorrectly, it can
result in leakage and damage to property.
● Make sure to use the factory-supplied condensate hose and hose clamp. Other makes can cause moisture leakage.
● Do not bend or twist the factory-supplied condensate hose. This could compromise the seal and result in moisture leakage.
● Do not apply an excessive force to the condensate pipe connection. This can also compromise the seal
properties of the connection.
● Verify that the installed unit is level with oor and ceiling surfaces. Any variance or inclination can cause
moisture to back up into the condensate pan, overow, and seepage onto ceiling or wall surfaces, and
cause damage to carpeted surfaces or furniture below.
● Do not install this system in close proximity to septic sewer lines where ammable and toxic gases can coalesce.
Inspect the condensate pan before the onset of winter to drain away all accumulated moisture in the pan.
● The heat exchanger of indoor units overheats whenever there is a slight amount of refrigerant circulating
during slowdown or stoppage. As a result, moisture in the condensate pan evaporates where it can affect ceiling or wall surfaces.
● After the drain check is completed, insert the rubber plug again and seal the gap with a silicon sealant.
Electrical Installation
In some cases, the packaged air conditioner may not be operated normally under the following cases:
● When electrical power for the packaged air conditioner is supplied from the same power transformer as the external equipment.
● When the power supply wiring for the external equipment and the packaged air conditioner are located close to each other.
Regarding that mentioned above, surge voltage may be inducted into the power supply wiring for the crated
unit due to a spike in power consumption for this device and an activation of the switch. Check the eld
regulations and standards before performing any electrical work in order to safeguard the power supply for the crated air conditioner unit.
P5417058-rev.1
7
Page 12
3. Before Installation
Air Inlet Grille
Side Cove
Louver
Side Cover
Securing Screw (M4)
Position for Securing Screw
(three)
3.1 Combinations of Outdoor Unit and Indoor Unit
The combination capacity of the indoor unit against the outdoor unit is selected depending on the outdoor unit capacity. Refer to the “Installation and Maintenance Manual” for the outdoor unit to decide the required combination of indoor and outdoor units, and the combination unit capacity.
3.2 Transportation and Handling
1. Transport the product as close to the installation location as possible before unpacking.
r
Lower Cover
2. Do not put any objects on the indoor unit.
3. Remove the side cover (shown below) when the indoor unit is moved after unpacking. If it isn't
removed, the side cover may be damaged and may cause injury.
Removing Side Cover
a. Open the air inlet grille. b. Remove the securing screw (M4).
c. Push the side cover forward to remove
the hooks and the hooking plate.
Hooking Plate
Hooks
d. Remove the side cover by lifting up.
4. When the indoor unit is unpacked, moved and installed, do not take out the air inlet grille, louver and lower cover. Additionally, do not apply an excessive force to them. The air inlet grille, louver and lower cover will become deformed or damaged.
5. The indoor unit covers are resin made. Do not apply an excessive force to the resin covers or allow them to fall.
6. Do not move the louver by hand. If moved, the louver mechanism will be damaged.
8
P5417058-rev.1
Page 13
NOTICE
3.3 Factory-Supplied Accessories
1. Check to ensure that the following accessories are packed with the indoor unit.
The screws, washers, and are nuts are packed in the pipe insulation.
Accessory Qty. Purpose
Suspension Bracket
Washer
Pipe Insulation (Large)
Pipe Insulation (Small)
Cable Band (Large)
Cable Band (Small)
Condensate Hose
Hose Clamp
Insulation
2 For Installing Indoor Unit
8 For Suspension Bracket
1
For Refrigerant Piping Connection
1
6 For Securing Insulation
1 For Securing Plug
1 For Connecting Condensate Pipe
2 For Connecting Condensate Hose
2 For Condensate Hose Connection
PVC Tube
Cable Band
Logo Label
2
For Separating Communication Cables and Wired Controller Cables from Power Supply Wirings; 7/16 ID (11 ID)
5
1 Logo Label for HITACHI Brand
1 Logo Label for YORK Brand
The controller and branch piping are optional accessories and are not included with the indoor unit. If necessary, please contact your distributor or contractor.
P5417058-rev.1
9
Page 14
2. Do not insert or leave any foreign objects inside the indoor unit and verify that no foreign objects
inch (mm)
inch (mm)
remain inside the indoor unit before installation and the test run. Failure to do this can result in equipment failure and damage to the unit.
3. Necessary Tools and Instrument List for Installation
No. Tool No. Tool
1 Handsaw 11 Wrench
2 Philips Screwdriver 12 Charging Cylinder
3 Vacuum Pump 13 Manifold Gauge
4 Refrigerant Gas Hose 14 Wire Cutter
5 Megohmmeter 15 Gas Leak Detector
6 Copper Pipe Bender 16 Level
7 Manual Water Pump 17 Clamp for Solderless Terminals
8 Copper Tube Cutter 18 Hoist (for Indoor Unit)
9 Brazing Kit 19 Ammeter
10 Hexagonal Wrench 20 Voltage Meter
NOTE: Use tools and measuring instruments (vacuum pump, gas hose, charging cylinder, and manifold gauge) exclusively for the refrigerant R410A.
• Install the indoor unit with an appropriate clearance around it for operation and maintenance working space, as shown in Fig. 3.1.
• Do not install ammable parts in the service space for the indoor unit.
• Install the indoor unit higher than 8 ft. (2.4m) from the oor level.
• Consider the air distribution from the indoor unit to the space of the room, and select a suitable location so that uniform air temperature in the room can be obtained.
• Avoid obstacles such as electric lights or partitions that may hamper the air inlet or the air outlet ow.
• Check to ensure that the ceiling has sufcient strength to hang the indoor unit.
Do not install the indoor unit in a machinery shop or kitchen where vapor from oil ows to the indoor
unit. Oil will deposit on the heat exchanger, thereby reducing the indoor unit performance and the plastic parts may deform, and in the worst case, break due to splashed oil during operation.
• Avoid an installation place where the indoor unit may be in contact with high humidity.
• Warm air may stay at the high ceiling space during the heating operation. Thus, the parallel installation of a circulator is recommended.
Avoid installing the air conditioning where direct airow blows from the air outlet to temperature
detecting devices such an alarm device or a control device. It may cause a failure of an alarm device or a control device.
Minimum service space to tighten the suspension bolt
Min. 11-13/16 (300)Min. 1-9/16 (40)
Minimum service space for auto louver motor
Min.
19-11/16
(500)
Min. 15-3/4
For Single Installation
Min. 1-9/16 (40) Min. 11-13/16 (300)
Min. 11-13/16 (300)
For Parallel Installation
NOTE:
If there is a cornice on the ceiling, measure the dimension from the front or undersurface.
Fig. 3.1 Space around Indoor Unit
10
Min. 5/16 (8)
(400)
P5417058-rev.1
Page 15
• For the indoor unit with a motion sensor, the detecting area for the motion sensor is shown in the gure
Detecting Area
29.5 ft (9m)
Floor-to-Ceiling Height
below.
Depth 23 ft (7m)
Detecting Area
Detecting Area
8.9 ft (2.7m)
2.6 ft (0.8m) from Floor Level
5.9 ft
(1.8m)
To avoid any corrosive action to the heat exchangers, do not install the indoor unit in an acidic or alkaline
23.6 ft (7.2m)
environment.
• The temperature and humidity inside the ceiling have the potential to exceed 86
o
F/RH (30oC/RH) (Relative
Humidity 80%). Thus, apply additional insulation materials to the indoor unit's external surface to avoid
condensation.
