Johnson Controls YEWS Series, YEWS100, YEWS200, YEWS210, YEWS130 Installation, Operation And Maintanance Instructions

...
Supersedes:
EN
AP1105
-IOM01(0316)
YEWS Water Cooled Screw Chiller
(Water Source Heat Pump)
Installation, Operation and Maintenance
Form No:AP1105-IOM01(1216) EN
YEWS High Efficiency Chiller With Single Compressor
STYLE E
Warning
The System is charged with refrigerant with a certain pressure
Improper operation during maintenance may cause serious damage to the system. All maintenance shall be done by York authorized technician, following the guide in York installation, operation and maintenance manual.
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components , and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibilities of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual posseses independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.
In complying with YORKs policy for continuous product improvement, the information contained in this document is subject to change without notice. While YORK makes no commitment to update or provide current information automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest YORK Applied Systems Service office.
It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment in question. If there is any question in the mind of operating/service personnel as to the applicability of these documents, then prior to working on the equipment, they should verify with the owner whether the equipment has been modified and if current literature is available.
CHANGEABILITY OF THIS DOCUMENT
Nomenclature
Y E W 100 HEA 50
Design Level 50-380V-3P-50Hz
53-400V-3P-50Hz 55-415V-3P-50Hz 64-460V-3P-60Hz 62-230V-3P-60Hz
A-HFC134a H - High efficiency AC B - High efficiency ITS P - Premium efficiency AC
Unit Model
Screw Compressor
High Efficiency
YORK
Water Cooled
S -
Special Design
HP
Heat Pump
S
YEWS-E Water Cooling Screw Chiller/Heat Pump
NOMENCLATURE
1 GENERAL MANUFACTURER INFORMATION
1.1 INTRODUCTION
1.2 WARRANTY
1.3 SAFETY
1.4 RESPONSIBILITY FOR SAFETY
1.5 ABOUT THIS MANUAL
1.6 MISUSE OF EQUIPMENT
1.7 EMERGENCY SHUTDOWN
1.8 SAFETY LABELS
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2.2 COMPRESSOR
2.3
2.4 REFRIGERANT CIRCUITS
2.5 CONDENSER
2.6 EVAPORATOR
2.7 POWER AND CONTROL PANEL
2.8 CONTROL PANNAL
2.9 MOTOR PROTECTION
2.10 KEYBOARD CONTROL
2.11OPTIONS
2.12 FUNCTIONAL DESCRIPTION
3 TRANSPRORTATION, HANDLING AND STORAGE
3.1 DELIVERY AND STORAGE
3.2 INSPECTION
3.3 RIGGING
4 INSTALLATION
4.1 GENERAL DESCRIPTION
4.2 LOCATION REQUIREMENTS
4.3 INSTALLATION OF VIBRATION ISOLATORS
4.4 PIPING CONNECTIONS
4.5 WATER TREATMENT
4.6 PIPEWORK ARRANGEMENT
4.7 CONNECTION TYPES &SIZES
4.8 REFRIGERANT RELIEF VALVE PIPING
4.9 ELECTRICAL CONNECTION
OIL SEPARATOR AND OIL SUMP
TABLE OF CONTENTS
1
1
1
1
1
1
2
2
3
3
4
4
4
5
5
5
5
5
6
6
6
7
7
10
10
10
10
12
12
12
12
14
15
15
15
15
16
YEWS-E Water Cooling Screw Chiller/Heat Pump
4.10 CONDENSER COOLING WATER SYSTEM
4.12 POWER WIRING
4.13 CONTROL PANEL WIRING
4.14 220VAC OUTPUT
4.15 SYSTEM INPUT
5 CONTROL CENTER
5.1 SAFETY NOTICE FOR THE OPERATION OF THE CONTROLLER
5.2 INITIALIZATION OPERATIONS
5.3 INSTRUCTIONS ON THE OPERATION
5.4 INSTRUCTIONS OF DISPLAY INTERFACE
5.4.1 INITIALIZATION INTERFACE
5.4.2 HOME INTERFACE
5.4.3 STATUS DISPLAY
5.4.4 PARAMETER SETTING
5.4.5 CLOCK SETTING
5.4.6 FAULT INQUIRY
5.5 GENERAL PARAMETERS SETTING AND DEFULT VALUES
5.6 FAULT IMFORMATION
5.7 MODBUS PROTOCOL
6 COMMISSIONING
6.1 PREPARATION
6.2 FIRST TIME START-UP
7 OPERATION
7.1 GENERAL DESCRIPTION
7.2 START-UP
7.3 NORMAL RUNNING AND CYCLING
7.4 OTHER NOTES
7.5 RUNNING DETECTION
8 MAINTENANCE
8.1 GENERAL REQUIREMENTS
8.2 DAILY MAINTENANCE
8.3 COMPRESSOR OIL
8.4 OIL FILTER
8.5 CONDENSER AND EVAPORATOR
8.6 CHECKING SYSTEM FOR LEAKS
4.11 VARIABLE PRIMARY FLOW
16
17
17
17
17
17
18
18
18
20
25
25
25
25
27
38
38
40
43
44
49
49
51
52
52
52
52
53
54
56
56
56
57
58
58
60
YEWS-E Water Cooling Screw Chiller/Heat Pump
8.7 EVACUATION AND DEHYDRATION OF UNIT
8.8 WORKING CONDITIONS
8.9 SCHEDULED MAINTENANCE
9 TROUBLE SHOOTING
9.1 SYSTEM TROUBLE SHOOTING ANALYSIS
9.2 SENSOR CALIBRATION CHARTS
10 TECHNICAL DATA
10.1 UNIT PHYSICAL PARAMETERS
10.2 WATER PRESSURE DROP
10.3 PHYSICAL DATAS
10.4 STARTING/OPERATION LIMITS OF UNIT
10.5 FOUNDATION DIAGRAM
10.6 DIMENSIONS
11 SPARE PARTS
11.1 RECOMMENDED SPARES
11.2 RECOMMENDED COMPRESSOR OILS
12 DECOMMISSIONING,DISMANTLING AND DISPOSAL
12.1 GENERAL DESCRIPTION
13. INSTALLATION INSTRUCTIONS FOR THE HF68 FLOW SWITCHES
13.1 APPLICATION
13.2 PARAMETERS
13.3 FLOW ADJUSTMENT RANGE AND MEDIA TEMPERATURE RANGE
13.4 INSTALLATION
13.5 WIRING
13.6 STEPS TO ADJUST THE FLOW SWITCH SETTINGS
ATTACHED DRAWINGS 1: YEWS electrical drawing-compressor for 50Hz power
ATTACHED DRAWINGS 2: YEWS electrical drawing-main board (YEWS100H/130H/170H/200H/210H) for 50Hz power
ATTACHED DRAWINGS 3: YEWS electrical drawing-main board (YEWS215P) for 50Hz power
ATTACHED DRAWINGS 5: YEWS electrical drawing-compressor for 60Hz power
ATTACHED DRAWINGS 6: YEWS electrical drawing-main board (YEWS100H&130H&170H&200H) for 60Hz power
ATTACHED DRAWINGS 7: YEWS electrical drawing-main board (YEWS215P) for 60Hz power
ATTACHED DRAWINGS 8: YEWS field connection for 60Hz power
ATTACHED DRAWINGS 9: Transformer for230V/3P/60Hz Application
61
61
61
62
62
64
65
65
65
66
66
68
69
70
70
70
71
71
72
72
72
72
72
72
73
YEWS-E Water Cooling Screw Chiller/Heat Pump
74
75
76
77
78
79
80
81
ATTACHED DRAWINGS 4: YEWS electrical drawing-main board(YEWS100P/130P/170P/200P) for 50Hz power
82
1 GENERAL MANUFACTURER INFORMATION
1
1.1 INTRODUCTION
YORK YEWS chillers (heat-pumps) are manufactured to
the highest design and construction standards to ensure
high performance, reliability and adaptability for all types
of air conditioning installations. The unit is intended for
cooling (hot) water solution and is not suitable for purp-
oses other than those specified in this manual.
This manual contains all the information required for cor-
rect installation and commissioning of the unit, together
with operating and maintenance instructions.
The manuals should be read thoroughly before attempting
to operate or service the unit. All procedures detailed in
the manuals, including installation, commissioning and
maintenance tasks must only be performed by suitably
trained and qualified personnel.
The manufacturer will not be liable for any injury or
damage caused by incorrect installation, commissioning,
operation or maintenance resulting from a failure to
follow the procedures and instructions detailed in the
manuals.
1.2 WARRANTY
YORK warrants all equipment and materials against
defects in workmanship and materials for a period of
eighteen (18) months from date of shipment, or twelve
(12) months from commissioning, whichever occurs first,
unless labor or extended warranty has been purchased as
part of the contract.
The warranty is limited to parts only replacement and
shipping of any faulty part, or sub-assembly, which has
failed due to poor quality or manufacturing errors. All
claims must be supported by evidence that the failure has
occurred within the warranty period, and that the unit has
been operated within the designed parameters specified.
All warranty claims must specify the unit model, serial
number, order number and run hours/starts. Model and
serial number information is printed on the unit
identification plate.
The unit warranty will be void if any modification to the
unit is carried out without prior written approval from
YORK.
For warranty purposes, the following conditions must be
satisfied:
The initial start of the unit must be carried out by trained
personnel from an Authorized YORK Service Centre.
Only genuine YORK approved spare parts, oils, coo-
lants, and refrigerants must be used. All the scheduled
maintenance operations detailed in this manual must be
performed at the specified times by suitably trained and
qualified personnel.
Failure to satisfy any of these conditions will automa-
tically void the warranty. See Warranty Policy.
1.3 SAFETY
YEWS chillers are designed and manufactured by the
factory within ISO 9000 , Chillers satisfied all the runn-
ing limits required by the manual and conform to the following Directives GB25131Safety requirements of Positive displacement and Centrifugal Waterchilling Packages
1.4 RESPONSIBILITY FOR SAFETY
Every care has been taken in the design and manufacture
of the unit to ensure compliance with the safety requir-
ements listed above. However, the individual operating or
working on any machinery is primarily responsible for:
Personal safety, safety of other personnel, and the
machinery.
Correct utilization of the machinery in accordance with
the procedures detailed in the manual.
YEWS-E Water Cooling Screw Chiller/Heat Pump
2
1.5 ABOUT THIS MANUAL
The following terms are used in this document to alert the
reader to areas of potential hazard.
A WARNING is given in this document to
identify a hazard, which could lead to personal
injury. Usually an instruction will be given, tog-
ether with a brief explanation and the possible
result of ignoring the instruction.
A CAUTION identifies a hazard which could
lead to damage to the machine, damage to other
equipment and/or environmental pollution.
Usually an instruction will be given, together
with a brief explanation and the possible result
of ignoring the instruction.
A NOTICE is used to highlight additional
information, which may be helpful to you but
where there are no special safety implications.
The contents of this manual include suggested best
working practices and procedures. These are issued for
guidance only, and they do not take precedence over the
above stated individual responsibility and/or local safety
regulations.
This manual and any other document supplied with the
unit are the property of YORK which reserves all rights.
They may not be reproduced, in whole or in part, without
prior written authorization from an authorized YORK
representative.
1.6 MISUSE OF EQUIPMENT
Suitability for Application
The unit is intended for cooling water and is not suitable
for purposes other than those specified in these
instructions. Any use of the equipment other than its
intended use, or operation of the equipment contrary to
the relevant procedures may result in injury to the
operator, or damage to the equipment. The unit must not
be operated outside the design parameters specified in
this manual.
Structural Support
Structural support of the unit must be provided as
indicated in these instructions. Failure to provide proper
support may result in injury to the operator, or damage to
the equipment and/or building.
Mechanical Strength
The unit is not designed to withstand loads or stresses
from adjacent equipment, pipework or structures.
Additional components must not be mounted on the unit.
Any such extraneous loads may cause structural failure
and may result in injury to the operator, or damage to the
equipment. The unit should only be lifted in accordance
with the instructions given in Section3 of this manual.
General Access
There are a number of areas and features, which may be a
hazard and potentially cause injury when working on the
unit unless suitable safety precautions are taken. (It is
important to ensure access to the unit is restricted to
suitably qualified persons who are familiar with the
potential hazards and precautions necessary for safe oper-
ation and maintenance of equipment containing high
temperatures, pressures and voltages.)
Pressure Systems
The unit contains refrigerant vapor and liquid under
pressure, release of which can be a danger and cause
injury.
The user should ensure that care is taken during
installation, operation and maintenance to avoid damage
to the pressure system. No attempt should be made to gain
access to the component parts of the pressure system
other than by suitably trained and qualified personnel.
Electrical
The unit must be earthed. No installation or maintenance
work should be attempted on the electrical equipment
without first switching power OFF, isolating and locking-
off the power supply. Servicing and maintenance on live
equipment must only be performed by suitably trained
and qualified personnel. No attempt should be made to
CAUTION
NOTE
WARNING
YEWS-E Water Cooling Screw Chiller/Heat Pump
3
gain access to the control panel or electrical enclosures
during normal operation of the unit.