Pay attention to the following points when the indoor unit is installed in a hospital or other facility where
there may be electromagnetic waves from medical equipment.
a. Do not install the indoor unit where the electromagnetic wave is directly radiated to the electrical box,
wired controller cable or wired controller.
b. Install the indoor unit and components as far as practical or at least 9.8 ft. (3m) from the electromagnetic
wave radiator.
c. Prepare a steel box and install the wired controller inside it. Prepare a steel conduit tube and wire the
wired controller cable in it. Then, connect the ground wire with the box and the tube.
d. Install a noise lter when the power supply emits electromagnetic interference (EMI).
P5417058-rev.1
11
Page 16
4. Installation Work
7/8 (22)
* Dimension for Suspension Bolt
Steel
5-7/8 to 6-5/16 inches
(100 to 150kg)
(W3/8 or M10)
I Beam
Suspension Bolt (W3/8 or M10)
4.1 Position of Suspension Bolts
1. Determine the nal location and installation direction of an indoor unit with care to spacing for piping
and wiring.
2. After the position of the indoor unit is determined, make holes in the ceiling to install the suspension bolts.
3. The positions of suspension bolts are shown below.
Upper Surface
4-3/4
(120)
inch (mm)
Model A B
(B)
A
11*
(280)*
7/8 (22)
(H,Y,C)ICS015B21S
(H,Y,C)ICS024B21S
(H,Y,C)ICS030B21S (H,Y,C)ICS036B21S
37-13/16
(960)
50
(1270)
62-3/16
(1580)
36-1/16
(916)
48-1/4
(1226)
60-1/2
(1536)
4. Ceiling Work: It is different depending on the building structure. Consult with an architect or an interior
nish worker for more information.
• Do not install electric light units and the indoor unit to the same ceiling furring. Otherwise, electric
lights may icker or vibrate during the indoor unit operation. When installing the indoor unit and
electric lights, a separate ceiling furring must be used for each.
4.2 Installation of Suspension Bolts
The structure for suspension should be strong enough.
For Steel Beam
For Concrete Slab
(150 to 160mm)
12
NOTES:
To hang the indoor unit, a strong wooden beam shall be utilized.
Span < 35-7/16 inches (90cm): 2 x 4 wood support
Span < 70-7/8 inches (180cm): 2 x 4 wood support
Insert 220 to 330 lb
Concrete
Suspension Bolt
P5417058-rev.1
Page 17
4.3 Mounting Indoor Unit
attached in the upper cap.
Suspension
Max. 1-15/16 inches (50mm)
of Indoor Unit
Suspension Bolt
1. Pattern Board for Installation
The pattern board for the installation is printed on the packing.
When making holes in the wall and ceiling, use the pattern board that has printed hole positions for suspension, refrigerant pipe and condensate pipe.
Upper Cap
The pattern board is
2. Hanging Indoor Unit
A. Hanging Indoor Unit with Suspension Bracket
a. Make holes in the ceiling for the suspension bolts. b. Remove the suspension brackets attached to the indoor unit.
c. Afx the suspension brackets to the suspension bolts (four places).
d. Mount the indoor unit to the suspension brackets. e. Tighten the four nuts and the securing screw for the suspension bracket.
Bolt
Tighten four accessory nuts.
Nut (Accessory)
Washer
Nut
Suspension Bolt
Suspension Bracket
Ceiling
Rear Side
1/4 inch
(6mm)
P5417058-rev.1
13
Page 18
B. Hanging Indoor Unit without Suspension Bracket
Suspension Bolt (Field-Supplied)
Max. 1-15/16 inches
1/16 ~ 3/8 inch
(1 ~ 10mm)
from horizontal
View from Right
1/16 ~3/8 inc
(1 ~ 10mm
from horizontal
Hook the supporting string into the rectangular holes.
Side Cover
Supporting String
(If there is not enough service space between the ceiling and the indoor unit, hang the indoor unit
using procedures of A above.)
a. Determine the position to install the
suspension bolt.
b. Afx the washer and nut to the suspension
bolt.
c. Mount the indoor unit to the suspension bolts.
Nut (Field-Supplied)
Washer (Field-Supplied)
Washer (Field-Supplied)
Nut (Field-Supplied)
Suspension Bolt
(50mm)
Ceiling
3. When the indoor unit is installed, create a down-slope toward the condensate pipe connection for
drainage. The gure at the right shows the right condensate pipe connection (before shipment). For the
left condensate pipe connection, create a down-slope toward the left.
(Condensate Pipe Connection)
View from Front
Lower the indoor unit 3/8 inch (10mm) when the optional drain-up mechanism is installed.
NOTE:
The ceiling surface may not be level. When the indoor unit is installed, using a level, check the alignment as it pertains to the condensate pipe connection down-slope. If the indoor unit is mounted with incorrect suspending position, it may deform and the abnormal vibration may occur.
4. Attach the side cover and the supporting string.
h
)
5. Remove the protection lm attached to the louver surface.
6. Remove the protection tape attached to the air inlet lter.
4.4 Installation of Wired Controller
The installation of the wired controller should be performed according to the installation manual for the wired controller.
14
P5417058-rev.1
Page 19
5. Refrigerant Piping Work
0.016 ~ 0.031R
Use the specied non-ammable refrigerant (HFC R410A) for the outdoor unit refrigerant system. Do not charge the unit with anything other than HFC R410A, such as hydrocarbon refrigerants (propane and isobutene), oxygen, and other ammable gases (acetylene, ammonia, and so forth), or any poisonous gases when installing, maintaining or moving the unit. These substances are volatile and dangerous and can result in re, explosion, and serious or fatal injuries.
For details of refrigerant piping work, vacuum pump and refrigerant charging, refer to the "Installation and Maintenance Manual" for the outdoor unit.
5.1 Piping Materials
1. Tolerances of refrigerant piping lengths depend on the combination with the outdoor unit.
Refer to the "Installation and Maintenance Manual" for the outdoor unit.
2. Select the piping size from the following table.
Table 5.1 Piping Size
inch (mm)
Model Gas Piping Liquid Piping (H,Y,C)ICS015B21S 1/2 (12.7) 1/4 (6.35) (H,Y,C)ICS024B21S
(H,Y,C)ICS030B21S
5/8 (15.88) 3/8 (9.52)
(H,Y,C)ICS036B21S
3. Prepare eld-supplied copper pipes.
4. Select clean copper pipes. Make sure there is no dust or moisture inside.
5. The refrigerant lubricating oil used in these units is Polyvinylether (PVE), a chemically stable, resilient, synthetic lubricant that, when combined with refrigerant R410A, maintains its compatibility, lubricity, and viscosity over extended periods of time and is impervious to heat, oxidation, moisture absorption and breakdown as long as it remains in a sealed system. Its chemical properties will remain intact only so long as moisture is not introduced into the system.
The gaseous element, PVE, is a moisture magnet that, once exposed to open air can quickly become saturated with moisture, lose its lubricity, and become useless. Minimize exposure to the open air, over the summer months, and in southern or tropical climates.
6. When cutting piping, do not use conventional tools such as saws or grinding wheel cutting disks that
produce harmful metallic lings and burrs that can damage a refrigerant system. Use a pipe cutter to eliminate metal lings produced by the cutting operation. After the cut is made, blow out each pipe
with dry compressed air or nitrogen to remove any residue before making pipe connections.
In Case of Getting the Pipe Through a Hole in the Wall
Correct
HoleHole
Attach a cap or put a plastic bag over the pipe end.