Refrigerants and Oils
Refrigerants and oils used in the unit are generally non-
toxic, nonflammable and noncorrosive, and pose no spe-
cial safety hazards. Use of gloves and safety glasses is,
however, recommended when working on the unit. The
build up of refrigerant vapor, from a leak for example,
does pose a risk of asphyxiation in confined or enclosed
spaces and attention should be given to good ventilation.
High Temperature and Pressure Cleaning
High temperature and pressure cleaning methods (e.g.
steam cleaning) should not be used on any part of the
pressure system as this may cause operation of the
pressure relief device(s). Detergents and solvents, which
may cause corrosion, should also be avoided.
1.7 Emergency Shutdown
In case of emergency, the control panel is fitted with an
emergency stop switch (red)which, when operated by
pressing the emergency stop switch removes the electrical
supply the control system and the microprocessor
controller, thus shutting down the unit.
1.8 Safety Labels
The following labels are fixed to each unit to give
instruction, or to indicate potential hazards which may
exist.
White symbol on blue background For safe
operation, read the Instructions firstly.
Black symbol on yellow background Warning:
Hot surface
Black symbol on yellow background Warning:
Isolate all electrical sources of supply before
opening or removing the cover, as lethal voltages
may exist
Black symbol on yellow background General
attention symbol
YEWS-E Water Cooling Screw Chiller/Heat Pump
4
2.1 INTRODUCTION
YORK YEWS series chillers (Heat pumps) are designed
for water cooling (heating) and to be located inside
building (Equipment room).
2.2 COMPRESSOR
A semi-hermetic screw compressor is provided to ensure
high operational efficiency and reliable performance.
Capacity control is achieved through slide valve. The
compressor is a positive displacement type characterized
by two helically grooved rotors, which are manufactured
from forged steel. The motor operator operates at 50Hz or
60Hz to directly drive the male rotor, which in turn drives
the female rotor on the light film of oil.
Each compressor is direct drive, semi-hermetic, rotary
twin screw type and includes the following items:
Two screw rotors, manufactured from forged steel.
A cast iron compressor housing precisely machined.
A built-in high efficient oil separator
An internal discharge check valve can prevent rotor
backspin during shutdown.
A suction vapor cooled, high efficient and reliable semi-
hermetic motor has overload protection: thermistor and
current overload protection.
A suction vapor screen and a serviceable oil filter are
installed in the compressor housing. For YEWS P serie
units, the oil filter is placed on the oil supply line.
Refrigerant vapor is sucked into the void created by the
unmeshing of the five lobed male and six lobed female
rotors. Further meshing of the rotors closes the rotor
threads to the suction port and progressively compresses
the vapor in an axial direction to the discharge port. The
vapor is compressed in volume and increased in pressure
before exiting at a designed volume at the discharge end
of the rotor casing. Since the intake and discharge cycles
overlap, a resulting smooth flow of vapor is maintained.
2 PRODUCT DESCRIPTION
The rotors are housed in a cast iron compressor housing
precision machined to minimize the void between the
housing and the rotors. Contact between the male and
female rotor is primarily rolling on a contact band on each
of the rotor's pitch circle. It result in virtually no rotor
wear and increased reliability.
The compressor incorporates a complete antifriction bear-
ing design for reduced power input and increased relia-
bility. Four separated, cylindrical, roller bearings handle
radial loads. Angular-contact ball bearings handle axial
loads. Together they maintain accurate rotor positioning at
all pressure ratios, thereby minimizing leakage and maint-
aining efficiency.
Motor cooling is provided by refrigerant vapor from the
evaporator flowing across the motor. Over load protection
includes overheat and current overload protections.
For YEWS H serie units, oil is removed from the
refrigerant using a built-in oil separator, and then returned
back to the compressor for lubrication. A plug-in heater
and a float ball type oil level swithch are located in the
compressor.
Motor Starting
Star/Delta (S/D) open transition starter is used for
compressor motor starting. The S/D starter utilizes 3
motor contactors and a starting relay. The starter allows
inrush current to be limited to approximately 33%LRA for
the first 4~10 seconds, with current changing to normal
running current when the Delta connection is established.
When the microprocessor initiates a start signal to run a
compressor, the applicable relays are energized. The tran-
sition of the relay contacts enables the 'Star' connection of
the motor start. The 'Star' connection of the motor start is
enabled for 4~10 seconds, then motor switchs to the
'Delta' connection.
Capacity Control
The compressors should start at the minimum load
YEWS-E Water Cooling Screw Chiller/Heat Pump
5
position and provide a capacity control within 25%~100%
by using one continuous function slide valves.
The capacity control valve at the minimum load position
when it starts up will ensure compressor starting at the
minimum motor load.
2.3 Oil separator and oil sump
YEWS system uses two stage oil separation designs, the
first stage is the compressor built-in oil separator, and the
second stage is the condenser internal oil separator. For
YEWS H serie units, all models has the oil sump located
in the first stage oil separator, the oil level should be
visible in the sight glass on compressor; but for YEWS P
serie units, the oil sump is located in the second stage oil
separator, there should be no visible oil level in the
compressor sight glass (the oil will be piped to the oil
sump inside the condenser).
All lubricant must flow through a renewable filter before
it is supplied to compressor to lubricate the bearings and
the rotors.
After lubricating the bearings, the oil is injected through
an orifice loacted in the closed thread near the suction end
of the rotors. The oil is automatically injected because of
the pressure difference between the discharge pressure and
the pressure at the suction end of the rotors. This
lubricates the rotors as well as provides an oil seal against
leakage around the r otors to assure r efrig erant
compression (volumetric efficiency).
For YEWS P serie units, a photoelectric type oil level
switch is usedand an oil heater are locaded on the oil
sump.
2.4 Refrigerant Circuits
The refrigerant circuit has a compressor, oil separator,
evaporator, condenser and a liquid line. Liquid line
components include: a manual shut-off valve, throttle
device , liquid injection piping (just for HP and ITS).
2.5 Condenser
The water-cooled condenser is a cleanable shell and tube
type, with 19mm thermally enhanced seamless copper
tubes and a builtin subcooler.
The design working pressure is 1.0MPa (gauge) on the
waterside. Flange connection HG20615 is provided for
water piping. The condenser shell is equipped with a
relief valve whose active pressure is 20.7 Bar. The
condenser is manufactured and tested according to China
National Standard GB151.
For HP unit, the external surface of the condenser shell
should be covered with 19mm-thick flexible closed-cell
foam for heat insulation purpose.
2.6 Evaporator
The evaporator is a shell and tube, falling film type heat
exchanger equipped with a relief valve whose active
pressure is 20.7 Bar.
The evaporator is manufactured and tested according to
China National Standard GB151.
The external surface of the evaporator shell is covered
with 19mm-thick flexible closed-cell foam for AC&HP
unit and 38mm us used for ITS unit. The water box
connection is equipped with HG20615 flanges for easier
connecting.
2.7 Power and Control Panel
All controls are factory-wired and function tested. The
panel enclosures are designed according to IP22 and are
manufactured from powder-painted steel.
The panel is divided into power supply section, control
section and start section. Power supply section and
control section have separated hinged, latched, and gasket
sealed doors.
The power panel contains: compressor starting contactor,
control wiring, compressor contacting solenoid and
YEWS-E Water Cooling Screw Chiller/Heat Pump
6
compressor overload protection module.
Compressor overload protection is achieved as following:
Motor protector sense the current of each phase of motor
current and the temperature of motor, and send
corresponding signals to the I/O Board.Then compare the
values with MLA setpoints and active to protect the motor
once the the values is higher than MLA setpoints.It
protects the compressor motors from damage due to:
Current overload, current imbalance (the error of the
current of each phase), miswire, motor over temperature,
uncalibrated, supply power phase loss.
The control panel include: Microcomputer keyboard, HMI
and microprocessor board.
2.8 Control panel
The HMI consists of a liquid crystal display, with light
emitting diode backlighting for outdoor viewing of
operating parameters and program points. It can display 8
rows and 120 characters in 2 languages (English or
Chinese). The keyboard has 20 keys, which is divided into
two kinds: Funtion keys and Programme keys.
The standard control function of microprocessor board
includes: chiller alarm contactor controlling, chilled water
pump controlling, chiller auto resetting when it is repower
on after a period of power off, optimizing the system
automaticly according to the running conditions
Unit operating firmware is stored in non-volatile memory
(Flash Memory) to protect chiller from failture for power
off. All field programmed setpoints are retained in the
EPROM register. A lithium battery backed real time clock
(RTC) supply the clock for the system control, and the
battery has 3 years memory.
2.9 Motor protection
The microprocessor provides the overcurrent protection to
ensure that the motor is free from the damages due to
excessive voltage and other overcurrent problems.
After the Star/Delta starter started for more than 10
seconds, the microprocessor will shut down and lock the
chiller for fault if the current exceeds the current
setpoints. It is required to reset the system switch
manually to eliminate the fault before restart the system.
And prior to start the chiller which stopped due to
overcurrent, chec-king should be done on the motor,
wiring and refrigerant system.
When it is found that the current is lower than 10% of
MLA (Max Loading Amps), the low current protection
will be initiated and the unit should be stopped. In that
case, prior to restart the system, unit resetting should be
done manually.
Motor protector
Motor protector is used to protect motor from overheat,
There are three PTC (Positive Temperature Coefficient)
thermistor installed in each phase of motor winding. The
resistance of thermistor will keep in 1K when the temperature is lower than 125, however, the resistance
of thermistor will increase as its temperature rise. When
the resistance value of sensor reach upto 13K, the motor
protector will be active and cut off the power supply of
motor. The chiller is not allowed to restart until the motor
is cooled down and the resistance value of sensor drop
down to 3.25K.
2.10 Keyboard control
Display
The parameters of each refrigerant circuit can be
displayed in 2 languages (English or Chinese),
All the displayed parameters are listed as follows:
Entering/Leaving chilled water temperature
Entering/Leaving cooling water temperature(Entering/le-
aving hot water temperature are diaplayed in heatpump
mode).
Time and date, start and stop time at ordinary days,
arrangement on holidays and status of manual setting.
YEWS-E Water Cooling Screw Chiller/Heat Pump
7
Compressor running hours and starting times.
Compressor running status.
System Suction/Discharge pressure, oil pressure, disch-
arge temerature.
Percentage of compressor current to Full Load Amps.
Cutout value and setpoints: Leaving Chilled (Hot) Water
Temperature, Low Evaporator Pressure , High Discharge
Temperature/Pressure , High/Low Amps , Low Chilled
Water Temperature , High Diacharge Pressure Unload,
High Compressor Amps unload.
Input
Setting the chilled (hot) water temperature.
Clock
Setting time, daily and holiday start/stop schedule.
Programming
Cutout setpoints: Low Evaporator pressure, High
Discharge Pressure, Low Evaporator temperature, High
Discharge Temperature, High Discharge pressure
unloading, OCC.
2.11 OPTIONS
YORK ISN building automation system can directly send
the communication signal to the standard control panel
through the standard RS485 connection.
Flow Switch
The gate type water flow switch has 10.3 bar DWP, which
is applicable to chilled water and cooling water lines.
25mm Spring Isolators
Level adjustable, spring and cage type isolators for
mounting under the unit base rails (Field mounted).
2.12 Functional Description
Low pressure liquid refrigerant enters the cooler and is
evaporated and superheated by the heat energy absorbed
from the chilled water passing through the cooler tube.
These low pressure vapor is sucked by the compressor
where the pressure and temperature are increased. The
high pressure and temperature refrigerant vapor combined
with oil is discharged into the oil separator, there, most of
the oil is separted and remaind in the oil reservoir. The oil
free vapor then enter the condenser and is condensed. The
fully condensed and subcooled liquid refrigerant then
enters the expansion valve where pressure reduction and
further cooling takes place before returning to the cooler.
YEWS-E Water Cooling Screw Chiller/Heat Pump
8
YEWS-E Water Cooling Screw Chiller/Heat Pump
YEWS- E SYSTEM FLO W CHA RT-1for YEWS100H/130H/170H/200H/210H
High pressure refrigerant line Low pressure refrigerant line
Oil line
Condenser
with internal oil separator
Compressor
Oil Eductor
Orifice
Evaporator
YEWS- E SYSTEM FLO W CHA RT-2for YEWS100P/130P/170P/200P /215P
YEWS-E Water Cooling Screw Chiller/Heat Pump
Condenser
with internal oil separator
Compressor
Oil Eductor
Orifice
Evaporator
Oil Filter
High pressure refrigerant line Low pressure refrigerant line
Oil line
9
3 TRANSPRORTATION, HANDLING AND STORAGE
3.1 DELIVERY AND STORAGE
To ensure consistent quality and maximum reliability, all
units are tested and inspected before leaving the factory.
The chiller may be ordered and shipped in any of the
following forms:
Form 1 (shipped complete)
Form 2 (shipped without refrigerant charge)
Units are containing nitrogen or refrigerant and YORK L oil YORK W oil in HP unitsunder
pressure. Units are shipped without export crating unless
crating has been specified on the Sales Order.
If the unit is to be put into storage, prior to installation, the
following precautions should be observed:
Ensure that the unit is not exposed to rain.
Ensure that all openings, such as water connections, are
securely capped.