Do not lay the pipe directly on the ground.
CorrectIncorrect Incorrect
Attach a cap or put a plastic bag over the pipe end.
In Case of Rain
Correct Incorrect
Rain water can come in.
Attach a cap or put a plastic bag over the pipe end.
Rubber Band
5.2 Piping Connection
1. Perform the aring work as shown below.
o
+
90
φA
φd
P5417058-rev.1
o
2
45
o
+
o
2
Diameter
(d)
inch (mm)
+0
A
-0.02 (-0.4)
1/4 (6.35) 0.36 (9.1)
3/8 (9.52) 0.52 (13.2)
1/2 (12.7) 0.65 (16.6)
5/8 (15.88) 0.78 (19.7)
15
Page 20
Fasten with cable bands at three locations along the pipe (Accessory).
2. Use the specic are nut attached with the unit.
A
pply a small amount
of oil to the flare face.
3. Verify that there are no scratches or burrs stuck to internal surfaces, or surface distortion at the ared opening.
4. Before tightening the are nut, apply a small amount of oil (eld-supplied) to the are face. (Do not
apply any oil to the backside of the are or the threads.) Tighten the liquid pipe are nut to the specied torque while using a backup wrench to prevent damage to the unit. Next, tighten the gas pipe are nut following the same procedures. Ensure that the are connections are leak free upon completion of the
work.
NOTE:
1. Refrigerant oil is eld-supplied. [Ethereal Oil FVC50K, FVC68D (Idemitsu Kousan Co. Ltd.)]
2. If refrigerant comes into contact with decorative panel surfaces, damage in the form of cracks can occur on panel surfaces. Use with caution.
Required Tightening Torque (JIS B 8607)
Pipe Size Tightening Torque
1/4 inch (6.35 mm) 10.3 - 13.3 ft·lbs (14 - 18 N·m)
Do not apply oil here.
3/8 inch (9.52 mm) 25.1 - 31.0 ft·lbs (34 - 42 N·m)
1/2 inch (12.7 mm) 36.1 - 45.0 ft·lbs (49 - 61 N·m)
5/8 inch (15.88 mm) 50.2 - 60.5 ft·lbs (68 - 82 N·m)
5. Wherever buried piping exists onsite, make sure there is a service doorway to provide adequate access to inspect piping sockets and elbows, and for interconnecting parts.
6. Suspend pipes at certain points and reinforce against earthquakes so that they are not damaged by an external force. Appropriate measures should be taken during installation to guard against possible damage or injury that might occur in an earthquake. Check local codes and refer to the Safety Section in this manual for additional information.
7. Do not tightly secure refrigerant piping to accommodate expansion and contraction.
8. Prevent the pipes from contacting weak portions such as a wall or ceiling. Otherwise, abnormal sound may be heard due to vibration of the piping.
9. Leak test all piping and connections. The procedures should be performed in accordance with the
"Installation and Maintenance Manual" for the outdoor unit.
10. If temperature and humidity inside the ceiling exceed 80.6°F (27°C)/RH80%, condensation occurs on the surface of the accessory insulation. Wrap additional insulation (approximately 3/16 to 3/8 inch (5~10mm) thickness) around the accessory insulation of the refrigerant pipe as a preventive measure.
11. Insulate each are connection ensuring no gap with accessory insulations to prevent condensation. Then insulate each refrigerant pipe as well.
● Do not apply excessive force to the are nut when tightening. If applied, the are nut may crack due to stress fracture and refrigerant leakage may occur. Use the correct torque specications.
● Make sure that a refrigerant leak test has been performed. Refrigerant (uorocarbon) for this unit is non-ammable, non-toxic, and odorless. If the refrigerant should somehow escape and come into contact with ame, toxic gas will form. This gas is heavier than air and will settle near oor areas and spread where it can cause asphyxiation to those nearby.
16
Securely fasten cable bands and vinyl tape in order to prevent the accumulation of moisture.
Affix the vinyl tape position at the vertical part (Insulation for Refrigerant Pipe (Accessory)).
Refrigerant Pipe (Field-Supplied)
Unit Side
Insulation Material (Factory-Supplied)
Check for any gap between the indoor unit and the insulation.
Insulation for Refrigerant Pipe (Field-Supplied)
P5417058-rev.1
Page 21
5.3 Piping Connection Work
to prevent dangling.
Upper Side
Right Side
View from Front
View from Bottom
Front
5-1/2 (140)
of Indoor Unit
7-15/16 (201)1-9/16 (40)
17) (Liquid Pipe)
4-3/16 (107) (Gas Pipe)
1-9/16 (40) (Condensate Pipe
5.3.1 Position of Piping Connection
The piping connection is performed inside the indoor unit. The pipe connection can be performed from three directions - rear, right and upper. For rear and upper pipe connection, the plastic cap is attached at the knockout hole for the refrigerant pipe and the condensate pipe. Cut out the knockout hole of the cap for piping and attach the cap again after running the refrigerant pipe through the cap.
Hole Position and Size
Ceiling
φ5-1/8130)
4-3/4 (120)
6-9/16 (166)
1/4 (6)
Right End of Indoor Unit
φ3-15/16100)
Wall
4-7/16 (113)
inch (mm)
Right End
5/16 (8)
NOTE: When the optional drain-up mechanism is attached, refer to the installation manual for the drain-up mechanism.
Position of Pipe Connection
Cap (Rear Side)
Gas Pipe
Suspension Band
Liquid Pipe
Rear Side
Condensate Pipe
1/4 (6)
3 (76)
P5417058-rev.1
If the liquid pipe contacts strongly to the plate, noise caused by refrigerant flowing may increase. Suspend the local liquid pipe using a suspension band
Cap (Rear Side)
5-3/4 (146) (Liquid Pipe)
3-11/16 (94) (Gas Pipe)
5-13/16 (147) (Condensate Pipe)
Condensate Pipe Connection (VP20, Left Side)
Condensate Pipe Connection
(VP20, Right Side)
8-1/16 (205) (Gas Pipe)
7-1/2 (190) (Liquid Pipe)
5-7/16 (138) (Condensate Pipe)
View from Front View from Right
1/4 (6)
inch (mm)
4-7/8 (124)
5-1/4 (134)
4-5/8 (1
7-15/16 (201)
)
17
Page 22
Piping from Rear Side
View from Front
1-9/16 (40)
9/16 (14)
View from Right
View from Bottom
Rear Side of Indoor Uni
)
Air Inlet Grille
Supporting String
r
inch (mm)
Upper Surface
Cap (Rear Side)
3 (76)
Condensate Pipe Connection (VP20, Left Side)
4-3/4 (121) 2-7/16 (62)
9/16 (15) 5-9/16 (142)
Piping from Right Side Piping from Upper Side
Cap (Upper Side)
Hole for Condensate Pipe Conncetion (Knockout hole)
4-3/4 (120)
6-1/16 (154)
t
4-5/8 (118) 2 (51)
6-7/16 (163)
3/4 (19)
5.3.2 Access of Piping Connection
Open the air inlet grille and perform the connecting work from the lower side.
1. Press and slide the cover of the air inlet grille in the direction of the arrow with ngers in the holes
on the cover.
2. Remove the supporting string from the side plate.
3. While the air inlet grille is being opened, depress the knobs of the hinge (
),
1
push the air inlet grille toward the arrow direction (2) and remove the air inlet grille.
Holes (Two or three places
Push
2
Hinge
Depress
1
Side Plate
Depress the knob of hinge and push the ai inlet grille forward.