The unit should be stored in a location where there is
minimal activity to limit the risk of accidental physical
damage.
To prevent inadvertent operation of the pressure relief
devices the unit must NOT be hot water or steam cleaned.
It is recommended to let the functionary on the storage
site keep the key of the control board.
It is recommended that the unit be periodically inspected
during storage.
If the unit is stored longer than six months, the relative
requirements for Long-Term Storage (50.20-NM9 /50.20-
CL9 / 50.20-NM1) must be followed.
3.2 INSPECTION
The unit shipment should be checked on arrival to see that
all major pieces, boxes and crates are received. Each unit
should be checked on the trailer or rail car when received,
before unloading, for any visible signs of damage. Any
damage of signs of possible damage must be reported to the
transportation company immediately for their inspection.
When received at the job site,all containers should be
opened and the contents checked against the packing list.
Any material shortage should be reported to YORK
immediately.
3.3 RIGGING
Each unit has four lifting holes(two on each end) in the end
sheets which should be used to lift the unit. Care should be
taken at all times during rigging and handling to avoid
damage to the unit and its external connections. Lift only
using holes shown in Figure 3-1.
If optional shipping skids are used, remove them before
lowering the unit to its mounting position. Rig the uni to its
final location on the floor or mounting pad by lifting the
unit (or shell assembly) with an overhead lift and lower the
unit to its mounting position.
Don't move the unit on rollers, nor lift it by forklift.
CAUTION
YEWS-E Water Cooling Screw Chiller/Heat Pump
10
Figure 3- 1 Rigging
YEWS-E Water Cooling Screw Chiller/Heat Pump
RIGGING INSTRUCTION
For liftin unit use spreader bar with 4 separate slings length of lifting elements must be adequate to clear all projections, the
strength of liting elements must be suitable for lifing weight.
11
4 INSTALLATION
4.1 General description
This instruction describes the installation of a model YEWS Rotory Scew Liquid Chiller/Heatpump. The unit is shipped as a single factory assembled, piped, wired and nitrogen or refrigerant charged package, requiring a minimum of field labor to make chilled water connections, condenser water connections, refrigerant atmospheric relief connections, and electrical power connections.
Acording the requirement of bargain, YORK representat­ive should provide the following service: Installation checking and, Initial starting and so on.
The YORK Warranty will be voided if the following restrictions are not adhered to:
1. No valves or connections should be opened under any circumstances because such action will result in loss of the factory charged refrigerant or nitrogen.
2. Do not dismantle or open the Unit for any reason except under the supervision of a YORK representative.
3. Do not make final power supply connections to the compressor motor or control panel.
4. Do not charge the compressor with oil.
5. Do not attempt to start the system.
6. Do not supply the evaporator with hot water(The temperature Limit is 100 F,38)or steam.
4.2 Location Requirements The unit should be located in an indoor location where temperature ranges from 4~ 43.The altitude shoude be less than 2000 meter.
The units are furnished with neoprene vibration isolator mounts for basement or ground level installations. Unit may by located on upper floor levels providing the floor is capable of supporting the total unit operating weight (in this application, the spring isolator is prefered).
A level floor, mounting pad or foundation must be pro-vided by others, capable of supporting the operating wei-ght of the unit
Clearances should be adhered to as follows: Rear, Ends and Above Unit - 610mm Front of Unit - 914mm Tube Removal - See following table
Model Tube removal space YEWS100 2100mm YEWS130/170/200/210 2650mm YEWS215 3800mm
4.3 Installation of Vibration Isolators
The optional vibration isolators can be loose shipped with the chiller.
Please refer to the foundation figures in Section 10 to decide proper installation position for the units.
Fixation-Installation
There are two methods: rubber pad and spring isolator.
Locating and installing isolator pads
The isolator pads should be located in accordance with the floor layout of the dimensional product drawing. After the isolator pads have been placed into position on the floor, lower the unit onto the pads. Make sure the pads are even with the edges of the mounting feet. When the unit is in place, remove the rigging equipment and check that the chiller is level, both longitudinally and transversely. See the following Fig.
The longitudinal alignment of the unit should be checked by placing a level on the top center of the evaporator shell under the compressor. Transverse alignment should be checked by placing a level on top of the shell end sheets at each end of the unit.
The unit should be level within 6.4mm from one end to the other end and from front to rear. If the chiller is not level within the amount specified, lift it and place shims between the isolation pad and the tube sheets.
YEWS-E Water Cooling Screw Chiller/Heat Pump
12
YEWS-E Water Cooling Screw Chiller/Heat Pump
SYSTE M OPERATING WEIGHT
Kg
UP TO 7423
Lbs.
UP TO 16365
PART NUMBER
028W1 4462-000
Checking the Isolator Pads Deflection
All isolator pads should be checked for the proper deflection
while checking the level of the unit. Each pad should be
deflected approximately 4 mm (0.15"). If an isolator pad is
under deflected, shim should be placed between the unit
tube sheet and the top of the pad to equally deflect all pads.
Installing Option Spring Isolators
In order to mount spring isolators, first remove the nuts and
screws on the spring isolator supports. Before the unit is
positioned, the isolator supports should be bolted to the unit
support. Position the 4 spring isolators, screw out the
adjusting screws on each isolator until they reach out to
match the isolator support holes. Then lower down the unit
on the adjusting screws. See the following Fig.
The leveling bolts should now be rotated one (1) turn at a
time, in sequence, until the unit end sheets are clear of the
floor or foundation by 22 mm (7/8") and the unit is level.
Check that the unit is level, both longitudinally and
transversely. If the leveling bolts are not long enough to level
unit due to an uneven or sloping floor or foundation, steel
shims (ground, if necessary) must be added beneath the
isolator assemblies as necessary.
After the unit is leveled, wedge and shim under each corner
to solidly support the unit in this position while piping
connections are being made, pipe hangers adjusted and
connections checked for alignment. Then the unit is filled
with water and checked for leaks. The leveling bolts should
now be finally adjusted until the wedges and shims can be
removed the unit should now be in correct level position,
clear of the floor or foundation and without any effect from
the weight of the piping.
13
4.4 Piping Connections General Requirements
The following piping recommendations are intended to ensure satisfactory operation of the unit. Failure to follow these recommendations could cause damage to the unit, or loss of performance, and may invalidate the warranty.
The maximum flow rate and pressure drop for the evaporator and condenser must not be exceeded at any time. Refer to Section 10 for details.
A flow switch must be directly in series with the evapo­rator/ condenser and wired back to the control panel using screened cable. For details refer to Electrical Connection .This is to prevent damage to the evaporator/ condenser caused by inadequate liquid flow. A paddle type flow swit­ches are suitable for 10 bar working pressure.