18
P5417058-rev.1
Page 23
6. Condensate Piping
NOTICE
Left Side
(Condensate Pipe Connection)
Silicon Sealant
Do not run condensate piping into underground areas near sanitary or sewage lines where toxic and corrosive gases can seep into the system. This creates a pathway for the ow of poisonous gas to penetrate inhabited areas.
● Check to ensure that the condensate pipe discharges moisture properly. If connected incorrectly, it can
cause structural damage to the indoor wall and ceiling surfaces and damage to property.
● Avoid sloping the condensate pipe upward as this impede drainage. Moisture can settle back into the unit
and it cause water leakage when the unit operation stops.
● Do not connect drainage with sanitary or sewer lines or any other condensate pipe.
● When the main condensate pipe is connected with other indoor units, the connected position of each
indoor unit must be higher than the main pipe. The pipe size of the main condensate pipe must be large enough according to the unit size and number of units.
● After performing condensate piping work and electrical wiring, check to ensure that water outow is
smooth as in the following procedures.
1. Connecting Direction of Condensate Pipe
The standard direction of the condensate piping connection is the right side as viewed from the front.
However, it can be performed from the left side when it is required due to building construction.
For Left Side Condensate Piping
Left Side Right Side
Cable Band
Condensate Pan
Insulation
Condensate Plug
Remove the condensate plug.
Right Side
Insert the Condensate plug into the drain adaptor by using a screwdriver.
Screwdriver
Condensate Plug
Wrap the insulation around the condensate pipe connection.
Condensate Plug
Drain Adaptor
P5417058-rev.1
19
Page 24
2. Connecting Condensate Hose
Hose Clamp
Hose Clamp
Condensate Pan
Condensate Hose
a. Insert the hose into the hose clamp. b. Push the condensate hose onto the drain adaptor until the hose reaches the end of the condensate
pan. (If the condensate hose is not inserted completely, it causes water leakage.)
c. Tighten the screw for the hose clamp to face the screw part downward as shown in the gure below
to prevent dripping of condensate.
d. Wrap the insulation (accessory) around the hose clamp to cover the condensate hose, condensate
pan, and hose clamp without any gaps. (If there is a gap, dripping of condensate may occur.)
3. Connecting Condensate Piping
a. Prepare a PVC piping with a 1 inch (26mm) outer diameter. b. When the condensate hose is used, do not create a raised part or twist. c. Insulate the PVC piping securely after connecting. d. Tighten the hose clamp after inserting the PVC piping. e. The condensate pipe must be performed with a down-slope pitch of 1/25 to 1/100. f. Wrap the insulation (accessory) around the hose clamp to cover the condensate hose, condensate
pan, and hose clamp without any gaps.
NOTE:
* Do not connect the condensate pipe with sanitary or sewage piping or any other drainage piping. * Do not tighten the condensate pipe and the refrigerant pipe together with the hose clamp.
(Accessory)
Drain Adaptor
Gluing is not required.
(Attach to indoor unit.)
Insulation (Attached to condensate hose)
Insulation (Accessory)
Connect tightly.
(Accessory)
Insulate without gap and wrap the tape around the connection.
Insulation (Field-Supplied)
Create down-slope for proper drainage.
PVC Piping (VP20, Field-Supplied)
Gluing is not required.
Insulation (Accessory)
NOTE:
Connect the eld-supplied condensate pipe to the condensate hose using PVC adhesive.
Perform rmly cleaning the connection surface, applying the adhesive, inserting the pipe, and retaining
and curing according to the adhesive manufacturer information.
Insert the condensate hose completely. If not, or twisted, it will cause water leakage.
Attach the hose clamp to the screw part upward but not allowing the screw part to touch the air lter.
If the PVC adhesive is used on the drain adaptor that is ABS resin, a crack and water leakage may
occur.
The tightening torque for the hose clamp should be 2.2 to 2.6 ft∙lbs (3.0 to 3.5N-m).
20
P5417058-rev.1
Page 25
4. After the condensate piping work is completed, check that water ows smoothly by pouring water into
Hose Clamp
Insulation
Rear Side Piping Right Side Piping
the condensate pan using a hose.
NOTE:
The optional drain-up mechanism is required when the condensate piping is connected from the upper surface of the indoor unit. For details, refer to the installation and maintenance manual for the drain-up mechanism.
(Accessory)
Pay attention not to splash water on the electrical parts such as the fan motor, the oat switch or
thermistors.
P5417058-rev.1
21
Page 26
7. Electrical Wiring
All electrical work must be done as outlined in this manual and in accordance with this manual.
Substandard work can result in re and damage to the unit.
● Use specied cables between units and choose the cables correctly. If not, an electrical shock or
re may occur.
Do not open the service cover or access panel for the indoor or outdoor units without turning OFF the main power supply. It can result in an electrical shock.
Turn OFF the main power switch of the indoor unit and the outdoor unit before attempting any electrical
wiring work or a periodical check is performed. Otherwise, the result will be an electric shock or a re.
● Check to ensure that the indoor fan and the outdoor fan have stopped before attempting any electrical wiring work or for any scheduled electrical work that is being performed.
● Tighten screws according to the following torque.
M3.5: 0.9 ft·lbs (1.2 N·m) M4: 0.7 to 1.0 ft·lbs (1.0 to 1.3 N·m)
Secure all cables together with cable bands and seal the connecting hole against moisture and insects.
● Run the electrical wiring through the connecting hole in the side cover when using conduit.
Secure the wired controller cable using the cable band inside the electrical box.
7.1 General Check
1. Make sure that the eld-selected electrical components: (main power switches, circuit breakers, wires, conduit connectors, and wire terminals) are properly labeled in accordance with electrical data
as specied in the Engineering Manual. Make sure that the components comply with the National
Electrical Code (NEC).
2. Conrm that the power supply voltage is within ±10% of the rated voltage.
3. Verify the capacity of the electrical wires. If the power supply capacity is too low, the system cannot be started due to a voltage drop.
4. Verify that the ground wiring is securely connected.
7.2 Electrical Wiring Capacity
7.2.1 Field Minimum Wire Sizes for Power Supply
This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized
measure for added protection to a properly grounded unit. Install appropriate sized breakers / fuses / overcurrent protection switches, and wiring in accordance with local, state and NEC codes and requirements. The equipment installer is responsible for understanding and abiding by applicable
codes and requirements. Failure to use a GFCI can result in electric shock or re.
Do not operate the system until all check points have been cleared.
▫ Conrm that the electrical resistance is more than one megaohm, by measuring the resistance
between the ground and the terminal of the electrical parts. If it is less than one megaohm, do not
operate the system until the source of the electrical drain is found and repaired. ▫ Conrm that the stop valves of the outdoor unit are fully opened, and then start the system. ▫ Apply power to the outdoor unit(s) at least 12 hours prior to operation of the system for preheating
of the compressor oil.
Do not touch any of the parts with hands at the discharge gas side since the compressor chamber and
the pipes at the discharge side are heated to temperatures higher than 194
o
F (90oC).
22
P5417058-rev.1
Page 27
7.2.2 Details of Electrical Wiring Connection
NOTICE
Outdoor Unit Power Supply
Indoor Unit Power Supply
GFCI and main switch for outdoor unit.
Outdoor Unit Power Supply
Indoor Unit Power Supply
GFCI and main switch for outdoor unit.
Details for electrical wiring capacity of the outdoor unit should be referenced according to the installation and maintenance manual for the outdoor unit. Adjusting the DIP switches may be required depending on the arrangement with the outdoor unit. Select wiring capacity according to Table 7.1. Install a Ground Fault Circuit Interrupter (GFCI) and main switch as shown in each of the system diagrams below.
Heat Pump System Heat Recovery System
Outdoor Unit
Main
GFCI
Switch
Indoor Unit
GFCI
Main
Switchbox
Switch
Refer to the “Installation and Maintenance Manual” for the connected outdoor unit for details of wire,
Indoor Unit
Indoor Unit
GFCI
GFCI
Main Switch
Main Switch
Refer to the “Installation and Maintenance Manual” for the connected outdoor unit for details of wire,
Change-Over
Switchbox
Outdoor Unit
Box
Indoor Unit
Indoor Unit
Indoor Unit
Table 7.1 Recommended Wiring Capacity and Sizes
Follow local electrical codes when selecting a GFCI device.
Model
Power
Supply
Minimum Wire Thickness
[AWG (mm
Power
Supply
Wiring Size
(Main)
Ground
Wiring
Size
2
)]
Communication
Cable Size
(H,Y,C)ICS015B21S
(H,Y,C)ICS024B21S 0.9
(H,Y,C)ICS030B21S 1.2
1~,
208/230V
60Hz
18
(0.82)
18
(0.82)
18
(0.82)
(H,Y,C)ICS036B21S 2.0
GFCI Main Switch
Nominal
Current
Nominal
Sensitive
Current
Nominal
Current
Fuse
[A] [mA] [A] [A] [A]
15 30 15 15
MCA
(Minimum
Circuit
Ampacity)
0.6
NOTE:
1. Follow local codes and regulations when selecting eld wires.
2. Select the GFCI with an activation speed of 0.1 sec. or less.
3. Total operating current is less than 12A.
● Conrm the recommended size GFCI as shown in Table 7.1.
● Communication cabling should be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper. Shielded cable must be considered for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors. When shielded cabling is applied, proper bonding and termination of the cable shield is required as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be considered per application and local code requirements. Total cable length must not exceed 3281 ft (1000m).
● Select the wiring size, Ground Fault Circuit Interrupter (GFCI) in accordance with the regulations for
each region, the "Installation and Maintenance Manual", and the dedicated electrical circuit that must be
used.
● Outside of the indoor unit, installation of the power supply wiring, communication cable, and wired controller cable should be spaced as far apart as possible.
P5417058-rev.1
23
Page 28
7.3 Position of Electrical Wiring Connection
(C)
12
NOTICE
Stranded Wire Single Wire
Connect it with
Connect it Direct
.
● The electrical wiring connection for the indoor unit is shown in Section 7.2.2. For details relating to the intermediate connections between the indoor unit and the decorative panel, refer to installation of the decorative panel.
● The connection at the terminal block for the indoor unit is shown in the gure below. Check the arrangement for the outdoor unit before performing any wiring. Tighten screws in the terminal block as
indicated in the torque specication table shown below.
Tightening Torque for Terminals
Screw Size Tightening Torque
TB1 M4
TB2 M3.5
0.7 - 1.0
(1.0 - 1.3
0.9
(1.2
ft·lbs N·m)
ft·lbs N·m)
Terminal Block for
Power Supply Wiring
TB1 (black)
S/L2R/L1
Mp/N
Terminal Block for
Communication Cable
TB2 (white)
AB
● Do not connect the main power supply wiring to the communication
line (Terminals A, B, 1, and 2 of TB2). If connected, the printed circuit board (PCB) is destroyed.
● Be aware of the following when wires are connected at the terminal block:
Screw
Attach a piece of insulation tape or a sleeve at each terminal.
Maintain the recommended distance between the electrical box
and the terminals to prevent a short circuit.
(B)
(A)
Maintain the recommended distance between terminals.
1. Connect the cable for the optional controller or the optional extension cable to the terminals inside the electrical box through the connecting hole of the cabinet.
2. Connect the power supply and the ground wiring to the terminals in the electrical box.
3. Connect the cables between the indoor unit and the outdoor unit to the terminals inside the electrical box.
4. Connect cables to their corresponding terminal number and the similarly marked band.
5. Connect the communication cable between those indoor units connected to the same outdoor unit.
6. Do not connect the main power supply wiring to the communication line (Terminals A, B, 1 and 2 of TB2). If connected, the printed circuit board (PCB) is destroyed.
7. Tightly clamp the power supply wiring and communication cables using the cable band inside the electrical box.
NOTE:
When stranded wire is used for the eld-wiring
connection, use the M4 crimping terminal. When the single wire is used, fashion it into the shape as shown at the right and connect it in order to tighten the washer uniformly. Tighten the screws at the terminal block
according to the torque specication as shown in the
table above.
24
Crimping Terminal.
As Shown Below
P5417058-rev.1
Page 29
8. All electrical work should be performed in strict accordance with electrical schematics in the
NOTE: Thermo-ON: Thermo-OFF:
Controller
Controller
A
Incorrect Wiring Reconnect wirings correctly.
PCB
"Installation and Maintenance Manual".
9. If Power Supply Voltage (208V/230V) is introduced into the Communication Line: If 208V/230V are applied to the communication line at (Terminals 1 and 2 of TB2) by mistake, the fuse on the PCB for the communication line will blow. In this case, perform the recovery work as shown in the diagrams below.
a. Reconnect the wirings correctly. b. Set the No.1 pin at DSW7 (on the PCB) to ON.
After the fuse is replaced and the PCB recovers, do not reintroduce 208V/230V into the communication
line. This voltage causes serious damage to the PCB, and it will not recover.
S
L1RL2
C 208V/230V
5V
AB12
AC 208V/230V
5V
10. Wired Controller Connections
a. Wired Controllers at each unit for an individual operation setting
Indoor Unit Indoor Unit
Outdoor Unit
Wired
A B
Wired
A B
b. Single Wired Controller for an individual operation setting
Indoor Unit
A B
Outdoor Unit
Indoor Unit
A B
S
L1RL2
AB12
DSW7
ON OFF
12
Set No.1 Pin at ON side.
Wired Controller
Communication cables for the wired controller are necessary.
c. Wired Controller connections between different refrigerant systems
Outdoor Unit
A B
Wired Controller
Individual
The outdoor unit and some indoor units are running.
The outdoor unit and some indoor units stay on, but don’t run.
Wired Controller
Simultaneous
(Thermo ON / OFF individually)
P5417058-rev.1
A BA B
Indoor UnitIndoor UnitIndoor Unit Indoor Unit
A B
Outdoor Unit
Wired Controller
Individual
25
Page 30
1. The DIP switch settings for the outdoor unit should be performed in accordance with the "Installation and
NOTICE
Indoor Unit
Switchbox
Indoor UnitIndoor Unit
Maintenance Manual" for the outdoor unit.
2. Be aware that communication cable for the wired controller is required in these instances:
a. The following functions are set to the sub unit, which is not installed with the wired controller.
● Remote ON/OFF function settings, (No.1, 2, and 3), (External Input / Output Function)
● Power supply ON/OFF functions, (No.1 and 2), (Function Selection)
● Prohibiting the wired controller after manual stoppage (External Input / Output Function)
● Group setting by the centralized controller
b. The combination of twin, triple, or quad is controlled by a single wired controller.
c The address for the indoor unit is changed from the wired controller.
d. The multiple panels with the motion sensor are controlled by a single wired controller.