The chilled water pump should be installed in the entering water pipe. Pipework and fittings must be separately supp­orted to prevent any loading on the unit. Flexible conn­ections are recommended which will also minimize trans­mission of vibrations to the building. Flexible connections must be used if the unit is mounted on antivibration mounts as some movement of the unit can be expected in normal operation.
Pipework and fittings immediately next to the evaporator should be readily dismantled to enable cleaning prior to operation, and to facilitate visual inspection of the heat exchanger nozzles.
A strainer must be mounted on the waterside of the evaporator and condenser respectively, preferably of 40 meshes, fitted as close as possible to the liquid inlet conn­ection, and provided with a local water cut-off switch.
The evaporator must not be exposed to too high flushing velocities or debris deposited during flushing. It is recom-
mended that a suitably sized by-pass and valve arrang-ement be installed to allow flushing of the pipework sys-tem. The by-pass can be used during maintenance to isol-ate the evaporator without disrupting flow to other units.
Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of the evap­orator and condenser.
Drain and vent valves (by others) should be installed in the connections provided in the cooler and condenser liquid heads. These connections may be piped to drain if desired.
Any debris left in the water piping between the strainer and cooler could cause serious damage to the tubes in the cooler and must be avoided. The installer/user must also ensure that the quality of the water in circulation is adequate, without any dissolved gases, which can cause oxidation of steel parts within the cooler.
Fig 4-1 Diagram of cooling water and chilled wa­ter pipe connection
YEWS-E Water Cooling Screw Chiller/Heat Pump
CAUTION
CAUTION
ISOLATORS SPRING
Kg
UP TO 3114
3115 TO 4453
4454 TO 5526
5527 TO 6927
6928 TO 8288
SYSTE M OPERATING WEIGHT
Lbs.
UP TO 6865
6866 TO 9818
9819 TO 12182
12183 TO 15272
15273 TO 18272
029W18479-001
029W18479-002
029W18479-003
029W18479-004
029W18480-001
PART NO
14
Quality requirement of water used in chiller
Name PH value(25) Conductivity(25) Chloridion Sulphate ion Acid wastage Total Hardness Calcium Hardness SiO
2
Unit
-
μs/cm
mg/L mg/L mg/L mg/L mg/L mg/L
6.58.0
800200200100200150
50
Corrosion
X X
X
X
Target
Allowable value
Fouling
X
X
X
X
Notes:
1. The user should make regular inspections on the water
quality before installation and in the process of using. If the
water quality does not meet the demands of using, the heat-
exchange tubes will be in the danger of fouling ,corrupting and even leakage when using the Defective water for
long term.
2. Corrupting testing about the influence of using Def­ective water whose qulity exeed the limits for long term
shows that, the chiller will fail to run normally due to the
heat-exchange tubes corrupting and leakage.
3. Fouling testing about the influence of usingDefecti­ve water whose qulity exeed the limits for long term
shows that, the chiller will has a decreaing on capacity due
to the heat-exchange tubes fouling.
4. The water should be drained out if the unit will stop for a
long time, it is suggested that the heat exchanging pipe
should be cleaned after each long-term stop.
5. User should be responsibility for the loss caused by the
poor water quality.
4.6 Pipework Arrangement
The following are suggested pi4pework arrangements for
single unit installations. For multiple unit installations, each
unit should be piped as per relative drawings.
4.7 Connection Types &Sizes
Please refer to Section 10 for connection sizes of each
model.
The piping connections of evaporator and condenser are
HG20615 welded flanges.
4.8 Refrigerant Relief Valve Piping
The evaporator and condenser are each protected against
internal refrigerant overpressure by refrigerant relief valves.
It is recommended that each valve should be piped to the
exterior of the building so that when the valve is activated
the release of high pressure gas and liquid cannot be a
danger or cause injury.
The size of any pipework attached to a relief valve must be of sufficient diameter so as not to cause resistance to the operation of the valve. Unless otherwise specified by local regulations, the internal diameter depends on the length of pipe required and is given by the following formula:
YEWS-E Water Cooling Screw Chiller/Heat Pump
4.5 Water Treatment
The unit performance provided in the Design Guide is
2
based on a fouling factor of (0.044m ./KW for
2
condenser and 0.0176m ./KW for evaporator). Dirt, scale, grease and certain types of water treatment will adversely affect the heat exchanger surfaces and therefore the unit performance. Foreign matter in the water system(s) can increase the heat exchanger pressure drop,
reducing the flow rate and causing potential damage to the heat exchanger tubes. YORK recommends that a water treatment specialist should be consulted to determine whether the proposed water composition will adversely affect the evaporator materials of carbon steel and copper. The pH value of the water flowing through the evaporator must be kept in a range between 6.5 and 8.0. The water quality of chiller should be in accordance with local code.
15
5
D =1.447 x L
Where: D =minimum pipe internal diameter in centimeters (cm)
L =length of pipe in meters (m)
If relief pipework is common to more than one valve, its cross sectional area must be at least the total required by each valve. Valve types should not be mixed on a common pipe. Precautions should be taken to ensure that the exit of relief valves/vent pipe remain clear of obstructions at all times.
4.9 Electrical Connection
YEWS product is suitable for 60Hz application, but the compressor can only be applied to 460V/60Hz, when the field power supply is 230V/60Hz, the transformer is necessary to make the chiller operation (the transformer will be shipped along with the chiller). And YEWS product control panel can only provide 220VAC power, please check if the equipment connected to the control panel is suitable for 220VAC voltage.
Please refer electrical drawingsfor 60Hz powerto find the details for field power connection.
The following connection recommendations are intended to ensure safe and satisfactory operation of the unit. Failure to follow these recommendations could cause harm to persons, or damage to the unit, and may invalidate the warranty.
No additional controls (relays, etc.) should be mounted in the control panel. Power and control wiring not connected to the York control panel should not be run through the control panel. If these precautions are not followed it could lead to a risk of electric shock. In addition, electrical noise could cause malfunctions or damage the unit and its controls.
Since some internal components are live when main power is switched on, the unit should not be switched on to the main power until it has been commissioned by York authorized personnel after connection.
All customer wiring at the jobsite must be routed to avoid high temperature areas (compressor shells, discharge piping, ambient coils and other hot surfaces) and sharp edges on the unit, to prevent damage to the wiring and possible short circuits. If these precautions are not followed it could lead to a risk of electrocution or damage to
Cooling tower
Pump
Bypass of condenser
Tee valve
Bypass
Cooling tower or other cooli­ng source
Cycling loop
Tee valve
Condenser
Pump
Direct Pressure Control
With YEWS-E units it is possible, if desired, to control the condenser cooling liquid inlet temperature/flow directly from the unit refrigerant pressure. The refrigerant pressure can either be used to control cooling tower effectiveness by controlling fans or dampers on the tower, or to control condenser water flow using a three way bypass valve.The purpose of this method is to keep a low and steady discharge pressure .But with the units using R134
YEWS-E Water Cooling Screw Chiller/Heat Pump
16
the unit and its controls.