7.4 Caution for Electrical Wiring
Do not connect the power supply wiring and the communication cable into one terminal. The manual switchbox is required when communication cable is required.
RL1SL2Mp
N
G F
S
C
I
RL1SL2Mp
N
RL1SL2Mp
N
Indoor Unit Indoor Unit Indoor Unit
RL1SL2Mp
N
G F
S
C
I
RL1SL2Mp
N
RL1SL2Mp
N
26
P5417058-rev.1
Page 31
7.5 Wiring Connections
Communication Cable
(Accessory)
TB2
Upper Side
ɸ7/8 inch (22.2mm) Conduit Opening
Electrical Box
and Communication Cable
Terminal Block (White)
Wire for Fan Motor
Wiring connections for the indoor unit are shown below.
1. The wiring connection for the indoor unit is shown in the gure below.
Cap
Communication Cable and Wired Controller Cable
ɸ1/2 inch (13mm) Opening
Rear Side
Cap
Power Supply Wiring
2. The wiring connection for the electrical box is as follows.
a. Open the air inlet grille. b. Remove the electrical box cover. c. Connect the communication cable, power supply wiring and wired controller cable.
PCB1
Terminal Block (Black)
Ground Screw (M5)
Power Supply Wiring
Wired Controller Cable
d. After the wiring is completed, attach the electrical box cover again with care in order not to pinch
wires.
NOTE
Insert the communication cable and wired
AB
12
TB1
S/L2
R/L1
Power Supply Wiring
Mp/N
controller cable into the PVC tube “VW-1 600V” (accessory) to separate from the power supply wiring for the indoor unit.
Afx both ends of the PVC tube with cable band
(accessory).
If shielded cable is used, terminate at the ground
terminal.
Install and secure all electrical wiring correctly through the opening, to the terminal blocks using
Secure the PVC Tube by Cable Band (Accessory)
Wired Controller Cable
PVC Tube “VW-1 600V”
the cable bands provided. Wiring should be spaced appropriately and rmly fastened to guarantee against short circuit, sparks, and re.
P5417058-rev.1
27
Page 32
ON
OFF
OFF
OFF
OFF
OFF
7.6 DIP Switch Settings
DSW4 (Unit Model Code Setting)
Unit No. Setting
1. Turn OFF the power supply to both indoor and outdoor units before adjusting DIP switch settings. Otherwise, the settings are invalidated and do not take effect.
2. Positions of DIP switches on the PCB are shown below.
DSW5 (Refrigerant System No. Setting)
RSW2 (Refrigerant System No. Setting)
DSW3 (Capacity Code No. Setting)
ON
1 2
DSW7
DSW7 (Fuse Recovery)
DSW6 (Tens Digit)
ON
1 2 3 4 5 6
Factory settings for DSW6 and RSW1 are set at "0".
For the units supporting H-LINK II, the Unit No. can be set for Max. 64 indoor units (No. 0 to 63).
OFF
RSW1 (Units Digit)
Setting Position
0
9
8
7
6
Set by inserting slotted screwdriver into the groove.
1
2 3
4
5
Ex.) Set at No.16 Unit
DSW6
1 2 3 4 5 6
Set No.1 Pin at ON side
Set at "6"
123456
RSW2
9
8 7
9
8 7
RSW1
0
1
2
3
4
6
5
ON
0
1
2
3
4
6
5
DSW4 DSW5
ON
ON
1 234
123 4 56
ON
ON
1 2
DSW9 DSW6
DSW6 (Indoor Unit No. Setting)
DSW9 (Optional Function Setting)
3. Unit No. Setting (RSW1 and DSW6) Setting is not required. Indoor unit numbers are set by the auto-address function. If an indoor unit number setting is required, set the unit number of all indoor units respectively and sequentially by following setting positions. It is recommended that you assign a number to each indoor unit beginning with “1”. A maximum of 64 indoor units per refrigerant system can be connected to an H-LINK ll System. Though the available numbers range from zero to 63, the applicable number for the
th
indoor unit in theory supplants the number
64 "zero". For the centralized control, this setting is required.
1 23456
DSW3
RSW1 (Indoor Unit No. Setting)
RSW1
0
9
8
7
6
ON
OFF
1
2
3
4
5
4. Capacity Code Setting (DSW3) No setting is required because of the factory setting. This switch is utilized for setting the capacity code that corresponds to the capacity of the indoor unit.
Indoor Unit Capacity
(MBH)
Setting Position
1 2 3 4 5 6
5. Unit Model Code Setting (DSW4) No setting is required. It is for setting the model code of the indoor unit.
28
15
ON
24 30 36
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
ON
1 2 3 4 5 6
1234
P5417058-rev.1
Page 33
6. Refrigerant System No. Setting (RSW2 and
12
ON
OFF
12
ON
OFF
NOTICE
12
ON
OFF
Refrigerant System No. Setting
DSW5)
DSW5 (Tens Digit)
This setting is required. The unit arrives with all settings in the OFF position.
1 2 3 4 5 6
Factory settings for DSW5 and RSW2 are set at "0".
For the units supporting H-LINK II, the ref. system No. can be set for Max. 64 cycles. (No. 0 to 63)
7. Fuse Recovery (DSW7)
Factory Setting
When introducing high voltage to terminals 1 and 2 of TB2,
the (0.5A) fuse on the PCB is cut. In such a case, rst, reconnect
the wiring correctly to TB2, and then adjust the number 1 pin to ON.
8. Optional Function Setting (DSW9) No setting is required. Setting positions at the factory are all in the OFF position.
ON
OFF
RSW2 (Units Digit)
Setting Position
0
9
8
7
6
Set by inserting slotted screwdriver into the groove.
1
2 3
4
5
Ex.) Set at No.5 Cycle
DSW5
ON
RSW2
0
9
8
7
6
OFF
1
2
3
4
5
1 2 3 4 5 6
Set All Pins OFF
Set at "5"
NOTE:
● The solid square “■” symbol signies the "ON" and "OFF" positions for DIP switches. The diagrams show
original factory settings.
● When the unit number and the refrigerant system are set, record the unit number and refrigerant system
to facilitate maintenance and servicing activities afterward.
All indoor and outdoor units must be shut down prior to attempting to make DIP switch adjustments. Otherwise, the settings do not take effect.
P5417058-rev.1
29
Page 34
7.7 Function Selection by Wired Controller
Each function can be selected with the wired controller. Refer to the “Installation and Maintenance Manual” for the wired controller and the “Engineering Manual” for details.
(1) Press and hold "Menu" and "Back/Help" simultaneously for at least 3
seconds during the normal mode (when unit is not operated). The Test Run menu is displayed.
(2) Select “Function Selection” from the Test Run menu and press “OK”.
(3) Select the indoor unit by pressing “
” and press “OK”. (This screen is NOT displayed when the number of indoor unit connected with the controller is 1 (one). In this case, (4) is displayed.)
Press "All" to select all the indoor units connected to the wired
controller.
(4) Press “ ” and select the item required to change.
Test Run Menu
Test Run
Function Selection
Thermistor Selection Input/Output Function 5
Function Selection
All
01-01
01-02
01-03
01-04
Function Selection:01-03
Item Setting
b6 00 b7 00
b8 00
b9 00 bA - -
Adj. Entr RtrnSel.
OK
01
/
03
Back
OK
Entr RtrnSel.
Back
OK
Entr RtrnSel.
02
/
17
Back
(5) Press “
” and change the setting.
Function Selection:01-03
Item Setting
b6 00 b7 00
b8 01
b9 00 bA - -
(6) Press “OK” to display the conrmation screen.