4.10 Condenser Cooling Water System For YEWS-E units, condensers are usually piped in conjunction with a cooling tower.
With water cooled units it is necessary to control the condenser water flow and/or temperature into the condenser to maintain refrigerant pressure as constant as possible to ensure satisfactory operation of the unit.
WARNING
refrigerant, it is essential that the discharge pressure should be higher than suction pressure for more than 3Bar.In that case, units should be controlled by a certain setpoint higher than suction pressure or be controlled by the suction pressure and a pressure difference.However, the temperature and flow rate of cooling water should not exceeds the allowable range.
Inlet Temperature Control For a cooling tower system the simplest forms of control is to use fan cycling, fan speed control, or air damper control, with the tower having a thermostat in its sump. This will ensure stable condenser cooling liquid temperature and should be adjusted to ensure a condenser cooling liquid entering temperature of not lower than 21to 24 at lower ambient conditions.
If these methods are not available, or a cooling tower is not the source of cooling water, then a three way valve recirculation system can be used with control based on condenser inlet liquid temperature as shown in the upward diagram. In this case the objective is to maintain the inlet cooling liquid temperature as low as possible, although still observing the minimum limit of 21to 24.
4.11 Variable Primary Flow
Johnson Controls recommends a maximum 10% per minute flow rate change, based on design flow, for variable primary applications. Provide 8-10 gallons per chiller ton (8.6-10.8 liter per cooling KW) system water volume. Insufficient system volume and rapid flow changes can cause control problems or chiller shutdowns. There are many other design issues to evaluate with variable primary flow systems. Consult the Johnson Controls Sales Office for more information about successfully applying YEWS chillers.
4.12 Power Wiring
The allowable variation range of power supply voltage equal to the rated voltage value ±10.
All electrical wiring should be carried out in accordance with local regulations.
In accordance with China National Standard it is the responsibility of the user to install current overload protection for input power supplies of York units.
All sources of supply to the unit must be taken via a common point of isolation (not supplied by York).
Single Point Power Supply Wiring
Models require field provided 380V(400V/415V)/3P / 50Hz power supply to the unit with circuit protection. Connecting power supply to the terminal block located in the power panel on site.
4.13 Control panel Wiring
The power connect to the I/O switch input terminal is 12VDC while the power connect to the I/O switch output terminal is 220VAC.
The wiring with 220VAC power must use the dry-contact (It is suggested to use the golden contact).If the dry-contact is part of a relay or a contactor, a capacitance-resistance suppresser wind ing must be used to restrain the Electromagnetic Interference.Make sure that the above precautions are followed to avoid the Electromagnetic Interference, which may result in the fault or damages on the unit or the controller.
The length of cable connected to these terminals should not exceed 7.5 meters.
4.14 220VAC Output Water pump starter
When the terminal 21 send out a 220VAC power, the water pump should be started.So the opening and stopping control of pump can be achieved by contactor and start/stop program.
Note: Power load should not exeed 5w.
Alarming contract
When the terminal 26 send out a 220VAC signal, the unit should be in the alarming status.
Note: Power load should not exeed 5w.
4.15 System input Flow switch
A suitable water flow switch must be connected to terminals 1 and 13 to provide adequate protection against loss of liquid flow.
Note: Contact Resistance <5Ω.
Remote Run/Stop
Connect a remote switch between 8 and 13 to provide remote start/stop if required.
Note: Contact Resistance <5w.
YEWS-E Water Cooling Screw Chiller/Heat Pump
17
5 CONTROL CENTER
5.1 Safety notice for the operation of the controller (1) Safety Notice contains all important matters
related with safety. Please strictly follow. Signals used in this manual:
A WARNING is given in this document to identify a hazard, which could lead to personal injury.
A CAUTION identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution.
A NOTE i s u sed to highlight additional information, which may be helpful to you but where there are no special safety implications.
(2) Installation
Please keep this technical manual well for reference at any time. Please also give this to other people operating this machine for reference.
Only the appointed accessory by YORK can be used, and please ask manufacturer or authorized dealer to provide the corresponding technical installation and technical service. Malfunction of controller or electric shock may be caused from improper installation of the controlling accessory. The user is prohibited to maintain the machine by itself, because electric shock or controller damage may be caused due to improper repair of the controller. Please consult the manufacturer for any repair demand.
(3) YORK-003 Control Board
YORK-003 control board must be installed on one stable panel without the accumulative rain or snow, leaf or other wastes in the host. The intensive circuit generally passes through the installation center; also AC220V passes the control panel. As for the installation location of outdoor control panel, the principle of power and signal wires connected separately should be followed to keep the distance between the control panel and contactor is above 100mm.
(4) XS08 HMI
XS08 HMI should be installed stably, otherwise, it may fall down to cause body injury or damage on controller.
It is required to adopt the specified cable for power supply. Please do not share the power with other electric appliance to avoid the danger due to overloading. It is required to use the fuse or breaker suited with the working pressure of controller. Please do not use the wire or fuse beyond the specified grade.
(5) Earthing
YOR K-0 03 co ntr ol boa rd and she ll of transformer must be connected with the ground wire. Please do not connect the ground wire with the fuel gas pipe, water pipe, or lightning protection conductor. Electric shock may be caused if it is improperly earthed. Please inspect regularly whether the connection between the earthing wire of controller and earth terminal and earthing electrode of unit is firm or not.
(6) Operation
Do not press the keypad with the sharper to avoid damaging the controller. Do not twist or drag the wire of the controller to avoid damaging the controller to further malfunction. Do not wipe the controller with the benzene, thinner or chemical cloth, otherwise, the component should be in malfunction. Do not use much strength on the screen or connection part to avoid the color variation.
5.2 Initialization Operations
After completing the installation and connection
of YEWS-E HMI, it is required to perform the initialization operation before putting into running.
(1) Situations for Initialization
When the HMI and the control board are interconnected to form the control system for the first time, it is required to be initialized.
If the HMI in the interconnected running control system is damaged, it must be replaced with the new centralized controller, it is required to be initialized, and it is the same case for control main board.
If the controller or main board in one control system
WARNING
NOTE
CAUTION
WARNING
CAUTION
WARNING
WARNING
CAUTION
WARNING
NOTE
YEWS-E Water Cooling Screw Chiller/Heat Pump
18
ON
1 2 3 4
AC Units
network needs to run upon exchanging with another control system network, it is required to be initialized.
(2) Process for Initialization Operation
Power off the control system.
If firmware of YORK-003 is 1.06 and previous versions(Suitable for YEWS100/130/170/200/210), detailed setting methods are shown in following figure:
ON
1 2 3 4
ITS Units
ON
1 2 3 4
HP Units
DIP switch can not be set by anyone except manufacture.
The measuring range of pressure sensor used in AC/ITS units: 0.41~5.1 Kg/cm2
The measuring range of pressure sensor used in HP units: 0~20.69 Kg/cm2.
If firmware of YORK-003 is 1.07 and last versions,DIP does not need to set in single system unit(Suitable for YEWS/100/130/170/200/210/215).
Control system power on.
Press F2 in the main interface of centralized controller to enter into the parameter setting interface-1, turn to the
next upon inputting the password.
Turn to the parameter setting interface-16. Please select the correct Model before doing the next operation.
Turn to the parameter setting interface-17, and move the cursor on the line of CLEAR RECORD to set all parameters as SYS1 or SYS2 by pressing 8, and press to confirm. Move the cursor on the line CLEAR FAULT RECORD to set all parameters as YES by pressing 8, and press to confirm. Move the cursor on the line of DEFAULT DATA to set the parameters as YES, press confirmation key to confirm.
Turn to the parameter setting interface-16, and move the cursor to the line of SYS1 FLA and SYS2 FLA (only set SYS1 on the single system) to select the correct FLA value via number 0 to 9. After correct setting, move the cursor on the line SYS1 CUR.OFFSET and SYS2 CUR.
OFFSET (only set SYS1 on the single system) of parameter setting interface-3 to set the correct value. The
default is 100, which can be set before the unit leaves the factory. The user and service personnel shall not attempt to modify the parameter; otherwise the unit may fail to be run properly.
Control system power off.
Power on again after powering off HMI and control board.
Return to the main interface by pressing F1, then press F1 to enter into Status display interface to view the co mm un ic at io n of HMI an d co nt ro l boar d. The communication status of centralized controller and control board will be displayed in Status display interface. If it is displayed in normal, please check the input status of AI and DI for each module via the display interface, then the startup can be done after confirmation.
Note: Only select the unit style E on unit
Model setting, example YEWS100HA50E or YEWS100HA50E-HP.
YEWS-E Water Cooling Screw Chiller/Heat Pump
NOTE
19
5.3 Instructions on the operation (1) Instruction of HMI Keypad
The unit will shut down when pressing this key. It will return to the main interface upon pressing this key in any interface. Function 1: Confirm the modified parameter. Function 2: Select the next modifying parameter in the parameter set interface.
Function 1: Press this key in the main interface to check the unit status, AI, DI and DO status. Function 2: Return to the main interface.
Function 1: Enter into the clock set interface by pressing this key in the main interface. Function 2: Turn to the previous page by pressing this key in the information inquiry, parameter set and fault inquiry interfaces.
The unit will start up when pressing this key. The fault happened can be inquired upon pressing this key. Function 1: Press this key to cancel the input value for the parameter modified before pressing the confirmation key. Function 2: Select the last modified parameter in the parameter set interface. Enter into the system set interface upon pressing this key in the main interface; modify the corresponding parameters according to the different password access.
Function 1: Enter into the fault inquiry interface upon pressing this key in the main interface. Function 2: Turn to next page by pressing this key in the information inquiry, parameter set and fault inquiry interfaces.
Function 1: Modifying the setting parameter. Function 2: 0 and 8 have the direction function when setting parameters, just as “△” and “▽”.
F1
F2
F3 F4
0 9
YEWS-E Water Cooling Screw Chiller/Heat Pump
20
(2) Instruction of HMI Interface
A0 B0 : Communication interface with control board. A1 B1 : Communication interface with upper computer V0 : Common ground end
Input the DC power of 10-24V, the end marked with 0V is low, while the other end is positive
Press for 1 minute, then loosen, the centralized controller will be reset.
Note
ISP
10-24V
0V
A0 B0 A1 B1 0V
Wiring diagram of HMI
Instruction:
A0, B0: Communication interface of HMI and mainbord
A1, B1: Communication interface of HMI and upward computer
0-24V: Pwer connction of HMI, among which 0V means the ground.
ISP: Interface for downloading mainbord programs
Symbol
CN5(KEY BUS)
CN6(ISP)
CN2
CN3
RST_SW
Description
Keyboard interface
Download interface of ISP program
485 communication port
Input power
Reset key
YEWS-E Water Cooling Screw Chiller/Heat Pump
21
(3) Instruction of Control board Interface
(4)Wiring diagram of control board
(a) Power and DO output interface diagram
Instruction
DO1-DO10 : Relay output
DO11-DO14 : Relay output
DO15A,DO15B : Bi-directional Thyristor output
L : AC220V live wire
N : Zero line
L
PE
N
Symbol
CON2(COMU)
COM DI1–DI12
CON3
VCC
0V AI13–AI16
+12V AI1–AI12 CN5CN6
COM1
COM2
DO15ADO15B DO16ADO16B
LN
PE
JP1
AI13–AI16Alignment needle
TEST
SW1
POWER(LED)
COM(LED)
RUN(LED)
Description
485 communication port
Common port of DI switch input
DI switch input
Blower speed adjusting interface.
+5V power with analog quantity input Ground end of analog quantity input
Analog input
+12V power output
Analog input
Expansion output
Output common port of relay
Output common port of relay
Thyristor output
Thyristor output
Note
Connect according to the marked A, B, positive and
negative terminal of power
The two COM ports are jointed together
12 DI switch inputs in all
PG motor speed adjustment
VCC of all 6 circuit is connected
Ground end of AI13 to AI16,All connected together
4-20ma 1-5V or NTC signal input
Ordinary NTC signal input
2*4 ways TTL level output
Common port of DO1 - DO10
Common port of DO11 -Do14
220VAC/50Hz
Connect or break the load resistance, operate according to the above diagram
Selection of AI13-AI16 analog quantity divided resistance,
the operating method refers to the panel
For downloading programs
Setting the main board address
Red, the light will be on if the power of main board is in normal situation
Green, communication success for one time, turning over
Yellow, flash in 0.5Hz frequency
AC power input
Safety ground end
485 resistance control of communication load
Selection of divided resistance
Test
Dial switch
Power indicating lamp
Communication indicating lamp
Running indicating lamp
COM1 : Common port of DO1-DO10 output
COM2 : Common port of DO11-DO14 output
DO16A,DO16B : Bi-directional Thyristor output
PE : Earthing
YEWS-E Water Cooling Screw Chiller/Heat Pump
22
Loading...
+ 61 hidden pages