Function Selection:01-03
(7) Select “Yes” and press “OK”.
The Test Run menu is displayed after the setting is conrmed. If “No” is pressed, the screen returns to (4).
(8) Press "Back/Help" on the Test Run menu to return to the normal mode.
Sel. Entr Rtrn
(Figure for Function Selection)
To set other units, press "Back/Help" at (4), (5) and the screen returns to (3). (If the number of indoor unit connected with the controller is 1 (one), the screen returns to (1).)
Adj. Entr RtrnSel.
OK
Confirm function
selection setting?
Yes No
OK
02
/
17
Back
Back
30
P5417058-rev.1
Page 35
Optional Function
No V When the card key is inserted (i.e. someone is in the room), then the contact turns ON.
Indoor Unit
Controller
Cooling Setpoint+R2
(A)
e
Cooling
Automatic COOL/HEAT Operation b8 -
Dual Setpoint r1 -
Cooling/Heating
(A)
Changeover Temperature
Setback Temperature Compensation (During card key removal, setpoint is setbacked)
* Not displayed when fahrenheit (oF) is selected to be displayed.
Function
Selection
Item
r2
r3
Cooling Setpoint
Heating Setpoint
Heating Setpoint-R2
Unit
o
o
(
o
o
(
00 01 02 03 04 05 06 07 08 09 10
Not
Available
Not
Available
F
(1.0)
(2.5)
Heating
2
4
C)
F C)
Setting Condition (Underlined Part is Factory Setting)
Available
Available
3
(1.5)
(3.0)6 (3.5)7 (4.0)8 (4.5)9 (5.0)
3*
(2.0)4 (2.5)5 (3.0)1 (0.5)
5
Indoor Temperatur
10
(5.5)1 (0.5)2 (1.0)3 (1.5)
7.8 Setback Operation
(1) Press and hold “Menu” and “Back/Help”on the wired controller simultaneously for at least three
seconds during the normal mode (unit stoppage). The Test Run menu is displayed.
3*
(2.0)
(2) Select “Input/Output” from the Test Run menu and press “OK”.
(3) Select either "Input 1" or "Input 2" and change the setting to "09".
(4) Build a circuit such as shown below.
Card Key
oltage "a" Contact
TB1
1
2
3
CN3
PSC-5RA
Test Run Menu
Test Run
Function Selection Thermistor Selection Input/Output
01
/
03
Function 5
Back
OK
Entr RtrnSel.
Input/Output:01-03
Item Setting Connector
Input 1 00 CN3 1-2
Input 2 00 CN3 2-3 Output1 00 CN7 1-2 Output2 00 CN7 1-3 Output3 00 CN8 1-2
Adj. Entr RtrnSel.
OK
Back
CN3
1 2 3
1 2 3
Wired
Refer to “Function Selection by Wired Controller” section for details.
P5417058-rev.1
(5) Temperature compensation for the setback function can be selected on the wired controller.
31
Page 36
8. Test Run
8.1 Before Test Run
Verify that there are no problems with the installation, and do not perform the test run until all the following procedures have been accomplished.
Refer to the "Installation and Maintenance Manual" for the outdoor unit for details on test run operations
from the outdoor unit.
Verify that refrigerant piping and the communication cable are connected to the same refrigerant system. If not, it will cause an abnormal operation and damage to instrumentation.
1. Verify that electrical resistance is more than one megaohm by measuring the resistance between the ground and the terminal for electrical components. If the electrical resistance is less than one
megaohm, do NOT operate the system until the electrical current outow to ground is detected and
repaired. Do not introduce any high voltage to the terminals of the communication cables
(TB2 [A, B, 1 and 2]).
2. Verify that each wire is connected correctly at the correct phase for the power supply. If they are incorrectly connected, the unit will not operate and the wired controller displays the alarm code “05”. In
this case, verify the phase for the primary power supply according to the “Attention” label afxed to the
back side of the service cover. Then, with the power supply turned OFF at the power supply, recreate the necessary connections.
3. Apply power to the outdoor unit(s) at least 12 hours prior to operation of the system for preheating of the compressor oil.
4. Verify that all DIP switch settings are correct. Refer to Section 7.6 “DIP Switch Settings”.
8.2 Test Run
After all installation work is completed, a test run should be performed.
1. Check to ensure that stop valves (gas and liquid) for the outdoor unit are fully opened.
2. Whenever indoor units are connected to the VRF system, perform the test run for the indoor units one by one sequentially and then check the refrigerant piping system and the electrical wiring system for conformity. (If these multiple indoor units are operated simultaneously, system conformity cannot be
veried.)
3. Perform the test run in accordance with the following procedures. Ensure that the test run is carried out without any problem. The following procedures show a case where a wired controller is utilized.
If other controllers are activated instead, refer to the "Installation and Maintenance Manual" for those
other controllers.
NOTE:
The outdoor unit may not operate depending on the indoor and outdoor temperature conditions. Refer
to the "Installation and Maintenance Manual" for outdoor units for details.
a. Press and hold “Menu” and “Back/Help” simultaneously for at least three seconds.
The Test Run menu is displayed.
Test Run Screen
Test Run Setting: 2 units
MODE
SPEED
Adj.Sel. ON Rtrn
COOL
AUTO
NOTE When the “00 unit” is displayed, the auto-address function is working. Cancel the “Test Run” mode and reset.
Back
32
P5417058-rev.1
Page 37
● The total number of connected indoor units is indicated on the Liquid Crystal Display (LCD). In
the case of a twin combination (set of two indoor units), the total number of the connected indoor units is displayed as “2 units”, and where there is a triple combination (set of three indoor units), the total number of the connected indoor units is displayed as “3 units”.
● If the number indicated is not equal to the actual number of connected indoor units, the auto-
address function is not performing correctly due to incorrect wiring or electrical interference. Turn OFF the power supply, and resolve the wiring issue after verifying the following items. (Do not repeat turning ON and OFF within a 10-second timespan.)
The power supply to the indoor unit is not turned ON or there is an incorrect wiring issue. Incorrect connection of the interconnecting cable between indoor units or a poorly connected
controller cable.
Incorrect setting of the rotary switch and DIP switch for the indoor unit printed circuit board
(PCB). (The setting is overlapped.)
● Press “
● Press “
b. Press “
On/Off” to start the Test Run.
” and set each item.
On/Off”. The RUN indicator turns ON and the operation starts. At this time, a two-hour OFF timer is set automatically.
c. Press “
” or “ ”, select “LOUV.” and select “ ” (auto-swing) by pressing “ ” or “ ”. The auto swing operation starts. Check the operating sound at the louvers. If abnormal sound is not generated, press “ ” or “ ” again to stop the auto swing operation. If abnormal sound is generated from the louvers, remove the face panel and adjust the louver accordingly.
correctly as in the following steps: (in cases of a decorative panel with a motion sensor).
1. Press and hold “Menu” and “Back/Help”
simultaneously for at least three seconds during the Test Run mode. The Check Menu screen “A” is displayed.
Select “Check 1” at the Check Menu
screen and press “OK”.
2. Screen “B” is displayed. (This screen is NOT displayed when only
one indoor unit is connected to the wired controller. In that case, screen “C” is displayed.)
3. Select the indoor unit by pressing
” and press “OK”.
The Check Data screen “C” is displayed.
“A”d. Verify that the motion sensor is operating
Check Menu
Check 1
Check 2 Alarm History Display Model Display Function 5
Sel. Entr Rtrn
“B”
Model Display:01-02 Model:F .08
01-01
01-02
01-03
01-04
“C”
IDU : ODU :
Check 1:01-03
Item Value L3 00
L4 00 P1 00 P2 10 q1 50
Next Page
S/N:000000
******
S/N:000000
******
OK Back
Back
01
/
02
01
/
07
Rtrn
4. Press “ ” to change the screen until it displays the Check screen “q2” to "q6".
P5417058-rev.1
33
Page 38
Checking the Motion Sensor
(for 30 seconds)
: Communication Data
1. Perform the motion detection (waving a hand) under the motion sensor of the selected indoor
unit for approximately 10 to 15 seconds.
2. Check the value of “q3” to "q6" after 30 seconds* from starting the motion detection at Item 1.
The detection information from the motion sensor against the motion detection is displayed in a range of 0% to 100%.
* The communication cable between the indoor unit and the wired controller is on a 30 second cycle.
Timing for motion detection and the detected information display is shown below.
NOTE:
Refer to the operator's manual for indoor
30 sec.
30 sec.
Cycle 30 seconds.
unit settings, setup of the motion sensor. (“Motion Sensor Setting”,
Motion Detection Detected Information
Display
“If Absent” and “Check Interval” can be set.)
3. Check that the value of “q3” to "q6" is neither 0% nor 100%.
If the value displayed is 0% or 100%, repeat the procedure from Item 1 above. If the same value
reappears, there may be a malfunction of the motion sensor.
Checking the Radiation Sensor
1. Check the value for “q2”. If that value differs greatly from the air temperature at the installation
location, a failure of the radiation sensor may occur. The radiation sensor will indicate readings from -22 to 140
o
F (-30 to +60oC).
2. Press “Back/Help” and return to the display.
e. Though temperature recordings by the thermistors are invalid during the test run phase, the
protection devices are valid.
f. For VRF System
According to the label; “Checking Method by 7-Segment Display” afxed to the inside of the front
cover of the outdoor unit, check temperature, pressure, and operation frequency, and interconnected indoor unit numbers by 7-Segment displays.
g. To complete the Test Run, press “
the set test run time to pass. When changing the Test Run time, press “ ” or “ ” to select “Test Time”. Then, set the test run time (30 to 600 minutes) by pressing “ ” or “ ”.
On/Off” again or wait for
Test Run: 2 units
MODE
SPEED
LOUV.
Test Time 120min
Inverter 60Hz
Adj.Sel. OFF
COOL
AUTO
34
P5417058-rev.1
Page 39
● The RUN indicator on the wired controller for the indoor unit ashes orange (0.5 second ON/ 0.5
Refrigerant System No. of Indoor Unit Having Tr
Same Refrigerant System as the Indoor Unit Having Trouble
Unit Model Code
second OFF), indicative of a fault or error having been generated with activation of protection devices during the test run phase. Alarm code, unit model code, and the number of interconnected indoor units
is displayed on the LCD as shown below. If the RUN indicator on the wired controller ashes for two
seconds ON and two seconds OFF, the source of the problem could be a failure in the communication cable between the indoor unit and the wired controller (a loose or severed connection). In this case, verify in Section 8.3 “Alarm Code” and perform the appropriate troubleshooting measures. Consult with an authorized service engineer, if the problem cannot be resolved at your end.
Indoor Unit No. of Indoor Unit
01-02
Alarm Code: 22
MODEL : F .02
I.U. :
IDU : ODU :
O.U. :
Sel. OP MODE
RCI-3.0FSN3
******
RAS-3HVRNM2
******
ouble
Chek
AlarmRst
Address
OK
Entr
Alarm Code:
MODEL : F . 02
01 - 02
22
Having Trouble
Alarm Code No.
Total No. of Indoor Units in the
Unit Model Code
The relationship between the unit model code and the unit model is shown in the table below.
Indication Unit Model
F VRF System
E Except Above Models
P5417058-rev.1
35
Page 40
8.3 Alarm Codes
NOTICE
Alarm (Troubleshooting) Code Table
Code
No.
01 Indoor Unit
02 Outdoor Unit
03 Communication
04-09 Problem with the outdoor unit. (Refer to the "Installation and Maintenance Manual" for outdoor units.)
11
12 Outlet Air Thermistor failure.
13 Freeze Protection Thermistor failure.
14 Gas Piping Thermistor failure.
19 Fan Motor Problem with Indoor Fan.
20-29 Problem with the outdoor unit. (Refer to the "Installation and Maintenance Manual" for outdoor units.)
31
32
35 Setting of indoor unit is incorrect. Indoor unit number duplicated in same refrigerant group.
36 Incorrect indoor unit combination.
38-59 Problem with the outdoor unit. (Refer to the "Installation and Maintenance Manual" for the outdoor unit.)
b0
b1
b5
EE Compressor Compressor protection alarm.
Category Nature of Problem Likely Cause
Sensor on
Indoor Unit
System
System
Activation of a protection device
(oat switch).
Activation of protection device. (Except for Alarm Code: 41, 42)
Communication failure between indoor and outdoor units.
Inlet Air Thermistor failure.
Incorrect capacity setting for indoor and outdoor units.
Incorrect setting of other indoor unit number.
Incorrect setting for unit capacity. Incorrect setting for unit capacity. Incorrect setting of unit and
refrigerant system number. Incorrect setting of indoor unit
number for H-LINK type.
Activation of the oat switch. (High water level present in
the condensate pan.) A problem exists in the piping. High Pressure Cut. (R410A: 601 psi (4.15MPa)), fan
motor lockup during the outdoor unit cooling operation. Incorrect wiring, loose terminals, disconnected wiring or a
blown fuse.
Loosely connected, disconnected, or severed connection.
Fan motor lockup. Fan motor protection control device for indoor unit activated.
Incorrect capacity code setting for combination, excessive
or insufcient total indoor unit capacity code.
Problem with a different indoor unit in the same refrigerant system. (Failure at the power supply, defective PCB.)
Indoor unit is designed for other refrigerant (R22 or R407C).
Unit number or refrigerant system > 64.
Interconnected indoor units are not supporting H-LINK II > 17.
This alarm code displays when the alarms such as damage to the compressor occur three times within a six­hour period.
● When the RUN indicator ashes every four seconds, there is a communication failure between the indoor
unit and the wired controller (loose connector, disconnected or incorrect wiring, or severed connection).
● Display of the alarm code “EE” means serious abnormality and burn out of the compressor.
Refer to the "Installation and Maintenance Manual" for the indoor/outdoor unit connections.
Do NOT operate the air conditioning just to run checks on electrical wiring until preparations for the test run phase are completed.
All the installation work of the air conditioning is completed. Forward this information to the building owner and request that they maintain all the equipment manuals and warranties.
Routine Preventive Maintenance
Perform routine preventative maintenance on the system to ensure high efciency performance and containment of refrigerant over the life of the product. During installation, record the results of the following eld
procedures for future reference:
1) Pressure and leak testing of eld installed piping and connection
2) Triple evacuation and nitrogen purge of eld installed piping
3) Total refrigerant quantity in the system including factory charge and trim charge volumes
This information should be included in the owners nal documentation including operation and maintenance
(O&M) manuals for project close-out. All technical service and maintenance procedures must be performed by trained and authorized personnel only.
36
P5417058-rev.1
Page 41
Page 42
© 2017 Johnson Controls, Inc.
P5417058-rev.1
Code No. LIT-12012967
Revised January 2018
Loading...